This document provides details for a federal contract opportunity to construct an inpatient medicine bed addition at the Kansas City VA Medical Center. The contractor will be responsible for demolishing existing structures, constructing a third-floor addition and renovating other areas to create a continuous inpatient unit. Additional work includes installing two elevators and accommodating portable MRI machines during construction. The project scope includes general construction, alterations, asbestos and lead remediation, civil and site work, electrical and telecommunications systems, mechanical, plumbing and fire protection systems. The contract will be awarded as a firm-fixed-price contract following a request for proposal issued in mid-March 2024 with a period of performance of approximately 466 calendar days. The solicitation will be conducted as a tiered set-aside giving priority to SDVOSB, VOSB, small business with HUBZone/8A, and large business concerns.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES - STRUCTURAL
1. General Information
A. The contractor shall verify dimensions and conditions before construction and notify the engineer of any discrepancies, inconsistencies, or difficulties affecting the work before proceeding.
B. The contractor shall coordinate all disciplines, verifying size and location of all openings, whether shown on structural drawings or not, as called for on architectural, mechanical, or electrical drawings. In the case of work in an existing building the contractor shall scan existing structure to locate all rebar in the area of the new core/opening using ground penetrating radar and notify the engineer of record for review prior to coring/cutting. Conflicts, inconsistencies, or other difficulties affecting structural work shall be called to the engineer's attention for direction before proceeding.
C. All design and construction work for this project shall conform to the requirements of the following governing design codes:
1.) International Building Code (IBC 2018) 2.) Minimum Design Loads for Buildings and Other Structures (ASCE7-16) 3.) Specification for Structural Steel Buildings (AISC 360-16)
Member Design Basis is Allowable Stress Design (ASD) Connection Design Basis is Allowable Stress Design (ASD)
4.) Structural Welding Code (AWS D1.4/D1.4M-17) 5.) Building Code Requirements for Structural Concrete (ACI 318-14) 6.) Building Code Requirements for Masonry Structures (TMS 402-16) 7.) North American Specification for the Design of Cold-Formed Steel Structural
Members (AISI S100-07/S1-1) 8.) Seismic Design Requirements H-18-8 9.) VA Structural Design Manual pg 18-10
D. These drawings are for this specific project and no other use is authorized.
2. Structural Load Design Criteria
A. Floor Live = 100psf B. Roof Live = 20 psf C. Snow: Pg = 20psf, Pf =17psf, Is = 1.2, Ce = 1.0, Ct = 1.0, Drift per ASCE/SEI 7 D. Lateral Loads:
1.) Wind: V = 122 mph, Exposure C Occupancy [Risk] Category IV, Iw=1.0 GCpi=+/-0.18 Design wind pressures to be used for the design of exterior component and cladding materials on the designated zones of wall and roof surfaces shall be per section 30.7 and Table 30.7-2 of ASCE/SEI 7. Tabulated pressures shall be multiplied by effective area reduction factors, exposure adjustment factors, and topographic factors where applicable
2.) Seismic: Ss = 0.096, S1 = 0.069 Occupancy [Risk] Category IV, Ie=1.5, Site Classification C; Sds = 0.083; Sd1 = 0.069 Seismic Design Category C Basic Seismic Force-resisting System (South Addition):
Steel Ordinary Moment-Resisiting Frame Equivalent Lateral Force Procedure R = 3.5; V = 0.036W; Omega = 3.0; Cd = 3.0
Basic Seismic Force-resisting System (North Addition):
Ordinary Reinforced Concrete Shear Walls Equivalent Lateral Force Procedure R = 4.0; V = 0.031W; Omega = 2.5; Cd = 4.0
E. This project is designed to resist the most critical effects resulting from the load combinations of section 1605.3 of the International Building Code.
3. Concrete
A. All concrete for foundations (walls, grade beams, footings and piers) shall develop minimum ultimate compressive design strength of 3500 psi in 28 days, but not less than 500 pounds of cement shall be used per cubic yard of concrete regardless of strengths obtained, not over 6 gallons of water per 100 pounds of cement and not over 4 inches of slump.
B. All concrete for interior flatwork shall develop minimum ultimate compressive design strength of 4000 psi in 28 days, but not less than 540 pounds of cement shall be used per cubic yard of concrete regardless of strengths obtained, not over
5.40 gallons of water per 100 pounds of cement and not over 4 inches of slump.
Concrete mix shop drawing shall contain testing data proving concrete design mix shrinkage is less than 0.034% at 28 days when tested according to ASTM C157 (air drying method only).
C. All concrete for exterior flatwork shall have a minimum design compressive strength of 4500 psi in 28 days, with not less than 560 pounds of cement per cubic yard of concrete, not over 5 gallons of water per 100 pounds of cement, with 6% +/- 1% air entrainment, and a maximum of 4 inches of slump.
D. All concrete for columns shall develop a minimum ultimate compressive design strength of 4000 psi in 28 days, but not less than 560 pounds of cement shall be used per cubic yard of concrete regardless of strengths obtained, not over 5 gallons of water per 100 pounds of cement and not over 4 inches of slump.
E. The preceding minimum mix requirements may have water-reducing admixtures conforming to ASTM C494 added to the mix at manufacturer's dosage rates for improved workability.
F. The preceding minimum mix requirements may have up to 15% maximum of the cement content replaced with an approved ASTM C618 Class C fly ash, provided the total minimum cementitious content is not reduced.
G. Combined aggregate (coarse plus fine) for all concrete shall be well graded from coarsest to finest with no more than 18 percent and not less than 8 percent retained on an individual sieve, except that less than 8 percent may be retained on coarsest sieve and on No. 50 and finer sieves. Submit this gradation report with the concrete mix design shop drawings.
H. All interior concrete slabs on grade shall be placed over 15 mil, Class A Vapor Barrier per ASTM E1745 with less than 0.01 perms, tested after mandatory conditioning. All joints shall be lapped and sealed per manufacturer's recommendations. All penetrations, as well as damaged vapor barrier material shall also be sealed per manufacturer's recommendation prior to concrete placement. Install barrier per manufacturer recommended details at all discontinuous edges (at interior columns, exterior edge of slab, etc.) to ensure terms of warranty are followed. The vapor barrier shall be placed over free-draining granular material as prescribed by the project soils report.
I. Basement foundation walls shall be braced at the base and top of wall by the contractor until the slab on grade at the base and the floor framing/slab at the top of wall is complete and the concrete has achieved 75% of the design strength. The contractor is responsible for engineering and design of the wall bracing, if required.
J. All concrete is reinforced concrete unless specifically called out as unreinforced.
Reinforce all concrete not otherwise shown with same steel as in similar sections or areas. Any details not shown shall be detailed per ACI 315 and meet requirements of ACI 318, current editions.
K. Control joints in dirt formed slab to be as shown on plans. Where not shown, limit controlled areas to not more than 144 square feet, or 12 feet on any side.
Slab panel side ratio shall not exceed 1 1/2 to 1.
L. Contractor shall verify that all concrete inserts, reinforcing and embedded items are correctly located and rigidly secured prior to concrete placement.
M. Construction joints in beams, slabs, and grade beams shall occur at midspan (middle third) unless noted otherwise. Provide 2 x 4 horizontal keys at construction joints for shear transfer.
N. No aluminum items shall be embedded in any concrete.
4. Reinforcing Steel
A. All reinforcing steel shall conform to the requirements of ASTM A615 or A706 grade 60 steel. Welded plain wire fabric shall be supplied in sheets and conform to the requirements of ASTM A185.
B. Clear minimum coverage of concrete over reinforcing steel shall be as follows:
1.) Concrete placed against earth: 3" 2.) Formed concrete against earth: 2" 3.) Slabs: 1" 4.) Beams or Columns: 1-1/2" 5.) Other 2" All coverage shall be nominal bar diameter minimum.
C. All dowels shall be the same size and spacing as adjoining main bars (splice lap 48 bar diameters or 24" minimum unless noted otherwise).
D. At corners of all walls, beams, and grade beams supply corner bars (minimum 2'-0" in each direction or 48 bar diameters) in outside face of wall, matching size and spacing of horizontal bars. Where there are no vertical bars in outside face of wall, supply 3 - #4 vertical support bars for corner bars.
E. Bars marked continuous and all vertical steel shall be lapped 48 bar diameters (2'-0" minimum) at splices and embedments, unless shown otherwise. Splice top bars near midspan and splice bottom bars over supports, unless noted otherwise.
F. At all holes in concrete walls and slabs, add 2 - #5 bars (opening dimension plus 96 diameters long) at each of four sides and add 2 - #5 x 5'-0" diagonally at each of four corners of hole. Openings in 8" thick walls are reinforced similar, but with 1 - #5 instead of 2 - #5, respectively.
5. Structural Steel
A. All structural steel beams and columns shall be ASTM A992, grade 50 steel and all miscellaneous steel shall be ASTM A36 grade steel (except at moment connections where plates shall be ASTM A572, grade 50). Hollow Structural Sections (HSS) shall be ASTM A500, grade B. Fabrication and erection shall be in accordance with AISC 303-05 "Code of Standard Practice for Steel Buildings and Bridges" in the 13th Edition of the AISC Steel Construction Manual.
B. All welding shall conform to the recommendations of the AWS.
C. All exterior steel and connections, and brick relief angles shall be hot-dip galvanized.
D. All bolts not otherwise specified shall be 3/4" diameter high strength (ASTM A325-N).
All bolts shall be fully pretensioned. All beam connections shall be designed per the AISC Manual of Steel Construction "Framed Beam Connections" for the indicated reactions or at least 0.4 x beam total shear capacity, Vn/Omega, shown in the maximum total uniform load tables, whichever is greater; and, shall account for eccentricity when the bolt line is more than 2" from the center of the support.
All connections must be two bolt minimum. Additional connection elements may not be specifically shown in the conceptual details in this set but may be required by the final connection design, such as stiffener plates, doubler plates, supplement/reinforcing plates or other connection material. Connection design and shop drawing preparation shall be completed under the direct supervision of a professional engineer licensed in the state the project is located and shop drawings and connection calculations shall bear his/her seal.
E. All anchor bolts shall be 3/4" diameter, ASTM F1554, Grade 36 unless noted otherwise.
Washers of minimum size and thickness for the given anchor diameter in Table 14-2 of the AISC Steel Construction Manual shall be provided at every column anchor bolt.
Washers shall have a standard size hole for the anchor bolt. At braced frames washers shall be welded all around to the column base plate with 3/16” fillet weld.
F. All openings in steel framed roof to have 4x4x5/16 angle frame set between beams.
Support mechanical equipment with 6x6x3/8 angles framed between beams .
G. Design and installation of steel decking shall comply with the recommendations of the Steel Deck Institute (SDI). All decking shall be galvanized unless noted otherwise.
H. Allow 2.5 tons of miscellaneous structural steel to be used as directed in the field for special conditions by the engineer of record. Cost for shop drawings, fabrication, delivery, detailing, and erection to be included.
6. Post Installed Anchors
A. Post-installed anchors shall be used only where specified on the drawings unless approved in writing by the engineer of record. See drawings for anchor diameter, spacing and embedment. Performance values of the anchors shall be obtained for specified products using appropriate design procedures and/or standards as required by the governing building code. Anchors installed in concrete shall have an ICC-ES Evaluation Service Report. Special inspection is required for all post installed anchors. The contractor shall coordinate an on-site meeting with the post installed anchor manufacturer field representative to educate the construction team on the anchor installation guidelines and requirements.
B. Mechanical anchors used in cracked and uncracked concrete shall have been tested and qualified for use in accordance with ACI 355.2 and ICC-ES AC193. All anchors shall be installed per the anchor manufacturer's written instructions.
C. Adhesive anchors used in cracked and uncracked concrete shall have been tested and qualified for use in accordance with ICC-ES AC308. All anchors shall be installed per the anchor manufacturer's written instructions.
D. Mechanical anchors used in solid grouted masonry shall have been tested and qualified for use in accordance with ICC-ES AC01. All anchors shall be installed per the anchor manufacturer's written instructions.
E. Adhesive anchors used in solid grouted masonry shall have been tested and qualified for use in accordance with ICC-ES AC58. All anchors shall be installed per the anchor manufacturer's written instructions.
F. Anchors used in hollow concrete masonry shall have been tested and qualified in accordance with ICC-ES AC106 or ICC-ES AC58 as appropriate. All anchors shall be installed per the anchor manufacturer's written instructions with appropriate screen tubes used for adhesives.
7. Foundations
A. The soil investigation was prepared by Engineering Surveys & Services. Their telephone number is (573) 449-2646.
B. Structural foundations consist of a network of straight shaft drilled piers (caissons) established on limestone capable of safely supporting 20ksf end bearing. Each pier hole shall be probed to a depth of 2'-0" below pier bottom and observed by the project soils engineer for suitable bearing material.
C. Basement walls are designed for an at rest lateral load of 50 pcf equivalent fluid pressure. See General Note 3-I for wall bracing requirements.
D. Contractor shall provide for dewatering at excavations from either surface water or seepage.
E. All foundation excavations shall be inspected by a qualified soil engineer, approved by the structural engineer, prior to placement of steel or concrete.
This inspection shall be at the owner's expense.
F. All concrete in the structural portion retaining the backfill shall have attained its design strength prior to being backfilled.
G. Moisture content in soils beneath building locations should not be allowed to change after footing excavations and after grading for slabs on grade are completed. If subgrade materials become desiccated or softened by water or other conditions, recompact materials to the density and water content specified for engineered fill.
Do not place concrete on frozen ground.
8. Drilled Piers
A. Piers not otherwise indicated shall be 30" diameter.
B. Unless otherwise indicated, tops of all piers shall have dowels to concrete grade beams and concrete walls or columns above. At grade beams, provide (6) #7 X 6'-0" dowels w/ standard ACI 90 degree hooks at top (length does not include hook). At columns, provide dowels to match size and spacing of of column vertical reinforcing w/ 48 bar diameter minimum lap and 48 bar diameter minimum embedment in pier. At concrete walls, provide dowels to match wall integral column vertical reinforcing (if present), otherwise provide (6) #7 x 6'-0" dowels w/ standard ACI 90 degree hooks.
C. Driving dowels into concrete after initial set is not allowed.
D. Refer to the specifications (sections for excavation and concrete) for other detailed requirements.
E. Pier concrete to have 6" slump.
9. Shop Drawing Review
A. Bob D. Campbell and Company, Inc. will review the General Contractor’s (GC) shop drawings and related submittals (as indicated below) with respect to the ability of the detailed work, when complete, to be a properly functioning integral element of the overall structural system designed by Bob D. Campbell and Company, Inc.
B. Prior to submittal of a shop drawing or any related material to Bob D. Campbell and Company, Inc., the GC shall:
1.) Review each submission for conformance with the means, methods, techniques, sequences and operations of construction and safety precautions and programs incidental thereto, all of which are the sole responsibility of the GC.
2.) Review and approve each submission.
3.) Stamp each submission as approved.
C. Bob D. Campbell and Company, Inc. shall assume that no submission comprises a variation unless the GC advises Bob D. Campbell and Company, Inc. with written documentation.
D. Bob D. Campbell and Company, Inc. shall review shop drawings and related materials with comments provided that each submission has met the above requirements. Bob D. Campbell and Company, Inc. shall return without comment unrequired material or submissions without GC approval stamp.
E. Shop drawings and related material (if any) required are indicated below.
Should Bob D. Campbell and Company, Inc. require more than ten (10) working days to perform the review, Bob D. Campbell and Company, Inc. shall so notify the GC.
1.) Concrete mix designs and material certificates including admixtures and compounds applied to the concrete after placement.
2.) Reinforcing steel shop drawings including erection drawings and bending details. Bar list will not be reviewed for correct quantities.
6.) Construction and control joint plans and/or elevations.
3.) Structural steel shop drawings including erection drawings and piece details. Include joist, decking and connector submittals. Include miscellaneous framing specified on the structural drawings, but do not submit framing specified on non-structural drawings for Bob D.
Campbell and Company, Inc. review.
4.) Structural steel connection design calculations submitted concurrently withstructural steel shop drawings.
5.) Miscellaneous anchors shown on the structural drawings.
6.) Standard details and bridging information for light gage metal framing.
Erection plans and details for light gage metal joists and lintels spanning more than 6’-0" shall be submitted. Standard wall framing need not be submitted.
10. Statement of Structural Special Inspections
A. The structural design for this project is based on completion of special inspections during construction in accordance with section 1704 of the International Building Code. The owner shall employ one or more qualified special inspectors to provide the required special inspections.
B. The special inspector shall furnish inspection reports to the COR, and any other designated person.
C. All discrepancies shall be brought to the immediate attention of the contractor for correction, then, if uncorrected, to the COR.
D. The special inspector shall submit a final signed report stating that the work requiring special inspection was, to the best of the inspector's knowledge, in conformance with the approved plans and specifications and the applicable workmanship provisions of the building code.
E. The following inspections and tests are required with the frequency (continuous or periodic) as defined within the referenced section or standard listed below. The
General Contractor shall provide notification to the inspector when items requiring inspection are ready to be inspected and provide access for those inspections.
1. Shop Fabrication – structural steel per Section 1704.2.5 unless AISC certified shop
2. Steel Construction per Section 1705.2 and the quality assurance requirements of
AISC 341 Chapter J (as referenced by AISC 360)
3. Cold-Formed Steel Deck per Section 1705.2.2 and the quality assurance requirements of SDI QA/QC.
4. Concrete Construction per Section 1705.3 and Table 1705.3
a. Reinforcing Steel Placement
b. Reinforcing Steel Welding
c. Cast in Place Anchors
d. Post Installed Anchors
e. Design Mix Verification
f. Concrete Sampling and Testing
g. Concrete Placement
h. Concrete Curing
i. Formwork Shape, Location and Dimensions
5. Verification of Soils per Table 1705.6
6. Inspections and Tests of Cast-In-Place Deep Foundation per Table 1705.8
G. Unless otherwise covered on architectural plans or specifications, vertical control joints in concrete wall shall be spaced at a maximum of 20'-0" on center and coordinated with the architect. Every other horizontal wall reinforcing bar shall be discontinuous at control joints except heavy top and bottom bars unless noted otherwise. Provide base seal waterstop style number 772 (by Greenstreak Inc. or approved equal) on dirt face side of wall at all walls below grade.
H. Accessories shall be as specified in latest edition of the ACI Detailing Handbook and the concrete Reinforcing Steel Institute Design Handbook. Maximum accessory spacing shall be 4'-0" on center, and all accessories on exposed surfaces are to have plastic coated feet.
I. All slabs and stairs not shown otherwise shall be 6" thick with #4 bars at 12" on center each way. All exterior porches and stoops not otherwise detailed may be constructed in any standard manner, solid or hollow, but must be reinforced with #4 bars at 12" on center each way minimum. Porches shall be doweled to adjacent walls or grade beams with #4 bars at 12" on center, hooked or embedded 48 diameters into both members. Slope porches 1/8" per foot for drainage unless noted otherwise.
J. Allow 1 ton of reinforcing bars #4 or larger to be used as directed in the field for special conditions by the engineer of record (labor for placing same to be included).
@ AT
& AND
Ø ROUND, DIAMETER
ADTL ADDITIONAL
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
ARCH ARCHITECTURAL
BLDG BUILDING
B/ BOTTOM OF
BM BEAM
BOTT BOTTOM
BRG BEARING
C CAMBER
CD-# CONCRETE DECK TYPE
CJ CONSTRUCTION/CONTROL JOIN
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
COORD COORDINATE
COV, CVR COVER
DBL DOUBLE
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DL DEAD LOAD
DWG DRAWING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
EMBED EMBEDMENT, EMBEDDED
ENGR ENGINEER
EOD EDGE OF DECK
EOR ENGINEER OF RECORD
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EXP EXPANSION
EXT EXTERIOR
EXTG, EXIST EXISTING
FD-# FLOOR DECK TYPE
FDN FOUNDATION
FF FAR FACE
FIN FINISH
FLR FLOOR
FS FAR SIDE
FTG FOOTING
FV FIELD VERIFY
STRUCTURAL ABBREVIATIONS
GA GAGE
GALV GALVANIZE(D)
GEN GENERAL
GR GRADE
HORIZ HORIZONTAL
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INFO INFORMATION
INT INTERIOR
JST JOIST
JT JOINT
K KIPS (1000 LBS)
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LBS, # POUNDS
Ld DEVELOPMENT LENGTH
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LSLT LONG-SLOTTED HOLE TRANSVERSE
LTWT LIGHTWEIGHT
M MOMENT FORCE
MAX MAXIMUM
MECH MECHANICAL
MFGR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MSRY MASONRY
MTL METAL
NF NEAR FACE
NS NEAR SIDE
NTS NOT TO SCALE
NW NORMAL WEIGHT
OC ON CENTER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
OVS OVERSIZED HOLE
P AXIAL FORCE
PAF POWDER ACTUATED FASTENER
PC PRECAST
PCF POUNDS PER CUBIC FOOT
PEMB PRE-ENGINEERED METAL BUILDING
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PJP PARTIAL JOINT PENETRATION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RAD RADIUS
RD-# ROOF DECK TYPE
REF REFERENCE
REINF REINFORCEMENT
REQD REQUIRED
REV REVISION
RLL ROOF LIVE LOAD
RTU ROOF TOP UNIT
SC SLIP CRITICAL
SCHED SCHEDULE(D)
SECT SECTION
SHT SHEET
SIM SIMILAR
SJ SAW JOINT
SL SNOE LOAD
SOG SLAB-ON-GRADE
SOG-# SLAB-ON-GRADE TYPE
SPCG SPACING
SPEC SPECIFICATION
SPRT SUPPORT
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT-SLOTTED HOLE TRANSVERSE
STD STANDARD
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STRUCT STRUCTURE, STRUCTURAL
T/ TOP OF
THRU THROUGH
TOS TOP OF STEEL, TOP OF SLAB
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V SHEAR FORCE
VERT VERTICAL
W/ WITH
W/0 WITHOUT
WF WIDE FLANGE
WL WIND LOAD
WP WORK POINT
WWF WELDED WIRE FABRIC
LEGEND:
W14x190
W14x22
T 117'-6"
LEVEL BEAM
DESIGNATION
STEEL BEAM SIZE
TOP OF BEAM ELEVATION
W14x22
T 133'-0"
SLOPING BEAM
DESIGNATION
STEEL BEAM SIZE
TOP OF BEAM ELEVATION
EACH END
T 132'-5"
120 kip
85'-0"
30" Dia.
900'-0" TOP OF PIER ELEVATION
ESTIMATED BOTTOM OF PIER ELEVATION
PIER DIAMETER
LOAD TO PIER (ASD)
CD-1
. . . . . . SPAN DIRECTION OF DECK
. . . . . . 6 1/4" LIGHTWEIGHT CONCRETE SLAB ON
COMPOSITE METAL DECK (4 1/4" LIGHTWEIGHT
CONCRETE OVER 2" DEEP, 18 GA. GALVANIZED
COMPOSITE DECK, 3-SPAN CONTINUOUS).
REINFORCE SLAB w/ 6x6-W2.1xW2.1 WWF.
. . . . . . COLUMN SIZE
BASE PLATE MARK (RE: SCHEDULE)
CD-2 . . . . . . 6 1/4" LIGHTWEIGHT CONCRETE SLAB ON
COMPOSITE METAL DECK (4 1/4" LIGHTWEIGHT
CONCRETE OVER 2" DEEP, 16 GA. GALVANIZED
COMPOSITE DECK, 3-SPAN CONTINUOUS).
REINFORCE SLAB w/ #5 REINFORCING BAR @ 12" o.c. EACH WAY.
SOCKET DEPTH IN ROCK @ BOTTOM OF PIER10'-0"
16"4- 1" DIA. (GR 105)A
ANCHOR RODSSHAPE
PER PLAN 1 1/2"x21"x21"
COLUMN BASE PLATE (txBxN)
COLUMN BASE PLATE SCHEDULE
EMBEDMENT
1. SEE PLAN FOR ORIENTATION OF COLUMNS.
2. PROVIDE PLATE WASHED & EMBEDDED PLATE PER SCHEDULE @ ALL ANCHOR BOLTS.
3. U.N.O. ALL THREADED ROD A.B's SHALL BE F1554 (36ksi) MATERIAL.
NOTES:
TYPE
BASE PLATE SHAPE (NOT TO SCALE)
GRID
PER
PLAN
MAXIMUM
HOLE SIZE PER
SCHEDULE
BASE PLATE
PER
SCHEDULE
COLUMN
PER PLAN
1½
F O
R ¾
D
IA
¾
F
O R
D
IA
F O
R
½
D
IA
PLAN
GRID
PER
PLAN
COLUMN
PER PLAN
M
IN
E
M B
E D
M E
N T
P E
R
/2
N
O N
3"
BOTTOM OF
FOOTING
S H
R
IN
K G
R O
U T
C O
LU
M
N B
A S
E P
LA
T
E S
C H
E D
U
LE
PLATE WASHER WITH 1/16" OVERSIZE
HOLE PER SCHEDULE WELD TO BASE
PLATE W/ 1/4" FILLET WELD ALL
AROUND AT BRACED FRAMES,
MOMENT FRAMES AND AS INDICATED
EMBEDDED ANCHOR
PLATE PER SCHEDULE
W/ NUT TOP & BOTTOM
T/CONCRETE
ELEVATION
COLUMN BASE PLATE AND
ANCHOR-ROD CRITERIA
ANCHOR-ROD
DIAMETER.
3/4"
7/8"
1"
1 1/4"
1 1/2"
MAX. BASE PLATE
HOLE DIAMETER.
1 5/16"
1 9/16"
1 7/8"
2 1/8"
2 3/8"
MIN. PLATE
WASHER SIZE.
2"
2 1/2"
3"
3 1/2"
4"
MIN. PLATE WASHER
THICKNESS
1/4"
5/16"
3/8"
1/2"
1/2"
1 3/4"
2"
2 1/2"
2 7/8"
3 1/4"
3 3/4"
4 1/2"
5"
5 1/2"
5/8"
3/4"
7/8"
GRID
PER
PLAN
EMBEDDED ANCHOR
PLATE SIZE
1/2"x2 1/2"x2 1/2"
1/2"x2 1/2"x2 1/2"
5/8"x3"x3"
5/8"x3 1/2"x3 1/2"
5/8"x3 1/2"x3 1/2"
3/4"x3 1/2"x3 1/2"
3/4"x3 1/2"x3 1/2"
3/4"x3 1/2"x3 1/2"
NOTES:
1. HOLE SIZES PROVIDED ARE BASE ON ANCHOR ROD SIZE AND CORRELEATE WITH ACI 117 (ACI, 2010)
2. CIRCULAR OR SQUARE WASHERS MEETING THE WASHER SIZE ARE ACCEPTIBLE.
3. HOLE IN PLATE WASHER SHALL BE 1/16" LARGER THAN ANCHOR DIAMETER.=
B
N
T Y
P
2"
TYP.
2"
A B
B
N
T Y
P
"TYP.
2"
24"8- 1 1/2" DIA. (GR 105)BPER PLAN 3"x30"x30"2
3/8
3/8
TYP. @ W10, W12
16"8- 3/4" DIA.BPER PLAN 1 1/4"x18"x18"3
16"8- 3/4" DIA.BPER PLAN 1 1/2"x20"x20"4
3/4
TYP. @ W14
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:4
:2
A
M
S001
GENERAL NOTES
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
Revisions: Date:
7-21-22
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:4
:3
A
M
S002
3D VIEW
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
F1 3D VIEW
Revisions: Date:
IF DEDUCT ALTERNATE 3 IS ACCEPTED,
DELETE STAIR IN MRI AREA
BEAMS TO SUPPORT
MECHANICAL EQUIPMENT
STAIR FRAMING IN MRI AREA
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:4
:3
A
M
S003
3D VIEW
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
F1 3D VIEW
Revisions: Date:
IF DEDUCT ALTERNATE 3 IS ACCEPTED,
DELETE STAIR IN MRI AREA
STAIR FRAMING IN MRI AREA
BEAMS TO SUPPORT
MECHANICAL EQUIPMENT
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:4
:3
A
M
S004
3D VIEW - FUTURE
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
F1 3D VIEW - FUTURE
Revisions: Date:
IF DEDUCT ALTERNATE 3 IS ACCEPTED,
DELETE STAIR IN MRI AREA
BEAMS TO SUPPORT
MECHANICAL EQUIPMENT
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:4
:4
A
M
S005
3D VIEW - FUTURE
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
F1 3D VIEW - FUTURE
Revisions: Date:
IF DEDUCT ALTERNATE 3 IS ACCEPTED,
DELETE STAIR IN MRI AREA
BEAMS TO SUPPORT
MECHANICAL EQUIPMENT
PP SS
A6
A5
W 14X109
W 14X109
W 14X109
W 14X109
NN RR TT
5'-10 3/4" 9'-5 3/4" 8'-5" 11" 7'-0 1/2"
'-1
F7
S303
F2
S303
HSS4X4X5/16
HSS4X4X5/16
HSS POSTS TO BEAR ON
EXISTING GRADE BEAM.
EXISTING GRADE BEAM.
FIELD VERIFY
RR.8
F3
S204
F6
S201
C8
S204
F1
S201
F3
S203
F5
S202
F3
S205
D3
S205
D7
S205
917'-0"
929'-0"
215 K
72" Dia.
917'-0"
929'-0"
140 K
72" Dia.
909'-0"
927'-0"
125 K
60" Dia.
10'-0"
909'-0"
927'-0"
125 K
60" Dia.
10'-0"
909'-0"
927'-0"
340 K
60" Dia.
10'-0"
909'-0"
927'-0"
940 K
90" Dia.
10'-0"
909'-0"
927'-0"
830 K
90" Dia.
10'-0"
917'-0"
933'-0"
225 K
72" Dia.
909'-0"
927'-0"
670 K
90" Dia.
10'-0"
909'-0"
927'-0"
725 K
90" Dia.
10'-0"
917'-0"
927'-0"
50 K
36" Dia.
917'-0"
927'-0"
480 K
72" Dia.
917'-0"
927'-0"
250 K
36" Dia.
917'-0"
927'-0"
265 K
72" Dia.
4" CONCRETE SLAB ON VAPOR
BARRIER PER GENERAL NOTES
ATOP 4" DRAINAGE FILL, ATOP 12"
LOW VOLUME CHANGE MATERIAL
PER GEOTECH REPORT. REINF.
SLAB w/ 6x6-W2.9xW2.9 WWF.
T/SLAB = 934'-0"
917'-0"
927'-0"
500 K
72" Dia.
S103 D9
S103 C8 S103
D8
S103 A8
S103 E8
S103 E8
REV.
S103 A9
S103 C9
1'-0"
8 1/4"
1'-1 3/4"
1'-0"
20'-6"
'-3
'-0
2'
-4
'-0
'-3
2' -1
"1
'-0
13'-5 3/4"
'-3
'-0
'-7
SJ
S J
A1
S200
TYP.
S400
F2
TEMPORARY SHORING OF EXISTING
RETAINING WALL (AS REQUIRED)
SHALL BE DESIGNED TO RESIST A
MINIMUM EQUIVALENT LATERAL
FLUID PRESSURE OF 50pcf AND
SURCHARGE LOADS WHERE
APPLICABLE. THE CONTRACTOR IS
RESPONSIBLE FOR ENGINEERING
AND DESIGN OF THE WALL BRACING
AS PART OF THE MEANS AND
METHODS OF CONSTRUCTION.
NOTE: THE DESIGN OF ANY TEMPORARY SHORING
AND/OR SOIL RETENTION ASSOCIATED WITH
EXCAVATION IN THIS AREA SHALL BE ENGINEERED
AND PROVIDED BY THE CONTRACTOR AS PART OF
THE MEANS & METHODS OF CONSTRUCTION.
DESIGN SHALL ACCOUNT FOR 50pcf EQUIVALENT
LATERAL FLUID PRESSURE AND SURCHARGE
LOADS WHERE APPLICABLE.
IF DEDUCT ALTERNATE 3 IS ACCEPTED,
DELETE STAIR IN MRI AREA
HSS4X
4X
1/
F7
S205
F8
S204
D3
S206
D7
S206
H S
S
X 4X
1/
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
matchline
A
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:4
:4
A
M
S100
FOUNDATION PLAN - AREA A
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
1/8" = 1'-0"F1 FOUNDATION PLAN AREA A
NOTES:
1. REFER TO GENERAL NOTES ON S001.
A5
NN RR TT
1'
-1
5'-10 3/4" 9'-5 3/4" 8'-5" 11" 7'-0 1/2"
B7
S303
F7
S303
F2
S303
W 8X
W 8X
3 1/2" NORMAL WEIGHT
CONCRETE SLAB ON 9/16"
DEEP, 26ga. GALV. FORM
DECK. REINFORCE SLAB
w/ 6x6-W2.1xW2.1 WWF
C6x8.2 @2'-0"oc MAX.
RR.8
E8
S304
W
X
CD-2
E8
S306
F3
S204
F6
S201
F1
S201
F3
S203
F5
S202
F3
S304
CD-2
W
X
W18X35 (20)
W
X
4" CONCRETE SLAB ON VAPOR
BARRIER PER GENERAL NOTES
ATOP 4" DRAINAGE FILL, ATOP 12"
LOW VOLUME CHANGE MATERIAL
PER GEOTECH REPORT. REINF.
SLAB w/ 6x6-W2.9xW2.9 WWF.
T/SLAB = 946'-0"
16'-0 1/4" 5'-11"
1'
-9
S103 D9
S103 C8
S103 D8
S103 A8
S103 E8
S103 E8
REV.
S103 A9
S103 C9
SJ
A1
S200
TYP.
S400
F2
IF DEDUCT ALTERNATE 3 IS ACCEPTED,
DELETE STAIR IN MRI AREA
H S
S
X 4X
1/
HSS4X4X1/4
W14X22 (10) W12X14 (8)
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
matchline
A
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:4
:5
A
M
S101
LEVEL 1 - AREA A
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
1/8" = 1'-0"F7 LEVEL 1 AREA A
NOTES:
1. REFER TO GENERAL NOTES ON S001.
A5
NN RR TT
'-1
5'-10 3/4" 9'-5 3/4" 8'-5" 11" 7'-0 1/2"
2" EJ
E J
E J
RR.8
E9
S305
C3
S304
F3
S304
E4
S305
C5
S305
E8
S304
C3
S307
CD-1
W
X
E8
S306
W
X
W24X103 (20)
W
X
(1
6)
CD-1
W14X22 (8)
12'-3 15/16" 9'-7 5/16"
1'
-9
'-2
'-0
160K-FT
S103 D9
S103 C8
S103 D8
S103 A8
S103 E8
S103 E8
REV.
S103 A9
S103 C9
S400
F2
H S
S
X 4X
1/
HSS4X4X1/4
W14X22 (10) W24X103 (12)
W12X14 (8)
W
X
(1
2)
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
matchline
A
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:5
:0
A
M
S102
LEVEL 2 - AREA A
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
1/8" = 1'-0"F7 LEVEL 2 AREA A
NOTES:
1. REFER TO GENERAL NOTES ON S001.
2. DESIGN MOMENT CONNECTIONS FOR THE FORCES INDICATED (TOTAL LOAD, ASD)
'-1
PP SS
A6
A5
NN RR TT
W
X49
W
X49
W
X49
W21X44 (18)
W
X
W
X
C
1/
2"
W
X
C
1/
2"
W
X
C
1/
2"
E2
S301
CD-2
E J
5'-10 3/4" 9'-5 3/4" 8'-5" 11" 7'-0 1/2"
A1
S300
TYP
2" EJ
W21X44 (6)
W21X44 (6)
E5
S301
E8
S301
E2
S302
E5
S302
E8
S302
RR.8
F3
S306
5'-10 13/16" 6'-6 9/16" 6'-6 9/16"
E9
S305
E4
S305
C5
S305
POUR SLAB RECESS TO SLOPE TO DRAIN.
REF. ARCHITECTURAL DRAWINGS (TYP. AT
NEW CONSTRUCTION)
W
X
(1
2)
W
X
W24X103 (20)
W
X
(1
6)
CD-1
W12X14 (8)
W14X22 (8)
E J
2" EJ
E3
S3084'-4 7/16"
9'-7 5/16"
'-9
'-2
'-0
S103 A8
S103 C8
S103 D8
S103 E8
160K-FT100K-FT
S103 E8
REV
S103 D9
S103 A9
S103 C9
S400
F2
B2
S303
W14X22
W14X22
AHU-01-3-1
4,872 lbs
H S
S
X 4X
1/
HSS4X4X1/4
E8
S307
W 18X
35 (3 2) C
1/2"
W
X
W33X130 (32)
W24X103 (12)
(8) #6 VERT
#4 TIES @ 12"oc
'-0
WALL REINFORCEMENT
NOT SHOWN FOR
CLARITY
1'-0" 1'-0"
#4 TIES @ 12"oc
(18) #6 VERT
WALL REINFORCEMENT
NOT SHOWN FOR
CLARITY
7"
'-0
2' -3
2'-0"
#4 TIES @ 12"oc
(14) #6 VERT
WALL REINFORCEMENT
NOT SHOWN FOR
CLARITY
'-1
'-0
2'-0"
#4 TIES @ 12"oc
(12) #6 VERT
WALL REINFORCEMENT
NOT SHOWN FOR
CLARITY
'-0
(8) #6 VERT
#4 TIES @ 12"oc
WALL REINFORCEMENT
NOT SHOWN FOR
CLARITY
(10) #6 VERT
#4 TIES @ 12"oc
WALL REINFORCEMENT
NOT SHOWN FOR
CLARITY
'-6
(8) #6 VERT
#4 TIES @ 12"oc
WALL REINFORCEMENT
NOT SHOWN FOR
CLARITY
'-0
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
matchline
A
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:5
:1
A
M
S103
LEVEL 3 - AREA A
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
1/8" = 1'-0"F1 LEVEL 3 AREA A
3/4" = 1'-0"A8 DETAIL
3/4" = 1'-0"C8 DETAIL
3/4" = 1'-0"D8 DETAIL
3/4" = 1'-0"E8 DETAIL
3/4" = 1'-0"A9 DETAIL
3/4" = 1'-0"C9 DETAIL
3/4" = 1'-0"D9 DETAIL
NOTES:
1. REFER TO GENERAL NOTES ON S001.
2. DESIGN MOMENT CONNECTIONS FOR THE FORCES INDICATED (TOTAL LOAD, ASD)
3. REFER TO SECTION F7/S300 FOR TYPICAL PATIENT LIFT SUPPORT DETAIL. PATIENT LIFTS ARE TO BE PROVIDED IN THE
PATIENT ROOMS AS INDICATED IN THE ARCHITECTURAL DRAWINGS AND SUSPENDED FROM THE STRUCTURE ABOVE.
DELEGATED UNISTRUT OR STRUCTURAL STEEL DESIGN IS TO BE PROVIDED BY OTHERS. COORDINATE w/ PATIENT LIFT EQUIPMENT MANUFACTURER & w/ MEP, DUCTWORK, & EQUIPMENT LOCATIONS. STRUCTURAL FRAMING & CALCULATIONS
TO BE PROVIDED BY THE DELEGATED DESIGN ENGINEER.
A5
NN RR TT
W21X44 (18)
W
X
W
X
C
1/
2"
W
X
C
1/
2"
W
X
C
1/
2"
W
X
C
1/
2"
E2
S301
'-1
0"
5'-10 3/4" 9'-5 3/4" 8'-5" 11" 7'-0 1/2"
CD-1
E J
E J
2" EJ
KNOCKOUT PANEL FOR
FUTURE OPENING
A1
S300
TYP
2" EJ
W21X44 (6)
W21X44 (6)
E5
S301
E8
S301
E2
S302
E5
S302
E8
S302
RR.8
F3
S306
5'-10 13/16" 5'-11 9/16" 5'-11 9/16" 5'-11 9/16" 7'-11 1/2"
E9
S305
E4
S305
C5
S305
CD-1
W
X
W24X103 (20)
W
X
(1
6)
W14X22 (8)
W14X22 (8)
E3
S308
2"
'-9
'-2
6' -0
4'-4 7/16"
9'-7 5/16"
160K-FT115K-FT
S103 D9
S103 C8
S103 D8
S103 A8
S103 E8
S103 E8
REV.
S103 A9
S103 C9
S400
F2
H S
S
X 4X
1/
HSS4X4X1/4
E8
S307
W16X31 (20) W16X31 (20)
W
X
W24X103 (12)
W
X
(1
2)
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
matchline
A
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:5
:2
A
M
S104
LEVEL 4 - AREA A
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
1/8" = 1'-0"F1 LEVEL 4 AREA A
NOTES:
1. REFER TO GENERAL NOTES ON S001.
2. DESIGN MOMENT CONNECTIONS FOR THE FORCES INDICATED (TOTAL LOAD, ASD)
3. REFER TO SECTION F7/S300 FOR TYPICAL PATIENT LIFT SUPPORT DETAIL. PATIENT LIFTS ARE TO BE PROVIDED IN THE
PATIENT ROOMS AS INDICATED IN THE ARCHITECTURAL DRAWINGS AND SUSPENDED FROM THE STRUCTURE ABOVE.
DELEGATED UNISTRUT OR STRUCTURAL STEEL DESIGN IS TO BE PROVIDED BY OTHERS. COORDINATE w/ PATIENT LIFT EQUIPMENT MANUFACTURER & w/ MEP, DUCTWORK, & EQUIPMENT LOCATIONS. STRUCTURAL FRAMING & CALCULATIONS
TO BE PROVIDED BY THE DELEGATED DESIGN ENGINEER.
2" EJ
KNOCKOUT PANEL FOR
FUTURE OPENING
E J
2" E
J
F4
S309
E9
S305
E4
S305
F3
S304
C5
S305
W
X
W24X103 (20)
W
X
(1
6)
CD-1
W24X103 (12) W12X14 (8)
W14X22 (8)
160K-FT
S103 A9
S103 C9
S103 D9
S103 C8
S103 D8
S103 A8
S103 E8
S103 E8
REV.
2'-2 11/16"
9'-7 5/16" 8'-8"
'-9
'-1
1"
'-3
'-9
'-1
H S
S
X 4X
1/
HSS4X4X1/4
W
X
(1
2)
E J
2" EJ
E J
E9
S305
E4
S305
F3
S304
C5
S305
W
X
W24X103 (20)
W
X
(1
6)
CD-1
W12X14 (8)
W14X22 (8)
F3
S307
160K-FT
S103 D9
S103 C8
S103 D8
S103 A8
S103 E8S103
E8
REV.
S103 A9
S103 C9
'-1
'-9
'-3
'-9
2'
-1
2'-2 11/16"
9'-7 5/16" 8'-8"
H S
S
X 4X
1/
HSS4X4X1/4
W
X
(1
2)
W24X103 (12)
2" E
J
2" EJ
E J
F3
S307
E9
S305
E4
S305
F3
S304
C5
S305
W
X
(1
2)
W
X
W24X103 (20)
W
X
(1
6)
CD-1
W12X14 (8)
W14X22 (8)
160K-FT
S103 D9
S103 C8
S103 D8
S103 A8
S103 E8
S103 E8
REV.
S103 A9
S103 C9
2'-2 11/16"
9'-7 5/16" 8'-8"
'-1
2' -9
'-1
'-9
'-3
H S
S
X 4X
1/
HSS4X4X1/4
W24X103 (12)
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
matchline
A
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:5
:3
A
M
S105
LEVEL 5, LEVEL 6, & LEVEL 7 - AREA A
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
1/8" = 1'-0"C1 LEVEL 5 AREA A
1/8" = 1'-0"F1 LEVEL 6 AREA A
NOTES:
1. REFER TO GENERAL NOTES ON S001.
2. DESIGN MOMENT CONNECTIONS FOR THE FORCES INDICATED (TOTAL LOAD, ASD)
NOTES:
1. REFER TO GENERAL NOTES ON S001.
2. DESIGN MOMENT CONNECTIONS FOR THE FORCES INDICATED (TOTAL LOAD, ASD)
1/8" = 1'-0"C6 LEVEL 7 AREA A
NOTES:
1. REFER TO GENERAL NOTES ON S001.
2. DESIGN MOMENT CONNECTIONS FOR THE FORCES INDICATED (TOTAL LOAD, ASD)
E J
E J
E9
S305
F3
S307
E4
S305
F3
S304
C5
S305
W
X
(1
2)
W
X
W
X
(1
6)
CD-1
W12X14 (8)
W14X22 (8)
W24X103 (12)
160K-FT
S103 D9
S103 C8
S103 D8
S103 A8
S103 E8
S103 E8
REV.
S103 A9
S103 C9
2'-2 11/16"
9'-7 5/16" 8'-8"
'-1
'-9
'-3
'-9
'-1 1"
H S
S
X 4X
1/
HSS4X4X1/4
W24X103 (20)
D4
S309
F8
S308
F2
S310
F7
S310
E5
S311
W
X
(1
6)
CD-1
W12X14 (8)
W14X22 (4)
W
X
(2
6)
W
X
W
X
4)
230K-FT
25 K-FT
S103 D9
S103 C8
S103 D8
S103 A8
S103 E8
S103 E8
REV.
S103 A9
S103 C9
6'-11 5/8" 4'-10 3/8" 8'-8"
2' -9
'-9
'-9
/8
"9 '-8
/2
4'-0 1/4" 4'-4 3/8"
W10X22W10X22
HOIST BEAM HOIST BEAM
W14X22
W24X146 (12)
W14X22 (4)
W14X22 (4)
D4
S309
F8
S308
F2
S310
F7
S310
E5
S311
W
X
(1
6)
CD-1
W14X22 (4)
W14X22 (4)
W
X
W
X
4)
W8X15 (6) C3
S312
F3
S312
130K-FT
25 K-FT
S103 D9
S103 C8
S103 D8
S103 A8
S103 E8
S103 E8
REV.
S103 A9
S103 C9
6'-11 5/8" 4'-10 3/8" 8'-8"
'-8
/2
'-9
/8
'-9
8 9/16"
4'-0"
2'-3 1/16"
1' -3
/1
6"
'-4
2'-11 3/8" 4'-0 1/4" 4'-4 3/8"
W
X
RTU-01-10-1
5,262 lbs
W8X15 (6)
W
X
(2
6)
W24X103 (12)
W14X22 (4)
W 8X
8)
W 8X
8)
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
matchline
A
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:5
:4
A
M
S106
LEVEL 8, LEVEL 9, & LEVEL 10 - AREA A
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
1/8" = 1'-0"C1 LEVEL 8 AREA A
1/8" = 1'-0"F1 LEVEL 9 AREA A
1/8" = 1'-0"C6 LEVEL 10 AREA A
NOTES:
1. REFER TO GENERAL NOTES ON S001.
2. DESIGN MOMENT CONNECTIONS FOR THE FORCES INDICATED (TOTAL LOAD, ASD)
NOTES:
1. REFER TO GENERAL NOTES ON S001.
2. DESIGN MOMENT CONNECTIONS FOR THE FORCES INDICATED (TOTAL LOAD, ASD)
NOTES:
1. REFER TO GENERAL NOTES ON S001.
2. DESIGN MOMENT CONNECTIONS FOR THE FORCES INDICATED (TOTAL LOAD, ASD)
1/8" SAW JOINT WHERE INDICATED ON
PLAN. DEPTH EQUALS 1/3 OF SLAB
THICKNESS. CUT WITHIN 8 HOURS OF
PLACING CONCRETE. FILL JOINT w/
SEALANT PER SPECS
NOTE: ANY OR ALL SAW
JOINTS MAY BE FORMED PER
TYPICAL CONSTRUCTION
JOINT DETAIL ON THIS SHEET
AT CONTRACTOR'S OPTION.
SLAB PER PLAN
VAPOR BARRIER
PER PLAN
DRAINAGE FILL
PER PLAN
LOW VOLUME CHANGE
MATERIAL PER
GEOTECH REPORT
D
IM
. P E
R P
L A
N D
IM
. P
E R
P L
A N
TYPICAL SAW JOINT
NOTED "SJ" ON PLAN
PREFORMED KEYED
CONSTRUCTION JOINT WITH
TOOLED EDGE ONE SIDE (FILL
JOINT w/ SEALANT PER SPECS)
TYPICAL CONSTRUCTION JOINT
NOTED "CJ" ON PLAN
1'-0" 1'-0" 1'-0"LOW VOLUME CHANGE
MATERIAL PER
GEOTECH REPORT
SLAB PER PLAN
SLAB
REINFORCING
DISCONTINUOUS
AT JOINT
VAPOR BARRIER
PER PLAN
DRAINAGE FILL
PER PLAN
D
IM
. P E
R P
L A
N D
IM
. P
E R
P L
A N
PROVIDE (3) CORNER BARS
TO MATCH SIZE & SPACING
OF WALL HORIZONTAL
REINFORCING.
OR 2'-0" MIN.
48 BAR DIAMETERS
PROVIDE VERTICAL
SUPPORT BARS FOR
CORNER BARS AT
LOCATIONS WITHOUT
WALL REBAR MAT.
O R
'-0
M
IN
B A
R D
IA
M
E T
E R
S
TYPICAL CORNER BARS AT
CONCRETE WALLS & FOUNDATIONS
TYPICAL T-INTERSECTION REINFORCING
AT CONCRETE WALLS & FOUNDATIONS
PROVIDE "L" BARS TO
MATCH SIZE &
SPACING OF WALL
HORIZONTAL
REINFORCING.
OR 2'-0" MIN.
48 BAR DIAMETERS
WALL REINFORCING
SHOWN IS ILLUSTRATIVE
ONLY.
PROVIDE VERTICAL
SUPPORT BARS FOR
"L" BARS AT
LOCATIONS WITHOUT
WALL REBAR MAT.
O R
'-0
M
IN
B A
R D
IA
M
E T
E R
S
1/2"
3/4"
1"
BASE SEAL WATERSTOP
STYLE NUMBER 772 (BY
GREENSTREAK INC. OR
APPROVED EQUAL) ON
DIRT SIDE OF WALL.
FIELD CUT ALTERNATE
HORIZ BARS AT CONTROL
JOINT. HEAVY TOP AND
BOTTOM BARS TO
CONTINUE THRU JOINT.
1/2" x 1" DEEP FORMED
BEVELED JOINT
MAXIMUM SPACING = 25'-0"
(COORDINATE LOCATIONS WITH ARCHITECT/ALIGN
WITH MASONRY CONTROL/EXPANSION JOINTS
ABOVE)
2X4 KEY WAY
VERTICAL WALL CONTROL JOINT
MAXIMUM SPACING = 100'-0"
VERTICAL WALL CONSTRUCTION JOINT
BASE SEAL WATERSTOP
STYLE NUMBER 772 (BY
GREENSTREAK INC. OR
APPROVED EQUAL) ON
DIRT SIDE OF WALL.
ALL BARS TO CONTINUE
THROUGH CONSTRUCTION
JOINT
OR 2'-0" MIN.
48 BAR DIA. LAP
SLAB PER
PLAN
EXISTING
CONCRETE SLAB ON
GRADE D
IM
. P
E R
P L
A N
TYPICAL AT NEW-TO-EXISTING SLAB ON GRADE
#4x2'-6" DOWELS @ 12"oc (DRILL & EPOXY
6" INTO EXISTING SLAB)
PROVIDE NEAT SAW CUT AT
EDGE OF EXISTING SLAB
1'-0"
SLAB PER
PLAN
1/2" ISOLATION JOINT.
FILL w/ COMPRESSIBLE
MATERIAL & SEALANT
AT TOP.
2-#4 CONT.
FACE OF EXISTING
BUILDING WALL OR
VERTICAL SURFACE
D
IM
. P E
R P
LA
N
TYPICAL SLAB EDGE DETAIL AGAINST EXISTING
BUILDING WALL OR VERTICAL SURFACE
1'-0"
SLAB PER
PLAN
TOOLED JOINT (FILL w/
SEALANT)
2-#4 CONT.
EXISTING
CONCRETE
BUILDING
SLAB &
FOUNDATION
D
IM
. P E
R P
L A
N
TYPICAL SLAB EDGE DETAIL AT EXISTING
BUILDING SLAB THRESHOLD
1/2" DIAMETER x 1'-0"
SMOOTH STEEL
DOWELS @12"oc GRID
PER
PLAN
GRID
PER
PLAN
18" M
IN. TIE LAP
PIER VERTICAL REINFORCING:
QUANTITY & BAR SIZE PER
SCHEDULE (EQUALLY SPACED
AROUND PERIMETER)
PIER TIES:
SPACING &
SIZE PER
SCHEDULE
COVER
3" CLEAR
PER PLAN
PIER SHAFT DIAMETER
PIER SHAFT
DIAMETER
MAXIMUM ALLOWABLE
LOAD TO PIER *
(20 KSF END BEARING)
PIER VERTICAL
REINFORCING PIER TIES
30" 98 k
PIER REINFORCING SCHEDULE
(6) #8 #4@16"
72" 565 k (20) #10 #4@16"
PIER NOTES:
1. ALL PIERS SHALL HAVE A MINIMUM LENGTH OF TWO TIMES
THE DIAMETER OF THE PIER.
2. END BEARING CAPACITY SHALL BE FIELD VERIFIED BY THE
PROJECT GEOTECHNICAL ENGINEER.
3. WHERE BOTTOM OF PIER ELEVATION IS REQUIRED TO
EXTEND TO A DEPTH GREATER THAN THE ESTIMATED
BOTTOM OF PIER ELEVATION, THE REINFORCING STEEL
CAGE SHALL BE HELD AT THE TOP OF THE PIER AND THE
BOTTOM OF THE PIER MAY BE UNREINFORCED FOR A DEPTH
NOT TO EXCEED 1.5 x THE PIER DIAMETER. IF THE PIER IS
REQUIRED TO RESIST UPLIFT OR THE BOTTOM OF THE PIER
MUST BE EXTENDED TO A DEPTH GREATER THAN 1.5 x THE
PIER DIAMETER, VERTICAL BARS SHALL BE LAPPED 48 BAR
DIAMETERS TO THE BOTTOM OF THE CAGE AND TIES SHALL
BE ADDED TO EXTEND THE REINFORCING THROUGH THE
FULL DEPTH OF THE PIER.
4. ANY PIER EXCAVATION THAT ENCOUNTERS GROUNDWATER
SEEPAGE SHALL BE TEMPORARILY CASED AND HAVE ALL
WATER REMOVED FROM THE HOLE PRIOR TO PLACEMENT
OF CONCRETE.
5. IN ADDITON TO PIER TIES INDICATED, PROVIDE FOUR (4)
EXTRA TIES @ 3" o.c. AT THE TOP OF EACH PIER.
6. UNLESS OTHERWISE INDICATED, TOPS OF ALL PIERS SHALL
HAVE DOWELS TO CONCRETE GRADE BEAMS & CONCRETE
COLUMNS ABOVE. AT GRADE BEAMS, PROVIDE (6) #7 x 6'-0" DOWELS w/ STANDARD ACI 90 DEGREE HOOKS AT TOP
(LENGTH DOES NOT INCLUDE HOOK). AT COLUMNS,
PROVIDE DOWELS TO MATCH SIZE & SPACING OF COLUMN
VERTICAL REINFORCING w/ 48 BAR DIAMETER MINIMUM LAP
& 48 BAR DIAMETER MINIMUM EMBEDMENT IN PIER. AT
CONCRETE WALLS AND SLABS, PROVIDE DOWELS TO
MATCH WALL INTEGRAL COLUMN VERTICAL REINFORCING (IF
PRESENT), OTHERWISE PROVIDE (6) #7 x 6'-0" DOWELS w/
STANDARD ACI 90 DEGRESS HOOK.
TYPICAL PIER REINFORCING DETAIL
90" 884 k (32) #10 #4@16"
60" 393 k (12) #10 #4@16"
36" 141 k (8) #8 #4@16"
* ADDITIONAL LOAD ACHIEVED w/ 1500 PSF SKIN
FRICTION PER GEOTECH REPORT
GRID
PER
PLAN
D
IM
. P E
R P
L A
N D
IM
. P
E R
P L
A N
1/2" ISOLATION JOINT.
FILL w/ COMPRESSIBLE
MATERIAL & SEALANT
AT TOP.
SLAB PER
PLAN
DIAMOND SHAPED
SLAB BLOCKOUT
AT COLUMN (TYP.)
"o c
T
IE
S
TOP OF COMPETENT
LIMESTONE (FIELD
VERIFY ELEVATION)
(U .N
.O
'-0
T
Y P
_______ CAPABLE OF
SAFELY SUSTAINING
____ksf END BEARING
(FIELD VERIFY).
PIER DIAMETER PER PLAN
2"Ø PROBE HOLES
AS REQUIRED BY
GEOTECHNICAL
ENGINEER FOR
VERIFICATION OF
BEARING
CAPACITY
VERTICAL REINFORCING
PER SCHEDULE.
PROVIDE STANDARD ACI
90 DEGREE HOOKS AT
TOPS OF ALL VERTICAL
BARS AT PIERS w/
BRACED FRAME
COLUMNS
CIRCULAR TIES
PER
SCHEDULE
COLUMN SIZE, BASE
PLATE, GROUT, &
ANCHOR BOLTS PER
PLAN & SCHEDULE
B5
S200
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
matchline
A
B
IM
/5
-0
In p at ie nt M e di ca l B ed A d di tio n
9/
T C
A E
R
V
A M
E D
C E
N T
E R
.r vt
/2
/2
:5
:4
A
M
S200
FOUNDATION SECTIONS
TRIPLE C THE A&E GROUP
2625 LINDELL BLVD. 2ND FLOOR, 2064
ST. LOUIS, MO 63108
MAT PERKINS
520-481-8548
589-017
B1
JULY 21, 2022 C Boos E Schmitz
ISSUED FOR BIDDING KCVA -Inpatient Medicine Bed Addition
4801 LINWOOD BLVD KANSAS CITY, MO 64128
3/4" = 1'-0"A1 SECTION
3/4" = 1'-0"A3 SECTION
3/4" = 1'-0"A5
TYPICAL INTERSECTING CONCRETE
WALL REINFORCING 3/4" = 1'-0"A7 VERTICAL WALL CONTROL JOINT
3/4" = 1'-0"B1 SECTION
3/4" = 1'-0"A10 SECTION
3/4" = 1'-0"B3 SECTION
3/4" = 1'-0"B5 TYPICAL PIER REINFORCING
3/4" = 1'-0"B7 SECTION
1'-8"
1'-0"
1'-0"
1'-0"
4"
/4
GRADE PER
ARCH/CIVIL
BEAM PER PLAN BEAM PER PLAN
946'-0"
934'-0"
PIER BEYOND
PER PLAN
(2) #9 CONT. (BOTTOM)
PIER DWLS PER
NOTE 6 ON B5/S200
#6 DWLS @ 12"oc
#4 @ 12"oc HORIZ
#4 @ 12"oc HORIZ
#6 @ 12"oc VERT
#4 x 5'-0" Lg DWLS @ 12"oc
2'-6"
2' -6
1'-0"
SLAB PER PLAN
(2) #4 CONT.
PIER BEYOND
PER PLAN
(2) #9 CONT. (BOTTOM)
PIER DWLS PER
NOTE 6 ON B5/S200
#4 @ 12"oc HORIZ
#6 @ 12"oc VERT
#4 @ 12"oc HORIZ
#6 @ 12"oc VERT
(2) #9 CONT. (BOTTOM)
3/4" x 4" x CONT. EMBED PL w/ 3/4" x 6" Lg HEADED STUDS @ 12"oc
SLAB ON DECK
PER…