This solicitation is for the Y1JZ-937CM3002 Tallahassee National Cemetery Ph 2 Expansion project. The Department of Veterans Affairs National Cemetery Administration is seeking mechanical, plumbing and electrical (MPE) services for gravesite expansion and related construction at the Tallahassee National Cemetery in Tallahassee, Florida. Bids are due by August 11, 2023. The awarded contract will have a period of performance of 365 days. The solicitation includes plans, specifications and drawings outlining the required MPE work.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MECHANICAL ABBREVIATIONS:

A/E ARCHITECT / ENGINEER

AFF ABOVE FINISHED FLOOR

AFW AIR FOIL WHEEL (FAN)

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND

REFRIGERATION INSTITUTE

ASHRAE AMERICAN SOCIETY OF HEAT

REFRIGERATION AIR

CONDITIONING ENGINEERS

ASME AMERICAN SOCIETY OF

MECHANICAL ENGINEERS

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BG BOTTOM GRILLE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER

HOUR

C CENTIGRADE (CELSIUS)

CAV CONSTANT AIR VOLUME

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

COP COEFFICIENT OF PERFORMANCE

CV CONSTANT VOLUME

D DAMPER - AUTOMATIC

Db DECIBELS

DB DRY-BULB TEMPERATURE

DEG DEGREE

DIA DIAMETER

DP DEW POINT TEMPERATURE

DPA DIFFERENTIAL PRESSURE

ASSEMBLY

DPS DIFFERENTIAL PRESSURE

SENSOR

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILLE

ENT ENTERING

ER EXHAUST REGISTER

ESP EXTERNAL STATIC PRESSURE

EX EXISTING

F FAHRENHEIT

FA FREE AREA

FC FLEXIBLE CONNECTION

FCW FORWARD CURVED WHEEL (FAN)

FD FIRE DAMPER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FRP FIBER REINFORCED POLYESTER

FSD COMBINATION FIRE SMOKE

DAMPER

FT FEET

FT WC FEET OF WATER COLUMN

FT-LB FOOT-POUND

FV FACE VELOCITY

GA GAUGE

GAL GALLONS

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GS GALVANIZED STEEL

HOA HAND/OFF/AUTOMATIC

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

ICF IN-LINE CENTRIFUGAL FAN

ID INSIDE DIAMETER

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH POUND

IS INSECT SCREEN

IV INLET VANES

J INTENTIONALLY LEFT BLANK

KG KILOGRAM

KG/HR KILOGRAM PER HOUR

kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR

L LITER

L/h LITERS PER HOUR L/m LITERS PER MINUTE L/s LITERS PER SECOND

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LVR LOUVER

M METER, SI UNIT

M/S METER PER SECOND

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT

AMPACITY

MCDB MEAN COINCIDENT DRY

BULB

MERV MINIMUM EFFICIENCY REPORTING

VALUE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MTD MEAN TEMPERATURE

DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

NA NOT APPLICABLE

NC NOISE CRITERIA

Nm NEWTON METER

NOAA NATIONAL OCEANIC &

ATMOSTPHERIC ADMINISTRATION

NOM NOMINAL

NPVL NON-STANDARD PART LOAD

VALUE

NTS NOT TO SCALE

OA OUTSIDE AIR

OAD OUTDOOR AIR DAMPER

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

Pa PASCAL

PCF POUNDS PER CUBIC FOOT

PD PRESSURE DROP

PEF PROPELLER (TYPE) EXHAUST FAN

PPM PARTS PER MILLION

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH –

ABSOLUTE

PSIG POUNDS PER SQUARE INCH –

GAGE

R/E RETURN OR EXHAUST

RA RETURN AIR

REA RELIEF AIR

RELAD RELIEF AIR DAMPER

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RLA RUN LOAD AMPERE

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SCFM STANDARD CUBIC FEET PER

MINUTE

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SDPR SMOKE DAMPER

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SI SQUARE INCHES

SMACNA SHEET METAL AND AIR

CONDITIONING CONTRACTORS'

NATIONAL ASSOCIATION

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SQ FT SQUARE FOOT (FEET)

SR SUPPLY REGISTER

SS STAINLESS STEEL

TAB TESTING, ADJUSTING, BALANCE

TG TRANSFER GRILLE

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

UL UNDERWRITERS LABORATORY

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VI VIBRATION ISOLATOR

VIF VERIFY IN FIELD

VIV VARIABLE INLET VANES

W WATTS

WB WET-BULB (TEMPERATURE)

WEF WALL EXHAUST FAN

YR YEAR

MI001

N/A

MMM SDP 51

MECHANICAL GENERAL NOTES

Project Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

TALLAHASSEE, FLORIDA

937CM3002

AUGUST 11, 2023

Office of Design and Construction

Service U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number

BID DOCUMENTS

VA FORM 08 - 6231

321 4 5 6 7 8 9

TALLAHASSEE NATIONAL CEMETERY

GRAVESITE EXPANSION

Fil e P ath : P

:\IF

SI

1-

T

AL

LA

HA

SS

EE

N

AT

L C

EM

ET

ER

Y

ME

P\

DR

AW

IN

GS

\S

HE

ET

S\

MI

1 M

EC

HA

NI

CA

L G

EN

ER

AL

N

OT

ES

.D W

G of 64

The LA Group

(518) 587-8100

AES Group

(303) 841-3922

CB Design Group

(888) 585-2234

Aqua Engineering

(970) 229-9668

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TEGR I TY FEDERA

L

S ERV I C E S

1. COORDINATE INSTALLATION WITH ALL TRADES PRIOR TO

COMMENCEMENT OF WORK.

2. COORDINATE WORK WITHIN THE COMMITTAL SHELTERS WITH THE

CEMETERY DIRECTOR TO AVOID CONFLICT WITH DAILY SCHEDULED

SERVICES. WORK IN THE COMMITTAL SHELTERS SHALL BE PHASED

SUCH THAT ONE SHELTER IS AVAILABLE FOR SERVICES AT ALL TIMES.

PROVIDE FENCING AND SCREENING AS NECESSARY TO OBSTRUCT

SITE LINES OF ACTIVE CONSTRUCTION AREAS IN THE COMMITTAL

SHELTERS.

SQUARE 1-WAY CEILING DIFFUSERS

LIMIT OF DEMOLITION

(WALL TYPE)

(WALL TYPE)

SUPPLY DUCT

EXHAUST DUCT

ROUND AND SQUARE 4-WAY CEILING DIFFUSERS

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING REGISTER OR GRILLE

EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE

EXHAUST OR RETURN REGISTER OR TOP GRILLE

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

CONNECT NEW DUCT TO EXISTING DUCT

D

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

R

RETURN DUCT

SQUARE 3-WAY CEILING DIFFUSERS

SQUARE 2-WAY CEILING DIFFUSERS

LINEAR SLOT DIFFUSER

FC

10x8

FLEXIBLE CONNECTION, EQUIPMENT,

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

LOUVER

FIRE/SMOKE DAMPER

FSD

VD

DUCT WITH SOUND LINING

FLEXIBLE DUCTWORK (INSULATED)

MANUAL VOLUME DAMPER

BACK DRAFT DAMPER

BDD

VIBRATION, OR SEISMIC

EXISTING DUCT TO BE REMOVED

EXISTING DUCT TO REMAIN

EXISTING FIRE DAMPER

MECHANICAL SYMBOLS: GENERAL NOTES:

WASTE GAS DETECTORWG

T THERMOSTAT

H HUMIDISTAT

clong Stamp clong Typewritten Text 8/8/23

EF-1 EF-1

SCALE:

MH101

P-528 BREAK ROOM SINK

NTS

FAUCET

LAMINAR FLOW

CONTROL DEVICE

WRIST BLADE

HANDLES

LOOSE KEY STOP

ESCUTCHEON

OFFSET

WASTE

TRAP

PARALLEL

TO WALL

CONNECT

TO EXISTING

PLUMBING

SS COUNTER TOP

MOUNTED SINK

BASIN

MH101

N/A

CDL SDP

SCALE: 14" = 1'-0"

0 2' 4' 12'8'

NORTH

GENERAL NOTES

1. COORDINATE INSTALLATION WITH ALL TRADES PRIOR TO

COMMENCEMENT OF WORK.

2. COORDINATE WORK WITHIN THE COMMITTAL SHELTERS WITH

THE CEMETERY DIRECTOR TO AVOID CONFLICT WITH DAILY

SCHEDULED SERVICES. WORK IN THE COMMITTAL SHELTERS

SHALL BE PHASED SUCH THAT ONE SHELTER IS AVAILABLE

FOR SERVICES AT ALL TIMES. PROVIDE FENCING AND

SCREENING AS NECESSARY TO OBSTRUCT SITE LINES OF

ACTIVE CONSTRUCTION AREAS IN THE COMMITTAL SHELTERS.

3. ELECTRICAL WORK IS SHOWN ON THE MECHANICAL PLANS

FOR COORDINATION PURPOSES ONLY.

MECHANICAL PLAN

Project Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

TALLAHASSEE, FLORIDA

937CM3002

AUGUST 11, 2023

Office of Design and Construction

Service U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number

BID DOCUMENTS

VA FORM 08 - 6231

321 4 5 6 7 8 9

TALLAHASSEE NATIONAL CEMETERY

GRAVESITE EXPANSION

Fil e P ath : P

:\IF

SI

1-

T

AL

LA

HA

SS

EE

N

AT

L C

EM

ET

ER

Y

ME

P\

DR

AW

IN

GS

\S

HE

ET

S\

MH

1 M

EC

HA

NI

CA

L P

LA

N.

DW

G of 64

The LA Group

(518) 587-8100

AES Group

(303) 841-3922

CB Design Group

(888) 585-2234

Aqua Engineering

(970) 229-9668

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TEGR I TY FEDERA

L

S ERV I C E S

MECHANICAL NOTES

1. INSTALL 1 SHUTTER MOUNT EXHAUST FAN (EF-1) ON THE

INTERIOR OF THE STORAGE CLOSET. INSTALL SHUTTER MOUNT

EXHAUST FAN CENTERED ON INTERIOR OF EXISTING EXHAUST

LOUVER ABOVE DOOR. COVER ALL REMAINING EXISTING LOUVER

SPACE WITH INTERIOR MOUNTED ALUMINUM BLANK OFF PLATE.

EXHAUST FAN SHALL BE CAPABLE OF MINIMUM 60 CFM. FAN

SHALL BE CORROSION RESISTANT. PROVIDE UL RATED CORD

AND PLUG 120 V ELECTRICAL CONNECTION. PROVIDE WIRE

SAFETY GUARD (INTAKE GUARD) ON EXPOSED INLET OF FAN AT

THE INTERIOR OF THE STORAGE CLOSET. UTILIZE EXISTING

BIRD/INSECT SCREEN ON EXISTING EXTERIOR LOUVER. EXHAUST

FAN SHALL BE CORROSION RESISTANT AND DESIGNED FOR

DAMP LOCATIONS.

CALCULATIONS:

COMMITTAL SHELTER STORAGE CLOSET SQFT: 90 SQFT

CEILING HEIGHT: 10 FT

TOTAL VOLUME: 900 CF

MINIMUM AIR CHANGES PER HOUR: 4

MINIMUM AIRFLOW REQUIREMENT: 60 CFM

SCALE:

MH101

COMMITTAL SHELTER 1 PLAN

1/4" = 1'-0" SCALE:

MH101

COMMITTAL SHELTER 2 PLAN

1/4" = 1'-0"

FAN SCHEDULE

MARK LOCATION

SYSTEM

AND/OR

SERVICE

MIN.

AIRFLOW

FAN MOTOR ELECTRICAL

REMARKSDIA

DRIVE

NOM POWER

PHASE VOLT POWER

CONNECTION

CFM IN HP

EF-1

COMMITTAL

SHELTER

CLOSET

EXHAUST 60 8 DIRECT

DRIVE 1/25 SINGLE 120 V CORDED

CORROSION RESISTANT,

PROVIDE GUARD OVER ALL

ROTATING COMPONENTS

PLUMBING FIXTURE SCHEDULE

TAG QUANTITY DESCRIPTION

WASTE

PIPE VENT PIPE COLD

WATER

HOT

WATER

WASTE

FIXTURE

UNITS

COLD

WATER

FIXTURE

UNITS

HOT

WATER

FIXTURE

UNITS

WRIST

BLADE

HANDLES

ELECTRIC

SENSOR REMARKS

IN IN IN IN

P-528 3 BREAK ROOM SINK 1.5 1.5 .5 .5 3 1.5 1.5 YES NO 1, 2, 3, 4, 5

REMARKS:

1.) CONNECT DHW/DCW TO THERMOSTATIC MIXING VALVE. PROVIDE MAXIMUM 110˚F.

2.) ELECTRONIC FAUCET SENSORS ARE PROHIBITED.

3.) COUNTERTOP MOUNTED STAINLESS STEEL SINK BASIN WITH HOT AND COLD WATER MIXING FAUCET

4.) FAUCET SHALL HAVE LAMINAR FLOW DEVICE OF BRASS OR STAINLESS STEEL TRIM.

5.) FAUCET WITH WRIST BLADE HANDLES AND FLOW-RATE OF 2.2 GPM.

clong Stamp clong Typewritten Text 8/8/23

1. CONTRACTOR SHALL COMPLY WITH ALL CURRENT APPLICABLE

CODES AND STANDARDS. ALL ELECTRICAL WORK SHALL BE IN

STRICT COMPLIANCE WITH THE CURRENT EDITION OF THE NEC.

ELECTRICAL WORK SHALL ALSO COMPLY WITH ANY APPLICABLE

FEDERAL AND STATE REGULATIONS. PROVIDE AND MAINTAIN

ELECTRICAL SAFETY AND WORKING CLEARANCES IN FRONT OF

AND AROUND ALL ELECTRICAL PANELS AND DISTRIBUTION

EQUIPMENT IN ACCORDANCE WITH NEC.

2. ALL MATERIAL SHALL CONFORM TO NEMA, ANSI AND U.S.

STANDARDS, WHICHEVER APPLIES AND SHALL BEAR THE

INSPECTION LABEL OF UNDERWRITER LABORATORIES, INC.

3. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION

ABOUT QUALITY AND GENERAL INSTALLATION REQUIREMENTS OF

ELECTRICAL CONSTRUCTION MATERIALS, ITEMS, AND DEVICES.

4. FOR QUALITY ASSURANCE, ALL EQUIPMENT SHALL BE UL LISTED

AND APPROVED. ALSO, PERFORM WORK IN ACCORDANCE WITH

THE NATIONAL ELECTRICAL CONTRACTOR ASSOCIATION (NECA)

"STANDARD OF INSTALLATION."

5. CONTRACTOR TO PATCH AND REPAIR ALL SURFACES TO A "LIKE

NEW" FINISH. IF ANY ADJACENT FINISH SURFACES ARE AFFECTED,

PROVIDE A SEAMLESS TRANSITION AND FINISH LEVEL.

6. PROVIDE SEALANT AROUND ALL ELECTRICAL OUTLETS, PLUMBING

FIXTURES, PIPING, AND EQUIPMENT ABUTTING OR PENETRATING

A WALL OR PARTITION INCLUDING FIRESTOPPING AT FIRE RATED

ASSEMBLES. PROVIDE FIRESTOPPING AROUND ALL

PENETRATIONS OCCURRING THROUGH FLOORS, WALLS, AND

CEILINGS AT FIRE-RATED ASSEMBLIES.

7. CLEAN ALL AREAS OF WORK UPON COMPLETION, INCLUDING BUT

NOT LIMITED TO: ALL EXISTING EQUIPMENT, FIXTURES, LIGHTS,

WINDOWS, BLINDS, AND REGISTERS. CONTRACTOR TO REPLACE

ANY CEILING TILES DAMAGED IN THE COURSE OF WORK. CLEAN

UP RESULTANT DEBRIS FROM THIS WORK AND REMOVE FROM

THE SITE. DISCONNECT AND REMOVE ALL TEMPORARY POWER

INCLUDING BUT, NOT LIMITED TO PANELS, FIXTURES, BOXES AND

WIRING.

8. COORDINATE DUST CONTROL PREVENTION MEASURES WITH COR.

9. CONTRACTOR ENCOURAGED TO VISIT ALL AREAS OF WORK,

INCLUDING WALKING THE SITE, MEASURING EXISTING

DIMENSIONS AND OBSERVING EXISTING CONDITIONS BEFORE

BIDDING WORK, ORDERING MATERIALS, AND/OR STARTING ANY

CONSTRUCTION WORK.

10.UNLESS NOTED OTHERWISE, ALL MATERIALS TO BE REMOVED

SHALL BE THE PROPERTY OF THE CONTRACTOR. DISPOSE OF ALL

WASTE MATERIAL IN APPROVED MANNER AND LOCATION,

COORDINATE MATERIALS FOR SALVAGE AND RECYCLING WITH

COR. THE CONTRACTOR SHALL USE ONLY DESIGNATED

PATHWAYS AS ESTABLISHED BY THE COR TO REMOVE ITEMS AND

MATERIALS FROM THE PROJECT BUILDING AND SITE.

11.CONTRACTOR TO USE ONLY APPROVED STAGING AREA FOR

STORAGE OF CONSTRUCTION MATERIALS.

12. THE EXTENT OF DEMOLITION AND RENOVATION WORK AS

INDICATED IN THESE DRAWINGS SHALL BE REVIEWED AND

COORDINATED WITH THE COR PRIOR TO THE COMMENCEMENT

OF WORK IN ORDER TO DETERMINE THE FULL EXTENT OF WORK

TO BE PERFORMED BY THE CONTRACTOR.

13.ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND

CORE DRILLING ALL PENETRATIONS THROUGH EXISTING FLOORS,

WALLS, ETC.

14.PLAN INSTALLATION OF NEW WORK AND CONNECTIONS TO

EXISTING WORK TO ENSURE MINIMUM INTERFERENCE WITH

REGULAR OPERATION OF EXISTING FACILITIES. COORDINATE ALL

SYSTEM SHUTDOWNS AFFECTING OTHER AREAS WITH COR. DO

NOT COMPROMISE NOR INTERRUPT ALARM, EMERGENCY, OR LIFE

SAFETY SYSTEMS.

15.CONTRACTOR TO COMPLETE WORK DURING BUSINESS HOURS.

WORK NECESSARY OUTSIDE OF BUSINESS HOURS REQUIRES

PRIOR APPROVAL OF COR AND CEMETERY DIRECTOR.

16.COORDINATE WITH COR FOR ACCEPTABLE WORK HOURS. THE

WORK IS NOT TO INTERFERE WITH FACILITY OPERATIONS. THOSE

AREAS THAT NEED TO BE COMPLETED AFTER HOURS TO BE

COORDINATED WITH COR. KEEP ALL BUILDING SYSTEMS SERVING

OCCUPIED AREAS FULLY OPERATIONAL AT ALL TIMES.

COORDINATE WITH COR AND COMPLY WITH THEIR REGULATIONS

FOR UTILITY SHUT DOWN, NOISE, AND VIBRATION. PROTECT AND

MAINTAIN ALL EXISTING BUILDING SYSTEMS INCLUDING ALL

SYSTEMS PASSING THROUGH AND ADJACENT TO AREAS

REQUIRED INCLUDING, BUT NOT LIMITED TO, WIRING, CONDUITS,

PIPING, DUCTWORK, AND OTHER UTILITIES TO SERVE OCCUPIED

AREAS. PROCEED WITH CARE AND CAUTION DURING DEMOLITION

TO AVOID AND MINIMIZE DAMAGE TO EXISTING CONSTRUCTION,

MATERIALS, SYSTEMS AND FINISHES TO REMAIN.

17.SCHEDULE TEMPORARY SHUTDOWNS WITH COR TWO (2) WEEKS

IN ADVANCE SO AS NOT TO INTERFERE WITH NORMAL DAYTIME

OPERATIONS AND AT NO ADDITIONAL COST.

18.GROUND THE ELECTRICAL SYSTEM INSULATED GROUNDING

CONDUCTOR INSTALLED WITH FEEDER CONDUCTORS IN ALL

CONDUITS WHETHER OR NOT INDICATED ON DRAWINGS. PROVIDE

GROUNDING CONDUCTOR IN ALL TELEPHONE AND CATV SERVICE

CONDUITS.

19.PROVIDE CONDUIT SO IT IS CONTINUOUS AND COMPLETE

BETWEEN PANELS, JUNCTION, OUTLET, PULL, AND FIXTURE

BOXES. KEEP CONDUIT CLEAN AND UNOBSTRUCTED INSIDE WITH

ENDS FREE OF BURRS AND OTHER PROJECTIONS WHICH WOULD

DAMAGE OR IMPEDE PULLING OF WIRE. INSTALL CONDUIT

PARALLEL AND PERPENDICULAR TO THE BUILDING LINES. ROUTE

ALL CONDUIT CONCEALED IN FINISHED AREAS EXCEPT WHERE

OTHERWISE NOTED.

20.UNLESS OTHERWISE NOTED, PROVIDE ALL WIRES AND CABLES AS

CONTINUOUS WITHOUT SPLICES OR TAPS IN CONDUIT RUNS.

INSTALL ALL WIRING IN CONDUIT OR AS OTHERWISE NOTED. MAKE

ALL SPLICES AT OUTLET BOXES, PULL BOXES, OR JUNCTION

BOXES. AT ALL JOINTS, SPLICE OR JOIN CONDUCTORS

MECHANICALLY AND SECURE.

21.DO NOT DRAW WIRE INTO CONDUIT UNTIL ALL WORK WHICH

COULD CAUSE INJURY TO THE CONDUCTORS IS COMPLETE.

22.SET ALL BOXES AND ENCLOSURES PLUMB, SQUARE, AND

SECURELY FASTENED. INSTALL BOXES IN FINISHED WALLS SO

THEY ARE FLUSH WITH FINISH SURFACE. INCREASE PULL AND

JUNCTION BOX SIZES FOR FINAL CONDUIT CONFIGURATIONS AND

ARRANGEMENTS.

23.COORDINATE INSTALLATION OF CONDUIT WITH OTHER TRADES

AND EQUIPMENT SUPPLIERS PRIOR TO ROUGH-IN. SUBMIT

WRITTEN CLARIFICATION REQUESTS IF DESIGN ADJUSTMENTS

ARE REQUIRED FOR COMPATIBILITY OR INTEROPERABILITY OF

EQUIPMENT.

24.CONDUIT RUNS ARE SHOWN FOR REFERENCE AND BIDDING

PURPOSES ONLY. CONTRACTOR SHALL VERIFY EXISTING FIELD

CONDITIONS AND DETERMINE SHORTEST AND LEAST DISRUPTIVE

ROUTE FOR CONDUIT RUNS. COORDINATE WITH OTHER TRADES

AND CONFIRM ROUTE SELECTION WITH OWNER PRIOR TO BID.

ANY DEVIATIONS FROM DRAWINGS IN DETAIL ON AS-BUILT

DRAWINGS BY CONTRACTOR.

25.ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. SIZE AND LOCATION

OF EQUIPMENT AND WIRING ARE SHOWN TO SCALE WHERE

POSSIBLE, BUT MAY BE DISTORTED FOR CLARITY ON THE

DRAWINGS. LOCATE OUTLETS AND EQUIPMENT AS SHOWN IN

ENLARGED DETAILS OR AS APPROVED BY THE COR.

26.THE PLANS DO NOT INDICATE ALL THE NECESSARY BENDS,

OFFSETS, PULL BOXES AND OBSTRUCTIONS. IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR TO INSTALL HIS WORK TO

CONFORM TO THE STRUCTURE, MAINTAIN HEADROOM AND KEEP

OPENINGS AND PASSAGEWAYS CLEAR. IT IS NOT INTENDED THAT

THE PLANS INDICATE ALL CONDUIT ROUTES, PULL BOXES, ETC.

ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR DETERMINING

ACTUAL CONDUIT ROUTING, QUANTITY, AND LOCATION OF PULL

BOXES WITHIN ACCESSIBLE LOCATIONS. PROVIDE SCREW-COVER

PULL BOXES IN CONDUIT RUNS AS REQUIRED TO LIMIT NUMBER

OF BEND TO NO MORE THAN THREE (3) OR 270 DEGREES TOTAL.

SIZE PULL BOXES IN ACCORDANCE WITH NEC. DOCUMENT ON

RECORD DRAWINGS THE SIZE AND LOCATION OF PULL BOXES

USED IN FEEDER CONDUIT RUNS.

27.TEST FOR GROUND CONTINUITY AND SHORT CIRCUITS, TO

ENSURE PROPER OPERATION OF ELECTRICAL EQUIPMENT.

REPAIR OR REPLACE FAULTY EQUIPMENT AT NO ADDITIONAL

COST TO THE PROJECT.

28.LABEL ALL ELECTRICAL EQUIPMENT WITH THEIR SOURCE OF

ELECTRICAL SUPPLY, EXCEPT LABEL BRANCH-CIRCUIT DEVICES

WITH THEIR CIRCUIT DESIGNATION - INCLUDING PANEL NAME AND

CIRCUIT BREAKER NUMBERS. LABEL BOTH THE INTERIOR AND

THE EXTERIOR SIDES OF FACEPLATES.

29.CONTRACTOR TO NOTE THAT WHEN A SPECIFIC DIRECTION IS

SPECIFIED SUCH AS "EAST", THAT DIRECTION IS "PLAN EAST" AND

NOT NECESSARILY "GEOGRAPHIC EAST".

30.LETTERS SUCH AS "WP", "GFCI" ADJACENT TO ANY SYMBOL

INDICATE SPECIAL CONSTRUCTION IS REQUIRED. "GFI" AND "GFCI"

INDICATE GROUND FAULT CIRCUIT INTERRUPTING FEATURE,

UNLESS NOTED OTHERWISE. SEE ABBREVIATIONS FOR

DEFINITIONS.

31.ALL PANELS SHOWN IN BOLD ARE BEING MODIFIED OR REPLACED.

PANELS SHOWN IN SCREENED OR FADED LINEWORK ARE FOR

REFERENCE, ARE EXISTING, OR ARE PERFORMED BY OTHER

TRADES BUT ARE NOT PART OF THIS SCOPE OF WORK.

32.PROVIDE NEW TYPE WRITTEN DIRECTORIES FOR ALL PANELS

INSTALLED OR MODIFIED UNDER THIS CONTRACT.

33.CONTRACTOR IS TO VERIFY AND CORRECT ALL PANEL

SCHEDULES OF PANELS THAT ARE BEING WORKED ON.

34.ENSURE LOCKS PROVIDED ON NEW PANELBOARDS ARE KEYED

TO MATCH EXISTING SITE KEYING. COORDINATE WITH COR AND

VA'S SPECIFIC DEPARTMENT FOR EXACT REQUIREMENTS.

35.LOCATE RECEPTACLES AND TELE/DATA JACKS AT 18" AFF UNLESS

NOTED OTHERWISE. LOCATE LIGHT SWITCHES 48" AFF UNLESS

NOTED OTHERWISE.

36.ELEVATIONS FOR ELECTRICAL EQUIPMENT ARE TO CENTER OF

DEVICE OR ENCLOSURE UNLESS NOTED OTHERWISE.

37.SIZES OF WIRE AND CABLE ARE BASED ON COPPER

CONDUCTORS. PROVIDE COPPER CONDUCTORS, NOT ALUMINUM.

SIMILARLY, PROVIDE TRANSFORMER WINDINGS AND

PANELBOARD BUSES AS COPPER, NOT ALUMINUM.

GENERAL NOTES

KW KILOWATT

WEATHERPROOF; WHILE IN-USE

XMFR

WP

W

TRANSFORMER

WEST

POLYVINYL CHLORIDE

NATIONAL ELECTRICAL CODE

SPECIFICATIONS

V

VA

TYP

VOLT AMPERE

VOLT

TYPICAL

SPEC, SPECS

S

REC, RECPT

REF

PVC

SOUTH

RECEPTACLE

REFERENCE

NEC

PH

PNL

PHASE

PANELBOARD

N

MAX

NORTH

MAXIMUM

ELECTRICAL OR ELECTRIC

GROUND FAULT CIRCUIT INTERRUPTER

GALVANIZED RIGID STEEL CONDUIT

KILOVOLT AMPERES

1,000 CIRCULAR MILS

(E), EXIST EXISTING

G, GND, GRD GROUND

K

KV

KVA

KCMIL, MCM

J-BOX

GRC

KEY

KILOVOLTS

JUNCTION BOX

FUT

GFI, GFCI

FIG

FUTURE

FIGURE

EQUIP

ENT

ELEC

DISC

DWG

ENTRANCE

EQUIPMENT

DISCONNECT

DRAWING

CU COPPER

CIRCUIT BREAKER

(NOT ALL ABBREVIATIONS ARE USED FOR THIS PROJECT)

AMPS INTERRUPTING CAPACITY (SYM RMS)

AMERICAN WIRE GAGE

C

CKT, CCT

CB

AWG

AIC

CIRCUIT

CONDUIT

ELECTRICAL ABBREVIATIONS

A, AMP AMPERE

AC ABOVE-COUNTER

U.O.N UNLESS OTHERWISE NOTED

AL ALUMINUM

EASTE UC UNDER-COUNTER

WHERE APPLICABLE

DEMO DEMOLISH

OR OPERATING ROOM

NEW WORK

EXISTING

(2#12+#12 GRD)1/2"C

QUANTITY OF GROUND WIRES

CONDUIT SIZE

CONDUIT RUN - SCHEMATIC DIAGRAM

QUANTITY OF PHASE AND NEUTRAL WIRES

WP

GFCI

15A

J

C

DUPLEX RECEPTACLE - 2P,3W GROUNDING TYPE

RECEPTACLE, 125V,NUMERAL ADJACENT IDENTIFIES

CURRENT RATING IN AMPS (NO DESIGNATION INDICATES

20A MIN.) GFCI INDICATES DEVICE WITH

INTEGRAL GROUND FAULT PROTECTION, WP INDICATES

WEATHERPROOF.

BRANCH CIRCUIT AND FEEDER WIRING. ARROWS AND

LETTER/NUMERALS IDENTIFY ABV. GRADE HOME-RUN

CIRCUITS. #12 CONDUCTORS UNLESS NOTED OTHERWISE.

ALL CONDUIT SHALL CONTAIN A GREEN INSULATED

GROUND WIRE SIZED IN ACCORDANCE WITH 2014 NEC

TABLE 250.122, UNLESS OTHERWISE NOTED.

LIGHTING AND APPLIANCE TYPE PANELBOARD. - SURFACE

MOUNTED

2P, 3W GROUNDING TYPE RECEPTACLE - 125V,

CONVENTIONAL DUPLEX, NEMA 5-20R. RECEPTACLE

COVERPLATE SHALL BE PROVIDED WITH LABEL STATING

"COMPUTER".

2P, 3W GROUNDING TYPE RECEPTACLE - 125V,

CONVENTIONAL DUPLEX, NEMA 5-20R. RECEPTACLE

POWERED THROUGH OCCUPANCY SENSOR LOCATED

WITHIN SAME AREA.

2P, 3W GROUNDING TYPE RECEPTACLE, EMERGENCY -

125V, CONVENTIONAL DUPLEX, NEMA 5-20R.

CEILING MOUNTED DUPLEX RECEPTACLE OUTLET

FLOOR DUPLEX RECEPTACLE OUTLET

FLOOR DUPLEX RECEPTACLE, EMERGENCY

FLOOR 4-PLEX RECEPTACLE OUTLET

SPECIAL RCPT, PROVIDE RECEPTACLE CONFIGURATION

NOTED

JUNCTION BOX, 4" SQUARE UNLESS NOTED OTHERWISE

SINGLE RECEPTACLE - 2P,3W GROUNDING TYPE

RECEPTACLE, 125V,NUMERAL ADJACENT IDENTIFIES

CURRENT RATING IN AMPS (NO DESIGNATION INDICATES

20A MIN.) GFCI INDICATES DEVICE WITH

INTEGRAL GROUND FAULT PROTECTION, WP INDICATES

WEATHERPROOF

TRANSFORMER - SIZE AS INDICATED ON DRAWING

POWER AND GROUNDING SYMBOLS

OS

WP

GFCI

15A

VFD VARIABLE FREQUENCY DRIVE

A A

A A

AA

A

A

A A

LIGHTING SYMBOLS

RECESS MTD. CAN LIGHTS. UPPER CASE LETTER

IDENTIFIES FIXTURE TYPE. DARKENED AREA INDICATES

EMERGENCY POWERED.

WALL MOUNTED COMPACT FLUORECENT, LED OR H.I.D.

LUMINAIRE, UPPER CASE LETTER IDENTIFIES FIXTURE

TYPE. DARKENED AREA INDICATES EMERGENCY

POWERED.

RECESS MOUNTED LED FIXTURE. UPPER CASE LETTER

DESIGNATES THE FIXTURE TYPE. DARKENED AREA

INDICATES EMERGENCY POWERED.

SURFACE MOUNTED LED FIXTURE W/ UPPER CASE LETTER

DESIGNATES THE FIXTURE TYPE. DARKENED AREA

INDICATES EMERGENCY POWERED.

WALL(SURFACE) MOUNTED LED FIXTURE W/ LENS. UPPER

CASE LETTER DESIGNATES THE FIXTURE TYPE. DARKENED

AREA INDICATES EMERGENCY POWERED.

2'X4' RECESS MOUNTED LED FIXTURE. UPPER CASE

LETTER DESIGNATES THE FIXTURE TYPE. DARKENED AREA

INDICATES EMERGENCY POWERED.

STRIP LIGHT LED FIXTURE W/ UPPER CASE LETTER

DESIGNATES THE FIXTURE TYPE. DARKENED AREA

INDICATES EMERGENCY POWERED.

CEILING FAN. NUMBER OF BLADES AND SIZE OF FAN ARE

REPRESENTATIVE AND MAY VARY. SEE NOTES, SCHEDULE,

OR SPECIFICATIONS FOR CEILING FAN REQUIREMENTS.

A

A

A A

CONDUIT STUB-UP

QUANTITY AND SIZE AS INDICATED ON PLANS

(#6 MIN. CONDUCTOR IF NOT SHOWN)

GROUND CONNECTION - TO STANDARD ROD

TYPE ELECTRODE TO NEAREST STRUCTURAL STEEL

T

EI001

N/A

MMM SDP 53

ELECTRICAL GENERAL NOTES

Project Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

TALLAHASSEE, FLORIDA

937CM3002

AUGUST 11, 2023

Office of Design and Construction

Service U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number

BID DOCUMENTS

VA FORM 08 - 6231

321 4 5 6 7 8 9

TALLAHASSEE NATIONAL CEMETERY

GRAVESITE EXPANSION

Fil e P ath : P

:\IF

SI

1-

T

AL

LA

HA

SS

EE

N

AT

L C

EM

ET

ER

Y

ME

P\

DR

AW

IN

GS

\S

HE

ET

S\

EI

1 E

LE

CT

RI

CA

L G

EN

ER

AL

.D

W G of 64

The LA Group

(518) 587-8100

AES Group

(303) 841-3922

CB Design Group

(888) 585-2234

Aqua Engineering

(970) 229-9668

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TEGR I TY FEDERA

L

S ERV I C E S

AutoCAD SHX Text P1-1 jlandrith PE Seal Colorado

X

SECTION 5

1,638 PRE-PLACED CRYPTS

(WITHIN 3'x8' PLOTS)

SECTION 8

968 PRE-PLACED URN CRYPTS

(WITHIN 4'x4' PLOTS)

SECTION 7

968 PRE-PLACED URN CRYPTS

(WITHIN 4'x4' PLOTS)

SECTION 6

968 PRE-PLACED URN CRYPTS

(WITHIN 4'x4' PLOTS)

SEC

SEC

SEC

SEC

SEC

SEC

SEC

SEC

SD

EX. WATER

VALVE (TYP.)

EX. WATER

VALVE (TYP.)

EX. WATER

VALVE (TYP.)

TR

EX. ELECTRICAL

TRANSFORMER (TYP.)

TR

TR

C

C

C

C

C

EX. COMMUNICATION

PEDESTAL (TYP.)

E

"DO NOT

ENTER"

SIGN

"DO NOT

ENTER"

SIGN

EX. WATER

STANDPIPE

(TYP.)

V V

M.U.

UNKNOWN UTILITY

POSSIBLY WATER

EUx

EU

x

EU

x

EUx

EU

x

T

T

EUxEUx EUx

EUx

EUx

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

EU

x

ELEC

ELEC

T

T

ELEC

ELEC

ES101

N/A

MMM SDP

NORTH

GENERAL NOTES

1. SITE PLAN HAS BEEN DEVELOPED FROM INFORMATION THAT

HAS NOT BEEN INDEPENDENTLY VERIFIED IN THE FIELD.

MINOR DISCREPANCIES MAY EXIST IN LOCATION, ROUTING,

ORIENTATION, QUANTITY, RENOVATIONS, ETC.

2. PRIOR TO BID AND COMMENCEMENT OF ANY WORK, VERIFY

FIELD CONDITIONS AS THEY PERTAIN TO THE DRAWINGS AND

THE WORK TO BE COMPLETED.

KEY NOTES

1. REMOVE EXISTING FIXTURES, CONDUCTORS, AND

TRANSFORMER BACK TO PANEL 'FLAG ASSEMBLY'. REPLACE

EXISTING LIGHTING WITH NEW ADJUSTABLE LUMEN LED

MEDIUM FLOOD LIGHT WITH BRASS BODY AND FULLY

ADJUSTABLE KNUCKLE MOUNTING. PROVIDE NEW

TRANSFORMER FOR EVERY 2 FIXTURES OR AS REQUIRED BY

THE MANUFACTURER FOR EACH FIXTURE GROUP IN

APPROVED OUTDOOR ENCLOSURE. TRANSFORMER

SECONDARIES CAN BE ROUTED WITHIN THE SAME CONDUIT.

TRANSFORMER SHOULD BE LOCATED WITHIN 15' OF THE

FIXTURE POINT OF CONNECTION. AVOID TRENCHING IN

CONCRETE SLABS AND REPAIR ANY DAMAGED PORTIONS OF

CONCRETE SLABS.

· THE BASIS OF DESIGN FIXTURE IS:

AW-LED-E66-MFL-A9-MAC-12.

ES101

SCALE:

ES101

ELECTRICAL SITE PLAN

NTS

ELECTRICAL SITE PLAN

Project Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

TALLAHASSEE, FLORIDA

937CM3002

AUGUST 11, 2023

Office of Design and Construction

Service U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number

BID DOCUMENTS

VA FORM 08 - 6231

321 4 5 6 7 8 9

TALLAHASSEE NATIONAL CEMETERY

GRAVESITE EXPANSION

Fil e P ath : P

:\IF

SI

1-

T

AL

LA

HA

SS

EE

N

AT

L C

EM

ET

ER

Y

ME

P\

DR

AW

IN

GS

\S

HE

ET

S\

ES

1 E

LE

CT

RI

CA

L S

IT

E

PL

AN

.D W

G of 64

The LA Group

(518) 587-8100

AES Group

(303) 841-3922

CB Design Group

(888) 585-2234

Aqua Engineering

(970) 229-9668

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TEGR I TY FEDERA

L

S ERV I C E S

Project Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

TALLAHASSEE, FLORIDA

937CM3002

AUGUST 11, 2023

Office of Design and Construction

Service U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number

BID DOCUMENTS

VA FORM 08 - 6231

321 4 5 6 7 8 9

TALLAHASSEE NATIONAL CEMETERY

GRAVESITE EXPANSION

Fil e P ath : P

:\IF

SI

1-

T

AL

LA

HA

SS

EE

N

AT

L C

EM

ET

ER

Y

ME

P\

DR

AW

IN

GS

\S

HE

ET

S\

ES

1 E

LE

CT

RI

CA

L S

IT

E

PL

AN

.D W

G of 64

The LA Group

(518) 587-8100

AES Group

(303) 841-3922

CB Design Group

(888) 585-2234

Aqua Engineering

(970) 229-9668

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TEGR I TY FEDERA

L

S ERV I C E S

SCALE:

ES101

ENLARGED FLAG ASSEMBLY

NTS

APPROXIMATE LOCATION

OF DISTRIBUTION PANEL 'DP1'

APPROXIMATE LOCATION

OF 'FLAG ASSEMBLY' PANEL

COMMITTAL SHELTER 1

COMMITTAL SHELTER 2

HONOR GUARD

EP101

EP101

EP101

PULLBOX

EXISTING FIXTURES (QTY 4) TO

ILLUMINATE AMERICAN FLAG.

FIXTURES MOUNTED 4' FROM

BASE OF POLE.

EXISTING LIGHTING:

BK LIGHTING - BDSLEDE23-MFL-A9-MAC-12-B-360L

LED 8.4W

LED MEDIUM FLOOD LIGHT WITH BRASS BODY MACHINED FROM

SOLID BILLET WITH FULLY ADJUSTABLE KNUCKLE MOUNTING.

SINGLE TRANSFORMER PROVIDED FOR EACH FIXTURE GROUP.

APPROXIMATE LOCATION OF

EXISTING LED TRANSFORMERS

TO BE REPLACED.

[2#10 + 10G] 1"C

EP101

EP101

EU x UNDERGROUND ELECTRICAL

LOW VOLTAGE UNDERGROUND ELECTRICALELEC

LEGEND:

J

TRANSFORMER LOCATED ABOVE ELECTRICAL PANEL 'CS 2'

WP

GFCI

EP101

N/A

MMM SDP

SCALE: 14" = 1'-0"

0 2' 4' 12'8'

NORTH

GENERAL NOTES

1. COORDINATE INSTALLATION WITH ALL TRADES PRIOR TO

COMMENCEMENT OF WORK.

2. SURFACE MOUNTED CONDUIT IS ONLY PERMITTED WITHIN

THE STORAGE CLOSET OF THE COMMITTAL SHELTER.

3. COORDINATE WORK WITHIN THE COMMITTAL SHELTERS WITH

THE CEMETERY DIRECTOR TO AVOID CONFLICT WITH DAILY

SCHEDULED SERVICES. WORK IN THE COMMITTAL SHELTERS

SHALL BE PHASED SUCH THAT ONE SHELTER IS AVAILABLE

FOR SERVICES AT ALL TIMES. PROVIDE FENCING AND

SCREENING AS NECESSARY TO OBSTRUCT SITE LINES OF

ACTIVE CONSTRUCTION AREAS IN THE COMMITTAL SHELTERS.

KEY NOTES

1. REMOVE EXISTING CEILING FAN. REMOVE EXISTING J-BOX

AND RETAIN CONDUIT, BUSHINGS, AND WIRING FOR

RECONNECTION. PROVIDE AND INSTALL A NEW FAN-RATED

J-BOX. PROVIDE AND INSTALL NEW OUTDOOR RATED, 120V

CEILING FAN TO EXISTING CIRCUIT MAINTAINED DURING

DEMOLITION.

2. REMOVE AND RETAIN EXISTING TRANSFORMER AND

MOUNTING BRACKET IN COMMITTAL SHELTER 2 FOR REUSE

AND REINSTALLATION. INTERCEPT AND EXTEND EXISTING

CONDUITS AND CONDUCTORS FOR THE TRANSFORMER AT

THE NEW LOCATION AS SHOWN ON THE DRAWINGS. ENSURE

THE NEC REQUIRED WORKING SPACE IS MET IN FRONT AND

ABOVE PANEL 'CS 2'.

3. LOCATION OF EXISTING ELECTRICAL PANEL TO REMAIN

DURING CONSTRUCTION. LOCKOUT TAGOUT ELECTRICAL

PANEL PRIOR TO COMMENCEMENT OF ANY WORK.

4. PROVIDE RECEPTACLE ABOVE DOOR FOR USE WITH CORD

AND PLUG CONNECTED EXHAUST FAN IN COMMITTAL

SHELTERS 1 AND 2. SEE PANEL SCHEDULES FOR ADDITIONAL

INFORMATION.

SCALE:

EP101

ELECTRICAL ENLARGED PLANS

1/4" = 1'-0"

ELECTRICAL ENLARGED PLANS

Project Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

TALLAHASSEE, FLORIDA

937CM3002

AUGUST 11, 2023

Office of Design and Construction

Service U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number

BID DOCUMENTS

VA FORM 08 - 6231

321 4 5 6 7 8 9

TALLAHASSEE NATIONAL CEMETERY

GRAVESITE EXPANSION

Fil e P ath : P

:\IF

SI

1-

T

AL

LA

HA

SS

EE

N

AT

L C

EM

ET

ER

Y

ME

P\

DR

AW

IN

GS

\S

HE

ET

S\

EP

1 E

LE

CT

RI

CA

L E

NL

AR

GE

D

PL

AN

S.

DW

G of 64

The LA Group

(518) 587-8100

AES Group

(303) 841-3922

CB Design Group

(888) 585-2234

Aqua Engineering

(970) 229-9668

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TEGR I TY FEDERA

L

S ERV I C E S

SCALE:

EP101 1/4" = 1'-0"

SCALE:

EP101 1/4" = 1'-0"

COMMITTAL SHELTER DEMO PLAN

COMMITTAL SHELTER POWER PLAN

AutoCAD SHX Text

AutoCAD SHX Text

GUN SAFE

AutoCAD SHX Text

9 SF

AutoCAD SHX Text

AutoCAD SHX Text

COVERED

AutoCAD SHX Text

PORCH

AutoCAD SHX Text

168 SF

AutoCAD SHX Text

AutoCAD SHX Text

LOCKERS

AutoCAD SHX Text

142 SF

AutoCAD SHX Text

AutoCAD SHX Text

MEN

AutoCAD SHX Text

112 SF

AutoCAD SHX Text

AutoCAD SHX Text

WOMEN

AutoCAD SHX Text

66 SF

AutoCAD SHX Text

AutoCAD SHX Text

ELECT/ MECH CL

AutoCAD SHX Text

52 SF

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

70 SF

AutoCAD SHX Text

AutoCAD SHX Text

HONOR GUARD

AutoCAD SHX Text

461 SF

AutoCAD SHX Text E

AutoCAD SHX Text K

AutoCAD SHX Text N

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text

PP

AutoCAD SHX Text M

AutoCAD SHX Text

PP

AutoCAD SHX Text T

AutoCAD SHX Text Mo

AutoCAD SHX Text Mo

AutoCAD SHX Text a

AutoCAD SHX Text M

AutoCAD SHX Text

WP

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text

PP

AutoCAD SHX Text

HG-1

AutoCAD SHX Text

'HG'

AutoCAD SHX Text

TO EF

AutoCAD SHX Text

TO EF

AutoCAD SHX Text

WP

AutoCAD SHX Text T

AutoCAD SHX Text T

EP601

N/A

MMM SDP

SCALE: NONE

EP601

COMMITTAL SHELTER

'CS1'

GENERAL NOTES

1. PANEL SCHEDULES AND LOADS ARE BASED UPON PREVIOUS

PROJECT DESIGN CALCULATIONS. THE TOTAL ANTICIPATED

LOAD WILL DECREASE FOR THIS PROJECT.

KEY NOTES

1. THE ANTICIPATED LOCATION OF THE AFFECTED PANEL CIRCUIT

FOR USE DURING DEMOLITION AND RENOVATION.

2. PROVIDE NEW 20A CIRCUIT BREAKER FOR NEW EXHAUST FAN

RECEPTACLE. PROVIDE NEW TYPED CIRCUIT DIRECTORY WITH

CIRCUIT LABELED 'EXHAUST FAN'. SEE 2/EP101 FOR

ADDITIONAL INFORMATION.

3. PROVIDE NEW 20A CIRCUIT BREAKER FOR NEW EXHAUST FAN

RECEPTACLE. PROVIDE NEW TYPED CIRCUIT DIRECTORY WITH

CIRCUIT LABELED 'EXHAUST FAN'. INSTALL THE RECEPTACLE IN

COMMITTAL SHELTER 2 IN ACCORDANCE WITH DETAIL 2/EP101.

PANEL SCHEDULES

Project Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

TALLAHASSEE, FLORIDA

937CM3002

AUGUST 11, 2023

Office of Design and Construction

Service U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number

BID DOCUMENTS

VA FORM 08 - 6231

321 4 5 6 7 8 9

TALLAHASSEE NATIONAL CEMETERY

GRAVESITE EXPANSION

Fil e P ath : P

:\IF

SI

1-

T

AL

LA

HA

SS

EE

N

AT

L C

EM

ET

ER

Y

ME

P\

DR

AW

IN

GS

\S

HE

ET

S\

EP

1 P

AN

EL

S

CH

ED

UL

ES

.D W

G of 64

The LA Group

(518) 587-8100

AES Group

(303) 841-3922

CB Design Group

(888) 585-2234

Aqua Engineering

(970) 229-9668

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TEGR I TY FEDERA

L

S ERV I C E S

SCALE: NONE

EP601

'FLAG ASSEMBLY'

SCALE: NONE

EP601

COMMITTAL SHELTER

'CS2'

SCALE: NONE

EP601

'HONOR GUARD'

AutoCAD SHX Text

BKR.

AutoCAD SHX Text

CKT. BREAKER

AutoCAD SHX Text

BKR.

AutoCAD SHX Text

CKT. BREAKER

AutoCAD SHX Text

ABC

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

SERVING

AutoCAD SHX Text

CONN.

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

COND.

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

WIRE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CLASS

AutoCAD SHX Text

PANEL `CS1' CIRCUIT SCHEDULE

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

SERVING

AutoCAD SHX Text

CONN.

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

COND.

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

WIRE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CLASS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 100A, 120/208V, 3%%C, 4W

AutoCAD SHX Text

50A MB

AutoCAD SHX Text

IER=10,000 AIC RMS SYM

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

AutoCAD SHX Text

LIGHTING

AutoCAD SHX Text

REC.

AutoCAD SHX Text

FANS

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

REC. AT PANEL

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

CONNECTED LOAD: 8.7A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text 2.1

AutoCAD SHX Text 8.3

AutoCAD SHX Text 6.6

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1.5

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text

IRRIGATION CONTROL 3

AutoCAD SHX Text

AutoCAD SHX Text 1"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BKR.

AutoCAD SHX Text

CKT. BREAKER

AutoCAD SHX Text

BKR.

AutoCAD SHX Text

CKT. BREAKER

AutoCAD SHX Text

ABC

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

SERVING

AutoCAD SHX Text

CONN.

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

COND.

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

WIRE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CLASS

AutoCAD SHX Text

PANEL `FLAG ASSEMBLY' CIRCUIT SCHEDULE

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

SERVING

AutoCAD SHX Text

CONN.

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

COND.

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

WIRE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CLASS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 100A, 120/208V, 3%%C, 4W

AutoCAD SHX Text

50A MB

AutoCAD SHX Text

IER=10,000 AIC RMS SYM

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

CONNECTED LOAD: 1.6A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LGTS-FLAG POLE

AutoCAD SHX Text 0.5

AutoCAD SHX Text 1.5

AutoCAD SHX Text

REC. AT PANEL

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

AutoCAD SHX Text

BKR.

AutoCAD SHX Text

CKT. BREAKER

AutoCAD SHX Text

BKR.

AutoCAD SHX Text

CKT. BREAKER

AutoCAD SHX Text

ABC

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

SERVING

AutoCAD SHX Text

CONN.

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

COND.

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

WIRE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CLASS

AutoCAD SHX Text

PANEL `CS2' CIRCUIT SCHEDULE

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

SERVING

AutoCAD SHX Text

CONN.

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

COND.

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

WIRE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CLASS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 100A, 120/208V, 3%%C, 4W

AutoCAD SHX Text

50A MB

AutoCAD SHX Text

IER=10,000 AIC RMS SYM

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

AutoCAD SHX Text

LIGHTING

AutoCAD SHX Text

REC.

AutoCAD SHX Text

FANS

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

REC. AT PANEL

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

CONNECTED LOAD: 8.6A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text 2.1

AutoCAD SHX Text 8.3

AutoCAD SHX Text 6.6

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1.5

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text

IRRIGATION CONTROL 4

AutoCAD SHX Text

AutoCAD SHX Text 1"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

BKR.

AutoCAD SHX Text

CKT. BREAKER

AutoCAD SHX Text

BKR.

AutoCAD SHX Text

CKT. BREAKER

AutoCAD SHX Text

ABC

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

SERVING

AutoCAD SHX Text

CONN.

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

COND.

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

WIRE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CLASS

AutoCAD SHX Text

PANEL `HG' CIRCUIT SCHEDULE

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

SERVING

AutoCAD SHX Text

CONN.

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

COND.

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

WIRE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

CLASS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 100A, 120/208V, 3%%C, 4W

AutoCAD SHX Text

100A MB

AutoCAD SHX Text

IER=10,000 AIC RMS SYM

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

AutoCAD SHX Text

CONNECTED LOAD: 77.6A

AutoCAD SHX Text

LGTS-RM.

AutoCAD SHX Text

INT./EXTERIOR

AutoCAD SHX Text

REC. RM.

AutoCAD SHX Text

EXTERIOR

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

5 REFRIG.

AutoCAD SHX Text 2,6

AutoCAD SHX Text 4,6

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AHU-4-1

AutoCAD SHX Text

HP-4-1

AutoCAD SHX Text

WH-4-1

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

AutoCAD SHX Text 10.2

AutoCAD SHX Text 6.6

AutoCAD SHX Text 1.5

AutoCAD SHX Text 6.6

AutoCAD SHX Text 8.3

AutoCAD SHX Text 8.3

AutoCAD SHX Text 8.3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1.5

AutoCAD SHX Text

IRRIGATION CONTROLLER

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3/4"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

GRINDER PUMP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EF-4-1

AutoCAD SHX Text 1.5

AutoCAD SHX Text

EF-4-1

AC ALTERNATING CURRENT

ACEG ALTERNATING CURRENT EQUIPMENT GROUND

AE ARCHITECT AND ENGINEER

AES ADVANCED ENCRYPTION STANDARD

AHJ AUTHORITY HAVING JURISDICTION

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

APC ANGLED PHYSICAL CONTACT

ARU AIR REMOVAL UNITS

ASD ASPIRATED SMOKE DETECTION

ASHRAE AMERICAN SOCIETY OF HEATING AND

AIR-CONDITIONING ENGINEERS

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BACnet BUILDING AUTOMATION AND CONTROL

NETWORKING PROTOCOL

BAS BUILDING AUTOMATION SYSTEM

BCM BRANCH CIRCUIT MONITORING

BCP BRANCH CIRCUIT PANELBOARD

BICSI BUILDING INDUSTRY CONSULTING SERVICE

INTERNATIONAL

BMS BATTERY MONITORING SYSTEM

CAB CHANGE ADVISORY BOARD

CANbus CONTROLLER AREA NETWORK BUS

CCH CLOSET CONNECTOR HOUSING

CDC CORE DATA CENTER

CE CLINICAL ENGINEERING

CFD COMPUTATIONAL FLUID DYNAMICS

CFM CUBIT FEET PER MINUTE

CFM VA OFFICE OF CONSTRUCTION AND FACILITIES

MANAGEMENT

CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED

CMLPS COMMUNICATION MAIN LIGHTNING PROTECTION

SYSTEM

CMP COMMUNICATIONS MULTIPURPOSE CABLE

CMOP CONSOLIDATED MAIL OUTPATIENT PHARMACY

CMP COMMUNICATIONS PLENUM

CMR COMMUNICATIONS RISER

CLPS COMMUNICATIONS LIGHTNING PROTECTION SYSTEM

CPAC CONSOLIDATED PATIENT ACCOUNT CENTER

CRAC COMPUTER ROOM AIR CONDITIONER

CRAH COMPUTER ROOM AIR HANDLER

CSC CAMPUS SUPPORT CENTER

DC DIRECT CURRENT

DCIE DATA CENTER AND INFRASTRUCTURE ENGINEERING

DCIM DATA CENTER INFRASTRUCTURE MANAGEMENT

DM DESIGN MANUAL

DPDT DOUBLE POLE DOUBLE THROW

DR DISASTER RECOVERY

DX DIRECT EXPANSION

(E) EXISTING

EBSR ENTERPRISE BASELINE AND STANDARD REVIEW

EC ELECTRONICALLY COMMUTATED

ED EQUIPMENT DISTRIBUTOR

EDICT ENTERPRISE DATA CENTER INFRASTRUCTURE

COLLABORATION TEAM

EDM ELECTRICAL DESIGN MANUAL

EGB EXTERNAL GROUNDING BUSBAR

EGC EARTH GROUNDING CONDUCTOR

EGS EARTH GROUND SYSTEM

EIA ELECTRONIC INDUSTRIES ALLIANCE

EMCS ENERGY MANAGEMENT CONTROL SYSTEM

EMI ELECTROMAGNETIC INTERFERENCE

EPO EMERGENCY POWER OFF

(E.R.) EXISTING RELOCATED

ESD ELECTROSTATIC DISCHARGE

EUD END USER DEVICE

FB FRONT BOTTOM

FCU FAN COIL UNITS

FDU FIBER DISTRIBUTION UNIT

FEC FACILITY TOTAL ELECTRICAL CONSUMPTION

FLPS FACILITY LIGHTNING PROTECTION SYSTEM

FM FRONT MIDDLE

FMS FACILITIES MANAGEMENT SERVICE

FSC FINANCIAL SERVICES CENTER

FSS FACILITY STANDARDS SERVICE

FT FRONT TOP

GbE GIGABIT ETHERNET Gb/s GIGABITS PER SECOND

GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED

HA HIGH AVAILABILITY

HAC HEALTH ADMINISTRATION CENTER

HC HORIZONTAL CROSS CONNECT

HCC HEALTH CARE CENTERS

HEC HEALTH ELIGIBILITY CENTER

HD HIGH DENSITY

HD HORIZONTAL DISTRIBUTION

HDA HORIZONTAL DISTRIBUTION AREA

HH HANDHOLE

HVAC HEATING, VENTILATION, AND AIR CONDITIONING

IAW IN ACCORDANCE WITH

ICC INTERMEDIATE CROSS CONNECT

IEC INTERNATIONAL ELECTROTECHNICAL COMMISSION

IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS

ENGINEERS

IO INFRASTRUCTURE OPERATIONS

IP INTERNET PROTOCOL

ISP INSIDE PLANT

IT INFORMATION TECHNOLOGY

ITOPST IT OPERATIONS AND SERVICES

ITS INFORMATION TRANSPORT SYSTEMS

LAN LOCAL AREA NETWORK

LED LIGHT EMITTING DIODE

LFMC LIQUID-TIGHT FLEXIBLE METAL CONDUIT

LP LIMITED POWER

LPS LIGHTNING PROTECTION SYSTEM

MATV MASTER ANTENNA TELEVISION

MCC MAIN CROSS CONNECT

MCR MAIN COMPUTER ROOM

MCOR MAIN COMPUTER OPERATORS ROOM

MID MOTION INTRUSION DETECTOR

MH MANHOLE

MM MULTIMODE

MPDU MASTER POWER DISTRIBUTION UNIT

MPO MULTI-FIBER PUSH ON

MSC MISSION SUPPORT CENTER

(N) NEW

NCA NATIONAL CEMETERY ADMINISTRATION

NDCOL NATIONAL DATA CENTER OPERATIONS AND LOGISTICS

NEC NETWORK ENTERPRISE CENTER

NEMA NATIONAL ELECTRICAL MANUFACTURES ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NETWORK INTERFACE CARD

NSC NETWORK SUPPORT CENTER

OIFO OFFICE OF INFORMATION FIELD OFFICE

OIT OFFICE OF INFORMATION & TECHNOLOGY

OEHRM OFFICE OF ELECTRONIC HEALTH RECORD

MODERNIZATION

O&M OPERATIONS AND MAINTENANCE

OM OPTICAL MULTIMODE

OMB OFFICE OF MANAGEMENT & BUDGET

OPC OUTPATIENT CLINIC

(P) PRESERVE

PACS PHYSICAL ACCESS CONTROL SYSTEM

PAS PUBLIC ADDRESS

PBB PRIMARY BONDING BUSBAR

PBX PRIVATE BRANCH EXCHANGE

PDU POWER DISTRIBUTION UNIT

PoE POWER-OVER-ETHERNET

POTS PLAIN OLD TELEPHONE SYSTEM

PSDM PHYSICAL SECURITY DESIGN MANUAL

PVC POLYVINYL CHLORIDE

PS POWER SUPPLY

PUE POWER USAGE EFFECTIVENESS

RB REAR BOTTOM

RBB RACK BONDING BUSBAR

RBC RACK BOUNDING CONDUCTOR

RCDD REGISTERED COMMUNICATIONS DISTRIBUTION

DESIGNER

RDC REGIONAL DATA CENTER

RDC REMOTE DISTRIBUTION CABINET

R&D RESEARCH & DEVELOPMENT

RFI RADIO FREQUENCY INTERFERENCE

RH RELATIVE HUMIDITY

RM REAR MIDDLE

RM(S) ROOM(S)

rPDU RACK POWER DISTRIBUTION UNIT

RT REAR TOP

RT REFRIGERATION TON

RU RACK UNIT

SAN STORAGE AREA NETWORK

SBB SECONDARY BONDING BUSBAR

SD SOLUTION DELIVERY

SD STANDARD DENSITY

SDO SECURED DOOR OPENING

SIEER SITE INFRASTRUCTURE ENERGY EFFICIENCY RATING

SM SINGLE-MODE

SMCS SPECIAL MEDICAL COMMUNICATIONS SYSTEMS

SSL SECURE SOCKETS LAYER

SOW SCOPE OF WORK

SWDW SHORT WAVELENGTH DIVISION MULTIPLEXING

TASTS TELECOMMUNICATIONS AND SPECIAL

TELECOMMUNICATIONS SYSTEMS

TBB TELECOMMUNICATIONS BONDING BACKBONE

TCO TELECOMMUNICATIONS OUTLETS

TEBC TELECOMMUNICATIONS EQUIPMENT BONDING

CONDUCTOR

TEC TOTAL DATA CENTER ENERGY CONSUMPTION

TER TELEPHONE EQUIPMENT ROOM

TGB TELECOMMUNICATIONS GROUND BAR

TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION

TIL TECHNICAL INFORMATION LIBRARY

TIP TELECOMMUNICATIONS INFRASTRUCTURE PLANT

TITEC TOTAL IT EQUIPMENT ENERGY CONSUMPTION

TPIEC TOTAL DATA CENTER PHYSICAL INFRASTRUCTURE

ENERGY CONSUMPTION

TR TELECOMMUNICATIONS ROOM

TUPSC TOTAL UPS LOAD ENERGY CONSUMPTION

UL UNDERWRITERS LABORATORIES INC

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

VA DEPARTMENT OF VETERANS AFFAIRS

VAMC VETERANS AFFAIRS MEDICAL CENTER

VACO VA CENTRAL OFFICE

VBA VETERANS BENEFITS ADMINISTRATION

VED VERTICAL EXHAUST DUCT

VESDA VERY EARLY SMOKE DETECTION APPARATUS

VHA VETERANS HEALTH ADMINISTRATION

VLA VENTED LEAD ACID

VRLA VALVE REGULATED LEAD ACID

VSD VARIABLE SPEED DRIVE

VOIP VOICE OVER INTERNET PROTOCOL

WAN WIDE AREA NETWORK

WC WATER COLUMN

zPDU ZONE POWER DISTRIBUTION UNIT

SPECIAL SYSTEM STANDARDS

INDUSTRY STANDARDS:

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

ELECTRONIC INDUSTRIES ALLIANCE (EIA)

TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)

BUILDING INDUSTRY CONSULTING SERVICE INTERNATIONAL

(BICSI)

TELECOMMUNICATIONS DISTRIBUTION METHODS MANUAL

(TDMM)

DESIGN STANDARDS:

OIT DESIGN GUIDE FOR INSIDE PLANT

TELECOMMUNICATIONS ENCLOSURE (TE)

(TELECOMMUNICATION WALL-MOUNTED CABINET)

NATIONAL CEMETERY ADMINISTRATION SPECIFICATION.

DEVELOPED BY: DATA CENTER AND INFRASTRUCTURE

ENGINEERING.

OEHRM SITE INFRASTRUCTURE REQUIREMENTS. JULY 1,

2021 | VERSION 3.1

ANSI/TIA-942-B RATING 1

GENERAL NOTES

1. THE TERM "PROVIDE", WHERE USED HEREIN, SHALL MEAN THE SAME

AS: SURVEYED, FURNISHED, INSTALLED, AND TESTED BY

CONTRACTOR.

2. THIS PROJECT CONSISTS OF SEVERAL PHASES TO ELIMINATE

COMPLETE BLACKOUT OF THE TELECOMMUNICATION RESOURCES

WHEN UPGRADING THE PHYSICAL LAYER.

3. REMOVE ALL ABANDONED CABLES THAT THIS PROJECT CAUSES TO BE

ABANDONED IN BUILDINGS, AND ALL ABANDONED CABLES, WHETHER

ABANDONED BY PROJECT OR NOT.

4. THICK BLACK LINES INDICATE NEW AND LIGHT SCREENED LINES

INDICATE EXISTING UNLESS OTHERWISE NOTED.

5. CABLE BEND RADII SHALL BE NO LESS THAN EIGHT TIMES THE CABLE

DIAMETER OR AS SPECIFIED BY THE CABLE MANUFACTURER;

WHICHEVER IS THE GREATER.

6. TWO METER LOOPS OF CABLE SHALL BE LEFT WITHIN EACH

COMMUNICATIONS ROOM/ENCLOSURE FOR FUTURE

MODIFICATIONS.SLACK SHALL BE COILED AND SUPPORTED. 0.5-METER

LOOP OF CABLE SHALL BE LEFT IN THE TRUNKING ON THE APPROACH

TO EACH NETWORK OUTLET.

7. TERMINATE PAIRS ACCORDING TO THE T568B WIRING SCHEME. PIN ALL

8 CONDUCTORS. MAXIMUM LINK LENGTH - 90 METERS, CHANNEL

LENGTH - 100METERS

8. COR RESERVES THE RIGHT TO DETERMINE WHETHER OR NOT THE

DESIGNATED "APPROVED EQUAL MANUFACTURER" IS EQUAL TO THE

"BASIS OF DESIGN MANUFACTURER" AND ACCEPTABLE FOR USE ON

THIS PROJECT.

9. CABLING MUST BE TESTED AFTER COMPLETION OF INSTALLATION. SEE

DIV 27 AND 28 SPECIFICATIONS FOR ALL REQUIRED TESTING.

10. FOR DISTRIBUTION TELECOMMUNICATIONS SPACE PURPOSES IT

EQUIPMENT ENCLOSURES WILL BE SD, UTILIZING LEGACY WHIP

DISTRIBUTION. HD ENCLOSURES ARE NOT UTILIZED IN THESE

CLASSIFICATIONS OF TELECOMMUNICATIONS SPACES. POWER

DENSITY IS LIMITED TO 5 KW PER ENCLOSURE.

11. FACILITY UPS SYSTEMS SHALL HAVE A PLANNED DESIGN LOAD WHICH

COVERS 100 % OF THE IT EQUIPMENT ELECTRICAL LOADS SIZED TO

PROVIDE 10 MINS OF BACKUP CAPACITY.ACTUAL LOADING ON THE UPS

SYSTEM IS LIMITED TO 85 % OF DESIGN CAPACITY.

12. HOOK AND LOOPS STRAPS EVERY 12 INCHES

SPECIAL SYSTEMS SYMBOLS

KEY NOTE

# DATA OUTLET

# = NUMBER OF CAT6A DROPS

PHASING PLAN

1. PROVIDE AND INSTALL ALL NEW EQUIPMENT PRIOR TO

REPLACING OR DISCONNECTING ANY CABLING.

2. ALL DOWN-TIMES TO OCCUR DURING THE EVENING AND

WEEKENDS.

ABBREVIATIONS

4 6

COMMUNICATION MANHOLE

TI001

TELECOMMUNICATIONS

GENERAL NOTES, SYMBOLS

JOL

DKC

Project Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

A

B

C

D

E

F

21 4 5 6 7 8 9

TALLAHASSEE, FLORIDA

937CM3002

AUGUST 11, 2023

Office of Design and Construction

Service U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number

BID DOCUMENTS

VA FORM 08 - 6231

321 4 5 6 7 8 9

TALLAHASSEE NATIONAL CEMETERY

GRAVESITE EXPANSION

Fil e P ath : P

:\IF

SI

1-

T

AL

LA

HA

SS

EE

N

AT

L C

EM

ET

ER

Y

ME

P\

DR

AW

IN

GS

\S

HE

ET

S\

-1

1-

3A -0

A

TI

1.D W

G of 64

The LA Group

(518) 587-8100

AES Group

(303) 841-3922

CB Design Group

(888) 585-2234

Aqua Engineering

(970) 229-9668

INTEGRITY

FEDERAL SERVICES

CIVIL ENGINEERING ● LANDSCAPE ARCHITECTURE ● PLANNING

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

Phone: 304-725-8456 www.ifs-ae.com

IN

TEGR I TY FEDERA

L

S ERV I C E S

1 4

1 4

4 6

5 2

6 3

1 4

(E) CMH-12

(E) CMH-11

(E) CMH-10

(E) CMH-09

(E) CMH-8

(E) CMH-7

(E) CMH-6

(E) CMH-5

(E) CMH-4

(E) CMH-3

(E) CMH-2

2 1

(E) CMH-1

(E) ADMINISTRATION BUILDING

(E) HONOR GUARD BUILDING

(E) MAINTENANCE BUILDING

(E)OSP-OM1

(E)O

SP-O

M

(E)O

SP-O

M

(E)OSP-OM

(E)OSP-OM1

(E)OSP-OM1

(E)OSP-OM1

(E)O

SP-O

M

(E)O

SP-O

M

(E)O

SP-O

M

(E)O

SP-O

M

(E)OSP-OM1

(E)OSP-OM1

(E)O

SP-O

M

(E)O

SP-O

M

(E)OSP-OM

(E)OSP-OM1

OSP-OS2

O

SP-O

S2 O

SP-O

S2

OSP-OS2

OSP-OS2

(E)OSP-OS2

(E)OSP-OS2

(E)O

SP-O

S2

OSP-OS2

O

SP-O

S2 O

SP-O

S2

OSP-OS2

OSP-OS2

OSP-OS2 OSP-OS2

OSP-OS2

O

SP-O

S2

O

SP-O

S2 O

SP-O

S2

O

SP-O

S2 O

SP-O

S2

OSP-OS2

TS101

N/A

JOL DKC

TELECOMMUNICATIONS SITE PLAN

SCALE:1 TELECOMMUNICATIONS SITE PLAN

NTS

# KEY NOTES:

1. EXISTING 96 STRAND SINGLE MODE FIBER AND SPLICE BOX IN

COMMUNICATION MANHOLE 1 (CMH-1) TO REMAIN.

2. EXISTING 24 SINGLE MODE FIBER…