4th Floor - Water Leak Damage Remediation - San Diego
Solicitation number
36E77618B0089
Issued by

About this file

36E77618B0089 0002 5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC.pdf

View the file

Other files

File Type Posted
36E77618C0039-000.docx DOCX document
36E77618B0089-0005000.docx DOCX document
36E77618B0089-0005001.docx DOCX document
36E77618B0089-0004001.docx DOCX document
36E77618B0089-0004000.docx DOCX document
36E77618B0089-0003000.docx DOCX document
36E77618B0089-0003001.pdf PDF
36E77618B0089-0003002.pdf PDF
36E77618B0089-0002000.docx DOCX document
36E77618B0089-0002004.pdf PDF
36E77618B0089-0002003.pdf PDF
36E77618B0089-0002001.pdf PDF
36E77618B0089-0001000.docx DOCX document
36E77618B0089-009.pdf PDF
36E77618B0089-005.pdf PDF
36E77618B0089-010.docx DOCX document
36E77618B0089-006.pdf PDF
36E77618B0089-008.pdf PDF
36E77618B0089-003.docx DOCX document
36E77618B0089-007.pdf PDF
36E77618B0089-004.pdf PDF
36E77618B0089-000.docx DOCX document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

151 Kalmus Drive, Suite F-4, Costa Mesa, California 92626 / P 714.547.4301 / F 714.547.4647 www.citadelenvironmental.com

September 4, 2015

Jorge Valdez Fire Protection and Life Safety Manager, Engineering Service

DEPARTMENT OF VETERAN AFFAIRS

3350 La Jolla Village Drive San Diego, California 92161

Re: CITADEL Project No. 5137.1182.0 Limited Moisture Investigation Report – Follow Up Assessment Date of Moisture Intrusion Event: August 7, 2015

VA San Diego Medical Center Floors 4W, 3W, 2W, 1W and Basement Kitchen San Diego, California 92161

Dear Mr. Valdez:

Enclosed please find a copy of the Limited Moisture Investigation Report prepared by Citadel Environmental Services, Inc. All work was conducted in accordance with Client-established protocols.

If after your review you have any questions or require additional information, please do not hesitate to telephone me at the Citadel Office in Costa Mesa at 714.547.4301.

Sincerely, CITADEL ENVIRONMENTAL SERVICES, INC.

Michelle Campbell, CMC, CDPH, CAC Certified Industrial Hygienist 10776 CP Director, Industrial Hygiene, Occupational Safety and Training

Enclosure

DEPARTMENTOFVETERANAFFAIRS
VASANDIEGOHEALTHCARESYSTEM,
3350LaJollaVillageDrive
SanDiego,California92161
LimitedMoistureInvestigationReport‐Follow
UpInvestigation

September 4, 2015

Citadel Project Number 5137.1182.0

VASanDiegoMedicalCenter
DateofMoistureIntrusionEvent:August7,2015
Floors4W,3W,2W,1WandBasementKitchen
3350LaJollaVillageDrive
SanDiego,California92161

CITADEL PROJECT NO. 5137.1182.0

LIMITED MOISTURE INVESTIGATION REPORT – FOLLOW UP INVESTIGATION

VA SAN DIEGO MEDICAL CENTER

3350 LA JOLLA VILLAGE DRIVE

SAN DIEGO, CALIFORNIA

SEPTEMBER 4, 2015

Table of Contents

1.0 BACKGROUND

2.0 SCOPE OF SERVICES

3.0 FIELD AND ANALYTICAL METHODOLOGY

4.0 OBSERVATIONS

7.0 DISCLAIMER AND LIMITATIONS

8.0 SIGNATURES

APPENDICES

Field Documentation ........................................................................................................................... …… A Photographic Documentation………………………………………………………………………………… B

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 1

1.0 BACKGROUND

Citadel Environmental Services, Inc. (“Citadel”), was contracted by the Veterans Administration San Diego Healthcare System (VASDHS) (the “Client”), to provide moisture consulting services in conjunction with a large scale moisture intrusion event impacting several areas on the west wing, Basement through Fourth Floor, of the Veterans Administration San Diego Medical Center (VASDMC), Building #1 (the “Building”).

Citadel conducted an initial emergency response assessment on August 7 and 8, 2015, after a fire sprinkler located inside the 4-West (4W) DLO Project Area was damaged just after midnight on August 7, 2015. The water from the flood traveled down to the lower floors via interstitial floor spaces (INT) to 3-West (3W), 2-West (2W), 1-West (1W), Stairwell 1 and the Basement Kitchen.

Citadel provided a summary of moisture measurements, observations and subsequent recommendations for remediation via a written report1, submitted via email on August 11, 2015.

Citadel was then asked by the Client to perform a follow-up moisture assessment of all affected areas on August 13, 2015. The objective of the follow up assessment was to document moisture levels of affected drywall materials and to ensure all affected areas were inspected and recommendations for remediation provided.

2.0 SCOPE OF SERVICES

Citadel Environmental Services, Inc. (Citadel) was contacted by Veterans Administration San Diego Healthcare System (VASDHS) (the “Client”) to provide moisture consulting services.

The scope of the investigation included:

1) Performing a follow up assessment, limited to impacted areas of 4W, 3W, 3W-INT, 2W, 2W- INT, 1W, 1W-INT and the Basement Kitchen, to document moisture levels and to inspect for visible signs of suspect microbial growth that may have developed in the 7 days since the moisture intrusion event occurred; and

2) Providing a written report to include all field documentation, moisture maps, photographic documentation, observations, methodologies and recommendations for the remediation.

Citadel’s Field Representative, Mr. Josh Hoover, conducted the follow up investigation from August 14 through August 31, 2015. Mr. Hoover is a California-Certified Site Surveillance Technician (CSST #14-5288). All work was performed under the general supervision of Ms. Michelle Campbell, an ABIH Certified Industrial Hygienist (CIH #10996 CP) and Certified Asbestos Consultant (CAC#09- 4519).

1 Refer to Citadel’s Limited Initial Moisture Investigation Report dated August 11, 2015

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 2

3.0 FIELD AND ANALYTICAL METHODOLOGY

Moisture Investigation

Citadel conducted visual inspections for signs of visible moisture damage and/or suspect microbial growth (SMG). The visual inspections were performed on August 14 and 17, 2015, and were limited to the following moisture-impacted areas of the Basement, 1W, 2W, 3W and 4W.

Citadel also conducted visual inspections of the 1W-INT, 2W-INT and 3W-INT floors.

In moisture-impacted areas, Citadel employed the use of a pin-type moisture meter (Delmhorst BD-2100) and a FLUKE® TiR infrared camera to check potentially impacted surfaces for relative moisture content. Materials were considered wet or impacted if their moisture content was greater than that of like materials from non-impacted areas of the building.

The Delmhorst uses two pin electrodes to detect differences in the capacitance of the signal to determine water content when the pins are inserted into the material so that they penetrate the surface of building materials. The FLUKE® TiR infrared camera is a non-contact device that detects infrared energy and converts the measurements to temperature readings. The camera then converts those temperature measurements into a thermal image on a video monitor which may also be saved as a jpg image.

The Delmhorst is designed to measure moisture levels in wood, concrete, EIFS, sheetrock, and other materials. It has a 6-40% moisture range for wood, a 0.2-50% range for gypsum and a 0 to 100 relative scale for all other non-wood materials. Regarding Sheetrock, readings below 0.5% indicate a dry condition, those between 0.5% and 1% correspond to borderline conditions, and readings over 1% indicate wet conditions. Elevated readings may represent ambient humidity, minor moisture intrusion, or the current status of a material previously wetted that has since partially dried out.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 3

4.0 OBSERVATIONS

Follow Up Investigation

The following visual observations (Table 1.0) were made at the time of the follow up investigation performed August 14 through August 31, 2015. Field documentation is presented in Appendix A.

Table 1.0 Summary of Visual Observations, August 14-31, 2015.

Location Moisture (%) Observations

Recommendations0F

FOURTH FLOOR

Corridor

Drywall:

1.1 – 8.2

IR Camera Used

Elevated moisture measurements were indicated for the following areas:

o N, S, E and W walls:

extending up from the floor approx. 1 foot (1F) for approx. 84 linear feet (84 LF).

Refer to Table 1.0 of Initial Investigation Report

Nuclear Room - Conference Room 4513

Drywall:

0.1 – 11.9 for the following areas:

o N and E walls:

extending up from the floor approx. 1F.

o S and W walls noted to be previously wet by dry at this time.

o Glue down carpet was saturated, now dry.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 4

Medicine Room 4506

Drywall:

0.8 – 8.8 for the following areas:

o N and E walls:

extending up from the floor approx. 1F for approx. 12 LF on N wall and 14 LF on E wall.

Refer to Table 1.0 of Initial Investigation Report

Corridor

Drywall:

0.9 – 19.1 for the following areas:

o N, S, E and W walls:

extending up from the floor approx. 1F for approx. 140 LF.

Room 4040 Drywall:

0.4 – 4.8 (limited access)

During follow up inspection, unable to view lower walls because of UEI equipment.

Medicine Room 4501

Drywall:

6.3 – 11.1 for the following areas:

o S wall: extending up from the floor approx.

1F for approx. 8 LF.

Medicine Corridor 4039A

7.7 – 25.9 for the following areas:

o N, S, E, and W walls and SE wall at ceiling:

extending up from the

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 5 approx. 8 LF.

Medicine Room 4505

Drywall:

0.1-12.1 for the following areas:

o E wall: extending up from the floor approx.

1F for approx. 70 LF.

o N, W and S walls noted to be dry.

Refer to Table 1.0 of Initial Investigation Report

Nuclear Medicine Corridor

Drywall:

0.1-6.4 for the following areas:

o E and W walls:

extending up from the floor approx. 1F for approx. 70 LF.

o S, NW and SW walls noted to be dry.

Glue down carpet saturated.

Refer to Table 1.0 of Initial Investigation Report

Room 4069 Drywall:

0.3 – 7.3 for the following areas:

o N and W walls:

extending up from the floor approx. 1F for approx. 18 LF.

o S and E walls noted to be dry at this time.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 6

Room 4066 Drywall:

1.1 – 16.9 for the following areas:

o N, S, E and W walls:

extending up from the approx. 35 LF.

Room 4070 Drywall:

0.1 – 14.7 for the following areas:

o N and W walls:

extending up from the floor approx. 1F for approx. 15 LF.

o S and E walls noted to be dry at this time.

Room 4070C Drywall:

0.1 – 20.2 for the following areas:

o East central divider and N walls:

extending up from the floor approx. 1F for approx. 12 LF.

o S and W walls noted to be dry at this time.

Room 4070A Drywall:

2.1 – 12.2 for the following areas:

o N, S, E and W walls:

extending up from the approx. 32 LF.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 7

Drywall:

3.9 – 5.4

No access.

Refer to Table 1.0 of Initial Investigation Report.

Room 4059 Drywall:

0.2 – 0.4

No elevated moisture measurements indicated.

Refer to Table 1.0 in the Initial Investigation Report.

Room 4520 Drywall:

2.7 – 3.2 for the following areas:

o N, S, E and W walls:

floor approx. 1F.

Refer to Table 1.0 in the Initial Investigation Report.

Room 4035 Drywall:

0.3 – 8.0 for the following areas:

o S and W walls:

extending up from the floor approx. 1F.

o N and E walls found to dry.

Remove the drywall materials extending up from the floor three (3) feet in the following areas:

o S and W walls; and o Continue to remove two (2) feet past last visible SMG.

Clean non-porous materials with an approved anti-microbial/anti-bacterial cleaning agent.

Room 4032 Drywall:

No further recommendations.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 8

Room 4078A Drywall:

0.1- 0.4

Glue down carpet stained/saturated.

Remove wet carpet.

Medical Library 4078/4078A

0.1 – 0.5 measurements indicated during the follow up inspection.

Carpet stained but dry at time of inspection.

Remove bookshelf along west wall and inspect building materials for water damage and SMG

Remove moisture stained carpet

Room 4514 Drywall:

Room 4515 Drywall:

N/A

N/A.

Room 4516 Drywall:

0.2 – 0.3

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 9

Room 4517 Drywall:

N/A.

Room 4518 Drywall:

Room 4518A Drywall:

Mild odor noted.

Room 4519 Drywall:

Mild odor noted.

Restroom

0.1 – 0.3

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 10

Room 4511 Drywall:

Room 4510 Drywall:

Room 4508 Drywall:

Room 4507 Drywall:

0.2

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 11

Room 4503 Drywall:

Room 4502 Drywall:

Room 4060 Drywall:

Room 4062 Drywall:

Room 4064 Drywall:

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 12

Room 4066 Drywall:

0.6 – 7.8 for the following areas:

o N, S, E and W walls.

Refer to Table 1.0 in Initial Investigation Report.

Tile walls

Drywall:

0.2 – 0.4

Drywall:

0.2 – 0.4

Room 4070D Drywall:

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 13

Drywall:

Tile walls

4070B

Room 4076 Refer to Corridor 4053

Part of Corridor 4053 Refer to Corridor 4053.

Room 4068 Drywall:

Toilet 4067 Drywall: All

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 14

Room 4050 N/A Room identified on floor plan but Citadel not able to locate.

N/A

Corridor 4039A, Rooms 4040, 4041, 4043, 4044, 4045, 4045A, 4045B, 4046, 4046A, 4047, 4048, 4049, 4049B

0.4 – 4.8

These rooms were recently demolished in conjunction with the 4W DLO project and no longer exist.

No SMG observed in work area.

Remove all remaining drywall materials, continuing two (2) feet past last visible signs of SMG and/or elevated moisture.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 15

THIRD FLOOR

Room 3046 Drywall:

6.5 – 12.7

Elevated moisture measurements were indicated for the following areas:

o Around upper window areas.

Remove the drywall materials in the following areas:

o Upper window areas; and o Continue to remove two (2) feet past last visible SMG.

Room 3046A Drywall:

9.6 – 14.2 areas:

o S wall: extending up from the floor approx.

10F for approx. 22 LF.

Room 3048 Drywall:

4.6 – 14.2 areas:

o N, W and E walls and NE wall at ceiling: extending down approx. 1F for approx. 35 LF.

Remove the drywall materials extending down from the ceiling three

(3) feet in the following areas:

o N, W and E walls;

o NE wall at ceiling; and o Continue to remove two (2) feet past last visible SMG.

Room 3060 Drywall:

0.1 – 0.5 areas:

o Follow up inspection found N, E and W walls wet: extending up from the floor to the ceiling for approx. 28 LF.

Room 3058 Drywall:

1.7 – 15.1

IR Camera Used

Elevated moisture measurements were indicated for the following areas:

o Follow up inspection found S and E walls, and

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 16

SW wall at ceiling wet:

floor approx. 1F for approx. 42 LF.

o 6 inches SMG observed.

Room 3058 Restroom

Drywall:

14.0 – 22.0 areas:

Room 3063 Drywall:

1.7 – 14.1 areas:

o Follow up inspection found N, and W walls wet: extending up from the floor approx. 1F for approx. 122 LF; and o Upper NW corner wet.

Room 3063A Drywall:

2.2 –17.4 areas:

o S wall; extending down from the ceiling 1F for length of wall.

0.3 – 22.5 areas:

o Walls outside rooms 3063A, 3056 and 3064:

extending up from the floor approx. 1F; and o SMG observed of approx. 6 inches on N wall.

o Walls of outside rooms 3063A, 3056, and 30654; and o Continue to remove two (2) feet past last visible SMG.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 17

Room 3056 Drywall:

2.2 – 15.1 areas:

o S, N, W walls: extending up from the floor approx.

8F for approx. 128 LF.

Room 3055 Drywall:

0.8 – 18.6 areas:

o N, S, E and W walls:

extending up from the floor approx. 1F for approx. 40 LF; and o Ceiling visibly wetted.

Remove the drywall materials extending up from the floor approximately three feet in the following areas:

o N, S, E and W walls;

o Entire ceiling; and o Continue to remove two (2) feet past last visible SMG.

Room 3065 Drywall:

1.2 – 17.1 areas:

o Follow up inspection found N and E walls wet:

extending up from the floor approx. 6F for approx. 38 LF; and o N central walls wet.

Remove the drywall materials extending up from the floor to ceiling in the following areas:

o N and E walls; and o Continue to remove two (2) feet past last visible SMG.

Room 3066 Drywall:

1.8 – 7.2 areas:

o N, S and W walls extending up from the approx. 46 LF.

o N, S and W walls; and o Continue to remove two (2) feet past last visible SMG.

Room 3053 Drywall:

0.8 – 7.6 areas:

o Follow up inspection found N, S and E walls wet: extending up from

Remove the drywall materials extending up from the floor to ceiling in the following areas:

o N, S, and E walls; and o Continue to remove two (2) feet past last visible SMG.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 18 the floor approx. 8F for approx. 20 LF.

Room 3053

Drywall:

0.8 – 7.6

Remove the drywall materials extending up from the floor to the ceiling in the following areas:

o N, S, E and W walls; and o Continue to remove two (2) feet past last visible SMG.

Room 3051 Drywall:

7.1 – 12.5 areas:

o Follow up inspection found S and E wall corners wet: extending

8F for approx. 42 LF.

Remove the drywall materials extending up from the floor to the ceiling in the following areas:

o S and E walls; and o Continue to remove two (2) feet past last visible SMG.

Room 3067 Drywall:

0.8 – 7.4 areas:

o N and S walls: extending

8F for approx. 42 LF.

Remove the drywall materials extending up from the floor to ceiling in o N and S; and o Continue to remove two (2) feet past last visible SMG.

Room 3068A Drywall:

Room 3068B Drywall:

Room 3067A Drywall:

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 19

Room 3078 Drywall:

0.8 – 4.7 areas:

o Follow up inspection found N wall wet:

extending up from the approx. 28 LF.

Staff Restoom Adj. to Room 3080

Drywall:

IR Camera Used

Elevated moisture measurements were indicated for the following areas:

o Hard lid ceiling: entire ceiling; and o E wall; extending down from the ceiling 1F for length of wall.

Remove the drywall materials in the following areas:

o Entire hard lid ceiling; and o Continue to remove two (2) feet past last visible SMG.

Remove the drywall materials extending up from the floor three (3) feet in the following areas:

o E wall;

bacterial cleaning agent

Room 3080 Drywall:

2.2 – 7.8

IR

Camera areas:

o W wall: extending up from the floor approx. 10F for approx. 22 LF.

Remove the drywall materials extending up from the floor twelve (12) o W wall; and o Continue to remove two (2) feet past last visible SMG.

Room 3080A Drywall:

IR

Room 3080B Drywall:

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 20

Room 3074 Drywall:

Room 3076 Drywall:

Room 3074A Drywall:

Room 3073 Drywall:

Room 3083 Drywall:

4.2 – 8.7

IR

areas:

o Follow up inspection found no elevated moisture measurements indicated.

2.1 – 8.9 areas:

Remove the drywall materials extending up from the floor twelve (12) o Continue to remove two (2) feet past last visible SMG.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 21

Outside Rooms 3069 and

IR

o Outside rooms 3069 and 3078: extending up from the floor approx. 10F for approx. 22 LF.

Room 3075 Drywall:

Room 3088 Drywall:

Room 3085 Drywall:

Room 3084 Drywall:

Room 3046A Drywall:

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 22

Room 3046B Drywall:

Room 3040

Room 3041 Drywall:

Room 3039 Drywall:

Room 3038 Drywall:

Room 3037 Drywall:

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 23

Room 3036 Drywall:

Room 3035 Drywall:

Room 3034 Drywall:

Room 3033 Drywall:

Room 3033B Drywall:

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 24

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 25

SECOND FLOOR

Room 2058 Drywall:

0.1 0.4

IR

areas:

o Follow up inspection found NW and SW wall at ceiling wet.

Remove drywall materials extending down from the ceiling six (6) feet in the following areas:

o NW and SW walls; and o Continue to remove two (2) feet past last visible SMG.

bacterial cleaning agent

Room 2058 areas:

o Follow up inspection found SE wall at ceiling wet approx. 1F for approx. 14 LF.

Refer to Table 1.0 of Initial Investigation Report.

Remove drywall materials extending down from the ceiling three (3) feet in the following areas:

o SE and W walls; and o Continue to remove two (2) feet past last visible SMG.

Room 2061 Drywall:

3.2 – 4.1

IR

areas:

o Follow up inspection found N, S, and W walls wet; extending down from the ceiling approx.

4F for approx. 4 LF; and o SE wall is wet from ceiling to floor.

Remove the drywall materials extending down from the ceiling six (6) feet in the following areas:

o N, S, SE and W walls; and o Continue to remove two (2) feet past last visible SMG.

Room 2062 Drywall:

3.2 – 16.4

IR

areas:

o Follow up inspection found N, S, E and W walls wet;

o N wall, SE and SW corners wet from ceiling to floor;

and

Refer to Table 1.0 of Initial Investigation Report.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 26 o Carpet dry.

Room 2056 Drywall:

0.3 – 8.2

IR

areas:

o Follow up inspection found S and W walls wet;

extending down from the ceiling approx. 1F for approx. 10 LF; and o SMG observed on S wall.

Room 2054 Drywall:

Room 2054

Drywall:

IR

Room 2052 Drywall:

Room 2052 Restrooms

Drywall:

IR

Room 2050 Drywall:

1.2 – 4.3 areas:

Refer to Table 1.0 of Initial Investigation Report.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 27 o Follow up inspection found N, E, and W walls wet: extending down approx. 1F for approx. 2 LF; and o SW upper wall at ceiling wet.

Room 2050

Drywall N/A

IR

Camera

Elevated moisture measurements were indicated for the following areas:

o Follow up inspection found S wall at ceiling wet; extending down approx. 1F for approx. 3

LF.

Drywall:

3.0 – 21.1

IR

areas:

o Follow up inspection found N, S, W and E walls wet; and o Upper walls outside of Rooms 2056 and 2062 extending approx. 6 F to approx. 9 LF

Room 2063 Drywall4.

4.2 – 16.1

IR

areas:

o Follow up inspection found S and W wall wets:

extending down approx.

1F for approx. 2 LF.

Room 2064 Drywall:

0.4 – 0.9

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 28 o Follow up inspection found N, S, E, and W walls wet; and o SE upper wall corners:

and extending down from the ceiling approx.

4F for approx. 2 LF.

Room 2049 Drywall:

0.2 0.4

IR

areas:

o Follow up inspection found NE wall at ceiling wet approx. 2 F for approx. 4 LF.

Remove the drywall materials extending down from the ceiling approx. three (3) feet in the following areas:

o NE wall.

Room 2068 Drywall:

2.2 – 8.0

IR

areas:

o N and W walls: extending up from the floor approx.

1F for approx. 36 LF; and o NW wall at ceiling:

extending down from the ceiling approx. 1F for

Room 2067 Drywall:

Room 2069 Drywall:

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 29

Room 2047 Drywall:

Room 2046 Drywall:

- Outside Room 2111

- Outside Room 2113

7.0 – 19.8

3.1 – 20.8 areas:

o S wall outside 2111:

extending up from the floor approx. 1F for approx. 8 LF;

o S wall outside 2113:

extending up from the floor approx. 1F for approx. 4 LF; and o Multiple wet 1F x 1F ceiling panels

Room 2096 Drywall:

Room 2094 Drywall:

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 30

Room 2090 Drywall:

6.4 – 6.6

IR

areas:

o Follow up inspection found East central wall at ceiling wet: extending down approx. 2F for approx. 2LF.

Room 2108 Drywall:

IR

Elevated moisture observed with IR camera for the following areas:

o Hard Lid Ceiling at Sprinkler Head adj. to door: approx. 2 square feet (2 SF)

Room 2111 Drywall:

areas:

o E upper wall at ceiling:

extending down from the approx. 2 LF.

Room 2113

0.7 – 9.0

IR

areas:

o Follow up inspection found NW wall at ceiling wet: extending down approx. 1F for approx. 1 LF; and o E central wall.

o N upper wall o NW wall at ceiling;

o E central wall; and o Continue to remove two (2) feet past last visible SMG.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 31

Drywall:

IR

Drywall:

IR

Elevated moisture observed for o Ceiling tiles o N. S, E and W walls; and o Continue to remove two (2) feet past last visible SMG.

Remove the drywall materials extending down from the ceiling two

(2) feet in the following areas:

o Ceiling tiles; and o Continue to remove two (2) feet past last visible SMG.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 32

FIRST FLOOR

Outside Room 1229

Drywall:

1.4 – 6.9

IR

areas:

o E wall outside room 1229S:

extending up from the approx. 14 LF.

Room 1230 Drywall:

1.0-10.2

IR

areas:

o E lower and NW lower walls; extending down from the ceiling approx.

1F for approx. 4 LF.

Room 1229 Drywall:

0.1 – 0.4

IR

areas:

o NW upper wall: extending

4F for approx. 1 LF.

Room 1228 Drywall:

9.0 – 35.2

IR

areas:

o S and E walls: extending down from the ceiling approx. 1F for approx. 4

LF.

o S and E walls; and o Continue to remove two (2) feet past last visible SMG.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 33

Drywall:

7.0 – 25.3

IR

areas:

o W wall.

Room 1226 Drywall:

o Ceilings and walls.

o Ceiling and walls; and o Continue to remove two (2) feet past last visible SMG.

Room 1231 Drywall:

1.0 – 3.8

IR

areas:

o S and W walls: extending down from the ceiling approx. 1F.

Remove the drywall materials extending down three (3) feet in the following areas:

o S and W walls; and o Continue to remove two (2) feet past last visible SMG.

Room 1231A Drywall:

0.2 –0.4

IR

areas:

o SE wall at ceiling:

extending down from the

Remove the drywall materials extending down three (3) feet in the following areas:

o SE wall at ceiling; and o Continue to remove two (2) feet past last visible SMG.

Room 1220 Drywall:

Drywall:

IR

Camera Used

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 34

Room 1242 Drywall:

o SE wall at ceiling.

Multiple stained ceiling tiles.

Remove the drywall materials extending down three (3) feet in the following areas:

o SE wall at ceiling; and o Continue to remove two (2) feet past last visible SMG.

Clean non-porous materials with an approved anti-microbial/anti-

Remove stained ceiling tiles.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 35

BASEMENT

B-125

Drywall:

4.0 – 13.5

IR

areas:

o NW lower wall: extending up from the floor approx.

1F for approx. 16 LF; and o NW upper wall: extending down from ceiling approx. 1F for approx.

1LF.

Multiple wet ceiling panels.

(3) feet in the following areas:

o NW upper wall; and o Continue to remove two (2) feet past last visible SMG.

Clean non-porous materials with an approved anti-microbial/anti-

Remove wet ceiling panels.

Room B134 Drywall:

3.0 – 18.9

IR

areas:

o N, S, E and W walls:

extending up from the floor approx. 1F for approx. 72 LF; and o Carpet tiles saturated.

Corridor B-

Drywall:

3.0 – 6.4

IR

areas:

o E wall: extending up from the floor approx. 1F for approx. 6 LF.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 36

Table Notes

Background drywall moisture measurements ranged: 0.1-0.4%

STAIRWELL 1

Stairwell 1From 4th floor to Ground floor

Drywall:

0.2 – 0.4

IR

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 37

Interstitial Floor Spaces

In addition to assessing occupied areas of the VASDMC, Citadel conducted a walkthrough inspection of the interstitial floor spaces as follows: 1W-INT; 2W-INT, and 3W-INT. The following observations were noted:

3W-INT: No visible moisture using IR camera and no visible signs of SMG observed;

2W-INT: No visible moisture using IR camera and no visible signs of SMG observed; and 1W-INT: No visible moisture using IR camera and no visible signs of SMG observed.

General Recommendations for the Remediation of Moisture-Impacted Materials

The following recommendations pertain to the removal of moisture-damaged and/or microbial-impacted building materials:

Removal of moisture-impacted and/or microbial-impacted materials should be performed in accordance with standard industry practice (IICRC S500 Standard & Reference Guide for Professional Water Damage Restoration & IICRC S520 Standard & Reference Guide for Professional Mold Remediation), by an experienced remediation contractor, utilizing negative pressure containment(s).

Consult the VASDMC O & M Program to identify asbestos-containing materials and their location.

All asbestos removal operations shall be performed by a Cal/OSHA-DOSH-registered and California-licensed asbestos contractor. All disturbances of asbestos-containing materials, and/or abatement operations, should be performed under the surveillance of a third-party Cal/OSHA Certified Asbestos Consultant retained by the Client.

All disturbances of asbestos-containing materials, and/or abatement operations, must be performed in accordance with the Cal/OSHA requirements set forth in 8 CCR 1529. Given the location of the subject facility, all asbestos abatement must also be performed in accordance with San Diego Air Pollution Control District (SDAPCD) requirements.

Finally, notification of the presence and location of asbestos-containing materials shall be made to all employees and vendors who work within the VASDMC, in accordance with California Health and Safety Code, Section 25915, et seq. (also known as Connelly Notification Bills).

Please note that the actual scope of work is subject to change based on actual field conditions once intrusive work (removing drywall, etc.) is completed.

Contact Citadel for final visual inspection, air monitoring (asbestos) and swab sampling (sewage indicator organisms - as deemed necessary) prior to releasing areas for occupancy.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 38

7.0 DISCLAIMER AND LIMITATIONS

This report has been prepared by Citadel Environmental Services, Inc. exclusively for our Client and their Authorized Representatives. The information contained herein pertains only to accessible materials reported by the Client to be present at the referenced property which were surveyed and assessed in accordance with a mutually agreed upon scope of work. The findings and recommendations presented are based upon observations of present conditions, and may not necessarily indicate future conditions. Citadel Environmental Services, Inc. implies no warranty to the accuracy of information provided them by the Client or outside agents and transmitted herein. The information contained herein may not be used, disclosed, or copied without written permission of the Client.

Reasonable effort was made by Citadel personnel to locate suspect microbial growth. However, for any facility the existence of unique or concealed microbial growth is a possibility. Conditions of microbial growth can change in short periods of time due to water intrusion, environmental conditions and other factors. Results of this report represent the conditions at the time of the investigation only. Citadel does not warrant, guarantee or profess to have the ability to locate or identify all microbial contamination in a facility.

3350 LA JOLLA VILLAGE DRIVE

5137 1182 0_VASD_4W_DLO_Sprinkler_Break_Second_Assessment_MLC|VASDHS 39

8.0 SIGNATURES

All work was conducted in accordance with Client-established protocols, and the standards of care and diligence normally practiced by recognized consulting firms in performing services of a similar nature.

Work Completed By:

[Signature available on field documentation]

Josh Hoover, MS, CSST Field Representative

[Signature available on field documentation]

Chris Roberts, CAC Senior Industrial Hygienist

Report Prepared By:

[Signature available on field documentation]

Chris Roberts, CAC Senior Industrial Hygienist

Report Reviewed By:

Michelle Campbell, CMC, CDPH, CAC Certified Industrial Hygienist #10996 CP Director, Industrial Hygiene, Occupational Safety and Training Services

Appendix A

&ÉÅÌÄ.$ÏÃÕÍÅÎÔÁÔÉÏÎ

Scanned by CamScanner

C ITA D D; NV RO NM I NTA I SERV C ES

INC

DA LY PRO JECT DO C UM ENTA TIO N

C LIENT VA S a n Die go PA G E O F

PRO J EC T N UM BER 5 13 7 1 18 2 0

' ' " V E ' - C e t Ho Z

PRO J EC T N A M E IH C o n t r a c t C O NTRA C TO R

PRO J EC T W O RK

A REA

PRO JEC T

SUPERV ISO R

LO C A TIO N

J o lla v Ma ge D r S ä n

TIM E (M IUTA RY) FIELD N O TES

A f / 2 7

£ l L / M C « } 5 ) " s ¢OT T C O» 5 »w 6 a 2 Z 1 5 o u T ++ p W

3 0 1 t w N E 1 0 N ) "

T Fo T T ¬ þ * L t

[ Cò?A/ T 7 { l3oó7 A' t S

1 ' Z 7 , m l50 b 7 l i? - an 1 R = H M

C ITA D EL REPRESENTA TIV E DA Y F A W

s IG N A T u R 220 1o

" U

\ DI NV RO NM ENTA L SERV C ES NC

DA ILY PRO JEC T DOC UM ENTA TIO N 1 áz/ $

Cp DH Co F1 N o 2

PRO JEC T N A M E 1H C o n t r a c t RA C TO R

PRO J EC T W O RK

A REA

PRO JEC T SU PERV ISO R

LO C A TIO N

3 3 5 0 La J o lla V i lla g e D r S ä n

TIM E (M IUTA RY) FIELD N O TES

A / -u w l ç T c v u s I T T

O Tn o 11 8 · K f D 1¢ ? F a we ¢

' W s l e J ò KETI EI v Æ t ó W E

Br i c K 6 - ô o o .

T( / æ r '

1 > ¥ r BZo d u E To V / í M Ç E m w s + m u Ê r l mr t t ¬ æ l Å j j l ï >

目甚目 E ) 了 1 四四 h ノW t 5 · / V

吻万周 田园 Z t l 匡招商阴

Vù 1 ö AÌ T W 3 , \ tq , a s E

* , 1 . m

ÆÞ O w 9 3 . ? - s , £

Bærc pn t t w w y - w m 1 m n ñ n r te y

C ITA D EL REPRESENTA TIV E

- J £

引 G N A T U

Re v b e d Ju v

] > y / 7 /

Ic ITA D EL EN V IRo NM ENTA L SERv Ic Es 1Nc RN.DA ILY PRO J ECT DO C UM ENTA TIO N W g/ å_

C LIENT

PRO J EC T W O RK

A REA

PRO JEC T JSUPERV ISO R

LO C A TIO N

TIM E (m r し wA RN L FIELD N O TES r« Lz o w P

L £ / ALtAI . s W c û ìe Al z e t ì I W - u J£ P l ノ疋 S r ^ £ j< u Ý( i l ^ W £ T t (K rm M 4

, W 1 , Z V t / E , V , E - t e £ I L I × / m k - w u r

20 6 Z , U . m 3 . 2 / b V & 4 E S tu c e}- 5 C r ) L I¢ / $ T ô F ( Jò K r a W Æi n ¢ y l 2 ò あ乙 u u i { Ær ol F , n Ä ] - Fò t t >D f f YF , 3 , / W Þ

Y / 2 ö F 2 F ( A · m £] i l

巴星图Tb - 网中TDシ H 、 Å初 S ガノF {む炜ガ厂 5 B详 分 秒

メ疗/ Y勿之 ポ小シ么

C ITA D EL REPRESENTA TIV E

- 3 F<c N / » ¢e

SiG NA TURE

Re v Be d Ju ]y 1o lo W (V W

S ca nn ed b y

C am

S ca nn er nn ed b y

C am

S ca nn ed b y

C am

S ca nn er

口

一

燃 canned by C am canner nn ed b y

C am

S ca

Appendix "

0ÈÏÔÏÇÒÁÐÈÉÃ.$ÏÃÕÍÅÎÔÁÔÉÏÎ

VASD 4W Flood Remediation Project Citadel Project No. 5137.1182.0

Limited Moisture Investigation 2nd Assessment Floors 4W, 3W, 2W, 1W & Basement Kitchen San Diego, California

PHOTO A: Room 4066 (08-31-15) View of west wall (elevated moisture detected). PHOTO B: Room 4069 (08-31-15)

View of east and south walls (dry condition noted).

PHOTO C: Room 4069 (08-31-15) View of West wall (elevated moisture detected).

PHOTO D: Room 4078A (08-18-15) View of stained/saturated glue down carpet.

PHOTO E: Room 4500 (08-14-15)

View of saturated glue down carpet. PHOTO F: Room 4513 (08-14-15) View of glue down carpet (dry condition noted).

San Diego, California

PHOTO G: Room 3046 (08-19-15) View of stained ceiling panel noted around upper window areas.

PHOTO H: Room 3058 (08-14-15) View of southwest wall at ceiling (elevated moisture detected).

PHOTO I: Room 3060 (08-14-15)

View east wall (elevated moisture detected).

PHOTO J: Room 3060 (08-14-15) View of west wall (elevated moisture detected).

PHOTO K: Room 3063 (08-14-15)

View of south and west walls (elevated moisture detected).

PHOTO L: Room 3065 (08-14-15) View of north central walls (elevated moisture detected).

San Diego, California

PHOTO M: Room 2050 (08-14-15) View of south wall (elevated moisture detected).

PHOTO N: Room 2056 (08-14-15) View of suspect microbial growth (SMG) noted on south wall.

PHOTO O: Restroom 2058 (08-14-15)

View of east wall (elevated moisture detected).

PHOTO P: Room 2062 (08-14-15) View of south wall (elevated moisture detected).

PHOTO Q: Room 2064 (08-17-15)

View of southeast upper wall (elevated moisture detected).

PHOTO R: Corridor 2108 (08-17-15) View of wet ceiling panels noted.

San Diego, California

PHOTO S: Room 1226 (08-17-15) View of water runoff from ceiling onto wall panels.

PHOTO T: Room 1229 (08-17-15) View of northwest upper wall (elevated moisture

PHOTO U: Room 1231 (08-17-15)

View of south and west wall (elevated moisture

PHOTO V: Room 1231A (08-17-15) View of southeast wall (elevated moisture detected).

PHOTO W: Corridor 1233 (08-17-15)

View of east wall (elevated moisture detected). PHOTO X: Room 1242 (08-17-15) View of multiple stained ceiling panels.

San Diego, California

PHOTO Y: Room B125B (08-18-15) View of multiple wet ceiling panels noted. PHOTO Z: Room B125B (08-17-15)

View of multiple wet ceiling panels noted.

PHOTO AA: Room B134 (08-17-15) View of carpet tiles saturated.

PHOTO BB: Room B134 (08-17-15) View of wet ceiling panels noted.

PHOTO CC: Corridor B140 (08-17-15)

View of east wall (elevated moisture detected). PHOTO DD: Corridor B140 (08-18-15) View of east wall (elevated moisture detected).

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 1

151 Kalmus Drive, Suite F-4 Costa Mesa, CA 92626

3350 La Jolla Village Drive, Floors 4W, 3W, 2W, 1W and Basement Kitchen, San Diego, CA Limited Moisture Investigation – Follow Up Assessment

Infrared Camera

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 2

IR002364.IS2

8/14/2015 8:08:27 AM

Visible Light Image

IR002365.IS2

8/14/2015 8:17:38 AM

IR002366.IS2

8/14/2015 8:33:28 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 3

IR002367.IS2

8/14/2015 8:45:43 AM

IR002368.IS2

8/14/2015 8:48:58 AM

IR002369.IS2

8/14/2015 9:05:47 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 4

IR002370.IS2

8/14/2015 9:07:19 AM

IR002371.IS2

8/14/2015 9:12:42 AM

IR002373.IS2

8/14/2015 9:49:11 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 5

IR002374.IS2

8/14/2015 9:58:49 AM

IR002375.IS2

8/14/2015 9:59:04 AM

IR002377.IS2

8/14/2015 10:28:22 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 6

IR002378.IS2

8/14/2015 10:31:03 AM

IR002379.IS2

8/14/2015 10:49:19 AM

IR002380.IS2

8/14/2015 10:49:59 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 7

IR002381.IS2

8/14/2015 11:06:00 AM

IR002382.IS2

8/14/2015 11:08:44 AM

IR002383.IS2

8/14/2015 11:23:18 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 8

IR002384.IS2

8/14/2015 11:23:25 AM

IR002385.IS2

8/14/2015 11:53:53 AM

IR002386.IS2

8/14/2015 12:56:46 PM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 9

IR002387.IS2

8/14/2015 1:10:57 PM

IR002388.IS2

8/14/2015 1:11:03 PM

IR002389.IS2

8/14/2015 1:37:00 PM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 10

IR002390.IS2

8/14/2015 1:41:24 PM

IR002391.IS2

8/14/2015 1:47:49 PM

IR002392.IS2

8/14/2015 1:48:01 PM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 11

IR002393.IS2

8/17/2015 8:29:57 AM

IR002394.IS2

8/17/2015 8:55:22 AM

IR002395.IS2

8/17/2015 9:01:07 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 12

IR002396.IS2

8/17/2015 10:02:28 AM

IR002397.IS2

8/17/2015 10:08:46 AM

IR002398.IS2

8/17/2015 10:18:29 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 13

IR002399.IS2

8/17/2015 10:51:04 AM

IR002400.IS2

8/17/2015 10:55:26 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 14

IR002411.IS2

8/18/2015 10:41:55 AM

IR002412.IS2

8/18/2015 10:42:59 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 15

IR002413.IS2

8/18/2015 10:45:43 AM

IR002415.IS2

8/18/2015 12:27:20 PM

IR002417.IS2

8/31/2015 10:32:42 AM

5137 1182 0_IR Camera Photos_Second_Assessment_MLC 16

IR002418.IS2

8/31/2015 10:39:02 AM

IR002420.IS2

8/31/2015 1:52:10 PM

2015-09-04T13:29:20-0700
Michelle Campbell
2015-09-04T13:29:42-0700
Michelle Campbell

File details come from the government source that posted it.