Technical Questions Tracking Sheet - EHRM Design Hines Training and Admin Space Support Phase 1 - 7.1.2021.pdf

PDF 154 KB Posted

Attached to
EHRM Infrastructure Demo - Phase I - Hines, IL Federal contract opportunity
Solicitation number
36C77621B0011
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document contains a technical questions tracking sheet for a solicitation to provide infrastructure demolition services at the Hines VA Medical Center in Hines, Illinois. The solicitation number is 36C77621B0011 and is set aside as a competitive opportunity for Service-Disabled Veteran-Owned Small Businesses. The contractor will demolish portions of the existing building as required by the drawings and specifications, with a contract value between $200,000 and $500,000. The tracking sheet includes questions and answers on infection control requirements, floor thicknesses, ceiling types, and the need for structural engineering support during demolition. A structural engineer must review any significant alterations to structural elements and inspect the work upon completion but does not need to be on site full time.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM Infrastructure Demo - Phase I - Hines, IL, newest first.
File Type Posted
ICRA EHRM Infrastructure Phase 1.pdf PDF
WebEx Info.pdf PDF
Amendment 0002 - EHRM Infrastructure Upgrades - Phase 1 Hines IL.pdf PDF
Amendment 0001 - Bldg 200_R2010.zip ZIP file
Amendment 0001 - EHRM Infrastructure Upgrades - Phase 1 - Hines IL.pdf PDF
Amendment 0001 - Technical Questions Tracking Sheet - EHRM Design Hines Training and Admin Space Support Phase 1 - 6.21.2021.pdf PDF
Amendment 0001 - Sign In 578-21-700 Pre-bid sign in.jpg JPG image
1) Hines VA Campus Site Plan.pdf PDF
17) Final SOW EHRM Infrastructure Upgrades - Phase 1 - Hines IL.pdf PDF
3) Pre-Construction Checklist.pdf PDF
10) Infection Control Barrier Sample.pdf PDF
12) Contractor Parking.pdf PDF
14) 578-21-700 Drawings.pdf PDF
16) DBA Cook.pdf PDF
36C77621B0011 EHRM Infrastructure Demo Hines IL 578-21-700.pdf PDF
4) Safety and Health During Construction Activities.pdf PDF
13) 578-21-700 Photos of Current Conditions.pdf PDF
15) 578-21-700 Specifications Book.pdf PDF
2) Hines COVID-19 Guidelines.pdf PDF
5) Interim Life Safety Measures (ILSM).pdf PDF
6) Infection Control Risk Assessment (ICRA).pdf PDF
8) Contractor PIV Instructions and Form.pdf PDF
9) Cutting Welding and Other Hot Work.pdf PDF
18) Contractor Saftey and Enviromental Record Evaluation Form.pdf PDF
7) Pre-Construction Risk Assessment (PCRA).pdf PDF
11) No Smoking Policy 10-1-19.pdf PDF
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNICAL QUESTIONS

AND RESPONSE TRACKING SHEET

RFI CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

1 What is the Infection Control level for this work? 6/30/2021: Please See ICRA EHRM Infrastructure Phase 1 attachment. JR-VA COR

2 Please confirm concrete floor thickness at each floor. Will floor scanning be required at each floor penetration?

07/01/2021: Floors 1 through 15 are 5 1/2" thick. Penthouse floor is 5" thick. The penthouse slab is normally reinforced so scanning is not expected for the doweling. JR-VA COR

3 Please confirm ceiling type of each floor near construction area. 07/01/2021: Bidders should assume all ceilings in the area of work are gypsum board or plaster ceilings. There may be one or two acoustical tile ceilings but those are easier to demolish.

JR-VA COR

4 Engage a professional engineer to survey condition of building to determine whether removing any element might result in structural deficiency or unplanned collapse of any portion of structure or adjacent structures during selective demolition operations”. Does prime contractor owe a professional engineer to be on site full time while demolition is being completed? Please provide a scope of work for engineer requirements?

6/30/2021: A structural engineer shall be consulted when structural elements are proposed to be altered and provide written guidance. The engineer does not need to present during the modification but must inspect any significant work after completion. JR-VA COR