06-01-14
SECTIONAL DOORS
08 36 13 - 1
SECTION 08 36 13
SECTIONAL DOORS
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies electrically operated thermal insulated sectional overhead steel doors.
1.2 MANUFACTURER'S AND INSTALLER'S QUALIFICATIONS
A. Manufacturer's regularly engaged in manufacturing items of type specified.
B. Installers under direct supervision of manufacturer's representative or trained personnel.
1.3 SUBMITTALS
A. Manufacturer's Literature and Data:
1. Brochures or catalog cuts.
2. Manufacturer's installation procedures and instructions.
3. Maintenance instructions, parts list.
B. Certificates:
1. Attest door, anchors and hardware will withstand the horizontal loads specified.
2. Attest door complies with thermal performance, air infiltration, and water infiltration requirements.
1.4 APPLICABLE PUBLICATIONS
A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by the basic designation only.
B. American National Standards Institute and Door and Access Systems
Manufacturers Association (ANSI/DASMA):
102-04 Sectional Overhead Type Doors
C. American Society for Testing and Materials (ASTM):
A36/A36M-12 Structural Steel
A227/A227M-06(2011) Steel Wire, Cold-Drawn for Mechanical Springs
A229/229M-12 Steel Wire, Oil-Tempered for Mechanical Springs
A653-11 Steel Sheet, Zinc-Coated (Galvanized) or Zinc
Iron Alloy Coated (Galvanized) by the Hot Dip
Process
C1036-11e1 Flat Glass
08 36 13 - 2
C1363-11 Thermal Performance of Building Materials and
Envelope Assemblies by Means of a Hot Box
Apparatus
E84-13a Surface Burning Characteristics of Building
Materials
E283-04(2012) Determining the Rate of Air Leakage through
Exterior Windows, Curtain Walls, and Doors
Under Specified Pressure Difference Across the
Specimen
E330-02(2010) Structural Performance of Exterior Windows, Curtain Walls, and Doors by the Uniform Static
Air Pressure Difference
E331-00(2009) Water Penetration of Exterior Windows, Curtain
Walls, and Doors by the Uniform Static Air
Pressure Difference
D. National Electrical Manufacturer's Association (NEMA):
ICS 2-00(R2005) Industrial Control and Systems: Controllers, Contactors, and Overload Relays
ICS 6-93(R2006) Industrial Control and Systems Enclosures
MG 1-11 Motors and Generators
E. National Fire Protection Association (NFPA):
70-11 National Electrical Code
F. National Association of Architectural Metal Manufacturers (NAAMM):
AMP 501 Metal Finishes Manual
PART 2 - PRODUCTS
2.1 MATERIALS
A. Steel: Comply with ASTM A653 for forming operations; ASTM A36 for structural sections.
B. Hard Drawn Spring Wire: ASTM A227.
C. Oil Tempered Spring Wire: ASTM A229.
D. Glass: ASTM C1036.
1. Clear Glass: Type 1, Class 1, Quality q5, 6 mm (1/4 inch) thick.
2. Fabricated into sealed insulating glass 25 mm (one inch) thick.
E. Weather-strips, Gaskets, and Thermal Breaks:
1. Neoprene, EPDM, PVC, silicone rubber, or other low conductance material.
2. Standard with door manufacturer.
08 36 13 - 3
2.2 DESIGN REQUIREMENTS
A. Wind Load: Design to withstand a horizontal or wind pressure in accordance with ASCE 7.
B. Thermal Performance: Minimum R Value of 12.0 for door when tested in accordance with ASTM C1363.
C. Air Infiltration: Maximum of 0.10 cfm at 24 Km (15 miles per hour) wind speed per foot of crack between door sections and door perimeter opening when tested in accordance with ASTM E283.
D. Water Infiltration: No infiltration when tested in accordance with ASTM
E331.
E. Comply with ANSI/NAGDM 102, for an Industrial door and specified design criteria, inside face mounted with tracks at jambs set back a sufficient distance to provide a clear opening when door is in open position.
F. Operation-Cycle Requirements: Door components and operators to operate for not less than 10,000 cycles.
2.3 FABRICATION
A. Steel Door Sections:
1. Form of hot-dipped galvanized steel not lighter than 0.6 mm thick
(24 gage) with longitudinal integral reinforcing ribs and flat bottom V-grooves install sections not less than 50 mm (2 inch) in thickness. Provide 2” thick double steel sandwich construction
(steel interior and exterior).
2. Meeting Rails: Interlocking joints with thermal breaks separating face sheets formed to provide weathertight closure and alignment for full width of door.
3. Height of Sections: Not to exceed 600 mm (24 inches); may be varied to suit door height.
4. Install glazing panels where indicated using rubber, thermal break gaskets standard with door manufacturer.
5. Insulation to have a flame spread rating of not more than 25 and a smoke development factor of not more than 50 when tested in accordance with ASTM E84.
6. Reinforced for hardware anchorage with not less than 2.6 mm (10 gage) galvanized steel.
B. Tracks:
1. Manufacturer's standard formed of hot-dipped galvanized steel.
08 36 13 - 4
2. Minimum 2.0 mm (14 gage) for 50 mm (2 inch) tracks and 2.5 mm (12 gage) for 75 mm (3 inch) tracks.
3. Fabricate vertical tracks with adjustable brackets for mounting at incline to continuous steel angle wall bracket.
4. Horizontal Track:
a. Reinforce with continuous steel angle anchored to vertical steel angle wall bracket and to ceiling angle supports.
b. Use vertical and cross or diagonal braced to obtain rigid installation of horizontal track.
5. Use minimum 2.3 mm (13 gage) galvanized steel angles.
C. Hardware:
1. Manufacturers standard hinges, brackets, rollers, locking devices and other hardware required for a complete installation.
2. Hinges and roller brackets minimum 2.3 mm (13 gage) galvanized steel.
3. Use rollers with ball bearings and case-hardened races.
2.4 ELECTRIC MOTOR OPERATORS
A. Complete with electric motor, machine cut reduction gears, steel chain and sprockets, magnetic brake, overload protection, brackets, push button controls, limit switches, magnetic reversing contactor, and other accessories necessary for proper operation, including emergency manual operator.
B. Design:
1. Design the operator for motor removal without disturbing the limit-switch timing and without affecting the emergency manual operators.
2. Make provision for emergency manual operation of door by chain-gear mechanism in case of electrical failure.
3. Arrange the emergency manual operating mechanism to immediately be put into and out of operation from the floor with a mechanical device to disconnect the motor from the operating mechanism when the emergency manual operating mechanism is engaged and not affect the timing of the limit switches.
4. Provide interlock with motor to prevent motor from operating when manual locks are activated.
C. Motors:
1. Conform to NEMA MG 1; maximum operation 3600 rpm.
2. Use high starting torque, reversible type, of sufficient horsepower and torque output to move the door in either direction from door
08 36 13 - 5 position, and produce door travel speed range of 0.20 to 0.30 m per second (8 to 12 inches per second), without exceeding the rated capacity.
3. Single-phase motors must not have commutation or more than one starting contact.
4. Motor Enclosures: Drip proof type or NEMA TENV type.
D. Controls:
1. Control Equipment: NEMA 2.
2. Control Enclosures: NEMA ICS 6, Type 12 or Type 4, except that contractor enclosures may be Type 1. Use weatherproof corrosion-resistant covers for exterior locations.
3. At door motors, use an enclosed, across-the-line type, magnetic reversing contactor, thermal overload protection, solenoid operated brake, limit switches, and remote control switches at locations indicated.
4. Control Switches:
a. Three push button type on interior, unless noted to be key activated.
b. Buttons marked, OPEN, CLOSE and STOP.
c. The OPEN and STOP Buttons: Momentary pressure or contact type.
d. CLOSE Button: Match existing being replaced- Momentary pressure or contact type.
e. Use key activated switch on exterior requiring constant pressure to operate.
f. Limit Switches: Manufacturers standard, position of switches readily adjustable.
5. Operation:
a. Open door upon activation of Open switch.
b. Close door-Match existing being replaced-upon activation of Close switch.
c. When the door is in motion, and the STOP button is pressed, door must stop instantly and remain in the stop position; from stop position, door may be operated in either direction by OPEN or
CLOSE button.
d. Limit switches automatically stop doors at their fully open and closed positions.
6. Push buttons full-guarded to prevent accidental operation.
08 36 13 - 6
7. Transformer: Use a control transformer in power circuits to reduce the voltage on control circuits to 120 volts or less.
8. Electrical Components: Conform to NFPA 70.
9. Safety Device:
a. Bottom door edge weather-strip safety device to immediately stop and reverse the door closing to full open position upon contact with an obstruction; door must open upon failure of device, component of device or component of control system.
b. Door closing circuit to be electrically locked out, and door to remain capable of manual operation until the failure or damage has been corrected.
c. Do not use as a limit switch.
d. Safety device connecting cable to motor to be flexible type SO cable with spring loaded automatic take up reel or equivalent device, as required for proper operation of the doors.
2.5 FINISHES
A. Steel:
1. Comply with NAAMM’s Metal Finishes Manual.
2. Clean surfaces free of scale, rust, oil and grease.
3. Galvanized Steel: Apply phosphate treatment.
4. Apply shop prime coat of corrosion inhibitive paint on exposed surfaces after fabrication.
5. Paint applied at the factory per manufacturer’s requirements.
6. Do not paint track, rollers, hinges, or locks.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install in accordance with approved shop drawings and manufacturer's instructions.
B. Locate anchors and inserts for tracks, brackets, motors, switches, hardware, and other accessories accurately.
C. Securely attach tracks to adjoining construction with not less than 9 mm (3/8 inch) diameter bolts, spaced near each end and not over 600 mm
(24 inches) apart.
D. Locate control switches where shown at least five feet above the floor line so that the operator will have complete visibility of the door.
E. Lubricate, properly adjust and demonstrate door to operate freely.
F. Upon completion, door openings to be weathertight and doors free from warp, twists, or distortion.
08 36 13 - 7
3.2 REPAIR
A. Repair zinc-coated surfaces both bare and painted, by the application of galvanizing repair compound.
B. Spot prime and apply finish paint to all repairs.
- - - E N D - - -
| SECTION 08 36 13 SECTIONAL DOORS |
| PART 1 - GENERAL |
| 1.1 DESCRIPTION |
| A. This section specifies electrically operated thermal insulated sectional overhead steel doors. |
| 1.2 MANUFACTURER'S AND INSTALLER'S QUALIFICATIONS |
| A. Manufacturer's regularly engaged in manufacturing items of type specified. |
| B. Installers under direct supervision of manufacturer's representative or trained personnel. |
| 1.3 SUBMITTALS |
| A. Manufacturer's Literature and Data: |
| 1. Brochures or catalog cuts. |
| 2. Manufacturer's installation procedures and instructions. |
| 3. Maintenance instructions, parts list. |
| B. Certificates: |
| 1. Attest door, anchors and hardware will withstand the horizontal loads specified. |
| 2. Attest door complies with thermal performance, air infiltration, and water infiltration requirements. |
| 1.4 APPLICABLE PUBLICATIONS |
| A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by the basic designation only. |
| B. American National Standards Institute and Door and Access Systems Manufacturers Association (ANSI/DASMA): |
| 102-04 Sectional Overhead Type Doors |
| C. American Society for Testing and Materials (ASTM): |
| A36/A36M-12 Structural Steel |
| A227/A227M-06(2011) Steel Wire, Cold-Drawn for Mechanical Springs |
| A229/229M-12 Steel Wire, Oil-Tempered for Mechanical Springs |
| A653-11 Steel Sheet, Zinc-Coated (Galvanized) or Zinc Iron Alloy Coated (Galvanized) by the Hot Dip Process |
| C1036-11e1 Flat Glass |
| C1363-11 Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus |
| E84-13a Surface Burning Characteristics of Building Materials |
| E283-04(2012) Determining the Rate of Air Leakage through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Difference Across the Specimen |
| E330-02(2010) Structural Performance of Exterior Windows, Curtain Walls, and Doors by the Uniform Static Air Pressure Difference |
| E331-00(2009) Water Penetration of Exterior Windows, Curtain Walls, and Doors by the Uniform Static Air Pressure Difference |
| D. National Electrical Manufacturer's Association (NEMA): |
| ICS 2-00(R2005) Industrial Control and Systems: Controllers, Contactors, and Overload Relays |
| ICS 6-93(R2006) Industrial Control and Systems Enclosures |
| MG 1-11 Motors and Generators |
| E. National Fire Protection Association (NFPA): |
| 70-11 National Electrical Code |
| F. National Association of Architectural Metal Manufacturers (NAAMM): |
| AMP 501 Metal Finishes Manual |
| PART 2 - PRODUCTS |
| 2.1 MATERIALS |
| A. Steel: Comply with ASTM A653 for forming operations; ASTM A36 for structural sections. |
| B. Hard Drawn Spring Wire: ASTM A227. |
| C. Oil Tempered Spring Wire: ASTM A229. |
| D. Glass: ASTM C1036. |
| 1. Clear Glass: Type 1, Class 1, Quality q5, 6 mm (1/4 inch) thick. |
| 2. Fabricated into sealed insulating glass 25 mm (one inch) thick. |
| E. Weather-strips, Gaskets, and Thermal Breaks: |
| 1. Neoprene, EPDM, PVC, silicone rubber, or other low conductance material. |
| 2. Standard with door manufacturer. |
| 2.2 DESIGN REQUIREMENTS |
| A. Wind Load: Design to withstand a horizontal or wind pressure in accordance with ASCE 7. |
| B. Thermal Performance: Minimum R Value of 12.0 for door when tested in accordance with ASTM C1363. |
| C. Air Infiltration: Maximum of 0.10 cfm at 24 Km (15 miles per hour) wind speed per foot of crack between door sections and door perimeter opening when tested in accordance with ASTM E283. |
| D. Water Infiltration: No infiltration when tested in accordance with ASTM E331. |
| E. Comply with ANSI/NAGDM 102, for an Industrial door and specified design criteria, inside face mounted with tracks at jambs set back a sufficient distance to provide a clear opening when door is in open position. |
| F. Operation-Cycle Requirements: Door components and operators to operate for not less than 10,000 cycles. |
| 2.3 FABRICATION |
| A. Steel Door Sections: |
| 1. Form of hot-dipped galvanized steel not lighter than 0.6 mm thick (24 gage) with longitudinal integral reinforcing ribs and flat bottom V-grooves install sections not less than 50 mm (2 inch) in thickness. Provide 2” thick double steel sandwich con... |
| 2. Meeting Rails: Interlocking joints with thermal breaks separating face sheets formed to provide weathertight closure and alignment for full width of door. |
| 3. Height of Sections: Not to exceed 600 mm (24 inches); may be varied to suit door height. |
| 4. Install glazing panels where indicated using rubber, thermal break gaskets standard with door manufacturer. |
| 5. Insulation to have a flame spread rating of not more than 25 and a smoke development factor of not more than 50 when tested in accordance with ASTM E84. |
| 6. Reinforced for hardware anchorage with not less than 2.6 mm (10 gage) galvanized steel. |
| B. Tracks: |
| 1. Manufacturer's standard formed of hot-dipped galvanized steel. |
| 2. Minimum 2.0 mm (14 gage) for 50 mm (2 inch) tracks and 2.5 mm (12 gage) for 75 mm (3 inch) tracks. |
| 3. Fabricate vertical tracks with adjustable brackets for mounting at incline to continuous steel angle wall bracket. |
| 4. Horizontal Track: |
| a. Reinforce with continuous steel angle anchored to vertical steel angle wall bracket and to ceiling angle supports. |
| b. Use vertical and cross or diagonal braced to obtain rigid installation of horizontal track. |
5. Use minimum 2.3 mm (13 gage) galvanized steel angles.
| C. Hardware: |
| 1. Manufacturers standard hinges, brackets, rollers, locking devices and other hardware required for a complete installation. |
| 2. Hinges and roller brackets minimum 2.3 mm (13 gage) galvanized steel. |
| 3. Use rollers with ball bearings and case-hardened races. |
| 2.4 ELECTRIC MOTOR OPERATORS |
| A. Complete with electric motor, machine cut reduction gears, steel chain and sprockets, magnetic brake, overload protection, brackets, push button controls, limit switches, magnetic reversing contactor, and other accessories necessary for proper oper... |
| B. Design: |
| 1. Design the operator for motor removal without disturbing the limit-switch timing and without affecting the emergency manual operators. |
| 2. Make provision for emergency manual operation of door by chain-gear mechanism in case of electrical failure. |
| 3. Arrange the emergency manual operating mechanism to immediately be put into and out of operation from the floor with a mechanical device to disconnect the motor from the operating mechanism when the emergency manual operating mechanism is engaged a... |
| 4. Provide interlock with motor to prevent motor from operating when manual locks are activated. |
| C. Motors: |
| 1. Conform to NEMA MG 1; maximum operation 3600 rpm. |
| 2. Use high starting torque, reversible type, of sufficient horsepower and torque output to move the door in either direction from door position, and produce door travel speed range of 0.20 to 0.30 m per second (8 to 12 inches per second), without exc... |
| 3. Single-phase motors must not have commutation or more than one starting contact. |
| 4. Motor Enclosures: Drip proof type or NEMA TENV type. |
| D. Controls: |
| 1. Control Equipment: NEMA 2. |
| 2. Control Enclosures: NEMA ICS 6, Type 12 or Type 4, except that contractor enclosures may be Type 1. Use weatherproof corrosion-resistant covers for exterior locations. |
| 3. At door motors, use an enclosed, across-the-line type, magnetic reversing contactor, thermal overload protection, solenoid operated brake, limit switches, and remote control switches at locations indicated. |
| 4. Control Switches: |
| a. Three push button type on interior, unless noted to be key activated. |
| b. Buttons marked, OPEN, CLOSE and STOP. |
| c. The OPEN and STOP Buttons: Momentary pressure or contact type. |
| d. CLOSE Button: Match existing being replaced- Momentary pressure or contact type. |
| e. Use key activated switch on exterior requiring constant pressure to operate. |
| f. Limit Switches: Manufacturers standard, position of switches readily adjustable. |
| 5. Operation: |
| a. Open door upon activation of Open switch. |
| b. Close door-Match existing being replaced-upon activation of Close switch. |
| c. When the door is in motion, and the STOP button is pressed, door must stop instantly and remain in the stop position; from stop position, door may be operated in either direction by OPEN or CLOSE button. |
| d. Limit switches automatically stop doors at their fully open and closed positions. |
| 6. Push buttons full-guarded to prevent accidental operation. |
| 7. Transformer: Use a control transformer in power circuits to reduce the voltage on control circuits to 120 volts or less. |
| 8. Electrical Components: Conform to NFPA 70. |
| 9. Safety Device: |
| a. Bottom door edge weather-strip safety device to immediately stop and reverse the door closing to full open position upon contact with an obstruction; door must open upon failure of device, component of device or component of control system. |
| b. Door closing circuit to be electrically locked out, and door to remain capable of manual operation until the failure or damage has been corrected. |
| c. Do not use as a limit switch. |
| d. Safety device connecting cable to motor to be flexible type SO cable with spring loaded automatic take up reel or equivalent device, as required for proper operation of the doors. |
| 2.5 FINISHES |
| A. Steel: |
| 1. Comply with NAAMM’s Metal Finishes Manual. |
| 2. Clean surfaces free of scale, rust, oil and grease. |
| 3. Galvanized Steel: Apply phosphate treatment. |
| 4. Apply shop prime coat of corrosion inhibitive paint on exposed surfaces after fabrication. |
| 5. Paint applied at the factory per manufacturer’s requirements. |
| 6. Do not paint track, rollers, hinges, or locks. |
| PART 3 - EXECUTION |
| 3.1 INSTALLATION |
| A. Install in accordance with approved shop drawings and manufacturer's instructions. |
| B. Locate anchors and inserts for tracks, brackets, motors, switches, hardware, and other accessories accurately. |
| C. Securely attach tracks to adjoining construction with not less than 9 mm (3/8 inch) diameter bolts, spaced near each end and not over 600 mm (24 inches) apart. |
| D. Locate control switches where shown at least five feet above the floor line so that the operator will have complete visibility of the door. |
| E. Lubricate, properly adjust and demonstrate door to operate freely. |
| F. Upon completion, door openings to be weathertight and doors free from warp, twists, or distortion. |
| 3.2 REPAIR |
| A. Repair zinc-coated surfaces both bare and painted, by the application of galvanizing repair compound. |
| B. Spot prime and apply finish paint to all repairs. |