36k unit specs.pdf
PDF 25 KB Posted
- Attached to
- MUR -Portable Air Conditioners - bjl
- Solicitation number
- 25-426DOC-MURPH-B-44797
- Issued by
- Jackson County, Illinois
About this file
This document appears to be technical specifications for a 36,000 BTU/h electronic climate control unit. The specifications cover the unit's electrical and physical characteristics, including voltage requirements, power consumption, fan types and airflows, compressor details, and dimensions and weight. The document also includes information on operating conditions, duct length maximums, and sound levels with and without ductwork. This seems to be an informational document rather than a solicitation for a state or local contract opportunity.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 60k unit specs.pdf | ||
| Standard Terms and Conditions -FACILITY1 - v.23.2~38.pdf | ||
| MUR Portable ACs BOA B44797~1.docx | DOCX document | |
| Standard Illinois Certifications - FACILITY - v.23.1~20.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MODEL NAME CLIMATE PRO K36
Electronic Features Control Programmable
Cooling Capacity Rating Conditions: 95°F, 60% RH 36,000 Btu/h
Electrical Characteristics
Voltage Requirement 208/230V, 1Phase, 60Hz
Total Power Consumption 4.3 kW
Current Consumption 19.6 amps
Recommended Fuse Size 30 amps
NEMA Plug Confi guration 6-30
Min. - Max. Voltage 198 -253
Fans: Motor Output Evaporator 0.23 kW
Condenser 0.38 kW
Evaporator
Fan Type Centrifugal
Max. Air Flow (hi/mid/low) 920/880/840 CFM
Max. External Static Pressure 0.6 IWG
Condenser
Fan Type Centrifugal
Max. Air Flow (hi/low) 1390/990 CFM
Max. External Static Pressure 0.5 IWG
Compressor Type Hermetic Rotary
Output 2.3 kW
Refrigerant Type R-410A
Dimensions W x D x H 31 x 55 x 53 in
Weight Net / Shipping 470/535 lb
Power Cord Gauge 12 AWG (3-core)
Length 6 ft
Condensate Tank Capacity 2@5 gal
Operating Conditions Min. 65°F (@ 50% RH)
Max. 95°F (@ 50% RH)
Max. Duct Length Per Cold Duct Hose 40 ft
Hot Duct Hose 60 ft
Max. Sound Level With Duct (hi/mid/low) 68/67/66 dB(A)
Without Duct (hi/mid/low) 70/69/68 dB(A)
TECHNICAL SPECIFICATIONS