Amendment 0004 - Addendum 2.pdf
PDF 13 MB Posted
- Solicitation number
- 36C77625B0031
About this file
This document is an Amendment (Amendment 0004) to a federal contract for expanding and enhancing a Community Living Center (CLC) located in Richmond, Virginia. The amendment includes multiple technical specification updates across various sections, with notable changes to plumbing drawings, mechanical drawings, and electrical specifications. Key modifications include adding a bariatric toilet, updating the Telecommunications Room to meet EHRM standards, and revising specifications for communication systems, grounding, cable trays, and structured cabling.
The project, identified as 652-19-311, involves detailed architectural and engineering modifications across multiple drawing sheets, with revisions to door sizes, call-outs, finishes, and technical specifications. Changes span sections like 22 13 00 (Facility Sanitary and Vent Piping) and 22 40 00 (Plumbing Fixtures), with specific updates to lint and grease interceptors, toilet specifications, and communication system components. The amendment is part of a larger VA project at the Hunter Holmes McGuire VA Medical Center in Richmond, Virginia, and is categorized as a Service-Disabled Veteran-Owned Small Business opportunity.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRIPLE C – THE A&E GROUP
OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE
410 Grand Avenue, Suite 201C � Laramie, Wyoming 82070 � Telephone: (307) 460-2054 � Fax: (307) 460-2053
Addendum 2
Project: 652-19-311 EXPAND & ENHANCE COMMUNITY LIVING CENTER – Richmond CLC
Date: 09/05/2025
Summary of Clarifications Changes within this addendum have been updated to reflect clarifications within the project to include door sizes, detail call outs and finishes changes/ clarifications. Changes have also been made to plumbing drawings and mechanical drawings to add a bariatric toilet and dryer box. Changes have been made to electrical drawings to update the Telecommunications Room to be in line with EHRM standards.
Specifications:
SECTION DESCRIPTION OF/REASON FOR CHANGE
22 13 00 Added section for Lint and grease interceptors and basis of design
22 40 00 Added Bariatric toilet specification and updated lavatory specification language
23 09 23 Revised paragraph 1.1.F.1 to indicate that this project is to connect into the existing ECC with full interoperability rather than providing a stand-alone ECC as previously indicated
27 05 26 Added spec section for Grounding and Bonding for Communication Systems
27 05 36 Added Spec Section for Cable Trays for Communications Systems
27 05 53 Added spec section for Identification for Communications Systems
27 10 00 Added spec section for Structured Cabling
27 11 16 Added spec section for Communications Cabinets, Racks, Frames, and Enclosures
27 11 19 Added spec section for Communications Termination Blocks and Patch Panels
27 11 26 Added spec section for Communications Rack Mounted Power Protection and Power Strips
27 13 13.13 Added spec section for Communications Copper Cable Splicing and Terminations
27 13 23 Added spec section for Communications Optical Fiber Backbone Cabling
CVE Verified Service-Disabled Veteran-Owned Small Business
TRIPLE C – THE A&E GROUP
OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE
410 Grand Avenue, Suite 201C � Laramie, Wyoming 82070 � Telephone: (307) 460-2054 � Fax: (307) 460-2053
27 15 13 Added spec section for Communications Copper Horizontal Cabling
27 15 13.13 Added spec section for Communications Optical Fiber Splicing and
Terminations
27 16 19 Added spec section for Communications Patch Cords, Stations Cords, and Cross Connect Wire
Drawing Changes:
SHEET NUMBER REVISION
NUMBER
DESCRIPTION OF/REASON FOR CHANGE
S-101 2 Noted grease and lint trap locations on sheet
A-102, A103 2 Changed double door width at corridor 133 and community corridor 108 from 7’-0” to 7’-4”
A-401 2 Added detail call out for swing up grab bars at restroom locations
A-402 2 Added detail call out for swing up grab bars at restroom location. Added keynote for slope at cabinetry. Updated keynotes to correct a missing keynote #4
AC101 2 Changed soffit depth at Multipurpose room to 1’-6” over millwork. Added dimension at soffit in Lounge, Staff room
A-503 2 Added swing up grab bar detail
A-511 2 Updated note on F8 detail for sink coordination with plumbing
A-601 2 Changed double door width at door # 108A and 108B from 7’-0” to 7’-4”
IN001 2 Removed text for PT-4, this tile is not used. PT-5 text change to note this will be used at wet locations.
IN101 2 PT-4 changed in rooms 104, 111,112,112A, 127, 140 to PT-5
IN501 2 Updated plywood detail
IN601 2 Finish legend updated PT-4 to be not used, PT-5 note was updated to list wet locations. Room finish schedule floor finish updated in rooms 104, 111,112,112A, 127, 140 to PT-
5. Plywood updated to show finishes. Sealed concrete updated to show static sealer is required.
PP001 2 Added bariatric toilet to plumbing schedule
PL101 2 Added Bariatric toilet and tag on plan
PP101 2 Added Bariatric toilet and tag on plan
MH101 2 Added Dryer box and secondary lint trap language to KN 1
MH102 2 Added louver for dryer exhaust at exterior wall
E001 2 Added symbols for overhead electrical outlets
E602 2 Updated information on the panel board schedules
E603 2 Updated information on the panel board schedules
EP101 2 Revised the layout of the Telecommunication Room
EY101 2 Revised the layout of the Telecommunication Room and added Wanderguard KN to both corridor sets of doors
End of ASI
Notes
Expand and Enhance Community Living Center Project #: 652-322
Table of Contents
00 01 10 - 1
CENTRAL VIRGINIA VA HEALTH CARE SYSTEM
EXPAND AND ENHANCE COMMUNITY LIVING CENTER
TABLE OF CONTENTS
SECTION 00 01 10
SECTIONS DIVISION AND SECTION TITLES DATE
PROJECT FILES
NOT USED
COVER PAGE
00 01 01 Project Title
DIVISION 00 — SPECIAL SECTIONS
00 01 01.10 Project Title 00 01 10 Table of Contents 11-2020 00 01 15 List of Drawing Sheets 06-2020 00 31 33 Subsurface Drilling and Sampling Information 4-18-2017 00 31 33.10 GER - CLC Expansion at McGuire VA 2-19-2015 00 41 13 Bid Form
DIVISION 01 — GENERAL REQUIREMENTS
01 00 00 General Requirements 03-2020 01 32 16.15 Project Schedules (Small Projects - Design-Bid-Build) 03-2020 01 33 23 Shop Drawings, Product Data, and Samples 05-2017 01 35 26 Safety Requirements 07-2020 01 42 19 Reference Standards 11-2020 01 45 00 Quality Control 02-2021 01 45 00.00 quality control reports 01 45 29 Testing Laboratory Services 11-2011 01 45 35 Special Inspections 03-2019 01 45 35.01 Schedule of Special Inspections Template 04-2018 01 57 19 Temporary Environmental Controls 01-2011 01 58 16 Temporary Interior Signage 07-2015 01 74 19 Construction Waste Management 09-2013 01 81 13 Sustainable Construction Requirements 10-2017 01 91 00 General Commissioning Requirements 10-2015
DIVISION 02 — EXISTING CONDITIONS
02 41 00 Demolition 08-2017 02 82 13.13 Glovebag Asbestos Abatement 09-2015 02 82 13.14 Hunter Holmes McGuire VA Medical Center - Richmond, VA - Asbestos
Reinspection Report - August 2019
DIVISION 03 — CONCRETE
03 30 00 Cast-In-Place Concrete 07-2019 03 45 00 Precast Architectural Concrete 02-2019
DIVISION 04 — MASONRY
04 05 13 Masonry Mortaring 10-2017 04 05 16 Masonry Grouting 02-2016 04 20 00 Unit Masonry 08-2017 04 72 00 Cast Stone Masonry 02-2015
00 01 10 - 2
DIVISION 05 — METALS
05 12 00 Structural Steel Framing 11-2018 05 31 00 Steel Decking 02-2016 05 36 00 Composite Metal Decking 10-2015 05 40 00 Cold-Formed Metal Framing 05-2016 05 50 00 Metal Fabrications 08-2018 05 51 00 Metal Stairs 10-2015 05 75 13 Decorative Perforated Panels
DIVISION 06 — WOOD, PLASTICS, AND COMPOSITES
06 06 60 Plastic Fabrications 06 10 00 Rough Carpentry 10-2017
DIVISION 07 — THERMAL AND MOISTURE PROTECTION
07 08 00 Facility Exterior Closure Commissioning 11-2016 07 11 13 Bituminous Dampproofing 02-2016 07 13 00 Sheet Waterproofing 04-2013 07 21 13 Thermal Insulation 10-2017 07 21 31 Sprayed Polyurethane Foam (SPF) Insulation - Medium Density 07 22 00 Roof and Deck Insulation 02-2016 07 40 00 Roofing and Siding Panels 10-2015 07 53 23 Ethylene-Propylene-Diene-Monomer Roofing 02-2016 07 60 00 Flashing and Sheet Metal 07-2014 07 71 00 Roof Specialties 10-2015 07 72 00 Roof Accessories 10-2015 07 81 00 Applied Fireproofing 10-2017 07 81 23 Interior Intumescent Fireproofing (IFP) 07 84 00 Firestopping 02-2016 07 92 00 Joint Sealants 10-2017 07 95 13 Expansion Joint Cover Assemblies 02-2016
DIVISION 08 — OPENINGS
08 11 13 Hollow Metal Doors and Frames 08-2016 08 14 00 Interior Wood Doors 02-2016 08 17 10 Integrated Door Assemblies 02-2016 08 31 13 Access Doors and Frames 02-2016 08 36 16.13 High Performance Barn (Sliding) Door 08 41 13 Aluminum-Framed Entrances and Storefronts 08-2016 08 44 13 Glazed Aluminum Curtain Walls 04-2020 08 51 13.11 Side-Hinged Aluminum Windows 08-2016 08 71 00 Door Hardware 04-2020 08 71 13 Automatic Door Operators 01-2021 08 80 00 Glazing 10-2015 08 87 33 Decorative Film 08 90 00 Louvers and Vents 05-2015
DIVISION 09 — FINISHES
09 05 16 Subsurface Preparation for Floor Finishes 02-2015 09 22 16 Non-Structural Metal Framing 06-2018 09 29 00 Gypsum Board 04-2020 09 30 13 Ceramic Porcelain Tiling 09-2015 09 51 00 Acoustical Ceilings 12-2018 09 65 13 Resilient Base and Accessories 02-2016 09 65 19 Resilient Tile Flooring 05-2018 09 68 00 Carpeting 10-2015 09 91 00 Painting 01-2016
DIVISION 10 — SPECIALTIES
00 01 10 - 3
10 14 00 Signage 10-2015 10 21 23 Cubicle Curtain Tracks 05-2015 10 22 19 Demountable Partitions 04-2016 10 25 13 Patient Bed Service Walls 01-2020 10 26 00 Wall and Door Protection 10-2015 10 28 00 Toilet, Bath, and Laundry Accessories 02-2016 10 44 13 Fire Extinguisher Cabinets 08-2018 10 50 20 Canopies
DIVISION 11 — EQUIPMENT
11 48 00 Cleaning and Disposal Equipment 11-2011 11 73 00 Ceiling Mounted Patient Lift System 08-2020
DIVISION 12 — FURNISHINGS
12 24 00 Window Shades 08-2017 12 32 00 Manufactured Wood Casework 09-2015 12 36 00 Countertops 12-2018 12 93 00 Exterior Site Furnishings
DIVISION 13 — SPECIAL CONSTRUCTION
13 05 41 Seismic Restraint Requirements for Non-Structural Components 01-2014
DIVISION 14 — CONVEYING EQUIPMENT
NOT USED
DIVISION 21 — FIRE SUPPRESSION
21 08 00 Commissioning of Fire Suppression System 11-2016 21 13 13 Wet-Pipe Sprinkler Systems 06-2015
DIVISION 22 — PLUMBING
22 05 11 Common Work Results for Plumbing 09-2020 22 05 19 Meters and Gauges for Plumbing Piping 09-2020 22 05 23 General-Duty Valves for Plumbing Piping 09-2020 22 07 11 Plumbing Insulation 09-2015 22 08 00 Commissioning of Plumbing Systems 11-2016 22 11 00 Facility Water Distribution 11-2019 22 13 00 Facility Sanitary and Vent Piping 09-2020 22 14 00 Facility Storm Drainage 09-2015 22 40 00 Plumbing Fixtures 09-2015 22 62 00 Vacuum Systems for Laboratory and Healthcare Facilities 09-2015 22 63 00 Gas Systems for Laboratory and Healthcare Facilities 09-2015
DIVISION 23 — HEATING VENTILATING AND AIR CONDITIONING
23 05 11 Common Work Results for HVAC 02-2020 23 05 12 General Motor Requirements for HVAC 02-2020 23 05 41 Noise and Vibration Control for HVAC Piping and Equipment 02-2020 23 05 93 Testing, Adjusting, and Balancing for HVAC 02-2020 23 07 11 HVAC and Boiler Plant Insulation 02-2020 23 08 00 Commissioning of HVAC Systems 02-2020 23 09 23 Direct-Digital Control System for HVAC-Add 2 23 21 13 Hydronic Piping 02-2020 23 21 23 Hydronic Pumps 02-2020 23 22 13 Steam and Condensate Heating Piping 02-2020 23 22 23 Steam Condensate Pumps 04-2020 23 23 00 Refrigeration Piping 02-2020 23 25 00 HVAC Water Treatment 02-2020 23 31 00 HVAC Ducts and Casings 02-2020 23 34 00 HVAC Fans 02-2020 23 36 00 Air Terminal Units 02-2020
Triple C Architect
Triple C Cloud+
Chad Architect
Chad Cloud+
00 01 10 - 4
23 37 00 Air Outlets and Inlets 02-2020 23 40 00 HVAC Air Cleaning Devices 03-2020 23 73 00 Indoor Central-Station Air-Handling Units 03-2020 23 81 00 Decentralized Unitary HVAC Equipment 03-2020 23 81 43 Air-Source Unitary Heat Pumps 03-2020 23 82 16 Air Coils 03-2020
DIVISION 25 — INTEGRATED AUTOMATION
25 10 10 Advanced Utility Metering System 02-2010
DIVISION 26 — ELECTRICAL
26 05 11 Requirements for Electrical Installations 01-2016 26 05 19 Low-Voltage Electrical Power Conductors and Cables 01-2017 26 05 26 Grounding and Bonding for Electrical Systems 01-2017 26 05 33 Raceway and Boxes for Electrical Systems 01-2018 26 05 41 Underground Electrical Construction 01-2017 26 05 73 Overcurrent Protective Device Coordination Study 01-2018 26 08 00 Commissioning of Electrical Systems 11-2016 26 09 23 Lighting Controls 01-2018 26 22 00 Low-Voltage Transformers 01-2018 26 24 13 Distribution Switchboards 01-2017 26 24 16 Panelboards 01-2018 26 25 11 Busways 01-2017 26 27 26 Wiring Devices 01-2018 26 29 11 Motor Controllers 01-2018 26 29 21 Enclosed Switches and Circuit Breakers 01-2017 26 32 13 Engine Generators 01-2018 26 33 53 Static Uninterruptible Power Supply 01-2017 26 36 23 Automatic Transfer Switches 01-2017 26 41 00 Facility Lightning Protection 01-2018 26 43 13 Surge Protective Devices 01-2017 26 51 00 Interior Lighting 01-2018 26 56 00 Exterior Lighting 01-2018
DIVISION 27 — COMMUNICATIONS
27 05 11 Requirements for Communications Installations 09-2019 27 05 26 Grounding and Bonding for Communications Systems 27 05 26 Grounding and Bonding for Communications Systems 06-2015 27 05 33 Raceways and Boxes for Communications Systems 10-2018 27 05 36 Cable Trays for Communications Systems 27 05 53 Identification for Communications Systems 27 08 00 Commissioning of Communications Systems 11-2016 27 10 00 Control, Communication and Signal Wiring 06-2015 27 10 00.1 Structured Cabling 27 11 00 Telecommunications Room Fittings 06-2015 27 11 16 Communications Cabinets, Racks, Frames, and Enclosures 27 11 19 Communications Termination Blocks and Patch Panels 27 11 26 Communications Rack Mounted Power Protection and Power Strips 27 13 13.13 Communications Copper Cable Splicing and Terminations 27 13 23 Communications Optical Fiber Backbone Cabling 27 15 00 Communications Structured Cabling 01-2016 27 15 13 Communications Copper Horizontal Cabling 27 15 13.13 Communications Optical Fiber Cable Splicing and Terminations 27 16 19 Communications Patch Cords, Station Cords, and Cross Connect Wire 27 51 16 Public Address and Mass Notification Systems 10-2018 27 52 23 Nurse Call and Code Blue Systems 10-2018 27 53 19 Distributed Radio Antenna (Within Building) Equipment and System 09-2019
00 01 10 - 5
DIVISION 28 — ELECTRONIC SAFETY AND SECURITY
28 05 00 Common Work Results for Electronic Safety and Security 04-2018 28 05 13 Conductors and Cables for Electronic Safety and Security 10-2018 28 05 26 Grounding and Bonding for Electronic Safety and Security 09-2011 28 05 28.33 Conduits and Backboxes for Electronic Safety and Security 09-2011 28 08 00 Commissioning of Electronic Safety and Security Systems 11-2016 28 13 00 Physical Access Control System 10-2011 28 23 00 Video Surveillance 09-2011 28 26 00 Wander Management System 28 31 00 Fire Detection and Alarm 10-2011 28 52 31 Emergency Call System 06-2015
DIVISION 31 — EARTHWORK
31 20 00 Earthwork 07-2016 31 66 13 Rammed Aggregate Pier Foundation Systems
DIVISION 32 — EXTERIOR IMPROVEMENTS
32 05 23 Cement and Concrete for Exterior Improvements 08-2016 32 12 16 Asphalt Paving 09-2015 32 17 23 Pavement Markings 08-2016 32 31 18 Pre-Fabricated Ornamental Aluminum Fence 32 90 10 Landscape Maintenance 32 91 10 Soil Prep 32 93 00 Planting
DIVISION 33 — UTILITIES
33 08 00 Commissioning of Site Utility Systems 11-2016 33 30 00 Sanitary Sewer Utilities 06-2013 33 40 00 Storm Sewer Utilities 12-2017 33 46 13 Foundation Drainage 10-2011 33 51 00 Natural-Gas Distribution 10-2011
DIVISION 34 — TRANSPORTATION
34 71 13 Passive Vehicle Barriers 04-2018
DIVISION 35 — WATERWAY AND MARINE
NOT USED
DIVISION 40 — PROCESS INTERCONNECTIONS
NOT USED
DIVISION 41 — MATERIAL PROCESSING AND HANDLING EQUIPMENT
NOT USED
DIVISION 42 — PROCESS HEATING, COOLING, AND DRYING EQUIPMENT
NOT USED
DIVISION 43 — PROCESS GAS AND LIQUID HANDLING, PURIFICATION AND
STORAGE EQUIPMENT
NOT USED
DIVISION 44 — POLLUTION AND WASTE CONTROL EQUIPMENT
NOT USED
DIVISION 45 — INDUSTRY-SPECIFIC MANUFACTURING EQUIPMENT
NOT USED
DIVISION 46 — WATER AND WASTEWATER EQUIPMENT
NOT USED
DIVISION 48 — ELECTRICAL POWER GENERATION
NOT USED
00 01 10 - 6
Facility Sanitary and Vent Piping
22 13 00 - 1
SECTION 22 13 00
FACILITY SANITARY AND VENT PIPING
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section pertains to sanitary sewer and vent systems, including piping, equipment and all necessary accessories as designated in this section.
B. A complete listing of common acronyms and abbreviations are included in Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.
1.2 RELATED WORK
A. Section 01 00 00, GENERAL REQUIREMENTS.
B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
C. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.
D. Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS.
E. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Seismic Restraint.
F. Section 07 84 00, FIRESTOPPING: Penetrations in rated enclosures.
G. Section 07 92 00, JOINT SEALANTS: Sealant products.
H. Section 09 91 00, PAINTING: Preparation and finish painting and identification of piping systems.
I. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING: Pipe Hangers and Supports, Materials Identification.
J. Section 22 07 11, PLUMBING INSULATION.
K. Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS
L. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
M. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
22 13 00 - 2
1.3 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. Where conflicts occur these specifications and the VHA standard will govern.
B. American Society of Mechanical Engineers (ASME):
A13.1-2007 ............................ Identification of Piping Systems
A112.36.2M-1991 .................. Cleanouts
A112.6.3-2019 ....................... Floor and Trench Drains
B1.20.1-2013 ......................... Pipe Threads, General Purpose (Inch)
B16.1-2015 ............................ Gray Iron Pipe Flanges and Flanged Fittings Classes 25, 125, and 250
B16.4-2016 ............................ Grey Iron Threaded Fittings Classes 125 and 250
B16.15-2018 .......................... Cast Copper Alloy Threaded Fittings, Classes 125 and 250
B16.18-2018 .......................... Cast Copper Alloy Solder Joint Pressure Fittings
B16.21-2016 .......................... Nonmetallic Flat Gaskets for Pipe Flanges
B16.22-2018 .......................... Wrought Copper and Copper Alloy Solder-Joint Pressure Fittings
B16.23-2016 .......................... Cast Copper Alloy Solder Joint Drainage Fittings: DWV
B16.24-2016 .......................... Cast Copper Alloy Pipe Flanges and Flanged Fittings, and Valves: Classes 150, 300, 600, 900, 1500, and 2500
B16.29-2017 .......................... Wrought Copper and Wrought Copper Alloy Solder-Joint Drainage Fittings: DWV
B16.39-2014 .......................... Malleable Iron Threaded Pipe Unions Classes 150, 250, and 300
B18.2.1-2012 ......................... Square, Hex, Heavy Hex, and Askew Head Bolts and Hex, Heavy Hex, Hex Flange, Lobed Head, and Lag Screws (Inch Series)
C. American Society of Sanitary Engineers (ASSE):
1001-2017 ............................. Performance Requirements for Atmospheric Type Vacuum
Breakers
1018-2001 ............................. Performance Requirements for Trap Seal Primer Valves – Potable Water Supplied
1044-2015 ............................. Performance Requirements for Trap Seal Primer Devices – Drainage Types and Electronic Design Types
1079-2012 ............................. Performance Requirements for Dielectric Pipe Unions
D. American Society for Testing and Materials (ASTM):
A53/A53M-2018 .................... Standard Specification for Pipe, Steel, Black And Hot-Dipped, Zinc-coated, Welded and Seamless
A74-2017 ............................... Standard Specification for Cast Iron Soil Pipe and Fittings
A888-2018a ........................... Standard Specification for Hubless Cast Iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Applications
B32-2008(R2014) .................. Standard Specification for Solder Metal
B43-2015 ............................... Standard Specification for Seamless Red Brass Pipe, Standard Sizes
22 13 00 - 3
B88-2016 ............................... Standard Specification for Seamless Copper Water Tube
B306-2013 ............................. Standard Specification for Copper Drainage Tube (DWV)
B687-1999(R2016) ................ Standard Specification for Brass, Copper, and Chromium-Plated Pipe Nipples
B813-2016 ............................. Standard Specification for Liquid and Paste Fluxes for Soldering of Copper and Copper Alloy Tube
B828-2016 ............................. Standard Practice for Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings
C564-2014 ............................. Standard Specification for Rubber Gaskets for Cast Iron Soil Pipe and Fittings
D2321-2018........................... Standard Practice for Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity-Flow Applications
D2564-2012(R3018) ............. Standard Specification for Solvent Cements for Poly(Vinyl Chloride) (PVC) Plastic Piping Systems
D2665-2014........................... Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings
D2855-2015........................... Standard Practice for Two-Step (Primer and Solvent Cement) Method of Joining Poly(Vinyl Chloride) (PVC) or Chlorinated Poly (Vinyl Chloride) CPVCP Pipe and Piping Components with Tapered Sockets
D5926-2015........................... Standard Specification for Poly(Vinyl Chloride) (PVC) Gaskets for Drain, Waste, and Vent (DWV), Sewer, Sanitary, and Storm Plumbing Systems
F402-2018 ............................. Standard Practice for Safe Handling of Solvent Cements, Primers, and Cleaners Used for Joining Thermoplastic Pipe and Fittings
F477-2014 ............................. Standard Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe
F1545-2015e1 ....................... Standard Specification for Plastic-Lined Ferrous Metal Pipe, Fittings, and Flanges
E. Cast Iron Soil Pipe Institute (CISPI):
2006 ...................................... Cast Iron Soil Pipe and Fittings Handbook
301-2012 ............................... Standard Specification for Hubless Cast Iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Applications
310-2012 ............................... Specification for Coupling for Use in Connection with Hubless Cast Iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping Applications
F. Copper Development Association, Inc. (CDA):
A4015-14/19 .......................... Copper Tube Handbook
G. International Code Council (ICC):
IPC-2018 ............................... International Plumbing Code
H. Manufacturers Standardization Society (MSS):
SP-123-2018 ......................... Non-Ferrous Threaded and Solder-Joint Unions for Use with
Copper Water Tube
22 13 00 - 4
I. National Fire Protection Association (NFPA):
70-2020 ................................. National Electrical Code (NEC)
J. Underwriters' Laboratories, Inc. (UL):
508-99 (R2013) ..................... Standard For Industrial Control Equipment
1.4 SUBMITTALS
A. Submittals, including number of required copies, shall be submitted in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES.
B. Information and material submitted under this section shall be marked “SUBMITTED UNDER SECTION 22 13 00, FACILITY SANITARY AND VENT PIPING”, with applicable paragraph identification.
C. Manufacturer's Literature and Data including: Full item description and optional features and accessories. Include dimensions, weights, materials, applications, standard compliance, model numbers, size, and capacity.
1. Piping.
2. Floor Drains.
3. Grease Removal Unit.
4. Cleanouts.
5. Trap Seal Protection.
6. Penetration Sleeves.
7. Pipe Fittings.
8. Traps.
9. Exposed Piping and Fittings.
D. Detailed shop drawing of clamping device and extensions when required in connection with the waterproofing membrane or the floor drain.
E. Complete operating and maintenance manuals including wiring diagrams, technical data sheets, information for ordering replaceable parts, and troubleshooting guide:
1. Include complete list indicating all components of the systems.
2. Include complete diagrams of the internal wiring for each item of equipment.
3. Diagrams shall have their terminals identified to facilitate installation, operation and maintenance.
F. Completed System Readiness Checklist provided by the CXA and completed by the Contractor, signed by a qualified technician and dated on the date of completion, in accordance with the requirements of Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS.
G. Submit training plans and instructor qualifications in accordance with the requirements of Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS.
1.5 QUALITY ASSURANCE
A. Bio-Based Materials: For products designated by the USDA’s bio-based Bio-Preferred Program, provide products that meet or exceed USDA recommendations for bio-based content, so long as products meet all performance requirements in this specifications section. For more information regarding the product categories covered by the Bio-Preferred Program, visit http://www.biopreferred.gov.
B. Refer to Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for additional sustainable design requirements.
1.6 AS-BUILT DOCUMENTATION
A. Comply with requirements in Paragraph “AS-BUILT DOCUMENTATION” of Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.
22 13 00 - 5
PART 2 - PRODUCTS
2.1 SANITARY WASTE, DRAIN, AND VENT PIPING
A. Cast iron waste, drain, and vent pipe and fittings.
1. Cast iron waste, drain, and vent pipe and fittings shall be used for the following applications:
a. Pipe buried in or in contact with earth.
b. Sanitary pipe extensions to a distance of approximately 1500 mm (5 feet) outside of the building.
c. Interior waste and vent piping above grade.
2. Cast iron Pipe shall be bell and spigot or hubless (plain end or no-hub or hubless).
3. The material for all pipe and fittings shall be cast iron soil pipe and fittings and shall conform to the requirements of CISPI 301, ASTM A888, or ASTM A74.
4. Cast iron pipe and fittings shall be made from a minimum of 95 percent post-consumer recycled material.
5. Joints for hubless pipe and fittings shall conform to the manufacturer’s installation instructions. Couplings for hubless joints shall conform to CISPI 310. Joints for hub and spigot pipe shall be installed with compression gaskets conforming to the requirements of
ASTM C564.
B. Copper Tube, (DWV):
1. Copper DWV tube sanitary waste, drain and vent pipe may be used for piping above ground, except for urinal drains.
2. The copper DWV tube shall be drainage type, drawn temper conforming to ASTM B306.
3. The copper drainage fittings shall be cast copper or wrought copper conforming to ASME
B16.23 or ASME B16.29.
4. The joints shall be lead free, using a water flushable flux, and conforming to ASTM B32.
2.2 PUMP DISCHARGE PIPING
A. Galvanized steel pump discharge pipe and fittings:
1. Galvanized steel pipe shall be Schedule 40 weight class conforming to ASTM A53/A53M, with square cut grooved or threaded ends to match joining method.
2. Fittings shall be Class 125, gray-iron threaded fittings conforming to ASME B16.4.
3. Unions shall be Class 150 hexagonal-stock body with ball and socket, metal to metal, bronze seating surface, malleable iron conforming to ASME B16.39 with female threaded ends.
4. Flanges shall be Class 125 cast iron conforming to ASME B16.1.
a. Flange gaskets shall be full face, flat nonmetallic, asbestos free conforming to
ASME B16.21.
b. Flange nuts and bolts shall be carbon steel conforming to ASME B18.2.1.
2.3 EXPOSED WASTE PIPING
A. Chrome plated brass piping of full iron pipe size shall be used in finished rooms for exposed waste piping connecting fixtures, casework, cabinets, equipment and reagent racks when not concealed by apron including those furnished by the Government or specified in other sections.
1. The Pipe shall meet ASTM B43, regular weight.
2. The Fittings shall conform to ASME B16.15 or ASTM D2665.
3. Nipples shall conform to ASTM B687, Chromium-plated.
4. Unions shall be brass or bronze with chrome finish. Unions 65 mm (2-1/2 inches) and larger shall be flange type with approved gaskets.
B. In unfinished Rooms such as mechanical Rooms and Kitchens, Chrome-plated brass piping is not required. The pipe materials specified under the paragraph “Sanitary Waste, Drain, and Vent Piping” can be used. The sanitary pipe in unfinished rooms shall be painted as specified in Section 09 91 00, PAINTING.
22 13 00 - 6
2.4 SPECIALTY PIPE FITTINGS
A. Transition pipe couplings shall join piping with small differences in outside diameters or different materials. End connections shall be of the same size and compatible with the pipes being joined. The transition coupling shall be elastomeric, sleeve type reducing or transition pattern and include shear and corrosion resistant metal, tension band and tightening mechanism on each end. The transition coupling sleeve coupling shall be of the following material:
1. For cast iron soil pipes, the sleeve material shall be rubber conforming to ASTM C564.
2. For dissimilar pipes, the sleeve material shall be PVC conforming to ASTM D5926, or other material compatible with the pipe materials being joined.
B. The dielectric fittings shall conform to ASSE 1079 with a pressure rating of 861 kPa (125 psig) at a minimum temperature of 82 degrees C (180 degrees F). The end connection shall be solder joint copper alloy and threaded ferrous.
C. Dielectric flange insulating kits shall be of non-conducting materials for field assembly of companion flanges with a pressure rating of 1035 kPa (150 psig). The gasket shall be neoprene or phenolic. The bolt sleeves shall be phenolic or polyethylene. The washers shall be phenolic with steel backing washers.
D. The di-electric nipples shall be electroplated steel nipple complying with ASTM F1545 with a pressure rating of 2070 kPa (300 psig) at 107 degrees C (225 degrees F). The end connection shall be male threaded. The lining shall be inert and noncorrosive propylene.
2.5 CLEANOUTS
A. Cleanouts shall be the same size as the pipe, up to 100 mm (4 inches); and not less than 100 mm (4 inches) for larger pipe. Cleanouts shall be easily accessible and shall be gastight and watertight. Minimum clearance of 600 mm (24 inches) shall be provided for clearing a clogged sanitary line.
B. Floor cleanouts shall be gray iron housing with clamping device and round, secured, scoriated, gray iron cover conforming to ASME A112.36.2M. A gray iron ferrule with hubless, socket, inside calk or spigot connection and counter sunk, taper-thread, brass or bronze closure plug shall be included. The frame and cover material and finish shall be nickel-bronze copper alloy with a square shape. The cleanout shall be vertically adjustable for a minimum of 50 mm (2 inches). When a waterproof membrane is used in the floor system, clamping collars shall be provided on the cleanouts. Cleanouts shall consist of wye fittings and eighth bends with brass or bronze screw plugs. Cleanouts in the resilient tile floors, quarry tile and ceramic tile floors shall be provided with square top covers recessed for tile insertion. In the carpeted areas, carpet cleanout markers shall be provided. Two way cleanouts shall be provided where indicated in the contract document and at every building exit. The loading classification for cleanouts in sidewalk areas or subject to vehicular traffic shall be heavy duty type.
C. Cleanouts shall be provided at or near the base of the vertical stacks with the cleanout plug located approximately 600 mm (24 inches) above the floor. If there are no fixtures installed on the lowest floor, the cleanout shall be installed at the base of the stack. The cleanouts shall be extended to the wall access cover. Cleanout shall consist of sanitary tees. Nickel-bronze square frame and stainless steel cover with minimum opening of 150 by 150 mm (6 by 6 inches) shall be furnished at each wall cleanout. Where the piping is concealed, a fixture trap or a fixture with integral trap, readily removable without disturbing concealed pipe, shall be accepted as a cleanout equivalent providing the opening to be used as a cleanout opening is the size required.
D. In horizontal runs above grade, cleanouts shall consist of cast brass tapered screw plug in fitting or caulked/hubless cast iron ferrule. Plain end (hubless) piping in interstitial space or above ceiling may use plain end (hubless) blind plug and clamp.
2.6 FLOOR DRAINS
A. General Data: floor drain shall comply with ASME A112.6.3. A caulking flange, inside gasket, or hubless connection shall be provided for connection to cast iron pipe, screwed or no hub outlets
22 13 00 - 7 for connection to steel pipe. The drain connection shall be bottom outlet. A membrane clamp and extensions shall be provided, if required, where installed in connection with waterproof membrane. Puncturing membrane other than for drain opening shall not be permitted. Double drainage pattern floor drains shall have integral seepage pan for embedding into floor construction, and weep holes to provide adequate drainage from pan to drain pipe. For drains not installed in connection with a waterproof membrane, a flashing membrane, 600 mm (24 inches) square or another approved waterproof membrane shall be provided.
B. Type C (FD-C) medium duty (non-traffic) floor drain shall comply with ASME A112.6.3. The type C floor drain shall have a cast iron body, double drainage pattern, clamping device, light duty nickel bronze adjustable strainer with round or square grate of 150 mm (6 inches) width or diameter minimum for toilet rooms, showers and kitchens.
C. Type S (FD-S) floor sink shall comply with ASME A112.6.3. The type S floor sink shall be constructed from type 304 stainless steel and shall be 300 mm (12 inches) square, and 200 mm (8 inches deep). The interior surface shall be polished. The double drainage flange shall be provided with weep holes, internal dome strainer, and heavy duty non-tilting loose set grate. A clamping device shall be provided.
2.7 TRAPS
A. Traps shall be provided on all sanitary branch waste connections from fixtures or equipment not provided with traps. Exposed brass shall be polished brass chromium plated with nipple and set screw escutcheons. Concealed traps may be rough cast brass or same material as the piping they are connected to. Slip joints are prohibited on sewer side of trap. Traps shall correspond to fittings on cast iron soil pipe or steel pipe respectively, and size shall be as required by connected service or fixture.
2.8 PRIMER VALVES AND TRAP SEAL PRIMER SYSTEMS
A. Trap Primer (TP-2): The trap seal primer valve shall be hydraulic, supply type with a pressure rating of 861 kPa (125 psig) and conforming to standard ASSE 1018.
1. The inlet and outlet connections shall be 15 mm or DN15 (NPS 1/2 inch)
2. The trap seal primer valve shall be fully automatic with an all brass or bronze body.
3. The trap seal primer valve shall be activated by a drop in building water pressure, no adjustment required.
4. The trap seal primer valve shall include a manifold when serving two, three, or four traps.
5. The manifold shall be omitted when serving only one trap.
2.9 PENETRATION SLEEVES
A. A sleeve flashing device shall be provided at points where pipes pass through membrane waterproofed floors or walls. The sleeve flashing device shall be manufactured, cast iron fitting with clamping device that forms a sleeve for the pipe floor penetration of the floor membrane. A galvanized steel pipe extension shall be included in the top of the fitting that shall extend 50 mm (2 inches) above finished floor and galvanized steel pipe extension in the bottom of the fitting that shall extend through the floor slab. A waterproof caulked joint shall be provided at the top hub.
2.10 INTERCEPTORS
A. Lint Interceptor (LINT): Acid Resistant Coated interior and exterior fabricated steel lint interceptor, non-skid secured cover with removable lift handle, aluminum lint intercepting secondary screen assembly, and permanent primary straining baffle with 3/8" [10 mm] diameter perforated holes. Regularly furnished with high inlet and low outlet. Note: size #3 and #7 covers are not furnished with a lift handle. Basis of Design is ZURN Z1185.
B. Grease Interceptor (GINT): Large capacity Acid Resistant Coated interior and exterior fabricated steel grease interceptor, rated at 100 GPM and 200 Lbs. grease capacity, with internal air relief by-pass, bronze cleanout plug and visible double wall trap seal with removable pressure
22 13 00 - 8 equalizing/flow diffusing baffle. Gasketed non-skid secured covers with removable lift handles, complete with flow control fitting. Includes encased fiberglass sensor box containing an electronic grease level sensor (specify right or left side)*, a fiberglass display box with one green power light, red grease level light, audio alarm and junction box. Regularly furnished with inlet and outlet in high position. Basis of design is ZURN Z117N-UN
PART 3 - EXECUTION
3.1 PIPE INSTALLATION
A. The pipe installation shall comply with the requirements of the International Plumbing Code (IPC) and these specifications.
B. Branch piping shall be installed for waste from the respective piping systems and connect to all fixtures, valves, cocks, outlets, casework, cabinets and equipment, including those furnished by the Government or specified in other sections.
C. Pipe shall be round and straight. Cutting shall be done with proper tools. Pipe shall be reamed to full size after cutting.
D. All pipe runs shall be laid out to avoid interference with other work.
E. The piping shall be installed above accessible ceilings where possible.
F. The piping shall be installed to permit valve servicing or operation.
G. The piping shall be installed free of sags and bends.
H. Seismic restraint shall be installed where required by code.
I. Changes in direction for soil and waste drainage and vent piping shall be made using appropriate branches, bends and long sweep bends. Sanitary tees and short sweep quarter bends may be used on vertical stacks if change in direction of flow is from horizontal to vertical.
Long turn double wye branch and eighth bend fittings shall be used if two fixtures are installed back to back or side by side with common drain pipe. Straight tees, elbows, and crosses may be used on vent lines. Do not change direction of flow greater than 90 degrees. Proper size of standard increaser and reducers shall be used if pipes of different sizes are connected.
Reducing size of drainage piping in direction of flow is prohibited.
J. Buried soil and waste drainage and vent piping shall be laid beginning at the low point of each system. Piping shall be installed true to grades and alignment indicated with unbroken continuity of invert. Hub ends shall be placed upstream. Required gaskets shall be installed according to manufacturer’s written instruction for use of lubricants, cements, and other installation requirements.
K. Cast iron piping shall be installed according to CISPI’s “Cast Iron Soil Pipe and Fittings Handbook,” Chapter IV, “Installation of Cast Iron Soil Pipe and Fittings”
L. Aboveground copper tubing shall be installed according to Copper Development Association’s (CDA) “Copper Tube Handbook”.
M. If an installation is unsatisfactory to the COR, the Contractor shall correct the installation at no additional cost or time to the Government.
3.2 JOINT CONSTRUCTION
A. Hub and spigot, cast iron piping with gasket joints shall be joined in accordance with CISPI’s “Cast Iron Soil Pipe and Fittings Handbook” for compression joints.
B. Hub and spigot, cast iron piping with calked joints shall be joined in accordance with CISPI’s “Cast Iron Soil Pipe and Fittings Handbook” for lead and oakum calked joints.
C. Hubless or No-hub, cast iron piping shall be joined in accordance with CISPI’s “Cast Iron Soil Pipe and Fittings Handbook” for hubless piping coupling joints.
22 13 00 - 9
D. For threaded joints, thread pipe with tapered pipe threads according to ASME B1.20.1. The threads shall be cut full and clean using sharp disc cutters. Threaded pipe ends shall be reamed to remove burrs and restored to full pipe inside diameter. Pipe fittings and valves shall be joined as follows:
1. Apply appropriate tape or thread compound to external pipe threads unless dry seal threading is required by the pipe service.
2. Pipe sections with damaged threads shall be replaced with new sections of pipe.
E. Copper tube and fittings with soldered joints shall be joined according to ASTM B828. A water flushable, lead free flux conforming to ASTM B813 and a lead-free alloy solder conforming to ASTM B32 shall be used.
3.3 SPECIALTY PIPE FITTINGS
A. Transition coupling shall be installed at pipe joints with small differences in pipe outside diameters.
B. Dielectric fittings shall be installed at connections of dissimilar metal piping and tubing.
3.4 PIPE HANGERS, SUPPORTS AND ACCESSORIES
A. All piping shall be supported according to the International Plumbing Code (IPC), Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING, and these specifications. Where conflicts arise between these the code and Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING the most restrictive or the requirement that specifies supports with highest loading or shortest spacing shall apply.
B. Hangers, supports, rods, inserts and accessories used for pipe supports shall be painted according to Section 09 91 00, PAINTING. Electroplated copper hanger rods, hangers and accessories may be used with copper tubing.
C. Horizontal piping and tubing shall be supported within 300 mm (12 inches) of each fitting or coupling.
D. Horizontal cast iron piping shall be supported with the following maximum horizontal spacing and minimum hanger rod diameters:
1. 40 mm or DN40 to 50 mm or DN50 (NPS 1-1/2 inch to NPS 2 inch): 1500 mm (60 inches) with 10 mm (3/8 inch) rod.
2. 75 mm or DN75 (NPS 3 inch): 1500 mm (60 inches) with 15 mm (1/2 inch) rod.
3. 100 mm or DN100 to 125 mm or DN125 (NPS 4 inch to NPS 5 inch): 1500 mm (60 inches) with 18 mm (5/8 inch) rod.
4. 150 mm or DN150 to 200 mm or DN200 (NPS 6 inch to NPS 8 inch): 1500 mm (60 inches) with 20 mm (3/4 inch) rod.
5. 250 mm or DN250 to 300 mm or DN300 (NPS 10 inch to NPS 12 inch): 1500 mm (60 inch) with 23 mm (7/8 inch) rod.
E.
F. Vertical piping and tubing shall be supported at the base, at each floor, and at intervals no greater than 4.6 m (15 feet).
G. In addition to the requirements in Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING, Floor, Wall and Ceiling Plates, Supports, Hangers shall have the following characteristics:
1. Solid or split unplated cast iron.
2. All plates shall be provided with set screws.
3. Height adjustable clevis type pipe hangers.
4. Adjustable floor rests and base flanges shall be steel.
5. Hanger rods shall be low carbon steel, fully threaded or threaded at each end with two removable nuts at each end for positioning rod and hanger and locking each in place.
6. Riser clamps shall be malleable iron or steel.
7. Rollers shall be cast iron.
22 13 00 - 10
8. See Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING, for requirements on insulated pipe protective shields at hanger supports.
H. Miscellaneous materials shall be provided as specified, required, directed or as noted in the contract documents for proper installation of hangers, supports and accessories. If the vertical distance exceeds 6.1 m (20 feet) for cast iron pipe additional support shall be provided in the center of that span. All necessary auxiliary steel shall be provided to provide that support.
I. Cast escutcheon with set screw shall be provided at each wall, floor and ceiling penetration in exposed finished locations and within cabinets and millwork.
J. Penetrations:
1. Fire Stopping: Where pipes pass through fire partitions, fire walls, smoke partitions, or floors, a fire stop shall be installed that provides an effective barrier against the spread of fire, smoke and gases as specified in Section 07 84 00, FIRESTOPPING. Clearances between raceways and openings shall be completely filled and sealed with the fire stopping materials.
2. Water proofing: At floor penetrations, clearances shall be completely sealed around the pipe and make watertight with sealant as specified in Section 07 92 00, JOINT
SEALANTS.
K. Exhaust vents shall be extended separately through roof. Sanitary vents shall not connect to exhaust vents.
3.5 TESTS
A. Sanitary waste and drain systems shall be tested either in its entirety or in sections.
B. Waste System tests shall be conducted before trenches are backfilled or fixtures are connected.
A water test or air test shall be conducted, as directed.
1. If entire system is tested for a water test, tightly close all openings in pipes except highest opening, and fill system with water to point of overflow. If the waste system is tested in sections, tightly plug each opening except highest opening of section under test, fill each section with water and test with at least a 3 m (10 foot) head of water. In testing successive sections, test at least upper 3 m (10 feet) of next preceding section so that each joint or pipe except upper most 3 m (10 feet) of system has been submitted to a test of at least a 3 m (10 foot) head of water. Water shall be kept in the system, or in portion under test, for at least 15 minutes before inspection starts. System shall then be tight at all joints.
2. For an air test, an air pressure of 34 kPa (5 psig) gauge shall be maintained for at least 15 minutes without leakage. A force pump and mercury column gauge shall be used for the air test.
3. After installing all fixtures and equipment, open water supply so that all p-traps can be observed. For 15 minutes of operation, all p-traps shall be inspected for leaks and any leaks found shall be corrected.
4. Final Tests: Either one of the following tests may be used.
a. Smoke Test: After fixtures are permanently connected and traps are filled with water, fill entire drainage and vent systems with smoke under pressure of .25 kPa (1 inch of water) with a smoke machine. Chemical smoke is prohibited.
b. Peppermint Test: Introduce 60 ml (2 ounces) of peppermint into each line or stack.
3.6 COMMISSIONING
A. Provide commissioning documentation in accordance with the requirements of Section 22 08
00, COMMISSIONING OF PLUMBING SYSTEMS.
B. Components provided under this section of the specification shall be tested as part of a larger system.
22 13 00 - 11
3.7 DEMONSTRATION AND TRAINING
A. Provide services of manufacturer’s technical representative for 4 hours to instruct each VA personnel responsible in operation and maintenance of the system.
B. Submit training plans and instructor qualifications in accordance with the requirements of Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS.
- - - E N D - - -
22 13 00 - 1
This page intentionally left blank.
Plumbing Fixtures
22 40 00 - 1
SECTION 22 40 00
PLUMBING FIXTURES
PART 1 - GENERAL
1.1 DESCRIPTION
A. Plumbing fixtures, associated trim and fittings necessary to make a complete installation from wall or floor connections to rough piping, and certain accessories.
B. A complete listing of all acronyms and abbreviations are included in Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.
1.2 RELATED WORK
A. Section 01 00 00, GENERAL REQUIREMENTS.
B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
C. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.
D. Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS.
E. Section 07 92 00, JOINT SEALANTS: Sealing between fixtures and other finish surfaces.
F. Section 08 31 13, ACCESS DOORS AND FRAMES: Flush panel access doors.
G. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.
H. Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS: Requirements for commissioning, systems readiness checklist, and training.
I. 22 13 00, FACILITY SANITARY AND VENT PIPING.
1.3 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. The American Society of Mechanical Engineers (ASME):
A112.6.1M-1997 (R2012) ...... Supports for Off-the-Floor Plumbing Fixtures for Public Use
A112.19.1-2013 ..................... Enameled Cast Iron and Enameled Steel Plumbing Fixtures
A112.19.2-2013 ..................... Ceramic Plumbing Fixtures
A112.19.3-2008 ..................... Stainless Steel Plumbing Fixtures
C. American Society for Testing and Materials (ASTM):
A276-2013a ........................... Standard Specification for Stainless Steel Bars and Shapes
B584-2008 ............................. Standard Specification for Copper Alloy Sand Castings for General Applications
D. CSA Group:
B45.4-2008 (R2013) .............. Stainless Steel Plumbing Fixtures
E. National Association of Architectural Metal Manufacturers (NAAMM):
AMP 500-2006 ...................... Metal Finishes Manual
F. American Society of Sanitary Engineering (ASSE):
1016-2011 ............................. Automatic Compensating Valves for Individual Showers and
Tub/Shower Combinations
22 40 00 - 2
G. NSF International (NSF):
14-2013 ................................. Plastics Piping System Components and Related Materials
61-2013 ................................. Drinking Water System Components – Health Effects
372-2011 ............................... Drinking Water System Components – Lead Content
H. American with Disabilities Act (A.D.A)
I. International Code Council (ICC):
IPC-2015 ............................... International Plumbing Code
1.4 SUBMITTALS
A. Submittals, including number of required copies, shall be submitted in accordance with Section
01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Information and material submitted under this section shall be marked “SUBMITTED UNDER SECTION 22 40 00, PLUMBING FIXTURES”, with applicable paragraph identification.
C. Manufacturer's Literature and Data including: Full item description and optional features and accessories. Include dimensions, weights, materials, applications, standard compliance, model numbers, size, connections, and capacity.
D. Operating Instructions: Comply with requirements in Section 01 00 00, GENERAL
REQUIREMENTS.
E. Completed System Readiness Checklist provided by the CxA and completed by the Contractor, signed by a qualified technician and dated on the date of completion, in accordance with the requirements of Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS.
F. Submit training plans and instructor qualifications in accordance with the requirements of Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS.
1.5 QUALITY ASSURANCE
A. Bio-Based Materials: For products designated by the USDA’s Bio-Preferred Program, provide products that meet or exceed USDA recommendations for bio-based content, so long as products meet all…