Attachment 11 - RFI Responses West LA New Police Station Project 691-370.xlsx
XLSX spreadsheet 180 KB Posted
- Attached to
- Y1DA--New Police Station Bldg. 216, WLA, VA Greater Los Angeles Healthcare System, 691 (VA-25-00008848)
- Solicitation number
- 36C77625R0014
About this file
This document is a Request for Information (RFI) response tracking sheet for the West LA New Police Station Project. The solicitation (36C77625R0014) is an SDVOSB set-aside for constructing a 17,476 SF Police Station on the West Los Angeles VA Healthcare System campus, with a total building area of 23,000 square feet. The project involves building a new facility with site development, including staff and patrol parking, and is located in a historical district requiring compliance with National Historic Preservation Act guidelines.
The RFI tracking sheet contains 189 technical questions and responses covering multiple disciplines including architectural, structural, mechanical, electrical, interiors, and landscaping. Key technical clarifications address ceiling tile specifications, window types, access control systems, fire alarm manufacturers, and equipment installation details. Notable specifications include using a Hirsch access control system connected to the VA's existing network, EST 4 by Edwards for fire alarms, and a Mitsubishi VRF system as the HVAC basis of design. The VA will handle system programming, while the contractor will assist with installation and ensure compatibility with existing VA infrastructure.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
TECHNICAL QUESTIONS AND RESPONSES TRACKING SHEET
36C7762XX0000
West LA New Police Station Bldg. 216 Construction
| # | Version | Received | Answered | Discipline | Reference | Contractor Question | Preliminary VA Response |
| 1 | v1 | 7/7/25 | 7/30/25 | Interiors | Specs / Drawings | Specification: Ceiling Tile - Please clarify the difference between ceiling tile ACT 1 & 2 On Page AF602 it calls for both of them Optima #3524. | It is clearly stated ACT one is General Offices and ACT 2 is washable specific for locker room, bathrooms to deal with moister. |
ACT-1 is for general offices and is to be Armstrong Optima #3254, ACT-2 is to be Armstrong Optima Health Zone #3215PB. ACT-2 is to be washable and is specific to locker rooms and bathrooms to deal with moisture. ~Interiors 2 v1 7/7/25 7/30/25 Interiors Specs / Drawings Specification: Ceiling Tile – There is different between the FS on Page AF 603 and the RCP. Stair 1 @ 2 call for open ceiling at FS, but on Page AEL128 & A129 Show 2x4 grid and tile. There is no ACT in the staircases. Drawing AE126 & AE127 show open to ceiling above. AE128 is a mistake showing Legend ACT.
Refer to the RCP plans for the ceiling type. The room finish schedule will be updated. ~Interior
| 3 | v1 | 7/7/25 | 7/30/25 | Interiors | Drawings | Specification: Ceiling Tile – In rooms 136,144,142,138,139,140,141 at call for ACT 3 RFC call for GWP. | Refer to the RCP plans for the ceiling type. The room finish schedule will be updated. |
| 4 | v1 | 7/7/25 | 7/30/25 | Interiors | Drawings | Specification: Ceiling Tile – Room 137 FS call for ACT 2 RFC call for ACT 3. | Refer to the RCP plans for the ceiling type. The room finish schedule will be updated. |
| 5 | v1 | 7/7/25 | 7/30/25 | Architectural | Drawings | Specification: Ceiling Tile – At room 122 ceiling height is 10’ and the Copy Alcove 122A is 9’ please provide a detail for the elevation change (AE127) | Refer to detail 7/A-609, provide ACT ceiling at appropriate elevations per AE127, with ACT finish on both sides of transition. |
| 6 | v1 | 7/7/25 | 7/30/25 | Architectural | Specs / Drawings | Door Number 105B, Type SB, is indicated to be a 7/9 x 7/0 Sliding Bypassing 4 Panel Symmetrical interior door assembly. Who is the intended manufacturer of this assembly? Is this assembly automatic or manual operation? | Door manufacturer to be provided by contractor for VA review and approval. Door is manual unless specified otherwise in hardware schedule or specs. |
| 7 | v1 | 7/7/25 | 7/30/25 | Architectural | Specs / Drawings | Fixed Window Type E1 is indicated on the Window & Skylight Schedule (B99890-A05-0065) |
Schedule defines E1 as "HM" hollow metal. Spec. & details B1/C1 define this as a Wausau Aluminum INvent Window.
| Is this window to be hollow metal? Or per spec. and details? | Follow the specification and detail drawings. E1 is Wausau Aluminum INvent per B1/C1. | |||||||
| 8 | v1 | 7/7/25 | 7/30/25 | Architectural | Specs / Drawings | Fixed Window Type E1 is indicated on Window & Skylight Schedule (B99890-A05-0065) | ||
| Schedule defines E1 with an STC Rating of 35, while Aluminum Window Specification defines 31. Which prevails? | Use STC 35 as shown in the schedule. Confirm with acoustical consultant if needed. | |||||||
| 9 | v1 | 7/30/25 | Architectural | Specs / Drawings | Fixed Window Type D1 is indicated on Window & Skylight Schedule (B99890-A05-0065) | |||
| Schedule defines D1 as an aluminum window, however detailing of this assembly defines a cased borrowed lite frame. Is this to be a window, or borrowed lite. And~in either instance what Manufacturer and Model should these assemblies be? | D1 is a window per schedule. Use aluminum window per spec. Manufacturer/model not specified; basis of design is Wausau unless noted otherwise. | |||||||
| 10 | v1 | 7/30/25 | Architectural | Drawings | Fixed Window Type D1 is indicated on Window & Skylight Schedule (B99890-A05-0065) | |||
| Schedule defines D1 with an STC Rating of 41, is this accurate? Glazing will need to be around 1-7/16" thick to achieve rating. If this STC is required, recommend casing opening with aluminum brake shape and utilizing four-sided channel system (picture framed) atop brake shape casing. | STC 41 is correct. Use glazing thickness per acoustical consultant recommendation (approx. 1-7/16"). Picture-framed aluminum casing is acceptable. | |||||||
| 11 | v1 | 7/30/25 | General | Specs | Specification is written for a top-riding double girder but it also references CMAA 74 and the isometric view of the 3T crane shows a top-riding single girder crane. Please confirm that the 3T crane should be a TRSG. | The 3T crane should be a Top-Riding Single Girder (TRSG) as shown in the isometric. | ||
| 12 | v1 | 7/30/25 | General | Does the project require the cranes to have footwalks? It not feasible for a 3T TRSG crane but it is typical for a larger double girder like the 20T unless there is no access. | Not required for 3T TRSG. Required for 20T double girder if access is needed. | |||
| 13 | v1 | 7/30/25 | General | Do any of the spaces in which the crane will operate have an NEC Hazardous Classification? It was mentioned in the spec with reference to certain parts but not clear if it was applicable. | No hazardous classification is indicated for crane spaces in the documents. | |||
| 14 | v1 | 7/30/25 | General | 1A requires runway rails to be installed with center-to-center distance and elevation within +1/8 IN. Please clarify if the intent is to require a rail installation at lesser tolerances than CMAA requires. This could have an impact on the long-term performance of the crane. | Yes, this is stricter than CMAA. Maintain ±1/8" as specified. | |||
| 15 | v1 | 7/30/25 | General | Do the cranes require NRTL acceptance? We are under the understanding the current regulations at SLAC require this. | Yes, NRTL listing is required per OSHA and VA standards. | |||
| 16 | v1 | 7/30/25 | Electrical | Specs | 28-13-00-38. 2.1 Products General calls for a Hirsch enterprise access control system with Hirsch Primis software. Hirsch Primis is not the Hirsch FICAM-compliant software. Hirsch Velocity software is the FICAM-compliant software on the GSA-approved product list and is the software product upon which the Greater Los Angeles VA network has standardized. Please confirm Hirsch Velocity is the desired software. | Use Hirsch Velocity, which is FICAM-compliant and standard for GLA VA network. | ||
| 17 | v1 | 7/30/25 | Electrical | The GLA VA network runs all of their Hirsch access control systems off their enterprise server housed and managed by the VA in the WLA campus. Is the system at the new PD to be a separate standalone system with its own server and software or will this system be managed by the GLA-wide server? | It will connect to the GLA-wide server housed at WLA campus. | |||
| 18 | v1 | 7/30/25 | Electrical | The current standard reader at GLA facilities is the Hirsch ScramblePad reader with built-in contactless FICAM-ready PIV/CAC card readers. Are standard non-scrambling keypad readers preferred at the new PD site? | No. Use Hirsch ScramblePad readers with contactless FICAM-ready PIV/CAC compatibility. | |||
| 19 | v1 | 7/30/25 | Electrical | Drawings | Project drawings EC11 and EC112 indicate that video cameras will be a future procurement. Confirm that the VMS/NVR is part of scope, and only cameras are a future purchase. | Yes, VMS/NVR are part of the current scope. Only cameras are future procurement. | ||
| 20 | v1 | 7/8/25 | 7/30/25 | General | RFP | The RFP indicates various volumes and factors that need to be included with our response and there are conflicting page counts. Item 2.8.B.2 indicates that Volume 1 is limited to 15 pages. Volume I appears to consist of Factors 1-3. Item 2.8.C.1 indicates that Factor 1 is limited to 5 pages. Item 2.8.C.2 indicates that Factor 2 is limited to 10 pages. Item 2.8.C.3, Factor 3, does not have a page limit. Please clarify the page limit on each Factor and that the total page count for Voume 1 will be the total of each Factor page limit. | Volume I = 15 pages total. Factor 1 = 5 pages, Factor 2 = 10 pages, Factor 3 = no limit. Total = 15 pages max. | |
| 21 | v1 | 7/8/25 | 7/30/25 | General | RFP | Item 2.8.B.2 indicates Volume II shall not exceed 20 pages, and consists of Factor 4. Item 2.8.C.4, Factor 4 does indicate a page constraint. Please confirm the page limit for Volume II, Factor 4. | Volume II is limited to 20 pages for Factor 4. | |
| 22 | v1 | 7/8/25 | 7/30/25 | General | RFP | Is the above-referenced project open only to general contractors who are on the MATOC contract, or is it open to any bidder meeting the set aside requirement? If it is restricted to MATOC contract holders, is there a list of contract holders? | This solicitation is an SDVOSB set-aside that is being solicitated openly. No MATOC contract holders task orders are being issued to fulfill this requirement. ~Michael Nostitz, VA | |
| 23 | v1 | 7/9/25 | 7/30/25 | Geotech | Geotech Report | Please provide the geotechnical report. | Not included in current documents. Document to be provided along with this comment tracker. | |
| 24 | v1 | 7/9/25 | 7/30/25 | General | RFP | Can the superintendent or SSHO fulfil the CQC Systems Manager role? | No. Per spec 01 45 00, CQC Manager must be a separate individual from SSHO and Superintendent. | |
| 25 | v1 | 7/9/25 | 7/30/25 | General | Can you please identify the laydown area? Will there be enough space to store equipment, a temp trailer, temp restrooms, and 3 40-foot storage containers? | The contractor must create their laydown area at the construction site. | ||
| 26 | v1 | 7/9/25 | 7/30/25 | Electrical | Specs | Per Fire Alarm Specification 28 31 00-06, Section 2.1 – Equipment and Material, General, the approved manufacturer is listed EST 4 by Edwards. Please confirm if Siemens is an approved fire alarm manufacture for this project. | Siemens is not listed as an approved manufacturer in Section 28 31 00-06. Only EST 4 by Edwards is approved unless otherwise modified by addendum. | |
| 27 | v1 | 7/10/25 | 7/30/25 | General | When is the anticipated construction start date? | As soon as the NTP is issued | ||
| 28 | v1 | 7/10/25 | 7/30/25 | General | Please provide location of where construction workers are expected to park. | Parking location for construction workers is not identified in the documents. VA to designate and confirm. The contractor will be responsible to draw up a plan where they will place their job trailer and conex boxes on the construction site. Parking will be discussed after award with contractor. Michael Nostitz, VA, COR | ||
| 29 | v1 | 7/10/25 | 7/30/25 | General | With the construction site being rather close quarters, where does the government anticipate providing alocation for office trailers. | The contractor will be responsible to locate job trailer on the construction site. | ||
| 30 | v1 | 7/10/25 | 7/30/25 | General | What are the liquidated damages for the job? | Liquidated damages will not be included in this solicitation | ||
| 31 | v1 | 7/10/25 | 7/30/25 | General | How many weather days is allocated for the job? | Refer to Division 01 or VA contract requirements. | ||
| 32 | v1 | 7/10/25 | 7/30/25 | Geotech | Geotech Report | Please provide a geotechnical soils report. Several subgrade sections are missing information and refer to geotech report for section depths. | Document provided with amendment | |
| 33 | v1 | 7/10/25 | 7/30/25 | Architectural | Please provide hazardous material report. Are there any Asbestos containing pipes that connect to building utilities? | Hazardous materials report is not included. VA to confirm and provide if applicable. It will be the contractor responsibility to confirm the absence of all hazardous material at the site before construction activities begin. The VA doesn't have hazardous material report. Michael Nostitz, VA, COR | ||
| 34 | v1 | 7/10/25 | 7/30/25 | General | Drawings | Drawings indicate several underground utilities that will be installed by another adjacent to the project site. Notes the utilities are assumed to be completed by start of police station project. Please confirm finish date of adjacent project. | Fire Hydrants were installed by others. There will be no other projects that will interfere with the new police station construction. | |
| 35 | v1 | 7/10/25 | 7/30/25 | Interiors | Drawings | Confirm scope location of carpet CPT-2?. | CPT-2 is to be used in open office and conference room areas. Replace CTP-1 with CPT-2 in the following rooms: 107, 107A, 107B, 121, 122, 201, 215, and 222. | |
| 36 | v1 | 7/10/25 | 7/30/25 | Interiors | Drawings | Confirm scope location of corner guards CG-2? | Use GG-1 throughout, CG-2 is not used. | |
| 37 | v1 | 7/10/25 | 7/30/25 | Structural | Specs | Please provide concrete reinforcing specifications. In concrete? | Relevant information regarding reinforcing steel is included in 03 30 00 specifications. | |
| 38 | v1 | 7/10/25 | 7/30/25 | Architectural | Drawings | Confirm scope location of roof type 3 per 3/A-609. | Roof Type 3 is shown in detail 3/A-609. Refer to roof plan for extents. | |
| 39 | v1 | 7/10/25 | 7/30/25 | Architectural | Drawings | Confirm scope location of Exterior Wall Joint Seal: Basis of Design: Seismic Colorseal as manufactured by Sika Emseal. | Seismic Colorseal is basis of design per spec. Refer to exterior wall sections for application locations. | |
| 40 | v1 | 7/10/25 | 7/30/25 | Interiors | Drawings | Confirm all items in furniture and equipment schedule identified with V/V or L_RE to be provided and installed by the VA. | Correct. The items listed as V/V and L_RE items uipment schedule are to be provided and installed by the VA. | |
| 41 | v1 | 7/10/25 | 7/30/25 | Interiors | Drawings | Confirm Casework (By VV) per note AF26 drawing AQ101 is by VA. B1 & E1/AE433 appears to show by contractor. | Casework is by contractor. | |
| 42 | v1 | 7/10/25 | 7/30/25 | Interiors | Drawings | Confirm Casework (By VV) per note AF26 drawing AQ101 is by VA. C5/AE435 appears to show by contractor. | Casework is by contractor. | |
| 43 | v1 | 7/10/25 | 7/30/25 | Interiors | Specs / Drawings | Confirm 12 32 00 Manufactured Wood Casework is per B1 & E1/AE433. | Correct. | |
| 44 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | Please provide spec for rated fire shutter per keynote FP01 drawing LS101. | Life Safety Plan is out of date fire protection at Stair 1 is now being provide by wall and double door. Reference Sheet AE114. | |
| 45 | v1 | 7/10/25 | 7/30/25 | Architectural / Mechanical / Structural | Drawings | Please provide detail of structure framing of [AS40] Mechanical screen to 3 sides per AS100. | See detail 3/S610 for structural framing at the on grade 3-sided mechanical screen | |
| 46 | v1 | 7/10/25 | 7/30/25 | Architectural | Drawings | Structure finish appears to be metal panel type 2 per [AE15] concrete transformer enclosure on AE202. | Confirmed. Metal panel type 2 is used for transformer enclosure per AE202. | |
| 47 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | Confirm “A sample warranty letter must be included with bid package or bid may be disqualified.” per 09 67 23.20 RESINOUS (EPOXY BASE) WITH VINYL CHIP BROADCAST (EPY-0/EPB-0) 1.7.B Warranty | Yes, a sample warranty letter must be included with the bid per Section 09 67 23.20, Part 1.7.B. | |
| 48 | v1 | 7/10/25 | 7/30/25 | Mechanical | Specs | What is the manufacturer and model number basis of design for the VRF system on this project. Different manufacturers have different piping requirements such as a 2-pipe or 3-pipe systems. The difference can be substantial in pricing the refrigerant piping on this project. Please have the Engineer of Record provide manufacturer and model numbers for all HVAC equipment. | Mitsubishi VRF system is basis of design. Refer to mechanical schedules and details on MP101–MP102. | |
| 49 | v1 | 7/10/25 | 7/30/25 | General | Please confirm finish date of adjacent project. | Project is complete. | ||
| 50 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | Please see substitution request for 09 67 23.20 Resinous Epoxy Base With Vinyl Chip Broadcast (RES 2). | Substitution request under review. Contractor to submit full technical data for evaluation. | |
| 51 | v1 | 7/10/25 | 7/30/25 | Architectural / Structural | After reviewing the current roof insulation specifications, our team has identified a potential Value Engineering (VE) opportunity that we believe could benefit the project. We would like to propose Lightweight Insulating Concrete (LWIC) as an alternative roof insulation system. LWIC offers several advantages, including improved durability, enhanced thermal performance, and long-term cost savings. Additionally, it provides excellent slope-to-drain capabilities and can help streamline the installation process. This being a police station, the emphasis on security is magnified and with our LWIC system, we essentially bond to the substrate ensuring no leaks/potential security breach. We are confident that this VE option meets or exceeds the performance requirements outlined in the project documents while offering potential cost and schedule efficiencies. | LWIC is not currently specified. Contractor may submit as a formal VE proposal for review. Must meet performance and security requirements. |
(KPFF Response:) Structural roof is concrete fill over metal deck. Adding a layer of LWIC to replace the rigid insulation on top of the concrete fill would increase the weight of the roof beyond the original loading criteria and may trigger a re-design of the primary structure. LWIC used in lieu of structural concrete is not sturcturally acceptable.
| 52 | v1 | 7/10/25 | 7/30/25 | Electrical | What is the VA’s preferred make and model of CCTV camera that should be used? We are thinking of compatibility with the existing CCTV system currently in operation at the VA. | VA to provide camera make/model under separate procurement. Contractor to ensure system compatibility with existing VA CCTV infrastructure. | ||
| 53 | v1 | 7/10/25 | 7/30/25 | General | Who is the VA’s preferred vendor/manufacturer for access controls? | There is no sole source vendor for access control. Hircsh | ||
| 54 | v1 | 7/10/25 | 7/30/25 | Electrical | Who is the VA’s preferred vendor/ manufacturer for fire alarm? | EST 4 by Edwards is the approved manufacturer per Specification 28 31 00-06. | ||
| 55 | v1 | 7/10/25 | 7/30/25 | Electrical | Who is the VA’s preferred vendor/manufacturer for Security Access Detection? Is there currently a system in the Hospital that this new system needs to be compatible with? | Hirsch system is standard. System must be compatible with existing VA infrastructure. | ||
| 56 | v1 | 7/10/25 | 7/30/25 | Structural | Specs | Specification section 05 12 00 Structural Steel part 1.5 A and B state that the steel fabricator and installer need to be AISC certified. Will the VA accept a steel fabricator and erector who is not AISC certified but is City of Los Angeles Certified through the City’s Department of Building and Safety program? Here is a link to the certification guidelines guidelines-for-approval-as-fabricator.pdf | See arch response to question 97. All variation requests to the contract documents shall be formally submitted for VA review. | |
| 57 | v1 | 7/10/25 | 7/30/25 | Interiors | Drawings | Sheet AF602 ACT-1 and ACT-2 both call for Armstrong Optima #3254. Notes are different but specified tile is exactly the same. Please clarify the difference between ACT-1 and ACT-2. | ACT-1 is for general offices and is to be Armstrong Optima #3254, ACT-2 is to be Armstrong Optima Health Zone #3215PB. ACT-2 is to be washable and is specific to locker rooms and bathrooms to deal with moisture. | |
| 58 | v1 | 7/10/25 | 7/30/25 | Architectural / Interiors | Drawings | There is a conflict between the enlarged reflected ceiling plan on sheet AE128 and AE129 and the room finish schedule on sheet AF603. Sheet AF603 calls for CP-0 at ceilings for Stair 1 and Stair 2. The enlarged RCP on sheets AE128 & 129 show what appears to be 2x4 ceiling tile. Please clarify if the VA would like ACT or painted Ceiling | Refer to the RCP plans for the ceiling type. The room finish schedule will be updated. | |
| 59 | v1 | 7/10/25 | 7/30/25 | Architectural / Interiors | Drawings | There is a conflict between the enlarged reflected ceiling plan on sheet AE127, and the room finish schedule on sheet AF603. The enlarged RCP on sheet AE127 shows Gypsum ceilings for rooms 136,138-142 and 144. The room finish schedule on sheet AF603 calls for ACT 3 for all these rooms. Please clarify which ceiling finish is required. | ACT-3 to be installed in rooms 140, 141, 142 & 144, at heights indicated on plans. GWP ceilings to be provided at rooms 136, 138 & 139. The room finish schedule will be updated accordingly. | |
| 60 | v1 | 7/10/25 | 7/30/25 | Architectural / Interiors | Drawings | Room finish schedule on sheet AF603 calls for ACT 2 in room 137. The reflected ceiling plan on sheet AE127 calls for ACT-3. Please clarify which ACT is required in room 137. | ACT-2 to be installed in room 137. | |
| 61 | v1 | 7/10/25 | 7/30/25 | Architectural | Drawings | The copy Alcove (room 122A) has a ceiling height of 9 feet. The Patrol office (room 122) has a ceiling height of 10 feet. No framed header is shown between the 2 ceiling heights. Please provide a detail of the difference between the two ceiling heights since there is not a header dividing the two areas. | Refer to detail 7/A-609, provide ACT ceiling at appropriate elevations per AE127, with ACT finish on both sides of transition. | |
| 62 | v1 | 7/10/25 | 7/30/25 | Electrical | Specs | Specification section 23 09 23 part 1.1.F states that the existing DDC is by Schneider Electric. Please confirm that the existing control system integrator is Siemens and that the referenced specification paragraph is incorrect. | Specification 23 09 23 appears to be incorrect. Siemens is the current integrator. Schneider Electric will be the DDC for the new police station not Siemens. | |
| 63 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | Specification section 07 42 13.23 part 2.1.B lists Alucobond as the wall panel manufacturer. It also says, “or approved equal”. We’d like to confirm that the VA does not have a sole source justification for Alucobond, and that the VA will accept any manufacturer that meets the buy American act, and that meets and/or exceeds the salient characteristics as laid out in the specifications? | Confirmed. The specifications provide required performance criteria for MCM panels and allow contractors to offer alternative panel options for VA review and approval. | |
| 64 | v1 | 7/10/25 | 7/30/25 | Landscaping | Drawings | Please provide clarification on the landscaping scope of work. The irrigation notes on sheet L1.10 states: “All proposed landscape areas shown on plan shall be irrigated. Square footage for the various planning areas are noted within the Landscape Planting Legend. Provide Irrigation to all adjacent areas during construction and restore to revised site layout once hydro-seed is placed.” A Landscape Planting Legend was not provided. All plants have been crossed out on sheet L5.10. Based on these facts we assume planting is not included in the scope of this project other than Hydro-seeding. | ||
| Please clarify what adjacent areas need irrigation during the course of the project. | Landscape Architect proposed the existing palms be reused elsewhere on the site since they are quite large and expensive to purchase – perhaps that is no longer the case, VA to confirm. Landscape architect was asked to just show hydroseed to all disturbed areas – nothing more. There was an irrigation plan with valves and mainline routing in the earlier submittals, but we believ the VA has removed irrigation from the scope, VA to confirm. We suggest that it is now design/build. | |||||||
| 65 | v1 | 7/10/25 | 7/30/25 | Landscaping | Drawings | Please confirm that the irrigation piping layout for the new hydro seeded lawn is a deferred submittal and will need to be designed and submitted by the landscaper after the project is awarded. | Yes, irrigation layout is a deferred submittal by landscape contractor. | |
| 66 | v1 | 7/10/25 | 7/30/25 | General | Based on the recommendations of the BST report, please confirm that a full time Archeologist during all digging operations will not be required for this project. | Based on BST report, full-time archaeologist is not required. Spot checks may be performed. | ||
| 67 | v1 | 7/10/25 | 7/30/25 | General | Specs / Drawings | Specification Section 00 01 15 List of Drawings includes a list of page numbers that are not in the drawings issued by the VA, for example the spec lists L1, L2 and L3, the plans only contain L1.10 and L5.10. The spec also lists 30-1 through 30-6, will the VA be issuing these pages or can these pages be ignored? | These pages are not part of the issued set. They can be disregarded unless issued by addendum. | |
| 68 | v1 | 7/10/25 | 7/30/25 | General | Specs | Per spec section 01 00 00 1.22 Tests, the contractor is to provide a commissioning plan. However, Specification Section 01 91 00 Commissioning in part 1.8.C states that the VA will engage the commissioning agent. The commissioning agent is the one who writes the commissioning plan. Plese confirm that the contractor will not be writing the commissioning plan, and we can disregard part 1.22 Tests. | CxA will provide commissioning plan. Contractor does not need to prepare it. | |
| 69 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | Per the RFP states under Factor 3 Professional Qualifications that no one individual may perform more than two of the key staffing positions. Spec section 01 35 26 part 1.9.C states that the SSHO has to be a separate qualified individual from the Prime contractors Superintendent and/or quality control manager with duties only as the SSHO. Which guidance are we to go by? Can the superintendent, if qualified, also serve as the SSHO as long as a separate individual serves as the QC Manager? | SSHO must be a separate individual. Superintendent and QC Manager may be the same person. | |
| 70 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | Spec section 01 45 00 part 3.4.B states that the QC manager may also serve as the project superintendent. Please confirm that based on this spec and RFP Factor 3, the VA will only require two personnel on site to run this project. Superintendent who also serves as QC & the SSHO | Confirmed. Superintendent may also serve as QC Manager. SSHO must be separate. | |
| 71 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | Spec Section 01 35 26 part 1.9.E states that all construction workers, which includes all subcontractors, must have been issued the OSHA 10 within the last 5 years. The OSHA 10 does not expire and is valid for life. Will the VA accept workers who have received their OSHA 10 longer than 5 years ago? | VA requires OSHA 10 within 5 years. Older cards are not acceptable. The purpose of the 5 year is to insure the worker has the lastest and greatest changes within the OSHA 10 training. | |
| 72 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | Spec Section 01 35 26 part 1.11.B requires a monthly job site inspection by a Certified Safety Professional or a Construction Safety and Health Technician. Will the VA be enforcing this requirement? | Yes, monthly inspections by certified safety personnel will be enforced. There will also be daily safety inspection that are documented by the GC. Weekly tailgate safety talks will also be required and documented with roster of all subs and GC employees. The VA will perform a weekly safety site walk performed by the COR or other VA repersentative. | |
| 73 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | This project includes sustainability specifications 01 81 13. Is the VA going for some kind of LEED rating? The spec requires 50% of construction waste to be diverted, are there consequences if this is not achieved or is this just the goal? | This is a requirement. Contractor must document compliance. | |
| 74 | v1 | 7/10/25 | 7/30/25 | Architectural | Specs | The sustainability specifications require building flush out prior to occupancy. Part 3.1.A.4 does not state how long the flush out should be. Will the VA provide a duration for this activity? |
The specifications under Section 07 84 00 require that firestopping installers are from a firm that has been approved by FM Global or been evaluated by UL and found to comply with UL requirements. We respectfully request clarification on the following: Would the VA accept a firestopping installer specifically for fire caulking, who has been trained and certified by the firestopping product manufacturer (e.g., Hilti, 3M, STI) in lieu of the qualifications listed for inspectors?
| Manufacturer-trained installers often receive hands-on instruction specific to the approved firestop systems being used on the project. Allowing such personnel to perform installations may help ensure compliance with UL-listed systems while maintaining schedule and cost efficiency. | Building Flush out period is two weeks UON. Firestopping installers shall be approved by FM Global or been evaluated by UL and found to comply with UL requirements. | |||||||
| 75 | v1 | 7/10/25 | 7/30/25 | Architectural | Drawings | We are unable to locate at detail that shows the hollow metal door and jamb conditions at the Terra Cotta panels on the exterior walls. Can the VA please provide a detail showing hollow metal door jamb and head details at the terra cotta panels? | Detailing efforts will take more time than allotted for comment responses. | |
| 76 | v1 | 7/11/25 | 7/30/25 | General | Regarding past performance, it has been our experience that a contracting official is reluctant to complete a PPQ when an official CPARS evaluation exists, since this is considered the “official” evaluation for the project. Would the VA consider allowing the offerors to include the CPARS evaluation for a project in lieu of the Past Performance Questionnaire contained within the solicitation documents? | CPARS evaluations should be used for all projects that contain them. The PPQ is offered for any project submitted to demonstrate past performance that does not have a CPARS evaluation. ~Michael Nostitz, VA, COR | ||
| 77 | v1 | 7/11/25 | 7/30/25 | Architectural | Drawings | On sheet AE202 elevation C2 2nd floor between column lines 1 and 2, the exterior wall pattern, where it is labeled AE07, does not match the legend. There are heavy vertical lines, with solid vertical lines between them. Which material type is this supposed to be? There are also several locations on elevation E2 where this same pattern occurs such as 2nd floor adjacent to windows between column lines D and E, also on the corner of the building 2nd floor column line E. | The AE07 pattern represents metal panel system MP-1. Refer to AE202 and AE410 for confirmation. | |
| 78 | v1 | 7/11/25 | 7/30/25 | General | Because of the potential for project overruns/delays on other projects, can we list more than one individual per position for Technical Factor 3, in case one or more individuals are not available? | Yes, multiple individuals may be listed per position to ensure availability. | ||
| 79 | v1 | 7/11/25 | 7/30/25 | General | Factor 3 Professional Qualifications states that the QC Manager is required to have a degree with a minimum of 5 years’ experience. Specification section 01 45 10 part 3.4.B states that the QC System Manager also serves as the Superintendent. Given that most superintendents have extensive relevant experience but lack a degree, will the VA consider a well-qualified superintendent with relevant experience as a quality control manager, in lieu of the degree requirement for QC Manager? | No. QC Manager must meet the degree and experience requirements per RFP. | ||
| 80 | v1 | 7/14/25 | 7/30/25 | Landscaping | Drawings | Please provide irrigation as-built plans. | See response to comment 64. | |
| 81 | v1 | 7/14/25 | 7/30/25 | Landscaping / Civil | Drawings | There is a discrepancy between sheets L1.10 and C1.20 regarding the legends or callouts for trees to be removed, relocated, or protected in place. Please clarify the status of these trees more clearly on the plans. | Trees identified on sheet L1.10 are to be evaluated for relocation or permanent removal. | |
| 82 | v1 | 7/14/25 | 7/30/25 | Landscaping | Drawings | Please provide size, image & new location of trees to be relocated. | Requires input from the VA. This will be determined when construction commences. Michael Nostitz, VA, COR | |
| 83 | v1 | 7/14/25 | 7/30/25 | Landscaping | Drawings | There is irrigation note shown on L1.10, which requires irrigation for all proposed landscape. However, there is no irrigation plan provided. Please provide irrigation plan. | See response to comment 64. | |
| 84 | v1 | 7/14/25 | 7/30/25 | Landscaping | Please clarify landscape maintenance period. | Maintenance period is 90 days after final acceptance. | ||
| 85 | v1 | 7/14/25 | 7/30/25 | General | Volume III: Administrative Information, page 12 of 92 after (e. paragraph): |
There is a note reading “The offeror shall provide their response to FAR 52.229-11 (d)”
| I cannot find this regulation on RFP – can you please provide or guide me as where to find it. | FAR 52.229-11 is located beginning on page 31 and ending on page 32 of the RFP. ~Michael Nostitz, VA, COR | |||||||
| 86 | v1 | 7/14/25 | 7/30/25 | Architectural | Specs | Please see substitution request for Metal Wall Panels (Corrugated) | Submit full technical data for review. Substitution may be accepted if compliant. | |
| 87 | v1 | 7/14/25 | 7/30/25 | Architectural | Drawings | Will Reglet & Counter flashing be required at exterior walls above roofing termination? F1/AE313 | Yes, provide Reglet and Counter flashing per detail F1/AE313. | |
| 88 | v1 | 7/14/25 | 7/30/25 | Architectural | Drawings | Need detail at soffit to fascia transition at wall section Grid 3 & Grid C. F9/AE313 | Refer to detail F9/AE313 for soffit-to-fascia transition. | |
| 89 | v1 | 7/14/25 | 7/30/25 | Architectural | Drawings | Please clarify base flashing notes on AE314 with detail F5/A-606; Does the metal flashing extend |
below grade, or only the aluminum faced membrane flashing? If the aluminum flashing is going to
| contact soil, we recommend changing it to stainless steel. | Only membrane flashing extends below grade. Metal flashing terminates above grade. | |||||||
| 90 | v1 | 7/14/25 | 7/30/25 | Architectural | Drawings | Typical window head flashing FH-3 may need to be modified to allow for installation of sealant & backer rod by glazing contractor. (Consider a similar version of FJ-1) | Contractor may propose alternate detail for review. Must maintain weatherproofing. | |
| 91 | v1 | 7/14/25 | 7/30/25 | Architectural | Drawings | Coordinate flashings with glazing sealant & backer rod at corrugated metal panels. (See D5/A-611) | Coordinate with glazing contractor. Submit shop drawings for review. | |
| 92 | v1 | 7/14/25 | 7/30/25 | Architectural | Specs | Specification 07 72 00 – 2.2 – C is calling for an aluminum scuttle hatch, 32” x 32”. This will not meet building code. Plans note a Bilco Type S-20 scuttle. The S-20 is a galvanized steel, 30” x 36” scuttle hatch that will meet code requirements. Please confirm that we are providing the S-20 and disregarding the 07 72 00 hatch specification. Confirm safety railing is not required. Confirm the hatch will be installed on a flat-roof condition, and will not require additional curb flashing. | Provide Bilco S-20 galvanized steel hatch (30"x36"). Safety railing not required. | |
| 93 | v1 | 7/14/25 | 7/30/25 | Architectural / Structural | Drawings | Please confirm the structural support structure for the mechanical equipment screen corrugated panels. Will there be additional horizontal girts as shown in detail C8/A-615? | Provide horizontal girts as shown in detail C8/A-615. | |
| 94 | v1 | 7/14/25 | 7/30/25 | Landscaping / Civil | Drawings | Please revise demo and landscape plans regarding existing trees. Landscape plan show relocate of trees per L1.10 within building footprint. Demo plan C1.20 shows demo and remove. | See response to comment 64. | |
| 95 | v1 | 7/14/25 | 7/30/25 | Civil | Confirm if existing concrete K-rails not shown on plans are to be removed by contractor or owner? | K Rails to be removed by contractor. | ||
| 96 | v1 | 7/14/25 | 7/30/25 | Civil | Drawings | Please revise Paving Plan C1.50 to show all new asphalt. Demo Plan C1.20 shows to remove all existing asphalt. | C1.50 identifies areas with new asphalt and areas with slurry seal. | |
| 97 | v1 | 7/14/25 | 7/30/25 | Architectural / Structural | Specs | 05 12 00 STRUCTURAL STEEL FRAMING section 1. Quality Assurance. Requires AISC certification, will LA City certification be accepted. | No. AISC certification is required per spec 05 12 00. | |
| 98 | v1 | 7/14/25 | 7/30/25 | Civil | Drawings | Please show limits of handrail at concrete ramp and stairs per AS100. Also are the handrail on one side or both sides. | Show handrails? Provide handrails on both sides of ramps and stairs per ADA and AS100. |
| 99 | v1 | 7/14/25 | 7/30/25 | Civil | Drawings | Please provide asphalt to landscape edge detail. | Refer to detail 13 on sheet C5.00 for asphalt-to-landscape transition with a flushed curb. |
| 100 | v1 | 7/14/25 | 7/30/25 | Electrical | Access Control System is Hirsch™ new panels connected to VA’s existing Hirsch Server via VA’s corporate network, correct? | Confirmed. Hirsch panels connect to VA’s existing server via VA network. | |
| 101 | v1 | 7/14/25 | 7/30/25 | Electrical | Do we help VA programming new Hirsch panels or does VA handle that? | VA will handle programming of new Hirsch panels. Contractor to coordinate installation only. | |
| 102 | v1 | 7/14/25 | 7/30/25 | Electrical | Drawings | DWG Sheet E-502, Detail 2 shows: Electric Strikes. Will these be the actual electrified door hardware or will it be Mortise/Cylindrical Locksets with built-in Request to Exit? Electrified Locksets are ALWAYS the more cleaner and more secure way to go. | Electrified locksets with built-in Request to Exit are preferred for security and cleanliness. |
| 103 | v1 | 7/14/25 | 7/30/25 | Electrical | Drawings | DWG Sheet E-502, Detail 2 shows: Request to Exit Pushbutton, Request to Exit PIR Motion Sensor, and Siren. Are these required? | Yes, all components shown are required per VA physical security standards. |
| 104 | v1 | 7/14/25 | 7/30/25 | Electrical | For Intercom System, is “Video Intercom” (video & voice) what is actually required? | Reference specification 28 26 00 for intercom system requirements. | |
| 105 | v1 | 7/14/25 | 7/30/25 | Electrical | For Intercom System, is Aiphone™ acceptable? If not, please specify brand? One Master Station only, correct? | Yes, please use Aiphone as it is used throughout the VA Campus. | |
| 106 | v1 | 7/14/25 | 7/30/25 | Electrical | For Intrusion System, is Bosch™ acceptable? If not, please specify brand. | Requires input from the VA. Bosch is acceptable. Michael Nostitz, VA, COR | |
| 107 | v1 | 7/14/25 | 7/30/25 | Electrical | Is there any integration required between Access Control and Intrusion? Or, are these systems to operate separately? | Systems are to operate separately. No integration required. | |
| 108 | v1 | 7/14/25 | 7/30/25 | Architectural | Specs | Under POLYVINYL CHLORIDE (PVC) ROOFING Section 07 54 19 1.1 Summary, it states that the PVC membrane will adhere to the insulated concrete deck. Confirm spec reads insulated concrete deck, is it indeed lightweight insulating concrete, drawings do not show this. Please provide insulated concrete manufacturer per Section 03 5216. | LWIC is not shown in drawings. If used, submit manufacturer per Section 03 52 16 for approval. |
| 109 | v1 | 7/15/25 | 7/30/25 | Electrical | DWG Sheet ET111, General Notes 6 indicates access system is Hirsch with Primis Software. This is different than what was discussed at jobwalk. At jobwalk it was indicated new Hirsch panels would connect to VA’s network. Please confirm. a) Hirsch panels onto VA’s network? b) Or, Hirsch panels with a “separate” Primis Software. c) If above “b”, is Primis on a physical PC (by VA), virtual environment (by VA), or Cloud-based (ACaaS)? | This is same comment as comment #188. The Hirsch system will be on the VA network and will not require a separate system. The contractor will be responsible to program and provide all necessary componets for a 100% operating system for construction completion turn over. | |
| 110 | v1 | 7/15/25 | 7/30/25 | Electrical | Drawings | DWG Sheet E-401, Key Notes 5 indicates (2) 16-Door Access Panels. Hirsch does not make a 16-Door Panel (they make 8-Door). Please specify whether it’s: a) (4) 8-Door Panels to handle BASE BID = (25) Doors. b) Or, (3) 8-Door Panels to Handle BASE BID (25 Doors) less ALT2 (5 Doors) = (20) Doors. c) Or, (4) 8-Door Panels to Handle BASE BID (25 Doors) less ALT2 (5 Doors) = (20) Doors. | Provide (4) 8-door access control panels. |
| 111 | v1 | 7/15/25 | 7/30/25 | Electrical | Is there a VA standard for an access control system or preferred system? | Hirsch | |
| 112 | v1 | 7/15/25 | 7/30/25 | Electrical | What is the current access control system at GLAVA? | Hirsch | |
| 113 | v1 | 7/15/25 | 7/30/25 | Electrical | Is a mobile credential an option? | Not needed. | |
| 114 | v1 | 7/15/25 | 7/30/25 | Electrical | Is there a surveillance camera preference? | Camera system will be installed by others | |
| 115 | v1 | 7/15/25 | 7/30/25 | Electrical | What are the current cameras manufacturers installed at GLAVA | Camera system will be installed by others | |
| 116 | v1 | 7/15/25 | 7/30/25 | Electrical | What is the current video management system installed at GLAVA? | Camera system will be installed by others | |
| 117 | v1 | 7/15/25 | 7/30/25 | Electrical | HID is the specified reader for this project? | Yes. | |
| 118 | v1 | 7/15/25 | 7/30/25 | Electrical | What is the current CAC CARD manufacturer used? | The VA uses PIV | |
| 119 | v1 | 7/15/25 | 7/30/25 | Electrical | Do the readers need to be FICAM compliant? | Yes, all readers must be FICAM compliant. | |
| 120 | v1 | 7/15/25 | 7/30/25 | General | Section A.3 Price/Cost Schedule includes a “Grand Total”. Since we’re providing a base bid plus 3 additional prices that will include the base bid excluding 3 different scopes of work, please advise as to how to complete that section. | Enter “N/A” on the total line if all CLINs are deducts. Do not sum deductive CLINs. | |
| 121 | v1 | 7/15/25 | 7/30/25 | Architectural / Mechanical | Specs | Please provide spec for LOUVERS AND VENTS. 08 90 00 per Exterior Building Envelope Notes #4.2 on S310 | Provide Specification 08 90 00 in upcoming addendum. |
| 122 | v1 | 7/15/25 | 7/30/25 | Architectural | Specs | Please provide spec for EXTERIOR SUN CONTROL DEVICES. 10 70 00 per Exterior Building Envelope Notes #4.4 on S310 | Provide Specification 10 70 00 in upcoming addendum. |
| 123 | v1 | 7/15/25 | 7/30/25 | Civil | Drawings | Confirm scope of 8” W and SD line to be demoed per Demo Plan C1.20. Utility Plan C1.40 and Demo Plan C1.20 do not show any reroute. | Underground utility investigation is needed to determine if the existing 8" W and SD lines are active. Contractor to verify and coordinate with the VA and design team prior to performing any demo and/or relcation work. |
| 124 | v1 | 7/15/25 | 7/30/25 | Architectural / Structural | Drawings | What is the Heights for all the CMU walls due to no height being given? | Reference Sheets AE201, AE 202 and AE 302 for building elevations and section for CMU wall heights. |
| 125 | v1 | 7/15/25 | 7/30/25 | Structural | Drawings | What is the type and thickness of the topping slab for the deck please? | Typical concrete deck thicknesses are called out 1/S703 with deck tags on the plan. |
| 126 | v1 | 7/15/25 | 7/30/25 | Interiors | Drawings | Please clarify the difference between ceiling tile ACT 1 & 2 On Page AF602 it calls for both of them Optima # 3254. | ACT-1 is for general offices and is to be Armstrong Optima #3254, ACT-2 is to be Armstrong Optima Health Zone #3215PB. ACT-2 is to be washable and is specific to locker rooms and bathrooms to deal with moisture. |
| 127 | v1 | 7/15/25 | 7/30/25 | Architectural / Interiors | Drawings | There is different between the FS on Page AF 603 and the RCP. Clarify please | Refer to the RCP plans for the ceiling type. The room finish schedule will be updated. |
| 128 | v1 | 7/15/25 | 7/30/25 | Architectural / Interiors | Drawings | Stair 1 @ 2 call for open ceiling at FS, but on Page AEL128 & A129 Show 2x4 grid and tile. Clarify please | Refer to the RCP plans for the ceiling type. The room finish schedule will be updated. |
| 129 | v1 | 7/15/25 | 7/30/25 | Architectural / Interiors | Drawings | In rooms 136,144,142,138,139,140,141 at call for ACT 3 - RFC call for GWP. Clarify please | Refer to the RCP plans for the ceiling type. The room finish schedule will be updated. |
| 130 | v1 | 7/15/25 | 7/30/25 | Architectural / Interiors | Drawings | Room 137 FS call for ACT 2 RFC call for ACT 3. Clarify please | Refer to the RCP plans for the ceiling type. The room finish schedule will be updated. |
| 131 | v1 | 7/15/25 | 7/30/25 | Architectural | Drawings | At room 122 ceiling height is 10’ and the Copy Alcove 122A is 9’ please provide a detail for the elevation change (AE127) Clarify please | Provide a framed soffit or transition detail. Coordinate with AE127. |
| 132 | v1 | 7/15/25 | 7/30/25 | Mechanical | Noise and Vibration Testing is listed with the Systems to be Commissioned. I have used Veneklasen when specific requirements are identified. Does the client want the CxA to include this in our proposal or have it performed when all equipment is operating at the design levels if needed? | Include in proposal. Testing to be performed when equipment is operating at design levels. | |
| 133 | v1 | 7/15/25 | 7/30/25 | Architectural / General | Is this a LEED project? | No, this is not a LEED-certified project. | |
| 134 | v1 | 7/15/25 | 7/30/25 | General | OPR – We can develop the Draft OPR as Add/Alternate. Does the client want a price for that? | Yes, provide a price for Draft OPR as an Add/Alternate. | |
| 135 | v1 | 7/15/25 | 7/30/25 | General | Commissioning Responsibility Matrix: OPR & BOD - CxA is required to compare both documents for continuity and completeness. The BOD updates will need to be coordinated with the AOR. We can update both as the project makes changes. | Yes, CxA may update both documents in coordination with AOR. | |
| 136 | v1 | 7/15/25 | 7/30/25 | Mechanical | What is the manufacturer and model number basis of design for the VRF system on this project. Different manufacturers have different piping requirements such as a 2-pipe or 3-pipe systems. The difference can be substantial in pricing the refrigerant piping on this project. Please have the Engineer of Record provide manufacturer and model numbers for all HVAC equipment | Mitsubishi VRF system is basis of design. Refer to MP101–MP102 for layout and details. | |
| 137 | v1 | 7/15/25 | 7/30/25 | Mechanical | Per Fire Alarm Specification 28 31 00-06, Section 2.1 – Equipment and Material, General, the approved manufacturer is listed EST 4 by Edwards. Please confirm if Siemens is an approved fire alarm manufacture for this project. | No. Only EST 4 by Edwards is approved unless modified by addendum. | |
| 138 | v1 | 7/15/25 | 7/30/25 | Architectural | Specs | The spec description references a quartz system, but in the footer and in the system name (Stonetec ERF), it appears to indicate a chip system instead. Could you please confirm which system type—quartz or chips—you would like us to match? | Use chip system (Stonetec ERF) as indicated in footer and system name. |
| 139 | v1 | 7/15/25 | 7/30/25 | Architectural | Specs | Reference Specification 07 40 00 Roofing and Siding Panels Part 2.3 – C – 2 & -3 call for Econolap ¾” … by Centria or approved equal. We would like to substitute an equal product from a local supplier. Specified product characteristics: Centria Econolap ¾” ¾” deep, 34-2/3” width, 24 Ga. G-90, sine-wave corrugation at 2-2/3” pitch. Substitution product characteristics: Metal Sales 7/8” Corrugated 7/8” deep, 34-2/3” width, 24 Ga. G-90, sine-wave corrugation at 2-2/3” pitch. | Submit full technical data for review. Substitution may be accepted if compliant with performance criteria. |
| 140 | v1 | 7/15/25 | 7/30/25 | Architectural | Will AWB behind metal panel systems be in the metal panel scope of work? | Yes, AWB is part of the metal panel system scope. | |
| 141 | v1 | 7/15/25 | 7/30/25 | Architectural | Will “Fashflash” and “R-guard Fashflash” that go into window openings, strip-in metal flashings, or go under metal flashings be in the finish trade scope of work, or in the flashing scope? | These products fall under the flashing scope of work. | |
| 142 | v1 | 7/15/25 | 7/30/25 | Architectural | Confirm that at the TerraCotta system, only the flashings in detail D7/A-614 will be in the Sheet Metal scope of work. All other flashings, closures, angles, etc., associated with the terracotta system will be part of the terracotta system. | Confirmed. Only flashings in D7/A-614 are in Sheet Metal scope. Others are part of terracotta system. | |
| 143 | v1 | 7/15/25 | 7/30/25 | Electrical | Drawings | Sumitomo Air Blown Fiber is the Campus Standard but does not appear in the Justification and Approval. Page ETS101 Keynote 2 indicates innerduct. The underground at West LA utilizes a Sumitomo Tube Cell system. Please confirm that all fiber optic cabling between the Building 500 and the New Police building will be Sumitomo ABF and that all current warranties on the Sumitomo ABF system will be required to be maintained. | Yes, the contractor must provide Sumitomo tube system. There are cell tube waiting in the manhole indicted on the drawings. The contractor must extend from the manhole to the new police station and in between the TR's with tube cell. The contractor will be rewsponsible to blow fiber from police station to Bldg 500 Main Computer Room (MCR). |
| 144 | v1 | 7/15/25 | 7/30/25 | General | A.3 price / cost schedule with 4 CLINS. Each of these clins are deducts and it shows a grand total at the bottom. Do you want to add all 4 CLINS together for a grand total or can we just add an N/A at the bottom on the total line since these are al deducts? | Mark “N/A” on total line since all CLINs are deducts. | |
| 145 | v1 | 7/15/25 | 7/30/25 | General | 2.8 Proposal Requirements B.1. - States to send all 3 volumes in separate emails not to exceed 3 emails. Is it acceptable to send all 3 in 1 email if we can get all 3 under 5 MB? Can the 5 MB be changed to 10MB Max to be sure we can get all 3 in the same email, but just different attachments? | Yes, all 3 volumes may be sent in 1 email if under 5MB. Limit remains at 5MB. | |
| 146 | v1 | 7/15/25 | 7/30/25 | General | 2.8 Proposal Requirements B states to use 12 point Times new Roman and usually this is no smaller than 11 point - can we use 11 point as there is a lot of info to fit into very few pages? | No. Use 12-point Times New Roman as specified. | |
| 147 | v1 | 7/15/25 | 7/30/25 | General | 2.8.C.2 - Factor 2 - Is the risk plan to be a Company Risk Management Plan or a Site-Specific Risk Management Plan or both? | Provide a site-specific Risk Management Plan. | |
| 148 | v1 | 7/15/25 | 7/30/25 | General | Would the VA like the projects used for past performance listed by Contract #? And will they do their own additional research into each one of these projects? If so, what will be used for this research? Will you be speaking with any employees currently at the GLA location on past performance? | Yes, VA may conduct its own research and contact GLA staff. | |
| 149 | v1 | 7/15/25 | 7/30/25 | Architectural | Drawings | Detail F1/AE313 seems to indicate a reglet & counterflashing. Detail F1/A-613 only shows a mud-sill flashing. Will Reglet & Counter flashing be required at exterior walls above roofing termination? | Yes, reglet & counterflashing are required at exterior walls above roofing termination. |