Department of Veteran Affairs Women's Health, 2nd Floor

Jesse Brown VA Medical Center Chicago, IL

October 28, 2024

100% Design Resubmittal Basis of Design Report – Volume 2

Project Number: 537-327

100% Design Submittal

Women’s Health, 2nd Floor

Jesse Brown VA Medical Center

Chicago, IL

February 28, 2024

TABLE OF CONTENTS

NARRATIVES

A. Architectural Narrative

B. Structural Narrative

C. Fire Protection Narrative

D. Plumbing Narrative

E. Mechanical Narrative

F. Electrical Narrative

G. Physical Security Narrative

H. Environmental Narrative

APPENDIX

TAB A. Cost Estimate

TAB B. Mechanical Calcs

And Equipment

TAB C. Structural Calculations

(Basis of Design - Vol. 2 & Vol. 3)

NOTE: ALL SECTIONS MAY NOT BE APPLICABLE OR INCLUDED IN INTERIM SUBMITTALS

100% Design Submittal

Women’s Health, 2nd Floor

Jesse Brown VA Medical Center

Chicago, IL

February 28, 2024

Basis of Design – Volume 2

TAB C. Structural Calculations

Attachment 2 Structural

Calculations

Design Criteria

Main Building RAM Structural System Model

Floor Map

RAM Steel 23.00.00.92

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: Existing 1st

10.1

10.1

31.5

31.5

40.5

40.5

41.5

41.5

44.5

44.5

A A

B.5 B.5

C C C.5 C.5

D.5 D.5

E.5 E.5

G G

J.1 J.1

N N

N.1 N.1 N.2 N.2 N.3 N.3 N.4 N.4

S S

R.1 R.1

U U

V.5 V.5

W W W.5 W.5 Y Y

BB BB

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Surface Loads

Label DL CDL LL Reduction PLL CLL Mass DL psf psf psf Type psf psf psf

Exist Floor 51.0 0.0 100.0 Unreducible 0.0 0.0 41.0

Exist Entry Floor 85.0 0.0 100.0 Unreducible 0.0 0.0 75.0

Page 2/2

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: Existing Roof

10.1

10.1

31.5

31.5

40.5

40.5

41.5

41.5

44.5

44.5

A A

B.5 B.5

C C C.5 C.5

D.5 D.5

E.5 E.5

G G

J.1 J.1

N N

N.1 N.1 N.2 N.2 N.3 N.3 N.4 N.4

S S

R.1 R.1

U U

V.5 V.5

W W W.5 W.5 Y Y

BB BB

L4

L4

L

L

L4

L

L

L2

L

L2

L

L2

L3

L3

L

L3

L

L3

L3

L

L3

L

L4

P3 P3

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Surface Loads

Label DL CDL LL Reduction PLL CLL Mass DL psf psf psf Type psf psf psf

Exist Floor 51.0 0.0 100.0 Unreducible 0.0 0.0 41.0

Exist Roof 51.0 0.0 25.0 Unreducible 0.0 0.0 41.0

Line Loads

Label DL CDL LL Reduction PLL CLL Mass DL k/ft k/ft k/ft Type k/ft k/ft k/ft

L2 Atrium Wall 1.500 0.000 0.000 Reducible 0.000 0.000 1.500

L3 Phouse Wall 1.450 0.000 0.000 Reducible 0.000 0.000 1.450

L4 New Wall 1.750 0.000 0.000 Reducible 0.000 0.000 1.750

Point Loads

Label DL CDL LL Reduction PLL CLL Mass DL kips kips kips Type kips kips kips

P3 Landing Load1 1.600 0.000 2.400 Unreducible 0.000 0.000 0.000

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof

10.1

10.1

31.5

31.5

40.5

40.5

41.5

41.5

44.5

44.5

A A

B.5 B.5

C C C.5 C.5

D.5 D.5

E.5 E.5

G G

J.1 J.1

N N

N.1 N.1 N.2 N.2 N.3 N.3 N.4 N.4

S S

R.1 R.1

U U

V.5 V.5

W W W.5 W.5 Y Y

BB BB

P1 P1

P2 P2

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Surface Loads

Label DL CDL LL Reduction PLL CLL Mass DL psf psf psf Type psf psf psf

New Concrete Roof 52.0 42.0 25.0 Unreducible 0.0 15.0 42.0

Exist Roof 51.0 0.0 25.0 Unreducible 0.0 0.0 41.0

New Phouse Roof 20.0 0.0 25.0 Unreducible 0.0 0.0 10.0

New Mtl Deck Roof 20.0 0.0 25.0 Unreducible 0.0 0.0 10.0

AHU 100.0 0.0 0.0 Reducible 0.0 0.0 0.0

Chiller 65.0 0.0 0.0 Reducible 0.0 0.0 0.0

Point Loads

Label DL CDL LL Reduction PLL CLL Mass DL kips kips kips Type kips kips kips

P1 Post Load 1.200 0.000 0.700 Unreducible 0.000 0.000 0.000

P2 Landing Load2 1.200 0.000 1.700 Unreducible 0.000 0.000 0.000

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: Penthouse Roof

10.1

10.1

31.5

31.5

40.5

40.5

41.5

41.5

44.5

44.5

A A

B.5 B.5

C C C.5 C.5

D.5 D.5

E.5 E.5

G G

J.1 J.1

N N

N.1 N.1 N.2 N.2 N.3 N.3 N.4 N.4

S S

R.1 R.1

U U

V.5 V.5

W W W.5 W.5 Y Y

BB BB

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Surface Loads

Label DL CDL LL Reduction PLL CLL Mass DL psf psf psf Type psf psf psf

New Phouse Roof 20.0 0.0 25.0 Unreducible 0.0 0.0 10.0

Gravity Beam Design

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: Penthouse Roof Beam Number = 722

SPAN INFORMATION (ft): I-End (-71.45,-537.81) J-End (-71.45,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Net Total load (in) = 0.589 L/D = 641 > 240 0.37

Standard Joist Selection

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 723

SPAN INFORMATION (ft): I-End (-67.59,-537.81) J-End (-67.59,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 2/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 724

SPAN INFORMATION (ft): I-End (-63.73,-537.81) J-End (-63.73,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 3/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 725

SPAN INFORMATION (ft): I-End (-59.88,-537.81) J-End (-59.88,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 4/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 726

SPAN INFORMATION (ft): I-End (-56.02,-537.81) J-End (-56.02,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 5/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 727

SPAN INFORMATION (ft): I-End (-52.16,-537.81) J-End (-52.16,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 6/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 728

SPAN INFORMATION (ft): I-End (-44.45,-537.81) J-End (-44.45,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 7/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 729

SPAN INFORMATION (ft): I-End (-40.59,-537.81) J-End (-40.59,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 8/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 730

SPAN INFORMATION (ft): I-End (-36.73,-537.81) J-End (-36.73,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 9/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 731

SPAN INFORMATION (ft): I-End (-32.88,-537.81) J-End (-32.88,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 10/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 732

SPAN INFORMATION (ft): I-End (-29.02,-537.81) J-End (-29.02,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 11/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 733

SPAN INFORMATION (ft): I-End (-25.16,-537.81) J-End (-25.16,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 12/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 734

SPAN INFORMATION (ft): I-End (-17.45,-537.81) J-End (-17.45,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 13/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 735

SPAN INFORMATION (ft): I-End (-13.59,-537.81) J-End (-13.59,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 14/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 736

SPAN INFORMATION (ft): I-End (-9.73,-537.81) J-End (-9.73,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 15/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 737

SPAN INFORMATION (ft): I-End (-5.88,-537.81) J-End (-5.88,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 16/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 738

SPAN INFORMATION (ft): I-End (-2.02,-537.81) J-End (-2.02,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 17/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC

Floor Type: Penthouse Roof Beam Number = 739

SPAN INFORMATION (ft): I-End (1.84,-537.81) J-End (1.84,-506.31)

Joist Size (User Selected) = 22K4

Total Beam Length (ft) = 31.50

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.077 0.096 --- NonR 0.000

31.500 0.077 0.096 0.000

2 0.000 0.000 0.000 --- NonR 0.000

31.500 0.000 0.000 0.000

Maximum Total Unif. Load at any location (lbs/ft) : 173.6

Maximum Allowable Total Unif. Load at any location (lbs/ft) : 550.0

Listed Uniform Capacities (lbs/ft)

Total for Strength: 274.0

L/360 for Deflection: 283.5

Allowable Stress Ratio: 1.00

Deflection Interaction Limit: 1.00

Design Loads Allowable Loads (lbs/ft) Ratio

Dead: 77.1 283.5

Live: 96.4 283.5

Total: 173.6 274.0 0.63

MOMENTS:

Span Cond Moment @ kip-ft ft

Center Max + 21.5 15.8

REACTIONS (kips):

Left Right

DL reaction 1.21 1.21

Max +LL reaction 1.52 1.52

Max +total reaction 2.73 2.73

DEFLECTIONS: (SJI Standard Camber = 3/8) Ratio

Dead load (in) = 0.429 L/D = 882 > 240 0.27

Live load (in) = 0.536 L/D = 706 > 240 0.34

Total load (in) = 0.964 L/D = 392

Page 18/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 2

SPAN INFORMATION (ft): I-End (-191.14,-526.18) J-End (-191.14,-499.18)

Beam Size (User Selected) = W21X73 Fy = 36.0 ksi

Total Beam Length (ft) = 27.00

COMPOSITE PROPERTIES (Not Shored):

Left Right

Deck Label --- Floor

Concrete thickness (in) 0.00 3.25

Unit weight concrete (pcf) 0.00 110.00 f'c (ksi) 0.00 3.00

Decking Orientation parallel perpendicular

Decking type Noncomposite VULCRAFT 2.0VL beff (in) = 33.50 Y bar(in) = 14.40

Mnf (kip-ft) = 748.24 Mn (kip-ft) = 617.25

C (kips) = 85.51 PNA (in) = 13.21

Ieff (in4) = 2248.33 Itr (in4) = 2768.19

Stud length (in) = 3.50 Stud diam (in) = 0.75

Stud Capacity (kips) Qn = 17.1 Rg = 1.00 Rp = 0.60

# of studs: Full = 34 Partial = 10 Actual = 10

Number of Stud Rows = 1 Percent of Full Composite Action = 30.80

LINE LOADS (k/ft):

Load Dist DL CDL LL Red% Type PartL CLL

1 0.000 0.142 0.000 0.070 --- NonR 0.000 0.000

27.000 0.142 0.000 0.070 0.000 0.000

2 0.000 0.073 0.073 0.000 --- NonR 0.000 0.000

27.000 0.073 0.073 0.000 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 5.00 kips 1.00Vn = 208.35 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center PreCmp+ 1.4DL 9.3 13.5 0.0 1.00 0.90 464.40

Init DL 1.4DL 9.3 13.5 --- ---

Max + 1.2DL+1.6LL 33.7 13.5 --- --- 0.90 555.53

Controlling 1.2DL+1.6LL 33.7 13.5 --- --- 0.90 555.53

REACTIONS (kips):

Left Right

Initial reaction 0.99 0.99

DL reaction 2.91 2.91

Max +LL reaction 0.94 0.94

Max +total reaction (factored) 5.00 5.00

DEFLECTIONS: Ratio

Initial load (in) at 13.50 ft = -0.019 L/D = 1718

> 360 0.02

Page 19/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Live load (in) at 13.50 ft = -0.013 L/D = 2531

> 360 0.01

Post Comp load (in) at 13.50 ft = -0.039 L/D = 8327 > 360 0.04

Net Total load (in) at 13.50 ft = -0.058 L/D = 5609 > 240 0.04

Page 20/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 3

SPAN INFORMATION (ft): I-End (-191.14,-526.18) J-End (-185.55,-526.18)

Beam Size (User Selected) = W27X114 Fy = 36.0 ksi

Total Beam Length (ft) = 5.58

Cantilever on left (ft) = 5.58

Mp (kip-ft) = 1029.00

POINT LOADS (kips):

Dist DL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL

0.000 2.91 0.00 0.0 0.94 0.00 0.0 0.00 0.0 0.00

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.114 0.000 --- NonR 0.000

5.583 0.114 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 5.76 kips 1.00Vn = 336.12 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Left Max - 1.2DL+1.6LL -30.0 5.6 5.6 1.00 0.90 926.10

Controlling 1.2DL+1.6LL -30.0 5.6 5.6 1.00 0.90 926.10

REACTIONS (kips):

Left Right

DL reaction --- 3.55

Max +LL reaction --- 0.94

Max +total reaction (factored) --- 5.76

DEFLECTIONS: Ratio

Left cantilever:

Dead load (in) = -0.003 L/D = 50222

Pos Live load (in) = -0.001 L/D = 167856 > 360 0.00

Pos Total load (in) = -0.003 L/D = 38656 > 240 0.01

Page 21/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 4

SPAN INFORMATION (ft): I-End (-191.14,-499.18) J-End (-185.55,-499.18)

Beam Size (User Selected) = W27X114 Fy = 36.0 ksi

Total Beam Length (ft) = 5.58

Cantilever on left (ft) = 5.58

Mp (kip-ft) = 1029.00

POINT LOADS (kips):

Dist DL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL

0.000 2.91 0.00 0.0 0.94 0.00 0.0 0.00 0.0 0.00

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.114 0.000 --- NonR 0.000

5.583 0.114 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 5.76 kips 1.00Vn = 336.12 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Left Max - 1.2DL+1.6LL -30.0 5.6 5.6 1.00 0.90 926.10

Controlling 1.2DL+1.6LL -30.0 5.6 5.6 1.00 0.90 926.10

REACTIONS (kips):

Left Right

DL reaction --- 3.55

Max +LL reaction --- 0.94

Max +total reaction (factored) --- 5.76

DEFLECTIONS: Ratio

Left cantilever:

Dead load (in) = -0.003 L/D = 50222

Pos Live load (in) = -0.001 L/D = 167856 > 360 0.00

Pos Total load (in) = -0.003 L/D = 38656 > 240 0.01

Page 22/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 5

SPAN INFORMATION (ft): I-End (-191.14,-450.31) J-End (-190.55,-439.06)

Beam Size (User Selected) = W12X19 Fy = 36.0 ksi

Total Beam Length (ft) = 11.27

Mp (kip-ft) = 74.10

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.012 0.006 --- NonR 0.000

11.265 0.000 0.000 0.000

2 0.000 0.142 0.070 --- NonR 0.000

11.265 0.127 0.062 0.000

3 0.000 0.019 0.000 --- NonR 0.000

11.265 0.019 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 1.75 kips 1.00Vn = 61.93 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center Max + 1.2DL+1.6LL 4.8 5.5 0.0 1.00 0.90 66.69

Controlling 1.2DL+1.6LL 4.8 5.5 0.0 1.00 0.90 66.69

REACTIONS (kips):

Left Right

DL reaction 0.93 0.88

Max +LL reaction 0.40 0.38

Max +total reaction (factored) 1.75 1.65

DEFLECTIONS: Ratio

Dead load (in) at 5.63 ft = -0.015 L/D = 8794

Live load (in) at 5.63 ft = -0.007 L/D = 2035

> 360 0.02

Net Total load (in) at 5.63 ft = -0.022 L/D = 6140 > 240 0.04

Page 23/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 16

SPAN INFORMATION (ft): I-End (-175.80,-526.18) J-End (-175.80,-499.18)

Beam Size (User Selected) = W18X46 Fy = 36.0 ksi

Total Beam Length (ft) = 27.00

COMPOSITE PROPERTIES (Not Shored):

Left Right

Deck Label Floor Floor

Concrete thickness (in) 3.25 3.25

Unit weight concrete (pcf) 110.00 110.00 f'c (ksi) 3.00 3.00

Decking Orientation perpendicular perpendicular

Decking type VULCRAFT 2.0VL VULCRAFT 2.0VL beff (in) = 81.00 Y bar(in) = 16.45

Mnf (kip-ft) = 531.50 Mn (kip-ft) = 400.91

C (kips) = 136.82 PNA (in) = 14.33

Ieff (in4) = 1392.56 Itr (in4) = 1994.64

Stud length (in) = 3.50 Stud diam (in) = 0.75

Stud Capacity (kips) Qn = 17.1 Rg = 1.00 Rp = 0.60

# of studs: Max = 27 Partial = 16 Actual = 16

Number of Stud Rows = 1 Percent of Full Composite Action = 28.15

LINE LOADS (k/ft):

Load Dist DL CDL LL Red% Type PartL CLL

1 0.000 0.497 0.000 0.244 --- NonR 0.000 0.000

27.000 0.497 0.000 0.244 0.000 0.000

2 0.000 0.046 0.046 0.000 --- NonR 0.000 0.000

27.000 0.046 0.046 0.000 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 14.06 kips 1.00Vn = 140.75 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center PreCmp+ 1.4DL 5.9 13.5 0.0 1.00 0.90 244.89

Init DL 1.4DL 5.9 13.5 --- ---

Max + 1.2DL+1.6LL 94.9 13.5 --- --- 0.90 360.82

Controlling 1.2DL+1.6LL 94.9 13.5 --- --- 0.90 360.82

REACTIONS (kips):

Left Right

Initial reaction 0.62 0.62

DL reaction 7.33 7.33

Max +LL reaction 3.29 3.29

Max +total reaction (factored) 14.06 14.06

DEFLECTIONS: Ratio

Initial load (in) at 13.50 ft = -0.027 L/D = 1217

> 360 0.03

Page 24/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Live load (in) at 13.50 ft = -0.072 L/D = 4489 > 360 0.08

Post Comp load (in) at 13.50 ft = -0.219 L/D = 1477 > 360 0.24

Net Total load (in) at 13.50 ft = -0.246 L/D = 1317 > 240 0.18

Page 25/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 19

SPAN INFORMATION (ft): I-End (-166.05,-526.18) J-End (-166.05,-499.18)

Beam Size (User Selected) = W18X46 Fy = 36.0 ksi

Total Beam Length (ft) = 27.00

COMPOSITE PROPERTIES (Not Shored):

Left Right

Deck Label Floor Floor

Concrete thickness (in) 3.25 3.25

Unit weight concrete (pcf) 110.00 110.00 f'c (ksi) 3.00 3.00

Decking Orientation perpendicular perpendicular

Decking type VULCRAFT 2.0VL VULCRAFT 2.0VL beff (in) = 81.00 Y bar(in) = 16.45

Mnf (kip-ft) = 531.50 Mn (kip-ft) = 400.91

C (kips) = 136.82 PNA (in) = 14.33

Ieff (in4) = 1392.56 Itr (in4) = 1994.64

Stud length (in) = 3.50 Stud diam (in) = 0.75

Stud Capacity (kips) Qn = 17.1 Rg = 1.00 Rp = 0.60

# of studs: Max = 27 Partial = 17 Actual = 17

Number of Stud Rows = 1 Percent of Full Composite Action = 28.04

LINE LOADS (k/ft):

Load Dist DL CDL LL Red% Type PartL CLL

1 0.000 0.485 0.000 0.237 --- NonR 0.000 0.000

27.000 0.497 0.000 0.244 0.000 0.000

2 0.000 0.046 0.046 0.000 --- NonR 0.000 0.000

27.000 0.046 0.046 0.000 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 13.95 kips 1.00Vn = 140.75 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center PreCmp+ 1.4DL 5.9 13.5 0.0 1.00 0.90 244.89

Init DL 1.4DL 5.9 13.5 --- ---

Max + 1.2DL+1.6LL 93.8 13.5 --- --- 0.90 360.82

Controlling 1.2DL+1.6LL 93.8 13.5 --- --- 0.90 360.82

REACTIONS (kips):

Left Right

Initial reaction 0.62 0.62

DL reaction 7.22 7.28

Max +LL reaction 3.23 3.26

Max +total reaction (factored) 13.84 13.95

DEFLECTIONS: Ratio

Initial load (in) at 13.50 ft = -0.027 L/D = 1217

> 360 0.03

Page 26/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Live load (in) at 13.50 ft = -0.071 L/D = 4548 > 360 0.08

Post Comp load (in) at 13.50 ft = -0.217 L/D = 1496 > 360 0.24

Net Total load (in) at 13.50 ft = -0.243 L/D = 1332 > 240 0.18

Page 27/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 23

SPAN INFORMATION (ft): I-End (-156.80,-526.18) J-End (-129.30,-526.18)

Beam Size (User Selected) = W27X94 Fy = 36.0 ksi

Total Beam Length (ft) = 27.50

COMPOSITE PROPERTIES (Not Shored):

Left Right

Deck Label Floor Floor

Concrete thickness (in) 3.25 3.25

Unit weight concrete (pcf) 110.00 110.00 f'c (ksi) 3.00 3.00

Decking Orientation parallel parallel

Decking type VULCRAFT 2.0VL VULCRAFT 2.0VL beff (in) = 44.31 Y bar(in) = 18.11

Mnf (kip-ft) = 1194.87 Mn (kip-ft) = 995.97

C (kips) = 119.72 PNA (in) = 16.84

Ieff (in4) = 4528.71 Itr (in4) = 5474.41

Stud length (in) = 3.50 Stud diam (in) = 0.75

Stud Capacity (kips) Qn = 17.1 Rg = 1.00 Rp = 0.75

# of studs: Full = 64 Partial = 17 Actual = 17

Number of Stud Rows = 1 Percent of Full Composite Action = 27.04

POINT LOADS (kips):

Dist DL CDL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL

9.500 7.08 0.76 0.00 0.0 3.09 0.00 0.0 0.00 0.0 0.00

18.500 7.02 0.82 0.00 0.0 3.04 0.00 0.0 0.00 0.0 0.00

LINE LOADS (k/ft):

Load Dist DL CDL LL Red% Type PartL CLL

1 0.000 0.094 0.094 0.000 --- NonR 0.000 0.000

27.500 0.094 0.094 0.000 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 15.13 kips 1.00Vn = 284.71 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center PreCmp+ 1.4DL 22.7 13.8 9.0 1.01 0.90 750.60

Init DL 1.4DL 22.7 13.8 --- ---

Max + 1.2DL+1.6LL 134.7 11.1 --- --- 0.90 896.37

Controlling 1.2DL+1.6LL 134.5 9.5 --- --- 0.90 877.69

REACTIONS (kips):

Left Right

Initial reaction 2.06 2.11

DL reaction 8.22 8.46

Max +LL reaction 3.02 3.11

Max +total reaction (factored) 14.69 15.13

Page 28/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

DEFLECTIONS: Ratio

Initial load (in) at 13.75 ft = -0.023 L/D = 1406

> 360 0.03

Live load (in) at 13.75 ft = -0.030 L/D = 1102

> 360 0.03

Post Comp load (in) at 13.75 ft = -0.091 L/D = 3625 > 360 0.10

Net Total load (in) at 13.75 ft = -0.114 L/D = 2882 > 240 0.08

Page 29/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 24

SPAN INFORMATION (ft): I-End (-156.42,-505.43) J-End (-147.30,-505.43)

Beam Size (User Selected) = W10X15 Fy = 36.0 ksi

Total Beam Length (ft) = 9.12

Mp (kip-ft) = 48.00

POINT LOADS (kips):

Dist DL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL

4.116 0.77 0.00 0.0 0.35 0.00 0.0 0.00 0.0 0.00

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.015 0.000 --- NonR 0.000

9.115 0.015 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 0.90 kips 1.00Vn = 49.63 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center Max + 1.2DL+1.6LL 3.6 4.1 5.0 1.64 0.90 43.20

Controlling 1.2DL+1.6LL 3.6 4.1 5.0 1.64 0.90 43.20

REACTIONS (kips):

Left Right

DL reaction 0.49 0.42

Max +LL reaction 0.19 0.16

Max +total reaction (factored) 0.90 0.76

DEFLECTIONS: Ratio

Dead load (in) at 4.42 ft = -0.012 L/D = 9476

Live load (in) at 4.42 ft = -0.005 L/D = 2289

> 360 0.02

Net Total load (in) at 4.42 ft = -0.016 L/D = 6702 > 240 0.04

Page 30/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 25

SPAN INFORMATION (ft): I-End (-156.30,-499.18) J-End (-129.30,-499.18)

Beam Size (User Selected) = W27X94 Fy = 36.0 ksi

Total Beam Length (ft) = 27.00

COMPOSITE PROPERTIES (Not Shored):

Left Right

Deck Label --- Floor

Concrete thickness (in) 0.00 3.25

Unit weight concrete (pcf) 0.00 110.00 f'c (ksi) 0.00 3.00

Decking Orientation parallel parallel

Decking type Noncomposite VULCRAFT 2.0VL beff (in) = 37.49 Y bar(in) = 17.56

Mnf (kip-ft) = 1159.73 Mn (kip-ft) = 995.01

C (kips) = 119.72 PNA (in) = 16.84

Ieff (in4) = 4478.38 Itr (in4) = 5216.73

Stud length (in) = 3.50 Stud diam (in) = 0.75

Stud Capacity (kips) Qn = 17.1 Rg = 1.00 Rp = 0.75

# of studs: Full = 53 Partial = 14 Actual = 14

Number of Stud Rows = 1 Percent of Full Composite Action = 26.30

POINT LOADS (kips):

Dist DL CDL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL

4.000 0.77 0.05 0.00 0.0 0.35 0.00 0.0 0.00 0.0 0.00

9.000 6.75 0.81 0.00 0.0 2.91 0.00 0.0 0.00 0.0 0.00

18.000 7.03 0.84 0.00 0.0 3.04 0.00 0.0 0.00 0.0 0.00

LINE LOADS (k/ft):

Load Dist DL CDL LL Red% Type PartL CLL

1 0.000 0.094 0.094 0.000 --- NonR 0.000 0.000

27.000 0.094 0.094 0.000 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 15.72 kips 1.00Vn = 284.71 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center PreCmp+ 1.4DL 22.5 13.5 9.0 1.01 0.90 750.60

Init DL 1.4DL 22.5 13.5 --- ---

Max + 1.2DL+1.6LL 130.5 13.2 --- --- 0.90 895.51

Controlling 1.2DL+1.6LL 129.5 9.0 --- --- 0.90 857.75

REACTIONS (kips):

Left Right

Initial reaction 2.13 2.10

DL reaction 8.76 8.32

Max +LL reaction 3.25 3.05

Max +total reaction (factored) 15.72 14.86

Page 31/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

DEFLECTIONS: Ratio

Initial load (in) at 13.50 ft = -0.023 L/D = 1439

> 360 0.03

Live load (in) at 13.50 ft = -0.028 L/D = 1138

> 360 0.03

Post Comp load (in) at 13.50 ft = -0.087 L/D = 3744 > 360 0.10

Net Total load (in) at 13.50 ft = -0.109 L/D = 2971 > 240 0.08

Page 32/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 30

SPAN INFORMATION (ft): I-End (-156.30,-439.06) J-End (-138.30,-439.06)

Beam Size (User Selected) = W16X31 Fy = 36.0 ksi

Total Beam Length (ft) = 18.00

Mp (kip-ft) = 162.00

POINT LOADS (kips):

Dist DL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL

9.000 2.69 0.00 0.0 1.27 0.00 0.0 0.00 0.0 0.00

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.031 0.000 --- NonR 0.000

18.000 0.031 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 2.96 kips 1.00Vn = 94.45 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center Max + 1.2DL+1.6LL 25.1 9.0 9.0 1.64 0.90 145.80

Controlling 1.2DL+1.6LL 25.1 9.0 9.0 1.64 0.90 145.80

REACTIONS (kips):

Left Right

DL reaction 1.62 1.62

Max +LL reaction 0.63 0.63

Max +total reaction (factored) 2.96 2.96

DEFLECTIONS: Ratio

Dead load (in) at 9.00 ft = -0.059 L/D = 3683

Live load (in) at 9.00 ft = -0.024 L/D = 8841 > 360 0.04

Net Total load (in) at 9.00 ft = -0.083 L/D = 2600 > 240 0.09

Page 33/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 31

SPAN INFORMATION (ft): I-End (-152.30,-505.43) J-End (-152.30,-499.18)

Beam Size (User Selected) = W10X15 Fy = 36.0 ksi

Total Beam Length (ft) = 6.25

Mp (kip-ft) = 48.00

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.232 0.114 --- NonR 0.000

6.248 0.229 0.113 0.000

2 0.000 0.015 0.000 --- NonR 0.000

6.248 0.015 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 1.49 kips 1.00Vn = 49.63 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center Max + 1.2DL+1.6LL 2.3 3.1 0.0 1.00 0.90 43.20

Controlling 1.2DL+1.6LL 2.3 3.1 0.0 1.00 0.90 43.20

REACTIONS (kips):

Left Right

DL reaction 0.77 0.77

Max +LL reaction 0.35 0.35

Max +total reaction (factored) 1.49 1.49

DEFLECTIONS: Ratio

Dead load (in) at 3.12 ft = -0.004 L/D = 1775

Live load (in) at 3.12 ft = -0.002 L/D = 3857

> 360 0.01

Net Total load (in) at 3.12 ft = -0.006 L/D = 1215

> 240 0.02

Page 34/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 32

SPAN INFORMATION (ft): I-End (-147.30,-526.18) J-End (-147.30,-499.18)

Beam Size (User Selected) = W18X55 Fy = 36.0 ksi

Total Beam Length (ft) = 27.00

COMPOSITE PROPERTIES (Not Shored):

Left Right

Deck Label Floor Floor

Concrete thickness (in) 3.25 3.25

Unit weight concrete (pcf) 110.00 110.00 f'c (ksi) 3.00 3.00

Decking Orientation perpendicular perpendicular

Decking type VULCRAFT 2.0VL VULCRAFT 2.0VL beff (in) = 81.00 Y bar(in) = 15.88

Mnf (kip-ft) = 626.37 Mn (kip-ft) = 478.86

C (kips) = 153.93 PNA (in) = 14.53

Ieff (in4) = 1619.04 Itr (in4) = 2309.07

Stud length (in) = 3.50 Stud diam (in) = 0.75

Stud Capacity (kips) Qn = 17.1 Rg = 1.00 Rp = 0.60

# of studs: Max = 27 Partial = 18 Actual = 18

Number of Stud Rows = 1 Percent of Full Composite Action = 26.38

POINT LOADS (kips):

Dist DL CDL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL

20.751 0.42 0.09 0.00 0.0 0.16 0.00 0.0 0.00 0.0 0.00

LINE LOADS (k/ft):

Load Dist DL CDL LL Red% Type PartL CLL

1 0.000 0.242 0.000 0.119 --- NonR 0.000 0.000

20.751 0.232 0.000 0.114 0.000 0.000

2 20.752 0.128 0.000 0.063 --- NonR 0.000 0.000

27.000 0.128 0.000 0.063 0.000 0.000

3 0.000 0.229 0.000 0.113 --- NonR 0.000 0.000

27.000 0.229 0.000 0.113 0.000 0.000

4 0.000 0.055 0.055 0.000 --- NonR 0.000 0.000

27.000 0.055 0.055 0.000 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 13.44 kips 1.00Vn = 152.47 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center PreCmp+ 1.4DL 7.4 13.9 0.0 1.00 0.90 302.40

Init DL 1.4DL 7.4 13.9 --- ---

Max + 1.2DL+1.6LL 90.5 13.5 --- --- 0.90 430.97

Controlling 1.2DL+1.6LL 90.5 13.5 --- --- 0.90 430.97

REACTIONS (kips):

Page 35/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Left Right

Initial reaction 0.76 0.81

DL reaction 7.08 6.75

Max +LL reaction 3.09 2.91

Max +total reaction (factored) 13.44 12.75

DEFLECTIONS: Ratio

Initial load (in) at 13.50 ft = -0.027 L/D = 1194

> 360 0.03

Live load (in) at 13.50 ft = -0.058 L/D = 5582 > 360 0.06

Post Comp load (in) at 13.50 ft = -0.176 L/D = 1836 > 360 0.20

Net Total load (in) at 13.50 ft = -0.204 L/D = 1592 > 240 0.15

Page 36/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 35

SPAN INFORMATION (ft): I-End (-147.30,-450.31) J-End (-147.30,-439.06)

Beam Size (User Selected) = W12X19 Fy = 36.0 ksi

Total Beam Length (ft) = 11.25

Mp (kip-ft) = 74.10

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.459 0.225 --- NonR 0.000

11.250 0.459 0.225 0.000

2 0.000 0.019 0.000 --- NonR 0.000

11.250 0.019 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 5.25 kips 1.00Vn = 61.93 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center Max + 1.2DL+1.6LL 14.8 5.6 0.0 1.00 0.90 66.69

Controlling 1.2DL+1.6LL 14.8 5.6 0.0 1.00 0.90 66.69

REACTIONS (kips):

Left Right

DL reaction 2.69 2.69

Max +LL reaction 1.27 1.27

Max +total reaction (factored) 5.25 5.25

DEFLECTIONS: Ratio

Dead load (in) at 5.63 ft = -0.046 L/D = 2955

Live load (in) at 5.63 ft = -0.022 L/D = 6276 > 360 0.06

Net Total load (in) at 5.63 ft = -0.067 L/D = 2009 > 240 0.12

Page 37/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 36

SPAN INFORMATION (ft): I-End (-138.30,-526.18) J-End (-138.30,-499.18)

Beam Size (User Selected) = W18X55 Fy = 36.0 ksi

Total Beam Length (ft) = 27.00

COMPOSITE PROPERTIES (Not Shored):

Left Right

Deck Label Floor Floor

Concrete thickness (in) 3.25 3.25

Unit weight concrete (pcf) 110.00 110.00 f'c (ksi) 3.00 3.00

Decking Orientation perpendicular perpendicular

Decking type VULCRAFT 2.0VL VULCRAFT 2.0VL beff (in) = 81.00 Y bar(in) = 15.88

Mnf (kip-ft) = 626.37 Mn (kip-ft) = 478.86

C (kips) = 153.93 PNA (in) = 14.53

Ieff (in4) = 1619.04 Itr (in4) = 2309.07

Stud length (in) = 3.50 Stud diam (in) = 0.75

Stud Capacity (kips) Qn = 17.1 Rg = 1.00 Rp = 0.60

# of studs: Max = 27 Partial = 19 Actual = 19

Number of Stud Rows = 1 Percent of Full Composite Action = 26.35

POINT LOADS (kips):

Dist DL CDL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL

9.938 0.09 0.09

19.875 0.09 0.09

LINE LOADS (k/ft):

Load Dist DL CDL LL Red% Type PartL CLL

1 0.000 0.459 0.000 0.225 --- NonR 0.000 0.000

27.000 0.459 0.000 0.225 0.000 0.000

2 0.000 0.055 0.055 0.000 --- NonR 0.000 0.000

27.000 0.055 0.055 0.000 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 13.30 kips 1.00Vn = 152.47 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center PreCmp+ 1.4DL 8.1 13.4 0.0 1.00 0.90 302.40

Init DL 1.4DL 8.1 13.4 --- ---

Max + 1.2DL+1.6LL 89.9 13.5 --- --- 0.90 430.97

Controlling 1.2DL+1.6LL 83.7 9.9 --- --- 0.90 395.91

REACTIONS (kips):

Left Right

Initial reaction 0.82 0.84

DL reaction 7.02 7.03

Max +LL reaction 3.04 3.04

Page 38/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Left Right

Max +total reaction (factored) 13.28 13.30

DEFLECTIONS: Ratio

Initial load (in) at 13.50 ft = -0.029 L/D = 1104

> 360 0.03

Live load (in) at 13.50 ft = -0.057 L/D = 5654 > 360 0.06

Post Comp load (in) at 13.50 ft = -0.174 L/D = 1860 > 360 0.19

Net Total load (in) at 13.50 ft = -0.204 L/D = 1592 > 240 0.15

Page 39/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 37

SPAN INFORMATION (ft): I-End (-138.30,-516.25) J-End (-129.30,-516.25)

Beam Size (User Selected) = W12X19 Fy = 36.0 ksi

Total Beam Length (ft) = 9.00

Mp (kip-ft) = 74.10

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.019 0.000 --- NonR 0.000

9.000 0.019 0.000 0.000

SHEAR (Ultimate): Max Vu (1.4DL) = 0.12 kips 1.00Vn = 61.93 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center Max + 1.4DL 0.3 4.5 9.0 1.14 0.90 52.43

Controlling 1.4DL 0.3 4.5 9.0 1.14 0.90 52.43

REACTIONS (kips):

Left Right

DL reaction 0.09 0.09

Max +total reaction (factored) 0.12 0.12

DEFLECTIONS: Ratio

Dead load (in) at 4.50 ft = -0.001 L/D = 1455

Live load (in) at 4.50 ft = -0.000

Net Total load (in) at 4.50 ft = -0.001 L/D = 1455

> 240 0.00

Page 40/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 38

SPAN INFORMATION (ft): I-End (-138.30,-506.31) J-End (-129.30,-506.31)

Beam Size (User Selected) = W12X19 Fy = 36.0 ksi

Total Beam Length (ft) = 9.00

Mp (kip-ft) = 74.10

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.019 0.000 --- NonR 0.000

9.000 0.019 0.000 0.000

SHEAR (Ultimate): Max Vu (1.4DL) = 0.12 kips 1.00Vn = 61.93 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center Max + 1.4DL 0.3 4.5 9.0 1.14 0.90 52.43

Controlling 1.4DL 0.3 4.5 9.0 1.14 0.90 52.43

REACTIONS (kips):

Left Right

DL reaction 0.09 0.09

Max +total reaction (factored) 0.12 0.12

DEFLECTIONS: Ratio

Dead load (in) at 4.50 ft = -0.001 L/D = 1455

Live load (in) at 4.50 ft = -0.000

Net Total load (in) at 4.50 ft = -0.001 L/D = 1455

> 240 0.00

Page 41/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 41

SPAN INFORMATION (ft): I-End (-138.30,-450.31) J-End (-138.30,-439.06)

Beam Size (User Selected) = W12X19 Fy = 36.0 ksi

Total Beam Length (ft) = 11.25

Mp (kip-ft) = 74.10

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.459 0.225 --- NonR 0.000

11.250 0.459 0.225 0.000

2 0.000 0.019 0.000 --- NonR 0.000

11.250 0.019 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 5.25 kips 1.00Vn = 61.93 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center Max + 1.2DL+1.6LL 14.8 5.6 0.0 1.00 0.90 66.69

Controlling 1.2DL+1.6LL 14.8 5.6 0.0 1.00 0.90 66.69

REACTIONS (kips):

Left Right

DL reaction 2.69 2.69

Max +LL reaction 1.27 1.27

Max +total reaction (factored) 5.25 5.25

DEFLECTIONS: Ratio

Dead load (in) at 5.63 ft = -0.046 L/D = 2955

Live load (in) at 5.63 ft = -0.022 L/D = 6276 > 360 0.06

Page 42/1129

DataBase: Chicago Womens Clinic Updated 02/26/24 10:38:21

Building Code: IBC Steel Code: AISC 360-16 LRFD

Floor Type: New roof Beam Number = 42

SPAN INFORMATION (ft): I-End (-138.30,-439.06) J-End (-120.30,-439.06)

Beam Size (User Selected) = W16X31 Fy = 36.0 ksi

Total Beam Length (ft) = 18.00

Mp (kip-ft) = 162.00

POINT LOADS (kips):

Dist DL RedLL Red% NonRLL StorLL Red% RoofLL Red% PartL

9.000 2.73 0.00 0.0 1.27 0.00 0.0 0.00 0.0 0.00

LINE LOADS (k/ft):

Load Dist DL LL Red% Type PartL

1 0.000 0.031 0.000 --- NonR 0.000

18.000 0.031 0.000 0.000

SHEAR (Ultimate): Max Vu (1.2DL+1.6LL) = 2.98 kips 1.00Vn = 94.45 kips

MOMENTS (Ultimate):

Span Cond LoadCombo Mu @ Lb Cb Phi Phi*Mn kip-ft ft ft kip-ft

Center Max + 1.2DL+1.6LL 25.4 9.0 9.0 1.64 0.90…