This is a moisture and mold evaluation report prepared by Terracon Consultants for VCI Builders regarding conditions at Lebanon National Cemetery in Lebanon, Kentucky, conducted on October 10-11, 2023. The evaluation covered three buildings: the Administration Building, Service Building, and Maintenance Building.
The investigation found significant issues in two buildings: The Administration Building's basement and southeast corner of the first floor showed elevated moisture levels, water damage, and fungal growth, with moisture levels up to 49.4% WME in the basement. The Service Building's attic exhibited elevated moisture levels of 13.3% WME, water damage, and fungal growth, with air samples indicating degraded indoor air quality from microbial growth. The Maintenance Building showed no significant moisture or mold issues. The report recommends determining water intrusion pathways, preparing remediation protocols, conducting restoration using trained workers, following ANSI/IICRC S520 standards for mold remediation, and performing post-restoration testing to verify effectiveness. Laboratory analysis confirmed the presence of various mold species including Cladosporium, Aspergillus, Acremonium, and Scopulariopsis in the affected areas.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Moisture and Mold
Evaluation Lebanon National Cemetery
20 State Highway 208
Lebanon, Kentucky 40033
October 31, 2023 | Report Number: N1237396
Prepared for:
VCI Builders, Inc.
Covington, Louisiana 70433
Prepared for:
Bluestone Coke, LLC
3500 35th Avenue North
Birmingham, Alabama
US USEPA ID No. ALD 000 828 848
611 Lunken Park Drive
Cincinnati, Ohio 45226
P (513) 321-5816
F (513) 321-0294
Terracon.com
Facilities | Environmental | Geotechnical | Materials I
October 31, 2023
VCI Builders, Inc.
56 Louis Prima Drive, Suite B
Covington, Louisiana 70433
Attn: Jordan Vandermeer
P (504) 684-4408
E Jordan.vandermeer@valiint.com
RE: Moisture and Mold Evaluation
Lebanon National Cemetery
20 State Highway 208
Lebanon, Kentucky 40033
Terracon Project No. N1237396
Dear Mr. Vandermeer, Terracon Consultants, Inc. (Terracon) is pleased to present the results of a moisture and mold evaluation conducted at the location referenced above. We appreciate the opportunity to provide services to you. If we can provide any additional environmental, occupational health, or safety-related services, please contact Brad Knipper at (513) 472-7027.
Sincerely, Terracon
Lem Weyer Bradley S. Knipper, M.S., CIH, CSP
Staff Scientist Senior Industrial Hygienist mailto:Jordan.vandermeer@valiint.com mailto:Jordan.vandermeer@valiint.com https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAA-nQ3PiYgrTLYmLrftvwCwhWvd41GYOd7 https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAA-nQ3PiYgrTLYmLrftvwCwhWvd41GYOd7
Moisture and Mold Evaluation | Report |
Lebanon National Cemetery | Lebanon, Kentucky
October 31, 2023 | Terracon Report No. N1237396
Facilities | Environmental | Geotechnical | Materials i
TABLE OF CONTENTS
EXECUTIVE SUMMARY ............................................................................................................................... I
PROJECT DESCRIPTION
1.1 Scope of Services
1.2 Standard of Care
SITE DESCRIPTION
EVALUATION CRITERIA
3.1 Visual Inspection
3.2 Moisture Measurement
3.3 Microbial Sampling
METHODS
4.1 Visual Inspection
4.2 Moisture Measurement
Infrared Imaging Moisture Meter
4.3 Microbial Sampling
Surface Sampling Air Samples for Total Fungal Structures
FINDINGS
5.1 Visual Inspection
5.2 Thermal Imaging
5.3 Moisture Measurement
5.4 Air Sampling
Administration Building Service Building Maintenance Building
5.5 Surface Sampling
CONCLUSIONS
RECOMMENDATIONS
LIMITATIONS
Appendix A: Photographs
Appendix B: Exhibits
Appendix C: Laboratory Reports
Moisture and Mold Evaluation | Report |
Lebanon National Cemetery | Lebanon, Kentucky
Facilities | Environmental | Geotechnical | Materials i
EXECUTIVE SUMMARY
Terracon Consultants, Inc. (Terracon) performed moisture and mold evaluation on October 10th and
11th for VCI Builders, Inc. at the Lebanon National Cemetery in Lebanon, Kentucky. The scope of the assessment included:
◼ Visual observations to document conditions.
◼ Infrared imaging to identify thermal anomalies that may indicate wet building materials
◼ Moisture measurement in building materials to confirm materials with elevated moisture content.
◼ Air samples for total fungal structures at indoor locations and at outdoor locations for comparison.
◼ Surface samples for microscopic examination and fungal culture analysis to document surface fungal growth.
◼ Report
Findings
◼ Administration Building: The basement and the southeast corner of the 1st floor have elevated building material moisture, and fungal growth on surfaces. Water damage was observed in the basement and southeast corner of the 1st floor. High moisture levels were also register in the basement during the evaluation.
◼ Service Building: The attic has elevated building material moisture and fungal growth on surfaces. Air samples indicate that the indoor air is being degraded by an indoor source of microbial growth. Water damage and elevated building material moisture levels were found in the attic.
◼ Maintenance Building: Air sampling indicates that the indoor air does not appear to be being degraded by an indoor source of microbial growth. Elevated moisture levels were not observed in the building materials of the of the building.
Recommendations
See report text for recommendations.
The report that follows this Executive Summary should be read in its entirety because it includes important information, such as more specific details about findings, regulatory requirements, and recommendations.
Moisture and Mold Evaluation | Report | Revision 1.0
Lebanon National Cemetery. | Lebanon, Kentucky
Facilities | Environmental | Geotechnical | Materials
PROJECT DESCRIPTION
Terracon Consultants, Inc. (Terracon), conducted a moisture and mold assessment for VCI
Builders, Inc. (Client) on October 10th and 11th 2023 at The Lebanon National Cemetery located at 20 State Highway 208 in Lebanon, Kentucky. The work was conducted in general accordance with Terracon Proposal No. PN1237296, dated September 6, 2023. Mr. Lem Weyer, Staff
Scientist, and Mr. Travis Rose, Environmental Technician, conducted the assessment for
Terracon.
The objective of the assessment was to document building conditions related to moisture intrusion and potential fungal growth on building materials, finishes, and furnishings.
1.1 Scope of Services
The scope of services included:
◼ Visual observations to document conditions.
◼ Infrared imaging to identify thermal anomalies that may indicate wet building materials
◼ Moisture measurement in building materials to confirm materials with elevated moisture content.
◼ Air samples for total fungal structures at indoor locations and at outdoor locations for comparison.
◼ Surface samples for microscopic examination and fungal culture analysis to document surface fungal growth.
◼ Report
1.2 Standard of Care
This evaluation was conducted based on information provided to Terracon by Client and was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale.
Terracon did not attempt to identify every potential exposure or hazard present. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during the assessment. The information contained in this report should not be relied upon to represent conditions that existed before or after this investigation. Terracon does not warrant the services of regulatory agencies, laboratories, or other third parties supplying information that may have been used in the preparation of this report.
SITE DESCRIPTION
The Lebanon National Cemetery is located at 20 State Highway 208 in Lebanon, Kentucky.
Terracon’s scope of services included the following three (3) site structures:
◼ The Administration Building (Building 1) is two-story building with an unfinished basement. The building consists of approximately 3,000 square feet (SF) of interior floor space. The interior floors of the building are wooden floorboards, and the interior walls are drywall and plaster. The exterior walls of the building are brick, and the building has a slope metal roof with a coating. The building is used as office and storage space.
◼ The Service Building (Building 2) is a one-story slab-on-gab building with an attic. The building consists of approximately 1,200 SF of interior floor space. The exterior walls of the building are brick, and the roof is a sloped shingled roof. The building is used as a garage and storage area for landscaping equipment and supplies.
◼ Maintenance Garage (Building 3) is a one-story slab-on-grade building with an addition.
The maintenance garage is a single-story building with approximately 2,400 SF of interior floor space. The exterior walls of the building are brick, and the roof is a sloped metal roof. The addition also has brick exterior walls and a sloped metal roof. The building is used as garage space with a breakroom and storage closets. The addition contains exterior facing restrooms.
EVALUATION CRITERIA
3.1 Visual Inspection
A visual inspection was conducted to document existing conditions and areas of impact. The inspection included:
◼ An examination of existing conditions.
◼ An examination for visible evidence of water damage.
◼ An examination for visible suspected fungal growth.
3.2 Moisture Measurement
Excess moisture in building materials may result in the growth of fungi or bacteria. Moisture content will vary building-to-building and across geography, depending on air intrusion pathways, air moisture levels and condensation, indoor environmental conditions, and bulk water intrusion.
3.3 Microbial Sampling
There are no State or Federal exposure limits established for fungal aerosols. There are currently no regulatory standards or medically based threshold limit or dose-response relationships for exposure to airborne or surface concentrations of fungal spores. Terracon relies upon experience, professional judgment, current scientific literature, guidelines and recommendations made by professional organizations and experts, and statistical methods in interpreting fungal sampling results.
Terracon relies on microscopic examination of samples to identify fungal growth on surfaces.
Building materials or building surfaces commonly have resident fungal spores that have settled out of the air or have been filtered out of the air with other particles. Fungal structures, such as hyphae and conidiophores (or other fruiting bodies) seen microscopically in surface samples, typically indicate fungal growth on surfaces, and are associated with the presence of moisture.
High variability in airborne fungal spore concentrations can exist in different geographic locations, during different seasons, and weather patterns, and over the course of a given day.
As a rule, indoor air fungal spore concentrations in a mechanically ventilated building are typically less than, but with a similar spore type distribution as fungal spore concentrations found in the outside environment. To help interpret the sampling results, we compared indoor air and outdoor air measurements.
Terracon interprets sample results for airborne fungi by comparing total airborne concentrations and the distributions of fungal spore genera in samples from indoor locations to samples from outdoor locations. The following comparisons are performed. Other information may be used for interpretation on a case-by-case basis.
◼ In general, total airborne fungal concentrations measured at indoor test locations should be lower than those outdoors.
o If total indoor air fungal spore concentrations are higher than those measured outdoors, indoor fungal sources may be suspected.
◼ In general, airborne fungal spore genera observed in samples at indoor test locations should have a similar distribution as those at outdoor locations.
o The consistent presence of moisture indicator fungal spores at test locations over and beyond background reference concentrations typically indicates a damp indoor environment.
o The dominating presence of one or more kinds of moisture indicator fungal spores at test locations and the absence of the same types at background reference locations typically indicates an indoor source and potentially degraded air quality.
Terracon collected total fungal spore air samples onto Allergenco-D® sampling cassettes using a portable sampling pump calibrated at a flow rate of 15 liters per minute, for five minutes. The flow rate was checked prior to the sampling using the factory-supplied rotameter. Samples were collected at representative indoor and outdoor sample locations.
After collection, the samples were delivered under chain-of-custody (COC) protocol to Eurofins
EMLab P&K (EMLab) in Marlton, New Jersey. EMLab is accredited by the AHIA® Laboratory
Accreditation Programs, LLC under the Environmental Microbiology Laboratory Accreditation
Program (#103005).
METHODS
4.1 Visual Inspection
The visual inspection may include:
◼ Documentation of material discoloration or odor that could indicate moisture intrusion, water damage and microbial growth
Destructive sampling or testing to inspect interior wall cavity spaces was not within the scope of work for this project.
4.2 Moisture Measurement
Building materials have different absorptive and moisture retention properties and will come into equilibrium with environmental moisture (as indicated by temperature and relative humidity levels) or become wet by contact with water. Terracon uses an infrared (IR) thermal imaging camera to evaluate thermal characteristics of building materials in areas of suspected water damage. A moisture meter is used to identify whether building materials were dry, damp, or wet at the time of the investigation if thermal anomalies are observed using the IR camera.
Infrared Imaging
Terracon used a FLIR C2 camera to collect IR thermal images. Thermal imaging allows the user to visualize temperature gradients in building materials. Wet or damp areas are typically cooler than adjacent dry areas because of evaporative cooling.
Moisture Meter
Terracon used a Protimeter Surveymaster™ moisture meter to measure the moisture levels of selected building materials. This is a dual mode instrument.
◼ Measure mode - This mode uses sharp metal pins that penetrate building materials and uses electrical conductivity to measure the moisture level of building materials between the two pins. A number readout and colored LED signals are elicited in this mode (0-
99.9). The number readout and LED signals/color scale are synchronous.
A calibration check was conducted onsite prior to the assessment. The moisture level value is reported as percent wood moisture equivalent (%WME). With this instrument, readings in wood from 16% to 19% may indicate un-acclimated lumber or minor moisture intrusion.
Readings above 19%, the moisture content at which framing lumber is typically kiln dried, may indicate moisture intrusion. Moisture readings greater than 24% are at levels where wood-deteriorating organisms are typically activated. Readings of >15% in other types of building materials may indicate elevated moisture; however, materials other than wood should be referenced to similar materials in the building that are not affected by atypical moisture conditions.
4.3 Microbial Sampling
Terracon shipped microbial samples under chain-of-custody (COC) protocol to EMLab, Marlton, New Jersey. EMLab is accredited by the AHIA® Laboratory Accreditation Programs, LLC under the Environmental Microbiology Laboratory Accreditation Program.
Surface Sampling
Terracon collected surface samples for microscopic examination. Samples were collected using
Mold Tape SlideTM samplers. The sample was labeled with a unique identifier, touched to the surface of interest, and then placed into a plastic shipping case. Samples were collected from surfaces exhibiting suspected fungal growth.
Air Samples for Total Fungal Structures
Terracon collected air samples for total fungal structures for microscopic examination using
Allergenco-D ® sampling cassettes and a portable sampling pump calibrated at a flow rate of 15 liters per minute, for 5 minutes. The flow rate was checked prior to the sampling using the factory-supplied rotameter.
FINDINGS
5.1 Visual Inspection
Terracon conducted a visual inspection that began with a walkthrough of the buildings. At the time of Terracon’s assessment, here was a musty odor in the basement of the administration building and the attic of the service building. There was suspected visible fungal growth observed on surfaces in the basement and 1st floor southeast corner of the administration building and on the east wall of the northeast storage room in the maintenance building.
Selected representative photographs are presented in Appendix A.
5.2 Thermal Imaging
The thermal characteristics of building interior walls and ceilings were observed utilizing the
FLIR C2 camera. Thermal anomalies indicating potential excessive moisture in remaining materials in the basement and at the northeast, southeast, and southwest corners on the 1st and 2nd floors of the administration building, and in the attic of the service building. Thermal images are in Appendix A with photographs.
5.3 Moisture Measurement
Moisture meter measurements were collected from gypsum wallboard and plaster walls within the administration building, Wood beams in the attic of the service building, and gypsum wall board in the maintenance building. All measurements were collected in the Measure Mode using metal pins that penetrate the material.
Measurements within the Administration building basement were 9.5% WME at the bottom of the basement stairs, 14.5% WME near the HVAC unit and 49.4% MWE at the north wall of the basement. The administration building 1st floor measurement at the southeast of the building was 22.0% WME and at the 1st floor southeast corner of the north room was 10.5% MWE. The measurement of the 2nd floor southwest corner of the west room was 10.5% WME and the 2nd floor East bathroom wall was 11.6% MWE. Measurement within the service building was
13.3% WME. The measurement within the maintenance building was 9.4% MWE at the east wall of the Northeast storage room and 10.6% MWE at the Middle South wall of the breakroom. A moisture map is in Appendix B.
5.4 Air Sampling
Air samples were collected before intensive inspections, measurements, or surface sampling.
Table 1 presents a summary of the fungal structure air samples for the Administration
Building. Table 2 presents a summary of fungal structure air samples for the Service Building.
Table 3 presents a summary of fungal structure air samples for the Maintenance Building.
In general, these results indicate indoor sources of fungi and degraded indoor air quality in the administration building central room, service building garage, and maintenance building garage. The laboratory analytical report is in Appendix C.
Administration Building
Air samples were collected before intensive inspections, measurements, or surface sampling.
Table 1 presents a summary of the fungal structure air samples for the Administration
Building.
Table 1
Total Spore Air Sample Results Summary
Administration Building
Sample Location Center of
Basement
1st Floor – Central
Room
Exterior West Side of
Building
Exterior East Side of Building
Sample # 01 02 03 04
Taxa Spores/m3
Alternaria - 120 27 290
Ascospores - 53 370 270
Basidiospores 160 800 1,900 2,600
Bipolaris/ Drechslera group
Cercospora - 53 - 110
Chaetomium 40 - - -
Cladosporium 590 6,500 3,900 4,500
Curvularia - - - -
Epicoccum - 80 27 490
Table 1
Administration Building
Sample Location Center of
Basement
1st Floor – Central
Room
Exterior West Side of
Building
Exterior East Side of Building
Sample # 01 02 03 04
Taxa Spores/m3
Ganoderma - - 53 -
Nigrospora - - - -
Penicillium/
Aspergillus type 800 160 110 640
Pithomyces 13 - - 67
Polythrincium - 13 - -
Rust - 27 80 790
Smuts, Periconia, Myxomycetes 27 93 67 40
Total 1,600 7,900 6,600 9,800
Outdoor air total fungal spores averaged 8,200 spores per cubic meter of air (spores/m3) and ranged from 6,600 spores/m3 to 9,800 spores/m3 for two samples. The indoor air total spore levels measured were lower than the outdoor air average and ranged from 1,600 spores/m3 to
7,900 spores/m3.
The outdoor air cladosporium spore average concentration for two air samples was 4,200 spores/m3. Indoor cladosporium levels in the admin central room on the first floor were higher than the outdoor air averaged at 6,500 spores/m3. Other spore types measured in indoor air samples, but not in the outdoor air, include Ganoderma and Plythrincium.
Service Building
Table 2 presents a summary of fungal structure air samples for the Service Building.
Table 2
Total Spore Air Sample Results Summary
Service Building
Sample Location Center of
Attic South Garage Bay
Exterior West Side of
Building
Exterior East Side of Building
Sample # 05 06 07 08
Taxa Spores/m3
Alternaria 13 67 93 240
Ascospores 160 110 370 320
Basidiospores 4,000 2,000 3,100 3,700
Table 2
Service Building
Sample Location Center of
Attic South Garage Bay
Exterior West Side of
Building
Exterior East Side of Building
Sample # 05 06 07 08
Taxa Spores/m3
Bipolaris/ Drechslera group
Cercospora - - 110 110
Chaetomium - - - -
Cladosporium 1,600 1,500 4,300 3,400
Curvularia - - 13 13
Epicoccum 53 27 80 230
Ganoderma 53 - 210 110
Nigrospora - - - -
Penicillium/
Aspergillus- type
- 160 - -
Pithomyces - - - -
Polythrincium - - - 40
Rusts 93 40 - -
Smuts, Periconia, Myxomycetes 93 - 270 93
Stachybotrys - - - -
Total 6,100 3,900 8,600 8,200
Outdoor air total fungal spores averaged 8,400 spores per cubic meter of air (spores/m3) and ranged from 8,200 spores/m3 to 8,600 spores/m3 for two samples. The indoor air total spore levels measured were lower than the outdoor air average and ranged from 3,900 spores/m3 to
6,100 spores/m3.
The outdoor air Penicillium/Aspergillus-like (Pen/Asp-like) spore average concentration for two air samples was 0 spores/m3. Indoor air Pen/Asp-like levels in the garage were higher than the outdoor air at 160 spores/m3. The outdoor air Rusts spore average concentration for two air samples was 0 spores/m3. Indoor air Pen/Asp-like levels in the center attic and the garage were higher than the outdoor air at 67 spores/m3 and ranged from 40 spores/m3 to 93 spores/m3. The outdoor air Basidospore spore average concentration for two air samples was
3,400 spores/m3. Indoor air Basidospore levels in the center of the attic were higher than the outdoor air at 4,000 spores/m3.
Maintenance Building
Table 3 presents a summary of fungal structure air samples for the Maintenance Building.
Table 3
Maintenance Building
Sample Location
Northeast
Storage
Room
Center of Maintenance
Garage
Exterior South Side of
Building
Exterior North
Side of Building
Sample # 09 10 11 12
Taxa Fungal Structures/m3
Alternaria 53 93 270 440
Ascospores 160 160 800 480
Basidiospores 960 2,600 8,700 7,400
Bipolaris/ Drechslera
Group
- 53 - 27
Cercospora - 110 130 150
Chaetomium - - -
Cladosporium 1,400 5,000 2,500 4,100
Curvularia 27 27 13 130
Epicoccum 27 80 93 240
Ganoderma - 110 - -
Nigrospora - - 93 150
Penicillium/
Aspergillus Type
- 1,900 - -
Pithomyces - 360 - 410
Polythrincium - - -
Rusts 40 1,400 - 2,8000
Smuts, Perconia, Myxomycetes 320 200 230 910
Total 3,000 12,000 13,000 17,000
Outdoor air total fungal spores averaged 15,000 spores per cubic meter of air (spores/m3) and ranged from 13,000 spores/m3 to 17,000 spores/m3 for two samples. The indoor air total spore levels measured were lower than the outdoor air average and ranged from 3,000 spores/m3 to 12,000 spores/m3.
The outdoor air Cladosporium) spore average concentration for two air samples was
3,300 spores/m3 and ranged from 2,500 spores/m3 to 4,100 spores/m3. Indoor air
Cladosporium levels in the maintenance garage were higher than the outdoor air average at
5,000 spores/m3. Outdoor air Pen/Asp-like spore average concentrations were 0 spores/m3.
Indoor air Pen/Asp- levels in the maintenance garage were higher than the outdoor air average at 1,900 spores/m3.
5.5 Surface Sampling
Table 4 presents a summary of results for surface samples analyzed by optical microscopy.
There were six surface samples collected. Four samples were collected from the administration building, one sample was collected from the service building and one sample was collected from the maintenance building. Surface samples were collected where discoloration or debris indicated suspected fungal growth. Acernonium, Aspergillus, Cladosporium, and
Scopulariopsis fungal structures were observed indicating fungal growth on surfaces sampled within the administration building and the attic of the service building. The laboratory analytical report is in Appendix C.
Table 4 Surface Tape Sample Results Summary
Sample ID and
Location
Mold Growth (Mycelial and/or Sporulating
Structures Observed)
Mold
Density
General
Impression
T-1
Administration Building:
Southwest Corner of
Basement
Cladosporium species (spores, hyphae, conidiophores) 1+ Mold Growth
T-2
Administration Building:
North Wall of Basement
Cladosporium species (spores, hyphae, conidiophores) 2+ Mold Growth
T-3
Administration Building:
Under Basement Stairwell
Acremonium (spores, conidiophores, hyphae)
Cladosporium (spores, conidiophores, hyphae)
3+
3+ Mold Growth
T-4
Administration Building:
Southeast Corner of 1st
Floor
Aspergillus (spores, conidiophores, hyphae)
Scopulariopsis (spores, conidiophores, hyphae)
4+
4+ Mold Growth
T-5
Service Building: West
Side of Attic
Cladosporium (spores, conidiophores, hyphae) 1+ Mold Growth
T-6
Maintenance Building:
Northeast Storage Room
None 0 None
*Mold density rating <1-4+ (<1 being the lowest and 4+ the highest) indicates the density of fungal growth structures observed.
CONCLUSIONS
Terracon has concluded the following based on this assessment:
◼ Administration Building: The basement and the southeast corner of the 1st floor have elevated building material moisture, and fungal growth on surfaces. Water damage was observed in the basement and southeast corner of the 1st floor. High moisture levels were also measured in the basement during the evaluation.
◼ Service Building: The attic has elevated building material moisture and fungal growth on surfaces. Air samples indicate that the indoor air is being degraded by an indoor source of microbial growth. Water damage and elevated building material moisture levels were found in the attic.
◼ Maintenance Building: Air sampling indicates that the indoor air does not appear to be being degraded by an indoor source of microbial growth. Elevated moisture levels were not observed in the building materials of the of the building.
RECOMMENDATIONS
Terracon recommends the following:
◼ Determine water intrusion pathways and make repairs.
◼ Prepare restoration and remediation protocols.
◼ Conduct restoration and remediation using trained workers that have experience with projects of similar scope and complexity.
◼ Fungal remediation should follow ANSI/IICRC S520 Standard and Reference Guide for
Professional Mold Remediation (latest edition).
◼ Post-restoration inspection and verification testing should be conducted following fungal remediation to ensure the effectiveness of environmental controls and air and surface cleaning.
LIMITATIONS
The level of effort and associated tasks completed for this assessment were limited to the scope of services outlined in the Proposal No. PN1237396 dated September 6, 2023. Terracon did not attempt to identify every potential exposure or hazard present during this assessment.
The results, findings, conclusions, and recommendations expressed in this report are based on information reported to Terracon by Client and conditions observed. No warranty, express or implied is made.
This report is prepared for the exclusive use of our Client for the specific application to the project discussed and has been prepared in accordance with generally accepted industrial hygiene practices. In the event any changes in conditions as outlined in this report are observed, the conclusions contained in this report cannot be considered valid unless the changes are reviewed, and the conclusions of this report are modified or verified in writing by the industrial hygienist.
APPENDIX A
Photographs
Administration Building: Basement
Mold Location
Administration Building: Basement
Mold Location
Service Building: Attic damaged/mold location
Service Building: Attic damaged roof location
APPENDIX B
Exhibits
Administration Building Basement Moisture Map
20 State Highway 208
Lebanon, Kentucky 40033
611 Lunken Park Drive Cincinnati, Ohio 45226
PH. (513) 321-5816 FAX. (513) 321-0294
N1237396
10/10/2023
BSK
LJW
BSK
BSK
N.T.S.
Project Manager:
Drawn by:
Checked by:
Approved by:
Project No.
Scale:
File Name:
Date:
Exhibit
N1227532Ex1DIAGRAM IS FOR GENERAL LOCATION
ONLY, AND IS NOT INTENDED FOR
CONSTRUCTION PURPOSES
Storage Room Basement
Storage RoomVisual Mold Growth
Water Damaged Area.
Moisture Level 14.2%
Water Damaged Area. Moisture Level 49.4%
Water Damaged Area
Administration Building 1st Floor Moisture Map
20 State Highway 208
Lebanon, Kentucky 40033
611 Lunken Park Drive Cincinnati, Ohio 45226
PH. (513) 321-5816 FAX. (513) 321-0294
N1237396
10/10/2023
BSK
LJW
BSK
BSK
N.T.S.
Project Manager:
Drawn by:
Checked by:
Approved by:
Project No.
Scale:
File Name:
Date:
Exhibit
N1227532Ex1DIAGRAM IS FOR GENERAL LOCATION
ONLY, AND IS NOT INTENDED FOR
CONSTRUCTION PURPOSES
Office
Restroom
Office Breakroom
Reception Area
Visual Mold Growth
Water Damaged Area.
Moisture Levels 22.0%
Administration Building 2nd Floor Moisture Map
20 State Highway 208
Lebanon, Kentucky 40033
611 Lunken Park Drive Cincinnati, Ohio 45226
PH. (513) 321-5816 FAX. (513) 321-0294
N1237396
10/10/2023
BSK
LJW
BSK
BSK
N.T.S.
Project Manager:
Drawn by:
Checked by:
Approved by:
Project No.
Scale:
File Name:
Date:
Exhibit
N1227532Ex1DIAGRAM IS FOR GENERAL LOCATION
ONLY, AND IS NOT INTENDED FOR
CONSTRUCTION PURPOSES
Bedroom
Restroom Bedroom
Office
Closet
No visible mold or water damage observed in this area
Service Building 1st Floor Moisture Map
20 State Highway 208
Lebanon, Kentucky 40033
611 Lunken Park Drive Cincinnati, Ohio 45226
PH. (513) 321-5816 FAX. (513) 321-0294
N1237396
10/10/2023
BSK
LJW
BSK
BSK
N.T.S.
Project Manager:
Drawn by:
Checked by:
Approved by:
Project No.
Scale:
File Name:
Date:
Exhibit
N1227532Ex1DIAGRAM IS FOR GENERAL LOCATION
ONLY, AND IS NOT INTENDED FOR
CONSTRUCTION PURPOSES
Men’s Restroom
Women’s Restroom
Garage Bay Garage Bay
Garage Bay
No visible mold or water damage observed in this area
Service Building Attic Moisture Map
20 State Highway 208
Lebanon, Kentucky 40033
611 Lunken Park Drive Cincinnati, Ohio 45226
PH. (513) 321-5816 FAX. (513) 321-0294
N1237396
10/10/2023
BSK
LJW
BSK
BSK
N.T.S.
Project Manager:
Drawn by:
Checked by:
Approved by:
Project No.
Scale:
File Name:
Date:
Exhibit
N1227532Ex1DIAGRAM IS FOR GENERAL LOCATION
ONLY, AND IS NOT INTENDED FOR
CONSTRUCTION PURPOSES
Attic
Visual Mold Growth Water damaged area.
Moisture level 13.3%
Maintenance Building Moisture Map
20 State Highway 208
Lebanon, Kentucky 40033
611 Lunken Park Drive Cincinnati, Ohio 45226
PH. (513) 321-5816 FAX. (513) 321-0294
N1237396
10/10/2023
BSK
LJW
BSK
BSK
N.T.S.
Project Manager:
Drawn by:
Checked by:
Approved by:
Project No.
Scale:
File Name:
Date:
Exhibit
N1227532Ex1DIAGRAM IS FOR GENERAL LOCATION
ONLY, AND IS NOT INTENDED FOR
CONSTRUCTION PURPOSES
Men’s Restroom
Women’s Restroom
HVAC
Room
Storage Room
Restroom
Breakroom
Garage
No visible mold or water damage observed in this area
APPENDIX C
Laboratory Reports
Approved by:
Technical Manager Ariunaa Jalsrai
Report for:
Brad Knipper Terracon - Cincinnati 611 Lunken Park Drive Cincinnati, OH 45226
Regarding:
Eurofins EPK Built Environment Testing, LLC Project: N1237396; Lehanon National Cemetary
EML ID: 3419279
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. Due to the nature of the analyses performed, field blank correction of results is not applied. The results relate only to the samples as received and tested. Information supplied by the client which can affect the validity of results: sample air volume.
Eurofins EPK Built Environment Testing, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results.
In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Spore trap analysis: 10-16-2023
Service SOPs: Spore trap analysis (EB-MY-S-1038) AIHA-LAP, LLC accredited service, Lab ID #103005
Eurofins EPK Built Environment Testing, LLC's LabServe® reporting system includes automated fail-safes to ensure that all AIHA- LAP, LLC quality requirements are met and notifications are added to reports when any quality steps remain pending.
EMLab ID: 3419279, Page 1 of 5Eurofins EPK Built Environment Testing, LLC
Eurofins EPK Built Environment Testing, LLC 3000 Lincoln Drive East, Suite A, Marlton, NJ 08053
(866) 871-1984 www.eurofinsus.com/Built Client: Terracon - Cincinnati C/O: Brad Knipper Re: N1237396; Lehanon National Cemetary
Date of Sampling: 10-11-2023 Date of Receipt: 10-13-2023 Date of Report: 10-16-2023
SPORE TRAP REPORT: NON-VIABLE METHODOLOGY
Location: 1:
Admin - Basement 2:
Admin - Central Room 1st Floor
3:
Admin - Outside
West
4:
Admin - Outside
East Comments (see below) None None None None
Lab ID-Version‡: 16638741-1 16638742-1 16638743-1 16638744-1
Analysis Date: 10/16/2023 10/16/2023 10/16/2023 10/16/2023 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 Alternaria 9 120 2 27 22 290 Ascospores 1 53 7 370 5 270 Basidiospores 3 160 15 800 36 1,900 49 2,600 Bipolaris/Drechslera group Cercospora 4 53 8 110 Chaetomium 3 40 Cladosporium 11 590 122 6,500 74 3,900 85 4,500 Curvularia Epicoccum 6 80 2 27 37 490 Ganoderma 1 53 Nigrospora Penicillium/Aspergillus types† 15 800 3 160 2 110 12 640 Pithomyces 1 13 5 67 Polythrincium 1 13 Rusts 2 27 6 80 59 790 Smuts, Periconia, Myxomycetes 2 27 7 93 5 67 3 40 Stachybotrys Stemphylium Torula Ulocladium Zygomycetes Background debris (1-4+)†† 3+ 3+ 2+ 3+ Hyphal fragments/m3 40 120 53 210 Pollen/m3 < 13 < 13 < 13 < 13 Skin cells (1-4+) 2+ 1+ 1+ 1+ Sample volume (liters) 75 75 75 75 § TOTAL SPORES/m3 1,600 7,900 6,600 9,800 Comments:
EMLab ID: 3419279, Page 2 of 5Eurofins EPK Built Environment Testing, LLC
Spore types listed without a count or data entry were not detected during the course of the analysis for the respective sample, indicating a raw count of <1 spore.
† The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted.
††Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher than reported. It is important to account for samples volumes when evaluating dust levels.
The analytical sensitivity is the spores/m^3 divided by the raw count, expressed in spores/m^3, per spore and per sample.
For more information regarding analytical sensitivity, please contact QA by calling the laboratory.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
§ Total Spores/m3 has been rounded to two significant figures to reflect analytical precision.
(866) 871-1984 www.eurofinsus.com/Built Client: Terracon - Cincinnati C/O: Brad Knipper Re: N1237396; Lehanon National Cemetary
Date of Sampling: 10-11-2023 Date of Receipt: 10-13-2023 Date of Report: 10-16-2023
SPORE TRAP REPORT: NON-VIABLE METHODOLOGY
Location: 5:
Service - Attic 6:
Service - South Garage
7:
Service - Outside
East
8:
Service - Outside
West Comments (see below) None None None None
Lab ID-Version‡: 16638745-1 16638746-1 16638747-1 16638748-1
Analysis Date: 10/16/2023 10/16/2023 10/16/2023 10/16/2023 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 Alternaria 1 13 5 67 7 93 18 240 Ascospores 3 160 2 110 7 370 6 320 Basidiospores 75 4,000 37 2,000 58 3,100 69 3,700 Bipolaris/Drechslera group Cercospora 8 110 8 110 Chaetomium Cladosporium 30 1,600 28 1,500 81 4,300 63 3,400 Curvularia 1 13 1 13 Epicoccum 2 27 6 80 17 230 Ganoderma 1 53 4 210 2 110 Nigrospora 4 53 Penicillium/Aspergillus types† 3 160 Pithomyces Polythrincium 3 40 Rusts 7 93 3 40 Smuts, Periconia, Myxomycetes 7 93 20 270 7 93 Stachybotrys Stemphylium Torula Ulocladium Zygomycetes Background debris (1-4+)†† 4+ 3+ 3+ 3+ Hyphal fragments/m3 110 120 270 80 Pollen/m3 < 13 < 13 < 13 < 13 Skin cells (1-4+) 2+ 1+ 1+ 1+ Sample volume (liters) 75 75 75 75 § TOTAL SPORES/m3 6,100 3,900 8,600 8,200 Comments:
EMLab ID: 3419279, Page 3 of 5Eurofins EPK Built Environment Testing, LLC
Spore types listed without a count or data entry were not detected during the course of the analysis for the respective sample, indicating a raw count of <1 spore.
† The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted.
††Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher than reported. It is important to account for samples volumes when evaluating dust levels.
The analytical sensitivity is the spores/m^3 divided by the raw count, expressed in spores/m^3, per spore and per sample.
For more information regarding analytical sensitivity, please contact QA by calling the laboratory.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Terracon - Cincinnati C/O: Brad Knipper Re: N1237396; Lehanon National Cemetary
Date of Sampling: 10-11-2023 Date of Receipt: 10-13-2023 Date of Report: 10-16-2023
SPORE TRAP REPORT: NON-VIABLE METHODOLOGY
Location: 9:
Maint. - NE Storage Room
10:
Maint. Garage
11:
Maint. Outside
South
12:
Maint. Outside
North
Comments (see below) None None None None
Lab ID-Version‡: 16638749-1 16638750-1 16638751-1 16638752-1
Analysis Date: 10/16/2023 10/16/2023 10/16/2023 10/16/2023 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 Alternaria 4 53 7 93 20 270 33 440 Ascospores 3 160 3 160 15 800 9 480 Basidiospores 18 960 49 2,600 163 8,700 139 7,400 Bipolaris/Drechslera group 4 53 2 27 Cercospora 8 110 10 130 11 150 Chaetomium Cladosporium 27 1,400 93 5,000 47 2,500 77 4,100 Curvularia 2 27 2 27 1 13 10 130 Epicoccum 2 27 6 80 7 93 18 240 Ganoderma 2 110 Nigrospora 7 93 11 150 Penicillium/Aspergillus types† 35 1,900 Pithomyces 27 360 31 410 Polythrincium Rusts 3 40 108 1,400 209 2,800 Smuts, Periconia, Myxomycetes 24 320 15 200 17 230 68 910 Stachybotrys Torula Ulocladium Zygomycetes Background debris (1-4+)†† 4+ 4+ 2+ 3+ Hyphal fragments/m3 40 320 170 520 Pollen/m3 < 13 < 13 < 13 < 13 Skin cells (1-4+) 2+ 3+ 1+ < 1+ Sample volume (liters) 75 75 75 75 § TOTAL SPORES/m3 3,000 12,000 13,000 17,000 Comments:
EMLab ID: 3419279, Page 4 of 5Eurofins EPK Built Environment Testing, LLC
Spore types listed without a count or data entry were not detected during the course of the analysis for the respective sample, indicating a raw count of <1 spore.
† The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted.
††Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher than reported. It is important to account for samples volumes when evaluating dust levels.
The analytical sensitivity is the spores/m^3 divided by the raw count, expressed in spores/m^3, per spore and per sample.
For more information regarding analytical sensitivity, please contact QA by calling the laboratory.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/Built Client: Terracon - Cincinnati C/O: Brad Knipper Re: N1237396; Lehanon National Cemetary
Date of Sampling: 10-11-2023 Date of Receipt: 10-13-2023 Date of Report: 10-16-2023
SPORE TRAP REPORT: NON-VIABLE METHODOLOGY
Location: 13:
Lab Blank 14:
Field Blank Comments (see below) None None
Lab ID-Version‡: 16638753-1 16638754-1
Analysis Date: 10/16/2023 10/16/2023 raw ct. spores/m3 raw ct. spores/m3 Alternaria Ascospores Basidiospores Bipolaris/Drechslera group Cercospora Chaetomium Cladosporium Curvularia Epicoccum Ganoderma Nigrospora Penicillium/Aspergillus types† Pithomyces Polythrincium Rusts Smuts, Periconia, Myxomycetes Stachybotrys Stemphylium Torula Ulocladium Zygomycetes Background debris (1-4+)†† None None Hyphal fragments/m3 N/A N/A Pollen/m3 N/A N/A Skin cells (1-4+) None None Sample volume (liters) 0 0 § TOTAL SPORES/m3 N/A N/A Comments:
EMLab ID: 3419279, Page 5 of 5Eurofins EPK Built Environment Testing, LLC
Spore types listed without a count or data entry were not detected during the course of the analysis for the respective sample, indicating a raw count of <1 spore.
† The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted.
††Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher than reported. It is important to account for samples volumes when evaluating dust levels.
The analytical sensitivity is the spores/m^3 divided by the raw count, expressed in spores/m^3, per spore and per sample.
For more information regarding analytical sensitivity, please contact QA by calling the laboratory.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
Approved by:
Technical Manager Ariunaa Jalsrai
Report for:
Brad Knipper Terracon - Cincinnati 611 Lunken Park Drive Cincinnati, OH 45226
Regarding:
Eurofins EPK Built Environment Testing, LLC Project: N1237396; Lehanon National Cemetary
EML ID: 3419279
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. Due to the nature of the analyses performed, field blank correction of results is not applied. The results relate only to the samples as received and tested.
Eurofins EPK Built Environment Testing, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results.
In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Direct microscopic exam (Qualitative): 10-16-2023
Service SOPs: Direct microscopic exam (Qualitative) (EM-MY-S-1039) AIHA-LAP, LLC accredited service, Lab ID #103005
Eurofins EPK Built Environment Testing, LLC's LabServe® reporting system includes automated fail-safes to ensure that all AIHA- LAP, LLC quality requirements are met and notifications are added to reports when any quality steps remain pending.
EMLab ID: 3419279, Page 1 of 2Eurofins EPK Built Environment Testing, LLC
(866) 871-1984 www.eurofinsus.com/Built Client: Terracon - Cincinnati C/O: Brad Knipper Re: N1237396; Lehanon National Cemetary
Date of Sampling: 10-11-2023 Date of Receipt: 10-13-2023 Date of Report: 10-16-2023
DIRECT MICROSCOPIC EXAMINATION REPORT
Background
Debris and/or Description
Miscellaneous Spores Present*
MOLD GROWTH: Molds seen with underlying mycelial and/or sporulating structures†
Other Comments††
General Impression
Lab ID-Version‡: 16638735-1, Analysis Date: 10/16/2023: Tape sample T-1: Admin - Basement SWC
Heavy None 1+ Cladosporium species (spores, hyphae, conidiophores)
None Mold growth
Lab ID-Version: 16638736-1, Analysis Date: 10/16/2023: Tape sample T-2: Admin - North Wall Bsement
Moderate None 2+ Cladosporium species (spores, hyphae, conidiophores)
None Mold growth
Lab ID-Version: 16638737-1, Analysis Date: 10/16/2023: Tape sample T-3: Admin - Under Stairwell
Moderate None 3+ Acremonium species (spores, hyphae, conidiophores) 3+ Cladosporium species (spores, hyphae, conidiophores)
None Mold growth
Lab ID-Version: 16638738-1, Analysis Date: 10/16/2023: Tape sample T-4: Admin - SEC 1st Floor
Light None 4+ Aspergillus species (spores, hyphae, conidiophores) 4+ Scopulariopsis species (spores, hyphae, conidiophores)
None Mold growth
Lab ID-Version: 16638739-1, Analysis Date: 10/16/2023: Tape sample T-5: Service - West Side Attic
Heavy Very few 1+ Cladosporium species (spores, hyphae, conidiophores)
None Mold growth
Lab ID-Version: 16638740-1, Analysis Date: 10/16/2023: Tape sample T-6: Maint. - NE Storage Room
Very Heavy Variety None None Normal trapping
* Indicative of normal conditions, i.e. seen on surfaces everywhere. Includes basidiospores (mushroom spores), myxomycetes, plant pathogens such as ascospores, rusts and smuts, and a mix of saprophytic genera with no particular spore type predominating. Distribution of spore types seen mirrors that usually seen outdoors.
† Quantities of molds seen growing are listed in the MOLD GROWTH column and are graded <1+ to 4+, with 4+ denoting the highest numbers.
†† Some comments may refer to the following: Most surfaces collect a mix of spores which are normally present in the outdoor environment. At times it is possible to note a skewing of the distribution of spore types, and also to note "marker" genera which may indicate indoor mold growth. Marker genera are those spore types which are present normally in very small numbers, but which multiply indoors when conditions are favorable for growth.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
The limit of detection is < 1+ when mold growth is detected.
For additional information necessary for the interpretation of the results, all readers are advised to refer to the document "Direct Exam Details Page" which is available on our website at:
www.emlab.com/services/mold-testing/direct-microscopic-exam-qualitative/
EMLab ID: 3419279, Page 2 of 2Eurofins EPK Built Environment Testing, LLC
(866) 871-1984 www.eurofinsus.com/Built Client: Terracon - Cincinnati C/O: Brad Knipper Re: N1237396; Lehanon National Cemetary
Date of Sampling: 10-11-2023 Date of Receipt: 10-13-2023 Date of Report: 10-16-2023
MoldSCORE™: Spore Trap Report Outdoor Sample: 3 Admin - Outside West
Fungi Identified Outdoor sample spores/m3 Raw Spores/ <100 1K 10K >100K count m3
Generally able to grow indoors* Alternaria 2 27 Bipolaris/Drechslera group ND < 13 Chaetomium ND < 13 Cladosporium 74 3,900 Curvularia ND < 13 Epicoccum 2 27 Ganoderma 1 53 Nigrospora ND < 13 Penicillium/Aspergillus types† 2 110 Stachybotrys ND < 13 Torula ND < 13 Seldom found growing indoors** Ascospores 7 370 Basidiospores 36 1,900 Rusts 6 80 Smuts, Periconia, Myxomycetes 5 67 Total 6,600
Location: 1 Admin - Basement Fungi Identified Indoor sample spores/m3 Raw Spores/
<100 1K 10K >100K count m3 MoldSCORE‡
100 200 300 Score
Generally able to grow indoors* Alternaria ND < 13 Bipolaris/Drechslera group ND < 13 Chaetomium 3 40 Cladosporium 11 590 Curvularia ND < 13 Nigrospora ND < 13 Penicillium/Aspergillus types† 15 800 Pithomyces 1 13 Stachybotrys ND < 13 Torula ND < 13 Seldom found growing indoors** Ascospores ND < 13 Basidiospores 3 160 Rusts ND < 13 Smuts, Periconia, Myxomycetes 2 27 Total 1,627
Final MoldSCORE 212
EMLab ID: 3419279, Page 1 of 4Eurofins EPK Built Environment Testing, LLC
(866) 871-1984 www.eurofinsus.com/Built Client: Terracon - Cincinnati C/O: Brad Knipper Re: N1237396; Lehanon National Cemetary
Date of Sampling: 10-11-2023 Date of Receipt: 10-13-2023 Date of Report: 10-16-2023
MoldSCORE™: Spore Trap Report Location: 2 Admin - Central Room 1st Floor
Fungi Identified Indoor sample spores/m3 Raw Spores/ <100 1K 10K >100K count m3
MoldSCORE‡ 100 200 300 Score
Generally able to grow indoors* Alternaria 9 120 Bipolaris/Drechslera group ND < 13 Chaetomium ND < 13 Cladosporium 122 6,500 Curvularia ND < 13 Epicoccum 6 80 Nigrospora ND < 13 Penicillium/Aspergillus types† 3 160 Polythrincium 1 13 Stachybotrys ND < 13 Torula ND < 13 Seldom found growing indoors** Ascospores 1 53 Basidiospores 15 800 Cercospora 4 53 Rusts 2 27 Smuts, Periconia, Myxomycetes 7 93 Total 7,907
Final MoldSCORE 240
Location: 5 Service - Attic Fungi Identified Indoor sample spores/m3 Raw Spores/
<100 1K 10K >100K count m3 MoldSCORE‡
100 200 300 Score
Generally able to grow indoors* Alternaria 1 13 Bipolaris/Drechslera group ND < 13 Chaetomium ND < 13 Cladosporium 30 1,600 Curvularia ND < 13 Ganoderma 1 53 Nigrospora 4 53 Penicillium/Aspergillus types† ND < 13 Stachybotrys ND < 13 Torula ND < 13 Seldom found growing indoors**…