378240 COMPONENT SPECIFICATIONS FOR BPU.pdf
PDF 194 KB Posted
- Attached to
- ELECTRICAL COMPONENTS FOR POWER UPGRADE
- Solicitation number
- 378240
About this file
This document contains product specifications for electrical equipment components required for a federal contract procurement. The specification document outlines three main categories of equipment: electric panel boards, main circuit breakers, and motor starters.
The electric panel board specifications detail two designations (A and B) of I-Line MB Panel (Interior) Panelboards. Designation A consists of a 480Y/277V 3-phase 4-wire 60Hz SCCR 65kA panelboard with a 600A/3P main circuit breaker, padlock-capable main disconnect, and three incoming feeder positions (3/0 to 500 kcmil copper conductors). The panel features a 68H x 42W x 9.5D Type 1 enclosure with surface-mounted door and includes standard copper bus bars and mechanical restraint provisions. Designation B is a similar 480Y/277V 3-phase panelboard with a 600A/3P main circuit breaker rated for 72 mounting inches, featuring a 91H x 32W x 9.5D Type 1 enclosure. Both panels include specified feeder configurations, standard nameplates with black surface and white lettering (3.50" Wide x 1.00" High), and enclosure/cover/trim assemblies with corresponding catalog numbers and drawing references.
The main circuit breaker specification describes a PJL3612DYP-Molded Case Circuit Breaker with UL/CSA rating, PowerPact P Frame, and 3-pole configuration rated at 600 Vac with 80% standard rating. The breaker accommodates interrupting ratings of 100kA @ 240V and 95kA @ 480V with 600 Vac capacity and provides handle padlock attachment options. The motor starter specifications include two NEMA Size designations—Size 2 (25 HP @ 460V 3-phase) and Size 4 (100 HP @ 460V 3-phase)—both featuring thermal magnetic circuit breaker combination starters with Class 8539 ratings, non-reversing 3-pole configurations, Type 1 enclosures, fused control transformers with 120V 60Hz coils, dual control fuses (primary and secondary), auxiliary contacts (normally open and closed), and pilot light assemblies with HAND-OFF-AUTO selector switches and LED status indicators.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SARC_Subcontractor Annual RepsCerts Rev 4.pdf | ||
| PR 378240 BUILDING POWER UPGRADE A.pdf | ||
| PUR-466_Proposal Certifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1) ELECTRIC PANEL BOARD SPECIFICATIONS
2) MAIN CIRCUIT BREAKER SPECIFICATIONS
3) MOTOR STARTER SPECIFICATIONS
File details come from the government source that posted it. Updated .