This document is a specification section for cold-formed metal framing required for the construction of a federal project at the Hunter Holmes McGuire VAMC in Richmond, VA. The section outlines the materials, design requirements, submittal requirements, and installation procedures for the cold-formed metal framing, including exterior non-load-bearing steel stud curtain wall. Key details include the required minimum steel thicknesses, galvanization, and fasteners. The contractor's structural engineer must provide signed and sealed calculations and shop drawings for the light gauge metal framing based on the loads shown in the construction documents. The work is part of the VA Project #652-323 "Improve Surgical Operating Access" solicitation, which has the solicitation number 36C77624B0023 and is being procured by the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hunter Holmes McGuire VAMC VA Project #652-323
Improve Surgical Operating Access Construction Bid Documents
Richmond, VA October 28,2024
1-01-21
05 40 00-1
SECTION 05 40 00
COLD-FORMED METAL FRAMING
PART 1 - GENERAL
DESCRIPTION
A. This section specifies materials and services required for installation of cold-formed steel, including tracks and required accessories as shown and specified. This Section includes the following:
1. Exterior non-load-bearing steel stud curtain wall.
RELATED WORK
A. Section 05 12 00, STRUCTURAL STEEL FRAMING: Structural steel framing.
B. Section 09 22 16, NON-STRUCTURAL METAL FRAMING: Non-load-bearing metal stud framing assemblies.
C. Section 09 29 00, GYPSUM BOARD: Gypsum board assemblies.
DESIGN REQUIREMENTS
A. Design steel in accordance with American Iron and Steel Institute
Publication "Specification for the Design of Cold-Formed Steel
Structural Members", except as otherwise shown or specified.
B. Structural Performance: Engineer, fabricate, and erect cold-formed metal framing to withstand design loads within limits and under conditions required.
1. Design Loads:
a. Gravity, wind and seismic loading as indicated on the drawings or in this specification.
2. Design framing systems to withstand design loads without deflections greater than the following:
a. Exterior Non-load-Bearing Curtain wall: Lateral deflection 1/720 of the wall height.
3. Design framing systems to provide for movement of framing members without damage or overstressing, sheathing failure, connection failure, undue strain on fasteners and anchors, or other detrimental effects when subject to a maximum ambient temperature change (range) of 67 degrees C (120 degrees F).
4. Design framing system to accommodate deflection of primary building structure and construction tolerances, and to maintain clearances at openings.
Richmond, VA October 28,2024
05 40 00-2
5. Design exterior non-load-bearing curtain wall framing to accommodate lateral deflection without regard to contribution of sheathing materials.
6. Engineering Responsibility: Engage a fabricator who assumes undivided responsibility for engineering cold-formed metal framing by employing a qualified professional engineer to prepare design calculations, shop drawings, and other structural data.
SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES. All items indicated below are required submittals requiring Contracting Officer’s Representative (COR) review and approval
B. Shop Drawings: Shop and erection drawings showing steel unit layout, connections to supporting members, and information necessary to complete installation as shown and specified.
C. Manufacturer's Literature and Data: Showing steel component sections and specifying structural characteristics.
D. Design of the light gauge for this project shall be provided by the contractor’s structural engineer for the loads shown on the construction documents. Submit signed and sealed calculations performed by a structural engineer with at least 5 years experience in the design of light gauge metal and registered in the state of the project.
Calculations shall be submitted with plans elevations and details for review and approval.
APPLICABLE PUBLICATIONS
A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.
B. American Iron and Steel Institute (AISI): Specification and Commentary for the Design of Cold-Formed Steel Structural Members (2016)
C. ASTM International (ASTM):
A36/A36M-19.............Standard Specification for Carbon Structural
Steel
A123/A123M-17...........Standard Specifications for Zinc (Hot-Dip
Galvanized) Coatings on Iron and Steel Products
A153/A153M-16a..........Standard Specifications for Zinc Coating (Hot-
Dip) on Iron and Steel Hardware
Richmond, VA October 28,2024
05 40 00-3
A307-14e1...............Standard Specifications for Carbon Steel Bolts, Studs, and Threaded Rod 60,000 PSI Tensile
Strength
A653/A653M-20...........Standard Specification for Steel Sheet, Zinc
Coated (Galvanized) or Zinc Iron Alloy Coated
(Galvannealed) by the Hot Dip Process
C955-18e1...............Standard Specification for Cold Formed Steel
Structural Framing Members
C1107/1107M-20..........Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Non-shrink)
E488/E488M-18...........Standard Test Methods for Strength of Anchors in Concrete Elements
E1190-11(2018)..........Standard Test Methods for Strength of Power-
Actuated Fasteners Installed in Structural
Members
D. American Welding Society (AWS):
D1.3/D1.3M-18...........Structural Welding Code-Sheet Steel
E. Military Specifications (Mil. Spec.):
MIL-P-21035B............Paint, High Zinc Dust Content, Galvanizing
Repair
F. VA Physical Security and Resiliency Design Manual October 1, 2020.
PART 2 - PRODUCTS
MATERIALS
A. Sheet Steel for joists, studs and accessories 16 gauge and heavier:
ASTM A653, structural steel, zinc coated CP60, with a yield of 340 MPa
(50 ksi) minimum.
B. Sheet Steel for joists, studs and accessories 18 gauge and lighter:
ASTM A653, structural steel, zinc coated G60, with a yield of 230 MPa
(33 ksi) minimum.
C. Galvanizing Repair Paint: MIL-P-21035B.
D. Nonmetallic, Non-shrink Grout: Premixed, nonmetallic, noncorrosive, nonstaining grout containing selected silica sands, Portland cement, shrinkage-compensating agents, plasticizing and water-reducing agents, complying with ASTM C1107, with fluid consistency and a 30 minute working time.
Richmond, VA October 28,2024
05 40 00-4
WALL FRAMING
A. Steel Studs: Complying with ASTM C 955. Manufacturer’s standard C-shaped steel studs of web depth indicated, with lipped flanges, and complying with the following:
1. Minimum Base-Steel Thickness(uncoated): 0.84 mm (0.0329 inch)
2. Flange Width: 35 mm (1-3/8 inches)
3. Web: Unpunched .
B. Steel Track: Manufacturer’s standard U-shaped steel track, unpunched, of web depths indicated, with straight flanges, and complying with the following:
1. Design Uncoated-Steel Thickness: Matching steel studs.
2. Flange Width: Manufacturer’s standard deep flange where indicated, standard flange elsewhere.
FRAMING ACCESSORIES
A. Fabricate steel framing accessories of the same material and finish used for framing members, with a minimum yield strength of 230 MPa (33 ksi).
B. Provide accessories of manufacturer’s standard thickness and configuration, unless otherwise indicated, as follows:
1. Supplementary framing.
2. Bracing, bridging, and solid blocking.
3. Web stiffeners.
4. Deflection track and vertical slide clips.
5. Stud kickers and girts.
6. Joist hangers and end closures.
7. Reinforcement plates.
ANCHORS, CLIPS, AND FASTENERS
A. Steel Shapes and Clips: ASTM A36, zinc coated by the hot-dip process according to ASTM A123.
B. Cast-in-Place Anchor Bolts and Studs: ASTM A307, Grade A, zinc coated by the hot-dip process according to ASTM A153.
C. Expansion Anchors: Fabricated from corrosion-resistant materials, with capability to sustain, without failure, a load equal to 5 times the design load, as determined by testing per ASTM E488 conducted by a qualified independent testing agency.
D. Power-Actuated Anchors: Fastener system of type suitable for application indicated, fabricated from corrosion-resistant materials, Richmond, VA October 28,2024
05 40 00-5 with capability to sustain, without failure, a load equal to 10 times the design load, as determined by testing per ASTM E1190 conducted by a qualified independent testing agency.
E. Mechanical Fasteners: Corrosion-resistant coated, self-drilling, self-threading steel drill screws. Low-profile head beneath sheathing, manufacturer’s standard elsewhere.
REQUIREMENTS
A. Welding in accordance with AWS D1.3
B. Furnish members and accessories by one manufacturer only.
PART 3 - EXECUTION
FABRICATION
A. Framing components may be preassembled into panels. Panels shall be square with components attached.
B. Cut framing components squarely or as required for attachment. Cut framing members by sawing or shearing; do not torch cut.
C. Hold members in place until fastened.
D. Fasten cold-formed metal framing members by welding or screw fastening, as standard with fabricator. Wire tying of framing members is not permitted.
1. Comply with AWS requirements and procedures for welding, appearance and quality of welds, and methods used in correcting welding work.
2. Locate mechanical fasteners and install according to cold-formed metal framing manufacturer’s instructions with screw penetrating joined members by not less than 3 exposed screw threads.
E. Where required, provide specified insulation in double header members and double jamb studs which will not be accessible after erection.
ERECTION
A. Handle and lift prefabricated panels in a manner as to not distort any member.
B. Securely anchor tracks to supports as shown.
C. At butt joints, securely anchor two pieces of track to same supporting member or butt-weld or splice together.
D. Plumb, align, and securely attach studs to flanges or webs of both upper and lower tracks.
E. All axially loaded members shall be aligned vertically to allow for full transfer of the loads down to the foundation. Vertical alignment shall be maintained at floor/wall intersections.
Richmond, VA October 28,2024
05 40 00-6
F. Install jack studs above and below openings and as required to furnish support. Securely attach jack studs to supporting members.
G. Install headers in all openings that are larger than the stud spacing in that wall.
H. Attach bridging for studs in a manner to prevent stud rotation. Space bridging rows as shown.
I. Studs in one piece for their entire length, splices will not be permitted.
J. Provide a load distribution member at top track where joist is not located directly over bearing stud.
K. Provide joist bridging and web stiffeners at reaction points where shown.
L. Provide end blocking where joist ends are not restrained from rotation.
M. Provide an additional joist under parallel partitions, unless otherwise shown, when partition length exceeds one-half joist span and when floor and roof openings interrupt one or more spanning members.
N. Provide temporary bracing and leave in place until framing is permanently stabilized.
O. Do not bridge building expansion joints with cold-formed metal framing.
Independently frame both sides of joints.
P. Fasten reinforcement plate over web penetrations that exceed size of manufacturer’s standard punched openings.
TOLERANCES
A. Vertical alignment (plumbness) of studs shall be within 1/960th of the span.
B. Horizontal alignment (levelness) of walls shall be within 1/960th of their respective lengths.
C. Spacing of studs shall not be more than 3 mm (1/8 inch) +/- from the designed spacing providing that the cumulative error does not exceed the requirements of the finishing materials.
D. Prefabricated panels shall be not more than 3 mm (1/8 inch) +/- out of square within the length of that panel.
FIELD REPAIR
A. Touch-up damaged galvanizing with galvanizing repair paint.
- - - E N D - - -