36E77619B0005-0001002.pdf

PDF 1 MB Posted

Attached to
Renovate 8W Hematology & Oncology - Iowa City
Solicitation number
36E77619B0005
Issued by

About this file

36E77619B0005 0001 Mechanical Addendum.pdf

View the file

Other files

File Type Posted
36E77619C0063-000.docx DOCX document
36E77619B0005-0003000.docx DOCX document
36E77619B0005-0003001.pdf PDF
36E77619B0005-0002003.docx DOCX document
36E77619B0005-0002001.doc DOC document
36E77619B0005-0002002.pdf PDF
36E77619B0005-0002000.docx DOCX document
36E77619B0005-0001001.pdf PDF
36E77619B0005-0001000.docx DOCX document
36E77619B0005-007.pdf PDF
36E77619B0005-002.docx DOCX document
36E77619B0005-006.pdf PDF
36E77619B0005-005.docx DOCX document
36E77619B0005-004.zip ZIP file
36E77619B0005-003.zip ZIP file
36E77619B0005-001.docx DOCX document
36E77619B0005-000.docx DOCX document
Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F

F

F

F

F

F

F

S S

S

SS

S S

SS

S S

S S

S

SS

S S

S S

S S

SS

S S

S S

J

K

L

M

N

P

R

T

12 13 14 15 16 17 18 19 20A 21 22

SERVICE CHIEF

8W06

EQUIP. ROOM

8W08

STAFF TOILET

8W10

STAFF TOILET

8W12

AUTHORIZED STAFF ONLY

8W14

CLEAN SUPPLY

8W14A

PHARMACY

8W19

NON-HAZARDOUS

COMPOUNDING

8W19A

ANTEROOM

8W19B

HAZARDOUS COMPOUNDING

8W19C

CHEMO STOR.

8W19D

CORRIDOR

8CW02

CORRIDOR

8CW02

CORRIDOR

8CW03

EXAM ROOM

8W18D

EXAM ROOM

8W18C

EXAM ROOM

8W18B

EXAM ROOM

8W18A

EXAM ROOM

8W16

SOILED HOLDING

8W15

PROCEDURE ROOM

8W17

TOILET

8W17A

CLINIC WORKROOM

8W18F

EXAM ROOM

8W18E

NURSES

STATION/AUTHORIZED

STAFF ONLY

8W13

WAITING AREA

8W13A

TOILET

8W11B

SCALE

8W11A

VITALS

8W11

FAMILY ROOM

8W09

PROVIDER WORKROOM

8W07

CASE MANAGER

8W05

CORRIDOR

8CW01

ELEC

8W09A

ELECT.

8W04

CORRIDOR

8CW01A

EXISTING ELEVATOR LOBBY

8CW01B

EXISTING OIT

8CW100

STAIR

8ST01

HAC

8W21

PHARMACY HAC

8W20

EX. TOILET

8W25C

STAFF

8W25E

STAFF

8W25A

INFUSION

8W25G

EX. NURSE STATION

8W25

EX. TREATMENT

8W25D

EXISTING TOILET

EXISTING TREATMENT

8W25F

STAIR

8ST04

E X

IS

T

IN

G

S H

A F

T

S

B x

8x8

16x816x1220x14 x

6x4

6x4

8x6

8"ø

12x10 x x

8"ø

8"ø

8"ø

8"ø

8"ø

12x4

12x10

8"ø

8"ø

8"ø

8"ø

8"ø

12x8 x

FCU-8W12

TU-8W19D

TU-8W17A

TU-8W17

TU-8W18F

H4-8W

FCU-8W18D

FCU-8W18C

FCU-8W18A

FCU-8W16

FCU-8W09

FCU-8W07

FCU-8W14

FCU-8W06

FCU-8W08

FCU-8W14A

FCU-8W13

FCU-8W11

6x6

6x6

"ø x

16x12 x

12x8

12x8

8"ø

6"ø

8"ø x x

20x10

8"ø

12x10

12x10

12x10 x

6x4

8"ø

SD2 330

SD2 330

SD2 330

10x12

SD2 330RG1

SD2 330

FCU-8W05

SD2 330SD2 300

SD1 80

SD2 350

SD2 210

SD2 265

SD2 250SD2 250

SD2 90

SD2 150SD2 150SD2 150

SD2 150

SD2 150

SD2 150

SD2 50

SD2 50

SD2 300

SD2 150

SD2 150

SD2 150 SD2 200

x

RG1

RG1

RG1

RG1

RG1

RG1 400

RG1

RG1

RG1

RG1

RG1

RG1

RG1

RG1

RG1

RH1 270

FD

FSD

FCU-8CW01A

FCU-8CW01B RG1

RG1

SD2 150

SD2 150

RG2 800

RG3 300

RG3 300

SD2 300

RG1 300

FCU-8CN01

6x4

6x4

12x8

EG1 130

FCU-8CW100

SD1 200

EG 75

EG 75

FCU-8W13A

FCU-8W11B

SD1 100

EG1 110

SD2 200

SD1 100

SD1 100

SD1 100

TAB-8-12

TAB-8-13

CAP EXHAUST DUCT

8"ø

8"ø 8"ø

14x6

12x8

8"ø

M-401

RG2 550

FD

EG1 75

6x6

SG1 400

RG3 400

8x8

6x4

8x8

6"ø

TU-8W15

TU-8W18E

7"ø 8"ø

10x10

6x4

6x4

6x4

8x6

8"ø

SD1 100

SD1 80

6"ø

8"ø

6"ø

10x8

6x6

6x6 x

6x4

6"ø

6x6

EG2 300

EG1 100

EG2 280

EG2 200

EG2 250

FD

10"ø

# KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

WALL RATING LEGEND

E

D C

B A

2 3 4 5 6 7

E D

C B

A

1 2 3 4 5 6 7

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

1-8W-

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

/3

/2

:3

:1

P

M

M-101

EIGHTH FLOOR MECHANICAL NEW

WORK PLAN

4 14RCM JT

Renovate 8W for Hematology and Oncology

601 Highway 6 West, Iowa City, IA 52246

06/12/2019

100% CONSTRUCTION DOCUMENTS

636A8-18-00118-023

0 4 8 16 NORTH

PLAN

01 1" STEAM HOSE FROM HUMIDIFIER STEAM

OUTLET TO DUCT HUMIDIFIER DISTRIBUTION

TUBE. PROVIDE STAINLESS STEEL

WATERTIGHT DUCT 6'-0" DOWNSTREAM OF

HUMIDIFIER DISTRIBUTION TUBE.

02 CAP 12x8 AND SEAL FOR FUTURE

CONNECTION.

03 ENLARGE EXISTING 6" HIGH PENETRATION

THROUGH EXIST. CONCRETE BEAM TO 12"

HIGH. DO NOT ENCROACH ON BOTTOM 10"

OR TOP 10" OF BEAM. X-RAY BEAM BEFORE

WORK IS DONE TO AVOID EXISTING

REINFORCEMENT.

04 ENLARGE DUCT TO 12/10 AND CONNECT TO

PAN AT BOTTOM OF JOIST AND TO TOP OF

EXIST. RETURN DUCT. EXISTING ACCESS

PANEL PROVIDES ACCESS.

05 CONNECT 12/10 TO EXISTING PAN AT

BOTTOM OF JOIST.

06 PROVIDE TEMPERATURE HUMIDITY AND AIR

PRESSURE DEVICES FOR MONITORING THIS

ROOM THROUGH THE BUILDING

AUTOMATION SYSTEM (BAS).

07 PROVIDE SENSORS AT ALL PHARMACY

MINCO REFRIGERATORS AND CONNECT TO

THE BAS. FOR MONITORING.

08 BALANCE OUTDOOR AIR IN 6X4 DUCT TO

EACH FCU TO 30 CFM. FCU-8W13A SHALL

HAVE OUTDOOR AIR BALANCED TO 100 CFM

09 EXISTING TO REMAIN.

10 PROVIDE 1/2" DIAMETER STEEL SECURITY

BARS INSIDE DUCT WELDED VERTICALLY

AND HORIZONTALLY AT 6" O.C. GRILL MAY BE

USED IF CONSTRUCTED OF 9 GAUGE

EXPANDED STEEL. ALIGN BARS WITH WALL

PENETRATION.

11 MAINTAIN EXISTING POINTS TO REMAIN

CONNECTED INCLUDING EXISTING

NUTRITION REFRIGERATOR CONNECTED TO

BAS.

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

BLDG. 1Scale: 1/8" = 1'-0"

EIGHTH FLOOR MECHANICAL NEW WORK PLAN

A SHADED AREAS NOT IN SCOPE.

B DIAGONAL HATCH AREA DENOTES FUTURE

CONSTRUCTION.

REVISION 1 07-30-19

DocuSign Envelope ID: CA3DCFB0-EECC-475B-AFF1-3C2606808C80

7/31/2019

S S

S S

S

SS

J

K

18 19 20 20A

J

K

18 19 20A

PHARMACY

8W19

NON-HAZARDOUS

COMPOUNDING

8W19A

ANTEROOM

8W19B

HAZARDOUS COMPOUNDING

8W19C

CHEMO STOR.

8W19D

SD2 150

SD2 150

SD2 200

RH1 270

RG1 500

RG2 800

RG3 300

RG3 300

RG2 550

SD2 150

PRESSURIZATION: NEGATIVE

SA: 1200 CFM EA: 1300 CFM

OA: 600 CFM RA: 0 CFM

FLOW DIFFERENTIAL: -100 CFM

PRESSURIZATION: NEGATIVE

SA: 200 CFM EA: 270 CFM

OA: 100 CFM RA: 0 CFM

FLOW DIFFERENTIAL: -70 CFM

PRESSURIZATION: POSITIVE

SA: 960 CFM EA: 800 CFM

OA: 400 CFM RA: 0 CFM

FLOW DIFFERENTIAL: +100 CFM

PRESSURIZATION: POSITIVE

SA: 660 CFM EA: 550 CFM

OA: 300 CFM RA: 0 CFM

FLOW DIFFERENTIAL: +110 CFM

PRESSURIZATION: POSITIVE

SA: 450 CFM EA: 0 CFM

OA: 225 CFM RA: 400 CFM

FLOW DIFFERENTIAL: +50 CFM

SH-1-400

SH-1-400

SH-1-400

SH-1-400 SH-1-400

SH-1-330

SH-1-330

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

E

D C

B A

2 3 4 5 6 7

E D

C B

A

1 2 3 4 5 6 7

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

1-8W-

/3

/2

:3

:1

P

M

M-601

MECHANICAL SCHEDULES

13 14RCM WRS

Renovate 8W for Hematology and Oncology

601 Highway 6 West, Iowa City, IA 52246

06/12/2019

100% CONSTRUCTION DOCUMENTS

636A8-18-00118-023

1. FAN POWERED HEPA DIFFUSER WITH CHARGE TEST PORTS, ROOM-SIDE ACCESSIBLE PREFILTER AND HEPA FILTER AND FAN. PROVIDE VARIABLE SPEED FAN WITH ECM MOTOR, 120 V, 300 W. SIMILAR TO ENVIRCO MAC10...

NOTES:

SH-1 HEPA SUPPLY DIFFUSER WITH FAN 400 [ 190 ] 660 [ 310 ] 0.700 [ 180 ] SURFACE 24 X 48 [ 305 x 203 ] 10 ø [305 ø ] 50 Db NONE WHITE 1

SG-1 SUPPLY REGISTER 80 [ 38 ] 400 [ 190 ] 0.090 [ 23 ] WALL 12 x12 [ 305 x 203 ] 12 x 12 [254 x 152] 25 OBD WHITE -----

SD-3 LOUVERED FACE 110 [ 52 ] 380 [ 180 ] 0.090 [ 23 ] CEILING 24 x 24 [ 600 x 600 ] 10 ø [254 ø] 22 NONE WHITE -----

SD-2 LOUVERED FACE 70 [ 33 ] 280 [ 130 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 8 ø [203 ø] 23 NONE WHITE -----

SD-1 LOUVERED FACE 40 [ 19 ] 160 [ 76 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 6 ø [152 ø] 19 NONE WHITE ----

CFM [L/s] CFM [L/s] IN WG [Pa]

MIN MAX

IN x IN [mm x mm] IN [mm ]

MARK TYPE

AIR FLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE

NC DAMPER FINISH NOTES

AIR DEVICE SCHEDULE (SUPPLY)

3. FAN POWERED HEPA EXHAUST GRILLE WITH ROOM-SIDE ACCESSIBLE PREFILTER AND HEPA FILTER AND FAN. PROVIDE VARIABLE SPEED FAN WITH EC MOTOR, 120 V, 200 W. SIMILAR TO ENVIRCO MAC10 RFAC. LOCATED IN HAZARDOUS STORAGE ROOM...

2. PROVIDE FILTER RETURN GRILLE WITH HINGED, LOUVERED GRILLE ACCESSIBLE FROM THE ROOM SIDE.. PROVIDE MERV 8 PLEATED FILTER PLUS A SPARE.

1. PROVIDE LOUVERED DESIGN WITH ANGLED BLADES SPACED AT 1/2" ON CENTER.

NOTES:

RH-1 HEPA RETURN GRILLE 900 [ 420 ] 1500 [ 710 ] 0.20 50 LAY-IN 24 x 24 [ 406 x 406 ] 24 X 24 [ 356 x 356 ] 25 - WHITE 3

RG-2 FILTER RETURN GRILLE 900 [ 420 ] 1500 [ 710 ] 0.20 50 LAY-IN 24 x 24 [ 406 x 406 ] 24 X 24 [ 356 x 356 ] 25 - WHITE 2

RG-1 FILTER RETURN GRILLE 400 [ 190 ] 400 [ 190 ] 0.20 50 LAY-IN 24 x 12 [ 356 x 356 ] 24 x 12 [ 305 x 305 ] 25 - WHITE 2

EG-2 EXHAUST GRILLE 200 [ 94 ] 450 [ 210 ] 0.10 25 WALL 12 x 12 [ 305 x 305 ] 12 x 12 [ 254 x 254 ] 15 OBD WHITE 1, 2

EG-2 EXHAUST GRILLE 800 [ 380 ] 1000 [ 470 ] 0.10 25 WALL 24 x 10 [ 305 x 305 ] 24 X 10 [ 254 x 254 ] 15 OBD WHITE 1

EG-1 EXHAUST GRILLE 70 [ 33 ] 250 [ 120 ] 0.10 25 WALL 8 x 8 [ 254 x 254 ] 8 x 8 [ 203 x 203 ] 13 OBD WHITE 1

CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm]

MIN MAXMARK TYPE

AIR FLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE

NC DAMPER FINISH REMARKS

AIR DEVICE SCHEDULE (EXHAUST/RETURN)

Scale: 1/4" = 1'-0"

EIGHTH FLOOR ROOM PRESSURIZATION PLAN 0 2 4 8 NORTH

PLAN

1. PROVIDE VARIABLE SPEED DRIVE AND DUCT FLANGE.

NOTE

8W-RF-101 NINTH FLOOR CLOSET... PHARMACY 1-AHU1 3800 [ 1800 ] 1.5 [ 380 ] INLINE CENTRIF. BI II 16 [ 400 ] 45% DIRECT 1725 1.8 2 [ 2 ] 1 208 1725 VARIABLE 1

CFM [L/s] IN [Pa] IN [mm] BHP HP [kW]

TYPE WHEEL CLASS

DIAMETER

MIN % EFF DRIVE

FAN MAX

RPM

NOMINAL...

PHASE VOLT RPM

SPEED

CONTROL

MARK LOCATION

AREA AND/OR BLDG

SERVED

SYSTEM AND/OR

SERVICE

AIR FLOW TSP

FAN MOTOR ELECTRICAL

CONTROL

SEQUENCE

REMARKS

FAN SCHEDULE

1-HU-8W14A STAFF LOUNGE 8W14 CLEAN STORAGE 8W14A 1-FCU-8W14A ELEC-STEAM DOM. CW 5 [ 2 ] 65 [ 18 ] 1.7 208 1 10 Automatic drain and fill controls, Provide two extra cylinders lbs/hr [kg/hr] °F [°C] KW VOLTS PHASE AMPS

FLOW EWTMARK LOCATION AREA AND/OR BLDG SERVED SYSTEM AND/OR SERVICE TYPE SOURCE OF MAKEUP WATER

WATER CONDITIONS

ELECTRICAL

REMARKS

STEAM HUMIDIFIER SCHEDULE

REVISION 1 07-30-19

2. PROVIDE TWO-WAY CONTROL VALVE.

1. PROVIDE 24 V TRANSFORMER, CONTROLS BOX., COIL ACCESS DOOR AND INLET FLOW PROBE.

NOTES:

TU-8W19A

INPATIENT PHARMACY

8W19

NONHAZARDOUS

COMPOUNDING 18W19A

EXISTING 8W 9 660 [ 310 ] 660 [ 310 ] 55 [ 13 ] 90 [ 32 ] 150 [ 66 ] 2.5 [ 10 ] 10 [ 30 ] 0.75 [ 19 ] CV HW 2 1, 2

TU-8W19

INPATIENT PHARMACY

8W19

INPATIENT PHARMACY

8W19 EXISTING 8W 8 450 [ 210 ] 450 [ 210 ] 55 [ 13 ] 90 [ 32 ] 150 [ 66 ] 1.7 [ 7 ] 10 [ 30 ] 0.75 [ 19 ] CV HW 2 1, 2

TU-8W18F

CLINIC WORKROOM

8W18F CLINIC WORKROOM 8W18F AHU1-102 7 300 [ 140 ] 100 [ 47 ] 55 [ 13 ] 90 [ 32 ] 150 [ 66 ] 0.4 [ 2 ] 10 [ 30 ] 0.75 [ 19 ] VAV HW 2 1, 2

TU-8W18E EXAM 8W18E EXAM 8W18E AHU1-102 7 330 [ 160 ] 120 [ 57 ] 55 [ 13 ] 90 [ 32 ] 150 [ 66 ] 0.5 [ 2 ] 10 [ 30 ] 0.75 [ 19 ] VAV HW 2 1, 2

TU-8W17A TOILET 8W17A TOILET 8W17A AHU1-102 6 180 [ 85 ] 100 [ 47 ] 55 [ 13 ] 90 [ 32 ] 150 [ 66 ] 0.4 [ 2 ] 10 [ 30 ] 0.75 [ 19 ] VAV HW 2 1, 2

TU-8W17 PROCEDURE ROOM 8W17 PROCEDURE ROOM 8W17 AHU1-102 8 350 [ 170 ] 300 [ 140 ] 55 [ 13 ] 90 [ 32 ] 150 [ 66 ] 1.2 [ 4 ] 10 [ 30 ] 0.75 [ 19 ] VAV HW 2 1, 2

TU-8W15 CORRIDOR 8CW03 SOILED HOLDING 8W15 AHU1-102 6 180 [ 85 ] 100 [ 47 ] 55 [ 13 ] 90 [ 32 ] 150 [ 66 ] 0.4 [ 2 ] 10 [ 30 ] 0.75 [ 19 ] VAV HW 2 1, 2

CFM [L/s] CFM [L/s] °F [°C] °F [°C] °F [°C] GPM [L/m] FT [kPa] IN [mm] TYPE ROWS

MAX MIN EAT LAT EWT FLOW MAX WPD PIPE SIZE TO COIL

MARK LOCATION EXISTING ZONE SERVED

SYSTEM AIR

HANDLING

INLET SIZE

DIA.

AIR FLOW HOT WATER HEATING COIL

CONTROL

TYPE

REHEAT COIL

REMARKS

SINGLE DUCT AIR TERMINAL UNIT SCHEDULE

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

E

D C

B A

2 3 4 5 6 7

E D

C B

A

1 2 3 4 5 6 7

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

1-8W-

/3

/2

:3

:1

P

M

M-602

MECHANICAL SCHEDULES

14 14RCM WRS

Renovate 8W for Hematology and Oncology

601 Highway 6 West, Iowa City, IA 52246

06/12/2019

100% CONSTRUCTION DOCUMENTS

636A8-18-00118-023

2. PROVIDE 120V TO 24V TRANSFORMER, TWO WAY CONTROL VALVE FOR HEATING AND CHILLED WATER, BACNET COMPATIBLE CONTROLLER.

1. AUTOMATIC FAN SPEED CONTROL WITH OVERRIDE SELECTOR. ADJUST FAN SPEED TO DELIVER THE COOLING SUPPLY AIRFLOW QUANTITY SHOWN ON THE PLAN DRAWING.

NOTES

FCU-8CN01 ELEVATOR LOBBY 8CN01 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8CW01B ELEVATOR LOBBY 8CW01 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8CW01A ELEVATOR LOBBY 8CW01 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W18D EXAM ROOM 8W18D HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W18C EXAM ROOM 8W18C HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W18B EXAM ROOM 8W18B HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W18A EXAM ROOM 8W18A HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W16 EXAM ROOM 8W16 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W13 NURSES STATION 8W13 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W14A CLEAN SUPPLY 8W14A HORIZONTAL RECESSED 300 LOW [ 140 ] 0.2 [ 50 ] 7.6 [ 2 ] 6.2 [ 2 ] 78 [ 26 ] 65 [ 18 ] 1.3 [ 17 ] 48 [ 9 ] 10.0 [ 30 ] 6.5 [ 2 ] 70 [ 21 ] 0.6 [ 2 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 ECM MOTOR 1, 2

FCU-8W14 STAFF LOUNGE 8W14 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1200 ECM MOTOR 1, 2

FCU-8W13A WAITING AREA 8W13A HORIZONTAL RECESSED 700 HIGH [ 330 ] 0.2 [ 50 ] 19.0 [ 6 ] 15.0 [ 4 ] 78 [ 26 ] 65 [ 18 ] 2.5 [ 33 ] 48 [ 9 ] 10.0 [ 30 ] 30.0 [ 9 ] 70 [ 21 ] 2.6 [ 10 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 ECM MOTOR 1, 2

FCU-8W12 STAFF TOILET 8W10, 8W12 HORIZONTAL RECESSED 300 LOW [ 140 ] 0.2 [ 50 ] 6.5 [ 2 ] 8.3 [ 2 ] 78 [ 26 ] 65 [ 18 ] 1.1 [ 14 ] 48 [ 9 ] 10.0 [ 30 ] 6.5 [ 2 ] 70 [ 21 ] 0.6 [ 2 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W11 VITALS 8W11 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8CW100 OIT HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W09 FAMILY ROOM 8W09 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W08 EQUIPMENT ROOM 8W08 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W07 OFFICE 8W07 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W06 SERVICE CHIEF 8W06 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

FCU-8W05 OFFICE 8W05 HORIZONTAL RECESSED 400 MEDIUM [ 190 ] 0.2 [ 50 ] 12.5 [ 4 ] 9.2 [ 3 ] 78 [ 26 ] 65 [ 18 ] 2.1 [ 28 ] 48 [ 9 ] 10.0 [ 30 ] 12.0 [ 4 ] 70 [ 21 ] 1.0 [ 4 ] 150 [ 66 ] 10.0 [ 30 ] 11 0.15 [ 110 ] 1 120 1150 ECM MOTOR 1, 2

CFM SPEED [L/s] IN WG [Pa] MBTUH [W] MBTUH [W] °F [°C] °F [°C] GPM [L/s] °F [°C] FT [kPa] MBTUH W °F [°C] GPM [L/m] °F [°C] FT [kPa] MERV RATING HP [W]

Db Wb

MIN SENS CAPACITY MIN TOTAL CAPACITY

EAT

FLOW EWT WPD MIN CAPACITY EAT Db FLOW EWT WPD POWER

PHASE VOLT RPM SPEED CONTROL REMARKS

MARK LOCATION TYPE

FAN AIR FLOW EXTERNAL APD

COOLING REQUIREMENTS HEATING REQUIREMENTS

FILTER

FAN MOTOR

FOUR PIPE FAN COIL UNIT SCHEDULE

1. SET EXISTING TAB-8W110C TO THE REVISED CFM OF 770 AND NEW EXHUAST VALVE EAV-8W110C TO THE CFM SHOWN ON THE DRAWING TO MAINTAIN THE NEGATIVE PRESSURE OFFSET.

Notes:

EAV-BW110c ROOM BW110C CV 10 [ 250 ] 950 [ 450 ] 1000 [ 470 ] 1.2 [ 300 ] ELEC BACNET CONSTANT EXHAUST 1

TAB-BW110 ROOM BW110 CV 8 [ 200 ] 430 [ 200 ] 600 [ 280 ] 1 [ 250 ] ELEC BACNET CONSTANT SUPPLY -

IN [mm] CFM [L/s] CFM [L/s] IN WG [Pa]

MARK LOCATION TYPE

SIZE DESIGN AIR FLOW MAX AIR FLOW APD AT MAX AIR FLOW

CONTROL TYPE CONNECT TO ECC APPLICATION NOTES

AIR FLOW CONTROL VALVE SCHEDULE

1. INSTALL REHEAT COIL DOWNSTREAM OF AIR CONTROL VALVE TAB-8W110.

Notes:

BW-HWC-110C ROOM 110C SEGREGATED COMPOUNDING REHEAT 430 [ 200 ] 700 [ 4 ] 0.2 [ 50 ] 0 [ -18 ] 55 [ 13 ] 11.8 [ 40 ] 1.2 [ ] 140 [ 60 ] 115 [ 46 ] 5 [ 15 ] 1

CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW] GPM [L/s] °F [°C] °F [°C] FT [kPa]

EAT LAT FLOW EWT LWT WPDMARK LOCATION AREA AND/OR BLDG SERVED APPLICATION

AIR FLOW MAX FACE VELOCITY APD

TEMPERATURES

TOTAL MIN CAPACITY

HOT WATER

REMARK

HEATING WATER COIL SCHEDULE

REVISION 1 07-30-19

S

SS

S S

SS

S S

S S

S

SS

S S

S S

S S

SS

S S

S S

J

K

L

M

N

P

R

T

12 13 14 15 16 17 18 19 20A 21 22

T

T

T

T

T T

T

T T

T

T

2"CHS

2"CHR

2"HHWR

2"HHWS

1 1/2"CHS

1 1/2"CHR

2"HHWR

2"HHWS

1 1/2"CHS

1 1/2"CHR

1 1/2"HHWR

1 1/2"HHWS

1 1/2"HHWR

1 1/2"HHWS

1 1/2"HHWR

1 1/2"HHWS

1 1/2"HHWS

1 1/2"HHWR

1 1/2"HHWS

1 1/4"HHWR

1 1/4"HHWS

1"HHWR

1"HHWS

1"CHS

1"CHR

1"HHWR

1"HHWS

1 1/2"CHS

1 1/2"CHR

3/4"HHWR

3/4"HHWS

3"HHWR

3"HHWS

OFFSET DOWN

BELOW BEAM (TYP)

1 1/2"HHWR

1 1/2"HHWS

1 1/2"CHR

1 1/2"CHS

1 1/2"CHS

1 1/2"CHR

1 1/2"HHWS

1 1/2"HHWR

1 1/2"HHWR

1 1/2"HHWS

1 1/2"CHR

1 1/2"CHS

"D

"D

1 1/2"HHWR

1 1/2"HHWS

1 1/2"CHR

1 1/2"CHS

1 1/2"HHWR

1 1/2"HHWS

1 1/2"CHR

1 1/2"CHS

1"D

1"CHR

1"CHS

1"D

FCU-8W14A

TU-8W19C

TU-8W17A

TU-8W17

TU-8W18F

H4-8W

FCU-8W18D

FCU-8W18C

FCU-8W18A

FCU-8W16

FCU-8W09

FCU-8W07

FCU-8W14

FCU-8W06

FCU-8W12

FCU-8W08

FCU-8W13

FCU-8W11

CORRIDOR

8CW01

CASE MANAGER

8W05

PROVIDER WORKROOM

8W07

FAMILY ROOM

8W09

VITALS

8W11

TOILET

8W11B

SCALE

8W11A

WAITING AREA

8W13A

CORRIDOR

8CW02

EXISTING OIT

8CW100

CORRIDOR

8CW01A

UTILITY ROOM

8W03

SERVICE CHIEF

8W06

EQUIP. ROOM

8W08

STAFF TOILET

8W12

STAFF TOILET

8W10 AUTHORIZED STAFF ONLY

8W14 CLEAN SUPPLY

8W14A

PHARMACY

8W19

CHEMO STOR.

8W19D

HAZARDOUS COMPOUNDING

8W19C

ANTEROOM

8W19B

NON-HAZARDOUS

COMPOUNDING

8W19A

EX. TOILET

8W25C

EX. NURSE STATION

8W25

EX. MEDICATION AND CLEAN

ROOM

8W25B

NURSES

STATION/AUTHORIZED

STAFF ONLY

8W13

SOILED HOLDING

8W15

PROCEDURE ROOM

8W17

TOILET

8W17A

CLINIC WORKROOM

8W18F

EXAM ROOM

8W18E

EXAM ROOM

8W18D

EXAM ROOM

8W18C

EXAM ROOM

8W18B

EXAM ROOM

8W18A

EXAM ROOM

8W16

STAIR

8ST04

PHARMACY HAC

8W20

HAC

8W21

ELECT.

8W04

HAC

8W02

EXISTING SHAFT

8SAW01

ELECT. CLOSET

8N01

ELEVATOR LOBBY

8CN01

EXISTING ELEVATOR LOBBY

8CS01

EXISTING PHARMACY

DUMBWAITER

8W01

ROOM

8S02

T T

T

T

T

T

T

T

CO

T

CO

T

2"HHWS

2"HHWR

1 1/4"CHR

1 1/4"CHS

CO

1/2"D

OFFSET

DOWN

T

CO

CO

FCU-8CW01A

FCU-8CW01B

3/4"HHWS

3/4"HHWR

3/4"CHR

3/4"CHS

3/4"D T

T T

TU-8W19

3/4" 3/4"

TU-8W19A

TU-8W19B

TU-8W19D

3/4"

3/4" 3/4"

3/4" 3/4" 3/4"

3/4" 3/4"

FCU-8CW100

TAB-8-13 TAB-8-12

1"D

EXISTING HHWS/R

PIPING

1/2"D

COORDINATE

LOCATION WITH

EXISTING ELECTRICAL

PANELS

3/4"CHR

3/4"CHS

3/4"HHWR

3/4"HHWS

FCU-8CN01

T

T

3/4"D

CO

CO

CO

EXISTING CHS/R

PIPING TO REMAIN

CO

M-401

M-301

M-301

T

1"D

1"D3/4"D

/4

"D

3/4"D

1"D

/4

"D

2"CHS

2"CHR

2"HHWR

2"HHWS

1"D3/4"D3/4"D

2"HHWS

2"HHWR

2"CHR

2"CHS

FCU-8W05

2"CHS

2"CHR

2"HHWS

2"HHWR

1"D

T

1 1/2"CHR

1 1/2"CHS

3/4"D

3/4"D

1"D

1"D

1"D

T

# KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

WALL RATING LEGEND

E

D C

B A

2 3 4 5 6 7

E D

C B

A

1 2 3 4 5 6 7

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

1-8W-

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

/3

/2

:3

:2

P

M

MP101

EIGHTH FLOOR MECHANICAL NEW

WORK PIPING PLAN

5 14RCM WRS

Renovate 8W for Hematology and Oncology

601 Highway 6 West, Iowa City, IA 52246

06/12/2019

100% CONSTRUCTION DOCUMENTS

636A8-18-00118-023

N

AREA OF WORK

KEY PLAN

SCALE: NO SCALE

BLDG. 1

Scale: 1/8" = 1'-0"

EIGHTH FLOOR MECHANICAL PIPING PLAN

01 1-1/2" DRAIN DOWN TO AIR GAP FITTING IN

CHASE. SEE 1-8W-P-102 FOR CONTINUATION.

02 EXISTING TO REMAIN.

03 VALVE AND CAP 1-1/2" HHWS, 1-1/2" HHWR,

1-1/2" CHS, AND 1-1/2" CHR PIPING.

04 CONNECT 3/4" HHWS, 3/4" HHWR, 3/4" CHS, 3/4"

CHR, AND 1/2" DRAIN PIPING TO NEW FCU.

TYPICAL ALL.

05 CONNECT DRAIN PIPING TO EXISTING DRAIN

RISER IN CHASE.

06 VALVE AND CAP 2-1/2" HHWS, 2-1/2" HHWR FOR

FUTURE CONNECTION.

07 1/2" INSULATED DRAIN PIPING DOWN ALONG

WALL TO ABOVE MOP BASIN. TERMINATE 1"

ABOVE RIM.

08 CONNECT NEW 3/4" CHS/R AND 3/4" HHWS/R TO

EXISTING 3/4" PIPING NEAR THIS LOCATION.

09 INSTALL THERMOSTAT AFTER NEW WALL

FINISH IS COMPLETED.

10 STEAM PIPE FROM HUMIDIFIER OUTLET TO

DISTRIBUTION TUBE IN DUCT TO CLEAN

SUPPLY 8W14A. SEE 1-8W-M-101.

0 4 8 16 NORTH

PLAN

A SHADED AREAS NOT IN SCOPE.

B DIAGONAL HATCH AREA DENOTES FUTURE

CONSTRUCTION.

REVISION 1 07-30-19

Sheets
M-101 - EIGHTH FLOOR MECHANICAL NEW WORK PLAN
M-601 - MECHANICAL SCHEDULES
M-602 - MECHANICAL SCHEDULES
MP101 - EIGHTH FLOOR MECHANICAL NEW WORK PIPING PLAN