20-365-Q13_Dwg Vol 4.pdf
PDF 20 MB Posted
- Solicitation number
- 36C77623B0055
About this file
This document provides details on a federal solicitation and related file. The solicitation number 36C77623B0055 from the Department of Veterans Affairs Technology Acquisition Center Austin is for infrastructure upgrades construction at the Dayton, Ohio VA medical center. Project number 552-21-701 involves upgrading the EHRM systems. The related file is a 20MB PDF titled 20-365-Q13_Dwg Vol 4 containing drawings for the infrastructure upgrades. The solicitation is for construction services with response due dates not specified. The award date was also not included.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C77623B0055 0005.docx | DOCX document | |
| 36C77623B0055 0004.docx | DOCX document | |
| 36C77623B0055 0003.docx | DOCX document | |
| Technical Questions.pdf | ||
| 552-21-701 Asbestos Informatio.zip | ZIP file | |
| Panel Cat Numbers Photo.docx | DOCX document | |
| Wage Determination - Montgomery County - Heavy-Highway.pdf | ||
| 36C77623B0055 0002.docx | DOCX document | |
| Attachment 7 - Ohio Tax Language 1.26.2023 - FINAL.docx | DOCX document | |
| S04 -PreBid Sign in.pdf | ||
| 36C77623B0055 0001.docx | DOCX document | |
| Attachment 4 - 852.219-75 Clause for EAS.docx | DOCX document | |
| Attachment 1 - Final Specs Volumes 1 and 2.zip | ZIP file | |
| Attachment 5 - Final Drawings Part 1 of 2.zip | ZIP file | |
| 36C77623B0055_1.docx | DOCX document | |
| Attachment 6 - Final Drawings Part 2 of 2.zip | ZIP file | |
| Attachment 2-DBA Wage Rate-Montgomery County - 8-4-23.txt | TXT text file | |
| Attachment 3 - Site Visit Info and Map.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
H H H H H
HH H H
HH
V A N
V A N
1 2 3 4 5 6
RETENTION
POND
POND
POND
POND
AVE.
WES
T
THIR
D
ST.
O H
IO
A V E
P E N N S Y L V A N
IA
A V E
P E N N S Y L V A N
IA
A V E
A V E
K
EN
TU
C K Y
A V E
NEW YORK
AVE.
O H
IO
A V E
TEN
N E S S E E
C O L O R A D O
A V E
BROWN
IN
D
IA
N A
A V E
A V E
WISCONSIN
McM
AHO
N
AVE.
MONUMENT
AVE.
WEST
TH
IRD
STRE
ET
CEMETERY
D R
DAKOTA
AVE.
D A K O T A
A V E
K A N S A S
A V E
AVE.
McMAH
ON
CEMETERY
IL
L
IN
O
IS
A V E
IOWA
KENTUCKY
AVE.
AVE.
A V E
G E T T Y S B U R G
S O U T H
L
IS
C U M
V E R M O N T
A V E
IOWA
AVE.
O R E G O N
A V E
U.S. ROUTE 35
U .S
. R O
U
TE 3
TEXAS
AVE.
H A W A
II
PL.
N E W
M E X
IC
O
P L A C E
N E W
M E X
IC
O
PL
P E N N S Y
LV
A N
IA
A V E N U E
P L
M
IC
H
IG
A N
AV
E.
M A
IN
E
C O N N E C T
IC
U T
A V E
A V E
M A R Y L A N D
A V E
MICHIGAN
AVE.
M
EX
IC
O
N E W
MASSACHUSETTS
BLVD.
M
IN
N E S O T A
A V E
KENTUCKY
AVE.
NEW
HAMPSH
IRE
DELAWARE
AVE
A V E
M
IN
N E S O T A
MISSOURI
AVE.
R H O D E
I S L A N D
A V E
WISCONSIN
AVE.
S Y L V A N
IA
W E S T
V
IR
G
IN
IA
A V E
WE
ST
V
IR
GI
NI
A
AV
E.
P E N N
A V E
W
IS
C O N S
IN
A V E
320E
320A
320B
320C
320D
120127
BUILDINGS IN SCOPE OF PROJECT
Discipline Call Out (General, Arch, Plumbing, Electrical, etc.)
Sheet No. Example 001. A 001
Sheet Number
Building Name Reference Letter Call Out (mAple, Pine, Liberty, etc.)
1151 Kildaire Farm Rd.
Raleigh, NC 27511 www.acg-pa.com
(919) 858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com
(843) 875-3637Project Mgr: Terry Barnes (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
/1
/2
:4
:3
P
M
G-001V4
COVER SHEET
1 1DGC
DAYTON EHRM
INFRASTRUCTURE
UPGRADES
DAYTON VA MEDICAL CENTER
4100 W THIRD STREET
DAYTON, OHIO 45428 APRIL 11, 2023
100% BID DOCUMENTS
552-21-70120-365-Q13
DAYTON EHRM INFRASTRUCTURE
UPGRADES
DAYTON VA MEDICAL CENTER
4100 W THIRD STREET
DAYTON, OHIO 45428
VA PROJECT #: 552-21-701
CLA
VOLUME 4 OF 5
DAYTON VA MEDICAL CENTER
PROJECT LOCATION MAP
Scale: 1" = 300'-0"
PROJECT SITE MAP
VOLUME 4 OF 5
Bldg No. No. Description Dwg of Dwg
G-001V4 COVER SHEET 1 1
ELECTRICAL
ET001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 117
ET002 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 2 117
ET501 TYPICAL TELECOM ROOM DETAILS 3 117
ET502 ELECTRICAL AND TECHNOLOGY DETAILS 4 117
ET503 TECHNOLOGY DETAILS 5 117
ET504 TECHNOLOGY DETAILS 6 117
ET505 ELECTRICAL CHANNEL RACK DETAILS 7 117
ET506 ELECTRICAL AND TECHNOLOGY CHANNEL RACK DETAILS 8 117
001 ET401 BUILDING 330, BASEMENT, TELECOM ROOM BC-101A PLANS 9 117
001 ET402 BUILDING 330, BASEMENT, TELECOM ROOM BC-129 PLANS 10 117
001 ET403 BUILDING 330, BASEMENT, DEMARK-2, ROOM BC-123d PLANS 11 117
001 ET411 BUILDING 330, FIRST FLOOR, TELECOM ROOM 1B-154 PLANS 12 117
001 ET412 BUILDING 330, FIRST FLOOR, TELECOM ROOM 1C-133 PLANS 13 117
001 ET413 BUILDING 330, FIRST FLOOR, TELECOM ROOM 1D-105A PLANS 14 117
001 ET414 BUILDING 310, FIRST FLOOR, TELECOM ROOM 1G-132 PLANS 15 117
001 ET415 BUILDING 340, FIRST FLOOR, TELECOM ROOMS 177A & PCA122 PLANS 16 117
001 ET416 BUILDING 335, FIRST FLOOR, TELECOM ROOM 115 PLANS 17 117
001 ET421 BUILDING 330, SECOND FLOOR, TELECOM ROOM 2B-101 PLANS 18 117
001 ET422 BUILDING 330, SECOND FLOOR, TELECOM ROOM 2D-117A PLANS 19 117
001 ET423 BUILDING 310, SECOND FLOOR, TELECOM ROOM 2E-143 PLANS 20 117
001 ET431 BUILDING 330, THIRD FLOOR, TELECOM ROOM 3B-102 PLANS 21 117
001 ET432 BUILDING 330, THIRD FLOOR, TELECOM ROOM 3C-100 PLANS 22 117
001 ET433 BUILDING 330, THIRD FLOOR, TELECOM ROOM 3D-108 PLANS 23 117
001 ET434 BUILDING 310, THIRD FLOOR, TELECOM ROOM 3E-135A PLANS 24 117
001 ET441 BUILDING 330, FOURTH FLOOR, TELECOM ROOM 4C-119 PLANS 25 117
001 ET442 BUILDING 330, FOURTH FLOOR, TELECOM ROOM 4D-106 PLANS 26 117
001 ET451 BUILDING 330, FIFTH FLOOR, TELECOM ROOM 5C-116 PLANS 27 117
001 ET452 BUILDING 330, FIFTH FLOOR, TELECOM ROOM 5D-106 PLANS 28 117
001 ET461 BUILDING 330, SIXTH FLOOR TELECOM ROOM 6C-115 PLANS 29 117
001 ET462 BUILDING 330, SIXTH FLOOR TELECOM ROOM 6D-144A PLANS 30 117
001 ET471 BUILDING 330, SEVENTH FLOOR, TELECOM ROOM 7C-118B PLANS 31 117
001 ET472 BUILDING 330, SEVENTH FLOOR, TELECOM ROOM 7D-108 PLANS 32 117
001 ET481 BUILDING 330, EIGHTH FLOOR, TELECOM ROOM 8C-116 PLANS 33 117
001 ET482 BUILDING 330, EIGHTH FLOOR, TELECOM ROOM 8D-106 PLANS 34 117
001 ET491 BUILDING 330, NINTH FLOOR, TELECOM ROOM 9C-113 PLANS 35 117
001 ET492 BUILDING 330, NINTH FLOOR, TELECOM ROOM 9D-105A PLANS 36 117
001 ET493A BUILDING 330, NINTH FLOOR, MAIN COMPUTER ROOM 9D-109, PHASE 1 37 117
001 ET493B BUILDING 330, NINTH FLOOR, MAIN COMPUTER ROOM 9D-109, PHASE 2 38 117
001 ET493C BUILDING 330, NINTH FLOOR, MAIN COMPUTER ROOM 9D-109, PHASE 3 39 117
001 ET493D BUILDING 330, NINTH FLOOR, MAIN COMPUTER ROOM 9D-109, FINAL PLAN 40 117
001 ET498 BUILDING 330, ROOF PLAN 41 117
001 ET601 BUILDING 330 FIBER RISER DIAGRAM 42 117
001 ET602 BUILDING 1, PARTIAL SINGLE-LINE DIAGRAMS 43 117
001 ET603 BUILDING 1, PARTIAL SINGLE-LINE DIAGRAMS 44 117
001 ET604 BUILDING 1, PARTIAL SINGLE-LINE DIAGRAMS 45 117
001 ET605 BUILDING 1, PARTIAL SINGLE-LINE DIAGRAMS 46 117
001 ET606 BUILDING 1, PANEL SCHEDULE 47 117
001 ET607 BUILDING 1, PARTIAL SINGLE-LINE DIAGRAMS 48 117
115 ET401 BUILDING 115, BASEMENT, TELECOM ROOM 6A 49 117
115 ET411 BUILDING 115, FIRST FLOOR, TELECOM ROOM 101A 50 117
115 ET421 BUILDING 115, SECOND FLOOR, TELECOM ROOM 201 51 117
115 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 52 117
120 ET401 BUILDING 120, BASEMENT, EXISTING TELECOM ROOM PLAN 53 117
120 ET411 BUILDING 120, FIRST FLOOR, TELECOM ROOM 102A PLANS 54 117
120 ET421 BUILDING 120, SECOND FLOOR, TELECOM ROOM 202A PLANS 55 117
120 ET431 BUILDING 120, THIRD FLOOR, TELECOM ROOM 302A PLANS 56 117
120 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 57 117
126 ET411 BUILDING 126, FIRST FLOOR, TELECOM ROOM 113 PLANS 58 117
126 ET421 BUILDING 126, SECOND FLOOR, TELECOM ROOM 202 PLANS 59 117
126 ET431 BUILDING 126, THIRD FLOOR, TELECOM ROOM 318 PLANS 60 117
126 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 61 117
127 ET411 BUILDING 127, FIRST FLOOR, TELECOM ROOM 114B PLANS 62 117
127 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 63 117
128 ET411 BUILDING 128, FIRST FLOOR, TELECOM ROOM 114A PLAN 64 117
128 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 65 117
131 ET411 BUILDING 131, FIRST FLOOR, TELECOM ROOM 104 PLANS 66 117
131 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 67 117
135 ET411 BUILDING 135, FIRST FLOOR, TELECOM ROOM 110B PLANS 68 117
135 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 69 117
143 ET411 BUILDING 143, FIRST FLOOR, TELECOM ROOM 1WH-8 PLANS 70 117
143 ET421 BUILDING 143, SECOND FLOOR, TELECOM ROOM 2WH-7 PLANS 71 117
143 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 72 117
147 ET411 BUILDING 147, FIRST FLOOR, TELECOM ROOM 101 PLANS 73 117
147 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 74 117
302 ET411 BUILDING 302, FIRST FLOOR, TELECOM ROOM 107, ELECTRICAL AND TECHNOLOGY
PLANS
75 117
302 ET421 BUILDING 302, SECOND FLOOR, TELECOM ROOM 205 76 117
302 ET431 BUILDING 302, THIRD FLOOR, TELECOM ROOM 308 PLANS 77 117
302 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 78 117
305 ET411 BUILDING 305, FIRST FLOOR, TELECOM ROOM 108 PLANS 79 117
305 ET412 BUILDING 305, FIRST FLOOR, TELECOM ROOM 116B PLANS 80 117
305 ET421 BUILDING 305, SECOND FLOOR, TELECOM ROOM M4B PLANS 81 117
305 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 82 117
315 ET411 BUILDING 315, FIRST FLOOR, TELECOM ROOM 145 PLANS 83 117
315 ET421 BUILDING 315, SECOND FLOOR, TELECOM ROOM 204A PLANS 84 117
315 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 85 117
320 ET401 BUILDING 320E, BASEMENT, TELECOM ROOM GE-122 PLANS 86 117
320 ET411 BUILDING 320, FIRST FLOOR, TELECOM ROOM 1E-101A PLANS 87 117
320 ET412 BUILDING 320, FIRST FLOOR, TELECOM ROOM 1A-01 PLANS 88 117
320 ET413 BUILDING 320, FIRST FLOOR, TELECOM ROOM 1B-181 PLANS 89 117
320 ET414 BUILDING 320, FIRST FLOOR, TELECOM ROOM 1C-146 PLANS 90 117
320 ET415 BUILDING 320, FIRST FLOOR, TELECOM ROOM 1D-181 PLANS 91 117
320 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 92 117
408 ET401 BUILDING 408, BASEMENT, TELECOM ROOM 4A PLANS 93 117
408 ET411 BUILDING 408, FIRST FLOOR, TELECOM ROOM 106G PLANS 94 117
408 ET421 BUILDING 408, SECOND FLOOR, TELECOM ROOM 205E PLANS 95 117
408 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 96 117
409 ET401 BUILDING 409, BASEMENT, TELECOM ROOM BCW-100 PLANS 97 117
409 ET402 BUILDING 409, BASEMENT, TELECOM ROOM 18A PLANS 98 117
409 ET411 BUILDING 409, FIRST FLOOR, TELECOM ROOM 303 PLANS 99 117
409 ET412 BUILDING 409, FIRST FLOOR, TELECOM ROOM EW-112 PLANS 100 117
409 ET421 BUILDING 409, SECOND FLOOR, TELECOM ROOM 247A PLANS 101 117
409 ET422 BUILDING 409, SECOND FLOOR, TELECOM ROOM EW-219 PLANS 102 117
409 ET431 BUILDING 409, THIRD FLOOR, TELECOM ROOM 347B PLANS 103 117
409 ET432 BUILDING 409, THIRD FLOOR, TELECOM ROOM EW-317 PLANS 104 117
409 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 105 117
410 ET401 BUILDING 410, BASEMENT FLOOR, TELECOM ROOM 4B PLANS 106 117
410 ET411 BUILDING 410, FIRST FLOOR, TELECOM ROOM WW-121B PLANS 107 117
410 ET412 BUILDING 410, FIRST FLOOR , TELECOM ROOM EW-149 PLANS 108 117
410 ET421 BUILDING 410, SECOND FLOOR, TELECOM ROOM WW-221B PLANS 109 117
410 ET422 BUILDING 410, SECOND FLOOR , TELECOM ROOM 236 PLANS 110 117
410 ET431 BUILDING 410, THIRD FLOOR, TELECOM ROOM WW-320B PLANS 111 117
410 ET432 BUILDING 410, THIRD FLOOR , TELECOM ROOM 349A PLANS 112 117
410 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 113 117
411 ET401 BUILDING 411, BASEMENT FLOOR, TELECOM ROOM 116, ELECTRICAL AND
TECHNOLOGY PLANS
114 117
411 ET411 BUILDING 411, FIRST FLOOR, TELECOM ROOM 125, ELECTRICAL AND TECHNOLOGY
PLANS
115 117
411 ET412 BUILDING 411, FIRST FLOOR, TELECOM ROOM 106, ELECTRICAL AND TECHNOLOGY
PLANS
116 117
411 ET601 SINGLE LINE DIAGRAM AND FIBER RISER DIAGRAM 117 117
SHEET NUMBERING
NOT FOR
CONSTRUCTIO
N
DocuSign Envelope ID: 34E48DAA-3F99-436D-A852-8CE206A0219D
4/20/2023 APRIL 11, 2023
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE, REFER TO ET501 FOR NEMA
TYPE
EQUIPMENT CONNECTION
AS
NOTED
E
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
120V SIMPLEX RECEPTACLE18"
2' X 2' RECESSED ARCHITECTURAL TROFFER
2' X 4' RECESSED ARCHITECTURAL TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT LENS TROFFER
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
VS: VACANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
DR: DUAL RELAY
VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER
OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, LOW VOLTAGE, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
OS
OS
LS
4' LINEAR STRIP - SUSPENDED---
L L
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
UPS UNINTERUPTABLE POWER
SUPPLY
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PDU POWER DISTRIBUTION UNIT
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BOD P/D BASIS OF DESIGN PART NUMBER
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HW HARD WIRED
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.
B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING
AREAS ARE APPROXIMATE ONLY (FIELD VERIFY).
C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS
REQUIRED. THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.
D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.
E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE
CONTRACTOR SHALL CUT OFF CONDUITS AND REMOVE WIRING.
F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.
G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND
CAP OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.
H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE
CUT OFF AND CAPPED OR PLUGGED.
I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE
COR/VA.
J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO
MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.
K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW AREAS.
L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT.
CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY
FEEDERS TO ACCOMPLISH THIS REQUIREMENT.
M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH
THIS REQUIREMENT.
N. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE OR ADJACENT STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT
PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC 300.21.
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO
SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.
PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
22. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT, SUCH AS DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED
PENETRATION.
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE
REMOVED FROM THE PREMISES.
B. ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
C. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH
OTHER TRADES.
D. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES
CONTINUATION THROUGH THE AREA.
E. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION
AND NEW CONSTRUCTION.
G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION.
RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.
H. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.
I. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR
SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
J. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION
OF POINT OF FEED WITH AN ENGRAVED BRASS TAG.
F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.
K. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN
UNCHANGED", UNLESS NOTED OTHERWISE.
IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHALL BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED
PENETRATION.
SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK
AREA, FOR THE STARTING POINT OF THE CALCULATIONS.
1151 Kildaire Farm Rd.
Raleigh, NC 27511 www.acg-pa.com
(919) 858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com
(843) 875-3637Project Mgr: Terry Barnes (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
/1
/2
:2
:5
A
M
ET001
ELECTRICAL GENERAL NOTES, SYMBOL
LEGENDS, AND ABBREVIATIONS
1 117TT
DAYTON EHRM
INFRASTRUCTURE
UPGRADES
DAYTON VA MEDICAL CENTER
4100 W THIRD STREET
DAYTON, OHIO 45428 APRIL 11, 2023
100% BID DOCUMENTS
552-21-70120-365-Q13
MULTIPLE
GG
ELECTRICAL SYMBOL LEGEND
LIGHTING SYMBOL LEGEND ELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES
GENERAL ELECTRICAL REMODELING NOTES
ELECTRICAL GENERAL NOTES
GENERAL ELECTRICAL DEMO NOTES
TEMPORARY FIRESTOPPING
METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
TELCO OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
ELECTRONIC LOCKING MECHANISM
DOOR CONTACT
REQUEST FOR EXIT SENSOR
CARD READER
(K - KEYPAD)
48"CR
ES
DC
RX
48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)
WIRELESS ACCESS POINT - N-4 PR UTP
WALL PHONEW
N
S
NURSE CALL PATIENT STATION WITH PILLOW SPEAKER
2 ADDITIONAL PUSHBUTTONS, 1/4 RECEPTACLE AND COVER
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
P NURSE CALL PATIENT BED INTERFACE RECEPTACLE
B NURSE CALL CODE BLUE STATION WITH COVER
E NURSE CALL EMERGENCY STATION WITH PULL CORD AND AUDIO +40" AFF IN
RESTROOM, +72" AFF IN SHOWER (V - VANDAL RESISTANT, PB - PUSH BUTTON)
D NURSE CALL DUTY STATION
M NURSE CALL MASTER STATION/CONSOLE
NURSE CALL DOME LIGHT
(Z - ZONE LIGHT, V - VANDAL RESISTANT)
IC
INTERCOM WITH CAMERA
IC
INTERCOM MASTER WITH PUSH TO RELEASE DOORM
NURSE CALL WIRELESS ANTENNASNW
N
TV OUTLET WALL MOUNTED
48"
54"
DESK
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
30-INCH DEEP CHANNEL RACK
6" VERTICAL CABLE MANAGER
NURSE CALL EQUIPMENT CABINET
MATV EQUIPMENT CABINET
CCTV EQUIPMENT CABINET
NCE
MATV
CCTV
WIRE MESH BASKET TRAY (4" X 18" UNLESS OTHERWISE NOTED)
N
N
FLOOR BOX FOR DATA
AS NOTED
DOOR
DOOR
ABOVE
DOOR
HEADWALL
18"
HEADWALL
/40"
40", 72"
18"
60"
CEILING
CEILING
6' TO TOP
6' TO TOP
FLOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
ELECTRONIC PANIC HARDWAREEP
DO DOOR OPERATOR
HANDWAVE
T
C
NURSE CALL STAFF TERMINAL
NURSE CALL PATIENT STATION WITH CALL CORD.
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
60"
HEADWALL
W WIRELESS PENDANT
L
KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"
PATIENT ROAM ALERT ANTENNACEILING
GROUND BUS
CEILING
DOOR
DOOR
48"
ABOVE
DOOR
NURSE CALL DOME LIGHT
FLOOR
FLOOR
FLOOR
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RATED TTB8"
N
M
PATIENT STATION (PB - PUSH BUTTON, M - MICROPHONE, K -KEYED)
88" MOTION DETECTOR
MD
FLOOR TWO POST OIT EQUIPMENT RACK
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
AREA OF REFUGE PANEL6' TO TOP
AREA OF REFUGE ANNUNCIATION PANEL6' TO TOP
AOF
AOFA
IC AREA OF REFUGE INTERCOM48"
AREA OF REFUGE STROBE LIGHTCEILINGSL
DP
DPP
DURESS PANIC ALARM PUSH BUTTON48"
DURESS PANIC ALARM PANEL6' TO TOP
N
SECURE WIRELESS ACCESS POINT - N-4 PR UTP
N
CEILING
S
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
CEILING
48"
CEILING
CEILING
TELEMETRY ANTENNA - 2-4 PRCEILING
ROBOT PHARMACY ANTENNA - 1-4 PRCEILINGR
ADO AUTOMATIC DOOR OPERATOR
AFF ABOVE FINISH FLOOR
BOD BASIS OF DESIGN
CCTV CLOSED CIRCUIT TELEVISION
COAX COAXIAL CABLE
COMM COMMUNICATION
COR CONTRACTING OFFICER REPRESENTATIVE
DC DOOR CONTACT SWITCH
DN DOWN
DO DOOR OPERATOR
DVC DIGITAL VOICE COMMAND
DVR DIGITAL VIDEO RECORDER
E EXISTING DEVICES
EEB EMERGENCY EXIT BUTTON
EL ELECTRICAL STRIKE
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FO FIBER OPTIC
FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
IT INTERCOMMUNICATION ROOM
MATV MASTER ANTENNA TELEVISION
MM MULTI MODE FIBER
NAC NETWORK APPLIANCE CIRCUIT PANEL
N NEW DEVICES
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
TECHNOLOGY ABBREVIATIONS LIST
OC ON CENTER
OIT OFFICE OF INFORMATION TECHNOLOGY
PACS PHYSICAL ACCESS CONTROL SYSTEM
PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM
PB PUSH BUTTON
PBB PRIMARY BONDING BUSBAR
PDU RACK POWER DISTRIBUTION UNITS
POE POWER OVER ETHERNET
PR PAIR
RBB RACK BONDING BUSBAR
RX REQUEST TO EXIT
SBB SECONDARY BONDING BUSBAR
SEP SERVICE ENTRANCE PROTECTION
SLC SIGNALING LINE CIRCUIT
SM SINGLE MODE FIBER
TBB TELECOM BACKBONE CONDUCTOR
TEL TELEPHONE
TGB TELECOM GROUND BUS BAR
TM TELEMONITORING
TMGB TELECOM MAIN GROUND BUS BAR
TP TWISTED PAIR
TR TELECOM ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
WM WIRE MANAGEMENT
WAP WIRELESS ACCESS POINT
UL UNDERWRITERS LABORATORY
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
TECHNOLOGY GENERAL NOTES
1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT
SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL
LISTING REQUIREMENT AND APPLICABLE BUILDING CODES.
4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION
METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607B OR 607A - GROUNDING AND BONDING REQUIREMENTS
FOR TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
6. COMPLY WITH THE LATEST ANSI/TIA/EIA 568B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING
STANDARD.
7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569B - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS
PATHWAYS AND SPACES.
8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN
ACT".
13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY
TESTING AGENCY.
16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE
MORE STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.
17. PROVIDE TIA/EIA CAT 6A COPPER OUTLETS AND CONNECTORS.
18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6A KEYSTONE JACK WIRED PER T568A OR T568B AS DIRECTED
BY THE COR.
19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE STANDARDS
SET FORTH BY THE VA HOSPITAL OIT.
20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.B PARAGRAPH 4.5.6.2.
21. VA WILL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. INSTALL CABLING AND
EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.
22. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
23. MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4" EMT.
24. DEVICES PLACED IN INTERCOMMUNICATION ROOM TO BE MOUNTED ON FIRE RETARDANT PLYWOOD.
25. PROVIDE OUTDOOR AND INDOOR CONDUITS, INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS
FOR A COMPLETE SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.
26. PROVIDE CABLE TRAY, LADDER TRAY J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING BOTH FIBER AND COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS, VERTICAL AND HORIZONTAL WIRE MANAGEMENT, GROUNDING BUS BARS, RACK MOUNTED GROUND BUS, GROUND CABLING, BONDING TO THE GROUNDING SYSTEM, GROUND CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, PDU'S, UPS'S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND
AS DESCRIBED IN THE SPECIFICATIONS.
27. PROVIDE J-HOOKS WHERE CABLE TRAY IS NOT SHOWN OR IF THERE IS OBSTRUCTION IN THE PATH OF THE CABLE TRAY, OR USE FLEXIBLE CONDUITS (NOT TO EXCEED 10 FEET), JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, COVER PLATES, LABELING, SUPPORT J-HOOKS AND CONDUITS, AS SHOWN
HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
28. PROVIDE 12 PORT WALL MOUNTED COPPER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT IN EACH NEW TR AND RUN 12-4PR CAT 6A CABLE BETWEEN THESE TR'S TERMINATE AND TEST, LABEL
EACH PORT.
29. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION SYSTEM (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN
AND AS DESCRIBED IN THE SPECIFICATIONS.
30. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
31. PROVIDE NEW FIRE ALARM SYSTEM DEVICES, FIRE ALARM PANEL, NAC PANEL, POWER SUPPLY, FOR A COMPLETE FIRE AND DETECTION SYSTEM, RED CONDUIT AND JUNCTION BOXES, COVERPLATES, LABELING, CABLING BOTH COPPER AND FIBER, PROGRAMMING, SOFTWARE, LICENSES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL FIRE ALARM SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
32. CAMERAS SHALL BE PANORAMIC MULTI-SENSOR AND SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION
ACT-NDAA.
GENERAL COMMUNICATION DEMO NOTES
A. ALL EXISTING CONDITIONS INCLUDING EQUIPMENT, CABINETS, CABLE TRAY, DEVICES, CONDUITS ARE
BASED ON BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
B. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. ALL OTHER NON-SALVAGEABLE MATERIAL SHALL BE REMOVED FROM THE PREMISES, LIKE PATCH PANEL, CABLES, JACKS, COVER PLATES, PATCH CORDS AND RELATED MATERIAL.
C. EXISTING CABLE TRAY SHALL REMAIN, BUT ALL COMMUNICATION CABLING SERVING WORK AREA OUTLETS SHALL BE REMOVED FROM THE CABLE TRAY, NO ABANDONED CABLE WILL BE ALLOWED TO REMAIN ABOVE
THE CEILING. INSTALL NEW CABLE TRAY NEXT TO THE EXISTING CABLE TRAY
D. EXISTING CONDUIT, SURFACE RACEWAY CAN BE REUSED FOR NEW WOA, BUT LOCATION SHALL BE
COORDINATED WITH THE COR.
E. EXISTING TR(OI&T) ROOM, ONCE ALL DATA CABLING SERVED OUT OF THIS TR IS REPLACED, CONFIRM WITH OI&T THAT NO ACTIVE DATA DROPS ARE SERVED OUT THE TR, UPON CONFIRMATION, COORDINATE
REMOVAL OF ALL VA OWNED NETWORK SWITCHES, REMOVE PATCH PANELS AND ALL ASSOCIATED
CABLING SERVED FROM DEMOLITION TR. BID DEMOLITION AND DISPOSAL OF THE TR RACKS, IF ANY NON- DATA COMPONENTS ARE HOUSED IN THESE RACKS, LEAVE THE RACK IN PLACE WITH THE UPS AND
POWER.
1. CONTRACTOR TO REFER TO TELECOMM ROOM PHASING NOTES, SHEETS A-001, FOR ADDITIONAL
INFOMATION.
1151 Kildaire Farm Rd.
Raleigh, NC 27511 www.acg-pa.com
(919) 858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com
(843) 875-3637Project Mgr: Terry Barnes (APOGEE)
Joint Venture An Alliance for Success
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
/2
/2
:0
:0
A
M
ET002
TECHNOLOGY GENERAL NOTES, SYMBOL
LEGEND, AND ABBREVIATIONS
2 117TT
DAYTON EHRM
INFRASTRUCTURE
UPGRADES
DAYTON VA MEDICAL CENTER
4100 W THIRD STREET
DAYTON, OHIO 45428 APRIL 11, 2023
100% BID DOCUMENTS
552-21-70120-365-Q13
MULTIPLE
GG
CONDITIONAL NOTE
DocuSign Envelope ID: 14462045-55B1-44B5-921D-B848E5CEEEF0
4/21/2023 APRIL 11, 2023
E
CR
DC ES RX
OS
J
E
M M
E E
OS
11 11
PANEL 'A' PANEL 'B'
ET5016
A-1,3,5
B-1,3,5
SBB
K
A-2
B-2
A-2
A-2NB-2
B-2
A-2
B-2
A
6FIRE RATED PATHWAYS
A-4
A
AA
13 14
PANEL A
FIRE RATED PATHWAYS
SSB
CABLE TRAY
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20RMOTOR-RATED
SWITCH
"B" PANEL"A" PANEL
CABLE TRAY
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
SSB
1'-8"
DATA PORT
OCCUPANCY SENSOR
LIGHT SWITCH
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
"B" PANEL
SBB
RECEPTACLE
NEMA 5-20R
NEC REQUIRED WORKING
CLEARANCE, 30" WIDE BY
36" DEEP BY 72" HIGH
RECEPTACLE
NEMA 5-20R
CAT. NO
CF105/300
CF105/450
CF105/500
CF105/600
CF150/150
CF150/200
CF150/300
CF150/450
CF150/500
CF150/600
CF150/900
DEPTH
(IN)
WIDTH
(IN)
CAT 6a 4-pr
PLENUM (0.35")
1151 Kildaire Farm Rd.
Raleigh, NC 27511 www.acg-pa.com
(919) 858-7420
108 Benton Lodge Road Suite B Summerville, SC 29485 www.cemsengineering.com
(843) 875-3637Project Mgr: Terry Barnes (APOGEE)
Joint Venture An Alliance for Success
# KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg. of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
ACG Project Number
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee - CEMS JV, LLC
/1
/2
:2
:0
A
M
ET501
TYPICAL TELECOM ROOM DETAILS
3 117TT
DAYTON EHRM
INFRASTRUCTURE
UPGRADES
DAYTON VA MEDICAL CENTER
4100 W THIRD STREET
DAYTON, OHIO 45428 APRIL 11, 2023
100% BID DOCUMENTS
552-21-70120-365-Q13
MULTIPLE
GG
1 ROOMS ARE COOLED WITH EITHER FAN
COILD UNITS (FCU) OR DUCTLESS
MINI-SPLITS. FOR FCUS, PROVIDE A 20A/1P
CIRCUIT FROM PANEL 'A' TO A MOTOR-RATED
TOGGLE SWITCH WITH A CONNECTION TO
THE UNIT. DUCTLESS MINI-SPLIT UNITS
SHALL BE POWERED FROM THEIR
ASSOCIATED OUTDOOR CONDENSING UNITS.
PROVIDE A CIRCUIT TO THE CONDENSING
UNIT, INCLUDING RACEWAYS
ANDCONDUCTORS TO POWER THE INDOOR
UNITS, AS SHOWN ON THE ET601 SHEETS.
REFER TO ET400 SERIES SHEETS FOR
EQUIPMENT TAGS. REFER TO MECHANICAL
DRAWINGS FOR EQUIPMENT SCHEDULES.
2 TELECOMMUNICATIONS CHANNEL RACK,19
INCHES WIDE, 30 INCHES DEEP, 84 INCHES
HIGH, 45RU, WHITE. PROVIDE ORTRONICS
(LEGRAND) MM2073038-W, OR APPROVED
EQUIVALENT. CONTRACTOR SHALL
COORDINATE ADDITIONAL DETAILS
INCLUDING BUT NOT LIMITED TO GROUNDING
AND BONDING DETAILS, DATA ELEVATIONS
AND POWER ELEVATIONS IN THE DRAWINGS.
3 VERTICAL CABLE MANAGEMENT CAGE WITH
DOOR, 6 INCHES WIDE, 84 INCHES HIGH,
45RU, WHITE. PROVIDE ORTRONICS
(LEGRAND) MM20VMD706-W, OR APPROVED
EQUIVALENT.
4 RACK POWER CONNECTION MOUNTED TO
THE SIDE OF THE CABLE TRAY. PROVIDE
RACK CONNECTION ACCORDING TO THE
POWER REQUIREMENTS TABLE ON THIS
SHEET. REFER TO RACK POWER ELEVATION
AND SCHEMATIC DIAGRAMS ON SHEET
ET505.
5 SECONDARY BONDING BUSBAR TO BE
LOCATED BEHIND OR TO THE SIDE OF THE
RACKS. TELECOMMUNICATIONS EQUIPMENT
SHALL BE BONDED ACCORDING TO THE
GROUNDING AND BONDING DETAILS. REFER
TO DETAILS 3 AND 4 ON SHEET ET503 FOR
MORE INFORMATION.
6 FIRE/SMOKE SLEEVE ASSEMBLIES. PROVIDE
UL LISTED ASSEMBLIES, STI EZ-PATH, SERIES
33 FIRE-RATED PATHWAY, OR APPROVED
EQUIVALENT. INSTALL SLEEVES ABOVE
DOOR HEADER AT AN ELEVATION
COORDINATED TO BE ABOVE THE EXISTING
CEILING HEIGHT IN THE ADJACENT
COORIDOR. REFER TO 400 SERIES ET
SHEETS FOR QUANTITIES.
7 DUAL TECHNOLOGY OCCUPANCY SENSOR.
PROVIDE SENSOR WITH PASSIVE-INFRARED
AND ULTRASONIC TECHNOLOGIES. THE
LIGHTS SHALL TURN ON AUTOMATICALLY
UPON SENSING MOTION, AND TURN OFF
AUTOMATICALLY AFTER 15 MINUTES OF
VACANCY.
8 PROVIDE NEW 4-INCH-HIGH WIRE MESH TRAY
AROUND THE ROOM AND ABOVE THE
CHANNEL RACKS, WITH WATERFALL
DROPOUTS INTO EACH RACK, 90 DEGREE
CORNERS AND ALL RELATED FITTINGS. SEE
WIRE MESH TRAY DETAIL ON ET504 FOR
MORE INFO. B.O.D.: CABLEOFIL CF105/600
AND CF150/600 SERIES OR EQUIVALENT.
9 RECEPTACLES, PROVIDE TWO RECEPTACLE
ON EACH WALL, AS SHOWN 1 FED FROM
PANEL A THE OTHER FROM PANEL B.
10 FIRE RETARDANT PLYWOOD BACKBOARD.
SEE ARCHITECTURAL.
11 LIGHTING AND APPLIANCE PANELBOARDS.
PROVIDE PANELS MOUNTED ON CHANNEL
STEEL SUPPORTS. UNLESS NOTED
OTHERWISE ON THE 400 SERIES ET SHEETS,
PANEL 'A' SHALL BE FED FROM A SOURCE
WITH GENERATOR BACKUP, AND PANEL 'B'
SHALL BE FED FROM A NORMAL UTILITY
SOURCE.
12 PROVIDE JUNCTION BOX WITH EMERGENCY
POWER TO THE PACS DOOR CONTROLLER.
13 PROVIDE MULTI SENSOR CAMERA AND
CONNECT TO EXISTING CAMERA SYSTEM.
LOCATION SHOULD BE COORDINATED WITH
THE CHANNEL RACK LAYOUT AND OIT.
14 PROVIDE CABLING FOR VA FURNISHED
WIRELESS ACCESS POINT.
15 PROVIDE SMOKE DETECTOR AND CONNECT
TO EXISTING CIRCUIT IN THE AREA.
Scale: 3/8" = 1'-0"
ELECTRICAL FLOOR PLAN - TYPICAL 3-RACK TR
Scale: 3/8" = 1'-0"
ELECTRICAL CEILING PLAN - TYPICAL 3-RACK TR
Scale: 3/8" = 1'-0"
PLAN WEST ELEVATION
Scale: 3/8" = 1'-0"
PLAN NORTH ELEVATION
Scale: 3/8" = 1'-0"
PLAN SOUTH ELEVATION
Scale: 3/8" = 1'-0"
PLAN EAST ELEVATION
PER PHASE CONNECTED LOAD: 2.39 kVA 1.67 kVA 1.67 kVA
SPACE -- 1 41 -- -- 42 1 -- SPACE
SPACE -- 1 39 -- -- 40 1 -- SPACE
SPACE -- 1 37 -- -- 38 1 -- SPACE
SPACE -- 1 35 -- -- 36 1 -- SPACE
SPACE -- 1 33 -- -- 34 1 -- SPACE
SPACE -- 1 31 -- -- 32 1 -- SPACE
SPACE -- 1 29 -- -- 30 1 -- SPACE
SPACE -- 1 27 -- -- 28 1 -- SPACE
SPACE -- 1 25 -- -- 26 1 -- SPACE
SPACE -- 1 23 -- -- 24 1 -- SPACE
SPACE -- 1 21 -- -- 22 1 -- SPACE
SPARE 20 A 1 19 0 0 20
17 0 0 18
2 20 A SPARE
15 0 0 16SURGE PROTECTIVE DEVICE 30 A 3
13 0 0 14
2 20 A SPARE
11 0 0 12 1 20 A PACS J-BOX
9 0 0 10 1 20 A CONDENSATE PUMPSPARE 60 A 3
7 0 0 8 1 20 A SPARE
5 1.67 0 6 1 20 A SPARE
3 1.67 0 4 1 20 A TELECOM ROOM LTGRACK CONNECTION 60 A 3
1 1.67 0.72 2 1 20 A TELECOM ROOM RCPT
LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME
ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction
MOUNTING: SURFACE FED FROM: LOCATION:
PANEL: A
VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC:
10,000 AMPS
SYMMETRICAL
PER PHASE CONNECTED LOAD: 2.39 kVA 1.67 kVA 1.67 kVA
SPACE -- 1 41 -- -- 42 1 -- SPACE
SPACE -- 1 39 -- -- 40 1 -- SPACE
SPACE -- 1 37 -- -- 38 1 -- SPACE
SPACE -- 1 35 -- -- 36 1 -- SPACE
SPACE -- 1 33 -- -- 34 1 -- SPACE
SPACE -- 1 31 -- -- 32 1 -- SPACE
SPACE -- 1 29 -- -- 30 1 -- SPACE
SPACE -- 1 27 -- -- 28 1 -- SPACE
SPACE -- 1 25 -- -- 26 1 -- SPACE
SPACE -- 1 23 -- -- 24 1 -- SPACE
SPACE -- 1 21 -- -- 22 1 -- SPACE
SPARE 20 A 1 19 0 0 20 1 20 A SPARE
17 0 0 18 1 20 A SPARE
15 0 0 16 1 20 A SPARESURGE PROTECTIVE DEVICE 30 A 3
13 0 0 14 1 20 A SPARE
11 0 0 12 1 20 A SPARE
9 0 0 10 1 20 A SPARESPARE 60 A 3
7 0 0 8 1 20 A SPARE
5 1.67 0 6 1 20 A SPARE
3 1.67 0 4 1 20 A SPARERACK CONNECTION 60 A 3
1 1.67 0.72 2 1 20 A TELECOM ROOM RCPT
LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME
ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction
MOUNTING: SURFACE FED FROM: LOCATION:
PANEL: B
VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC:
10,000 AMPS
SYMMETRICAL
GENERAL NOTES:
A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY COR, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR
MISMATCHED OR INACCURATE…