This is a solicitation for kitchen hood and portable fire extinguisher inspection, maintenance, and cleaning services for the Sioux Falls VA Healthcare System. The request was issued by the Department of Veterans Affairs, Network 23 Contracting Office on June 4, 2026, with quotes due by June 18, 2026 at 3:00 PM CDT. Technical questions must be submitted by June 15, 2026 at 10:00 AM CST to scott.morrison2@va.gov.
The contract is a firm fixed-price, total service disabled veteran-owned small business (SDVOSB) set-aside for one base year (September 14, 2026 to September 13, 2027) plus four optional years. The estimated contract value is $19.5 million with a principal NAICS code of 541990 (All Other Professional, Scientific, and Technical Services). Services include monthly portable fire extinguisher inspections (4,800 inspections annually across approximately 400 devices), semi-annual kitchen hood inspections and cleaning at three locations, server room clean agent fire suppression system inspections and maintenance per NFPA 2001 standards, and various maintenance tasks. Contractor personnel must be NFPA 10 and NFPA 96 certified with minimum two years' experience. All quotes must include a completed Limitations on Subcontracting certificate of compliance stating the contractor will not pay more than 50 percent of contract value to non-SDVOSB subcontractors. Invoices will be submitted monthly through the VA's Tungsten Electronic Invoicing System, with payment by electronic funds transfer.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26326Q0772 0002.pdf | ||
| 36C26326Q0772 0002_1.docx | DOCX document | |
| SITE VISIT RESULTS.docx | DOCX document | |
| 36C26326Q0772 0001.pdf | ||
| 36C26326Q0772 0001_1.docx | DOCX document | |
| Para Q.docx | DOCX document | |
| Attach B - deep_cleaning_instructions.pdf | ||
| 36C26326Q0772_1.docx | DOCX document | |
| S02.WD15-5369.txt | TXT text file | |
| Attach C - Electronic Fire Extinguisher Inspection Log.xlsx | XLSX spreadsheet | |
| Attach A - Sapphire Maintenance.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAGE 1 OF 1. REQUISITION NO.
2. CONTRACT NO. 3. AWARD/EFFECTIVE DATE 4. ORDER NO. 5. SOLICITATION NUMBER 6. SOLICITATION ISSUE DATE
a. NAME b. TELEPHONE NO. (No Collect Calls) 8. OFFER DUE DATE/LOCAL
TIME
9. ISSUED BY CODE 10. THIS ACQUISITION IS UNRESTRICTED OR SET ASIDE: % FOR:
SMALL BUSINESS
HUBZONE SMALL
BUSINESS
SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
WOMEN-OWNED SMALL BUSINESS
(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM
EDWOSB
8(A)
NAICS:
SIZE STANDARD:
11. DELIVERY FOR FOB DESTINA-
TION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
12. DISCOUNT TERMS
13a. THIS CONTRACT IS A
RATED ORDER UNDER
DPAS (15 CFR 700)
13b. RATING
14. METHOD OF SOLICITATION
RFQ IFB RFP
15. DELIVER TO CODE 16. ADMINISTERED BY CODE
17a. CONTRACTOR/OFFEROR CODE FACILITY CODE 18a. PAYMENT WILL BE MADE BY CODE
TELEPHONE NO. UEI: EFT:
PHONE: FAX:
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER
18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED
SEE ADDENDUM
19. 20. 21. 22. 23. 24.
ITEM NO. SCHEDULE OF SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
(Use Reverse and/or Attach Additional Sheets as Necessary)
25. ACCOUNTING AND APPROPRIATION DATA 26. TOTAL AWARD AMOUNT (For Govt. Use Only)
27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA ARE ARE NOT ATTACHED.
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________ 29. AWARD OF CONTRACT: REF. ___________________________________ OFFER
COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND DATED ________________________________. YOUR OFFER ON SOLICITATION
DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY (BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE
ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER)
30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED
AUTHORIZED FOR LOCAL REPRODUCTION (REV. NOV 2021)
PREVIOUS EDITION IS NOT USABLE Prescribed by GSA - FAR (48 CFR) 53.212
7. FOR SOLICITATION
INFORMATION CALL:
STANDARD FORM 1449
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30
438-26-4-1115-0750
36C26326Q0772 06-04-2026
Scott Morrison scott.morrison2@va.gov 605-336-3230 06-18-2026
3:00pm CDT
36C263
Department of Veterans Affairs
Network 23 Contracting Office (NCO 23)
Sioux Falls VA Healthcare System
2501 W. 22nd St.
Sioux Falls, SD 57105
X 100
X
541990
$19.5 Million
N/A
X
Department of Veterans Affairs
2501 W 22nd St.
Sioux Falls SD 57105
Network 23 Contracting Office (NCO 23)
Sioux Falls VA Healthcare System
Tungsten Electronic Invoicing
VA Tungsten Number: AAA544240062 va.registration@tungsten-network.com
Refer to VAAR 852.232-72
See CONTINUATION Page
Request for quotes for Fire Extinguisher and Kitchen Hood inspection, maintenance and cleaning as specified in the statement of work below.
All services shall take place at the Sioux Falls, SD VA
Health Care System.
All technical questions must be in writing and received by
06/15/2025 by 10:00AM CST to scott.morrison2@va.gov
This requirement is being solicitated as a Total Service
Disabled Veteran-Owned Small Business Set Aside.
All offerors shall fill out the certificate of compliance
For limitations on subcontracting (LOS) at C.5 and return
With quote. Failure to sign LOS form will result in quote
Being unresponsive.
Period of Performance: 09-14-2026 to 09-13-2027 plus Four (4) Option Years.
All quotes must be received by 06-18-2025 at 3:00pm CST
Email quote to scott.morrison2@va.gov.
See CONTINUATION Page
438-3660162-1115-855100 2543 0100501X3
438-26-4-1115-0750
X 1(one)
Jeff Brown
NCO2316L2-65423
36C26326Q0772
Table of Contents
SECTION A
A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS
AND COMMERCIAL SERVICES
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA
B.2 PRICE/COST SCHEDULE
ITEM INFORMATION
SECTION C - CONTRACT CLAUSES
C.1 52.212-4 CONTRACT TERMS AND CONDITIONS—COMMERCIAL PRODUCTS
AND COMMERCIAL SERVICES (OCT 2025)
C.2 52.217-6 OPTION FOR INCREASED QUANTITY (MAR 1989)
C.3 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999)
C.4 52.217-9 OPTION TO EXTEND THE TERM OF THE CONTRACT (MAR 2000) ... 29
C.5 52.219-14 LIMITATIONS ON SUBCONTRACTING (OCT 2022)
C.6 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS
(DEVIATION APR 2026)
C.7 52.228-5 INSURANCE—WORK ON A GOVERNMENT INSTALLATION (JAN 1997)
C.8 VAAR 852.204-72 PERSONNEL VETTING AND CREDENTIALING (MAR 2026)
C.9 VAAR 852.201-70 CONTRACTING OFFICER’S REPRESENTATIVE (DEC 2022)
C.10 VAAR 852.204-70 PERSONAL IDENTITY VERIFICATION OF CONTRACTOR
PERSONNEL (DEVIATION) (MAR 2026)
C.11 VAAR 852.219-73 VA NOTICE OF TOTAL SET-ASIDE FOR CERTIFIED
SERVICE-DISABLED VETERAN-OWNED SMALL BUSINESSES (JAN 2023)
(DEVIATION)
C.12 VAAR 852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING—
CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION (JAN 2023)
(DEVIATION)
C.13 VAAR 852.232-72 ELECTRONIC SUBMISSION OF PAYMENT REQUESTS
(NOV 2018)
C.14 VAAR 852.240-70 COMPLIANCE WITH PUBLIC LAW 119-37, SECTION 258
(MAR 2026)
C.15 VAAR 852.242-71 ADMINISTRATIVE CONTRACTING OFFICER (OCT 2020) . 45
C.16 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)
SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS
SECTION E - SOLICITATION PROVISIONS
E.1 52.212-1 INSTRUCTIONS TO OFFERORS—COMMERCIAL PRODUCTS AND
COMMERCIAL SERVICES (SEP 2023)
E.2 52.212-2 EVALUATION—COMMERCIAL PRODUCTS AND COMMERCIAL
SERVICES (NOV 2021)
E.3 52.212-3 OFFEROR REPRESENTATIONS AND CERTIFICATIONS—
COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (OCT 2025) (DEVIATION
FEB 2025)
E.4 52.216-1 TYPE OF CONTRACT (NOV 2025) (DEVIATION)
E.5 52.233-2 SERVICE OF PROTEST (SEP 2006)
E.6 52.240-90 SECURITY PROHIBITIONS AND EXCLUSIONS REPRESENTATIONS
AND CERTIFICATIONS (NOV 2025) (DEVIATION)
E.7 52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB
1998)
E.8 VAAR 852.233-71 ALTERNATE PROTEST PROCEDURE (OCT 2018)
SECTION B - CONTINUATION OF SF 1449 BLOCKS
B.1 CONTRACT ADMINISTRATION DATA
1. Contract Administration: All contract administration matters will be handled by the following individuals:
a. CONTRACTOR:
b. GOVERNMENT: Contracting Officer 36C263
Network 23 Contracting Office (NCO 23)
Sioux Falls VA Healthcare System
2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:
[X] 52.232-33, Payment by Electronic Funds Transfer—System For Award Management, or
[] 52.232-36, Payment by Third Party
3. INVOICES: Invoices shall be submitted in arrears:
a. Quarterly []
b. Semi-Annually []
c. Other [X] MONTHLY
4. GOVERNMENT INVOICE ADDRESS: All Invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment
Requests.
Tungsten Electronic Invoicing System VA Tungsten Number is: AAA544240062 va.registration@tungsten-network.com Refer to VAAR Clause 852.232-72
5. INVOICING INSTRUCTIONS:
In addition to information required for submission of a “proper” invoice in accordance with FAR 52.212-4 (g), all invoices must include:
• Name and Address of Contractor
• Contractor’s Invoice Date and Invoice Number
• Contract Number, Task Order Number, and/or Purchase Order Number
• Date(s) of Service
• Cost of service, i.e., hourly rate, quantity, job cost, trip, etc.
• Total price
Electronic Invoice Submission Method. Invoice(s) shall be electronically submitted through the
Tungsten Network: https://www.tungsten-network.com/customer-campaigns/veterans-affairs/.
The VA-FSC pays all associated transaction fees for VA orders.
The Tungsten direct vendor support number is 877-489-6135 for VA contracts. During
Implementation (technical set-up) Tungsten will confirm your Tax Payer ID Number with the VA-
FSC. This process can take up to five (5) business days to complete to ensure your invoice is automatically routed to your Certifying Official for approval and payment. https://www.tungsten-network.com/us/support/’. The VA-FSC pays all associated transaction fees for VA orders.
For additional information, please contact:
• Tungsten Support, Phone: 1-877-752-0900, Email: va.registration@tungsten-network.com
• Department of Veterans Affairs Financial Service Center, Phone: 1-877-353-9791, Email: vafscched@va.gov
ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:
AMENDMENT NO DATE
B.2 STATEMENT OF WORK (SOW)
TITLE: Kitchen Hood and Portable Fire Extinguisher Inspection Contract
GENERAL OVERVIEW: The scope of work includes the provision of all labor, materials, equipment, tools, supervision and quality assurance necessary to complete services as described below.
• Portable fire extinguisher inspection/maintenance
• Portable fire extinguisher replacement
• Kitchen hood cleaning
• Kitchen hood inspection/maintenance
• Clean agent suppression system inspection/maintenance
The contractor is responsible for reviewing all items within the Statement of Work to assure that the contractor can meet all required work and inspection criteria.
DEFINITIONS AND ACRONYMS:
1. CO – Contracting Officer
2. SFVAHCS – Sioux Falls VA Health Care System https://www.tungsten-network.com/customer-campaigns/veterans-affairs/ mailto:vafscched@va.gov
3. VATR – VA Technical Representative
4. VHA – Veteran’s Health Administration
5. FE – Fire Extinguisher
6. NFPA – National Fire Protection Association
7. VCS – Veterans Canteen Service
8. NFS – Nutrition and Food Services
9. EFEIL – Electronic Fire Extinguisher Inspection Log (owner provided Excel spreadsheet)
PLACE OF PERFORMANCE:
Sioux Falls VA Health Care System (SFVAHCS) Campus 2501 West 26th Street Sioux Falls, SD 57105
Areas of inspection include the SFVAHCS main campus and all outbuildings. Contractor shall coordinate work schedule with the VATR. SFVAHCS Main Campus work hours are Monday through Friday 8:00 am to 4:30pm Central Standard Time (CST), except national holidays. Work may be required to be performed outside of normal duty hours if mutually agreed upon by the VATR and Contractor. Any work resulting in hours outside of 8:00am to 4:30pm CST as a result of operational impacts shall occur at no additional expense to the government. Kitchen hood and duct cleaning will have a 6:00pm start time.
PERIOD OF PERFORMANCE:
This will be a single firm fixed priced contract, with one (1) base and up to four (4) option years:
Period Period Begins Period Ends
Base 09-14-2026 09-13-2027
Option Year 1 09-14-2027 09-13-2028
Option Year 2 09-14-2028 09-13-2029
Option Year 3 09-14-2029 09-13-2030
Option Year 4 09-14-2030 09-13-2031
Exercise of option years will be made at Government’s discretion based on continued need for services, Contractor performance, and availability of funds in a given fiscal year.
AUTHORIZED SERVICES: Only those services specified herein are authorized under this contract. Prior to performing any service of a non-contract nature, the CO must be advised of the reasons for this additional work. Only the CO may authorize additional services, and reimbursement will not be made unless prior authorization has been obtained.
GOVERNMENT RESPONSIBILITIES:
1. The contractor will be provided with means to gain access to the work areas.
2. Provide the EFEIL for contractor use.
3. Badges and parking:
a. All Contractor personnel are required to wear identification (I.D.) badges issued by the SFVAHCS Engineering office during the entire time they are on the SFVAHCS grounds.
b. It is the responsibility of the Contractor’s personnel to park in the appropriate designated parking areas. The SFVAHCS shall not validate or make reimbursement for parking violations of the Contractor’s personnel under any circumstance.
4. Personnel requirements: The Government reserves the right to accept or reject Contractor’s staff for the rendering of services. Complaints concerning Contract Personnel’s performance or conduct shall be dealt with by the Contractor, VATR and the final decision made by the CO.
5. Any VA staff member may stop contractor’s work if any immediate danger to life and health item/activity is found during performance of services.
CONTRACTOR RESPONSIBILITIES:
1. Overall Reporting requirements and due dates (covers all sections outlined in Scope of Work):
a. All work shall be completed in accordance with all applicable Federal, State and Local guidelines/specifications/design standards and in compliance with NFPA.
b. Contractor shall respond to VHA inquiries or questions and provide revised documents (if necessary) during period of performance of the contract.
c. Contractor shall respond to questions within one calendar day if found to be in error by inspection entities or VHA staff and U.S. Occupational Safety and Health Administration (OSHA) Regulations, with special emphasis on NFPA 101, 80 and 105 most current editions.
d. This contract will aid VHA staff in defending the report to external inspection entities where errors or omissions are suspected.
e. All reports, quotes, and other contract documents shall be delivered to the VATR no later than 14 calendar days after completion of the inspection, testing, maintenance, or any other work.
f. All reports will have a reference to the most current version of NFPA and Joint Commission section including relevant paragraphs.
g. Each “Scope of Work” section may have separate reports in PDF and/or excel format individual files named for the work completed. Coordinate report grouping with VATR.
h. Contractor shall email invoices to VATR to sign and return prior to uploading to Tungsten.
2. Contractor shall closely follow established procedures outlined in owner provided EFEIL.
The “Guide” tab provides instructions for common matters related to managing the fire extinguisher data. Features are also added to identify and eliminate duplicates. Any spreadsheet drop down options, structural revisions, or any functional changes will be completed by the Owner. The EFEIL spreadsheet will be emailed between the contractor and the VA at a minimum of once per month as a shared record keeping resource.
3. The Contractor is responsible for safety during the performance of all work. The Contractor shall perform all work in accordance with the latest Occupational Safety and Health Administration (OSHA) regulations. The Contractor shall coordinate their work with VA Safety through the VATR. The Contractor shall be responsible for any damage to public or private property resulting from his/her activities and shall repair or otherwise make whole such damage at no cost to Owner. The Contractor shall provide a safety plan before beginning work.
4. Immediately notify the VATR and VA Safety Office in the event of an accident related to the performance of the work.
5. Conform to the specific safety requirement established by this contract.
6. Comply with the safety rules of the Government property that concern related activities not directly addressed in this contract.
7. Take all reasonable steps and precautions to prevent accidents and preserve the life and health of contractor and Government personnel performing, or in any way coming in contact, with the performance of this contract.
8. Take such additional immediate precaution as the CO may reasonably require for safety and accident prevention purposes.
9. Contractor is expected to perform services and maintain staffing levels such that services are conducted per inspection intervals defined in contract.
10. Contract holder shall be on campus during any subcontractor work.
11. Contractor shall establish PPE requirements with VATR upon contract award for various spaces within the hospital.
QUALIFICATIONS OF CONTRACTOR PERSONNEL:
1. Training certifications specific to NFPA sections outlined in “Scope of work”.
2. Contractor shall have minimum of 2 years’ experience and be trained/certified in NFPA
96 (Kitchen Hood Inspection for Health Care Facilities). The Inspector shall be familiar with the hood and fire suppression and fire alarm interlock components and their operation. Listed below is a list of areas of expertise:
a. Kitchen Hood inspection experience
b. Portable FE experience
3. Contractor personnel shall have a minimum of 2 years’ experience performing FE and kitchen hood inspections; at Government discretion, CO or VATR reserves the right to verify this experience by requesting documentation from Contractor.
4. Contractor shall obtain all licenses and certifications required by Federal, State, and Local environmental laws and regulations necessary to adhere to the specifications of this contract. The Contractor shall submit all plans, notifications, reports, submittal documents, and fees required by Federal, State, and Local environmental laws and regulations to the appropriate Federal, State, and Local authority and/or agency as necessary to adhere to the specification of this contract. All required licenses and certifications required by Federal, State, and Local environmental laws and/or regulations shall be considered a contract deliverable upon award.
Scope of work:
A. Service: Server Room Clean Agent Fire Suppression System Inspection
• Work: Visual inspection per NFPA 2001 11.2.2. Visual inspection to include: (1) Releasing panel is powered and free of supervisory, trouble or alarm conditions (2) Manual controls are unobstructed (3) System shows no physical damage or condition preventing operation (4) Pressure gauges in operating range (5) Equipment has not been changed or modified (6) All previously noted deficiencies have been corrected
• Schedule: Monthly
• Quantity: 12 inspections per contract year
• Location(s): Server Room 2096 in Building 5
• Reporting requirements: If any deficiencies are noted, notify the VATR in writing and submit a quote to correct as outlined in the parts for repair section of the SOW
• Qualifications: NFPA 2001 Certification
• Procedure: Contractor shall sign and date the tag
B. Service: Server Room Clean Agent Fire Suppression System Inspection
• Work: NFPA 2001 -11.3 Inspection strategy at the contractors’ option between pressure check, weight or pressure loss
• Schedule: Semi-annual inspection and tag replacement
• Quantity: 2 inspections per contract year
• Location(s): Server Room 2096 in Building 5
• Reporting requirements: NFPA 2001 11.3.6. An inspection tag shall be provided and include the following information: (1) Date of inspection (2) Person and organization performing the inspection (3) Type of Agent (4) Gross weight of the container and net weight of the agent (as applicable)
• Qualifications: NFPA 2001 Certification
• Procedure: NFPA 2001
C. Service: Server Room Clean Agent Fire Suppression System Maintenance
• Work: Visual inspection of compressed gas cylinders
• Schedule: 5 years
• Quantity: 1 time during contract cycle (OY 4 only)
• Location(s): Server Room 2096 in Building 5
• Reporting requirements: Cylinder inspection - Contractor shall provide and install a tag with contractor signature and date, attached to each cylinder, along with a suitable inspection report.
• Qualifications: NFPA 2001 Certification
• Procedure: NFPA 2001 and Section 3 of CGA C-6 Standard for visual inspection of steel compress gas cylinders, except that the containers need not be stamped while under pressure
D. Service: Server Room Clean Agent Fire Suppression System Maintenance
• Work: All systems inspected, serviced and tested for operation. Discharge tests are not required. Testing per manufacturer’s instruction: (1) Ensure that hazard has not changed from what the system was designed to protect. While surveying the hazard, check for new hazards. (2) Check all nozzles to ensure they are in place and free of damage, corrosion and obstructions both internally and externally (3) Check the condition of the piping to ensure that it is properly secured in the hangers and that all fittings are connected tightly (4) Check all warning nameplates/signage in area to ensure they are in place, mounted securely, readable and not damaged (5) Check that all tanks are secured in brackets and free of damage corrosion and other missing components (6) Ensure tanks are free of damage or corrosion and check last hydro date (7) Verify tank discharge hoses have no structural problems like abrasions or weather checking and are properly connected (8) Remove all actuators from the tank valves and check the condition. The actuators will remain OFF until the final step. (9) Tank weighing options -covered in semi-annual inspection SOW section (10) Check the condition of the control panel for tempering, corrosion or damage (11) Ensure all detectors are in place, clean, and not damaged; check sensitivity in Auto-pulse control system as required (12) Ensure all pull stations are in place, and not blocked or damaged. Operate each pull station to ensure that they operate the correct panel. Reset each pull station. (13) While checking the detectors and electric pull stations, inspect each alarm device and verify that they operate properly when energized. Reset the alarm circuit after each test. (14) When all tests are completed, reset control panel and all accessory electrical equipment (15) Reset all electric (16) Install all electric/ pneumatic actuators on tank valves. Hand tighten. (17) Inform personnel that system is back in service
• Schedule: Annual
• Quantity: 1 time during contract year
• Location(s): Server Room 2096 in Building 5
• Reporting requirements: Record the annual maintenance on tag attached to unit AND forward a copy of the report to VATR
• Qualifications: NFPA 2001 Certification
• Procedure: As outlined in attachment A) Sapphire maintenance
E. Service: VCS and NFS Kitchen Hood and Exhaust Systems Inspection and Cleaning
• Work: The entire exhaust system shall be inspected for grease buildup 2 times per year using a grease depth gauge. The entire exhaust system (to include hoods, grease removal devices, fans ducts and other appurtenances) to be cleaned to remove contaminants twice per year.
• Schedule: Biannually – hood inspection and cleaning in one mobilization
• Quantity: 4 times during contract year (2 inspections, x2 hoods)
• Location(s): VCS and NFS hoods, regardless of location
• Reporting requirements:
Kitchen Exhaust System Grease Build up Inspection Report:
• NFPA 96 12.6.13 – Labeling o Contractor shall include one NFPA 12.6.13.1 label affixed to hood system when hoods are both INSPECTED and CLEANED. Label includes:
▪ Date service was performed
▪ Name of person who performed work
▪ Name, address and phone number of service provider
• NFPA 96 12.6.14 and VA Specific Reporting Requirements:
o A written report will identify current condition of each kitchen hood, connected ductwork, and exhaust fans. Handwritten notes are not an acceptable format for final reports.
o Date inspection was performed o Name of Technician who performed work o Name, address and phone number of service provider o Photo of each kitchen hood and associated ductwork at inlet and outlet o Kitchen hood room number and location o Measurement of grease thickness on hood surface o Measurement of grease thickest grease found in ductwork o Measurement of grease thickness found in exhaust fan o Areas that are inaccessible and were not inspected o Areas that are accessible but were not inspected o Location of duct access panel(s) o Locations of visible leakage from ductwork o Locations of leaking access panels o Applicable codes o If any deficiencies are noted, notify the VATR in writing and submit a quote to correct as outlined in the parts for repair section of the SOW
Post Kitchen Exhaust System Cleaning Report:
• NFPA 96 12.6.13 – Labeling o Contractor shall include one NFPA 12.6.13.1 label affixed to hood system when hoods are both INSPECTED and CLEANED. Label includes:
▪ Date service was performed
▪ Name of person who performed work
▪ Name, address and phone number of service provider
• NFPA 96 12.6.15 and VA Specific Reporting Requirements:
o A written report will identify current condition of each kitchen hood, connected ductwork, and exhaust fans. Handwritten notes are not an acceptable format for final reports.
o Date inspection was performed o Name of Technician who performed cleaning o Name, address and phone number of service provider o Photo of each kitchen hood and associated ductwork at inlet and outlet o Kitchen hood room number and location o Measurement of grease thickness on hood surface after cleaning, at the same location as inspection o Measurement of grease thickest grease found in ductwork after cleaning, at the same location as inspection o Measurement of grease thickness found in exhaust fan after cleaning, at the same location as inspection o Areas that are inaccessible and were not cleaned o Areas that are accessible but were not cleaned o Location(s) of duct access panel(s) o Location(s) of visible leakage from ductwork o Location(s) of leaking access panels o Applicable codes o If any deficiencies are noted, notify the VATR in writing and submit a quote to correct as outlined in the parts for repair section of the SOW
• Qualifications: NFPA 96 Certifications
• Procedure: Acceptable cleaning methods are (1) Manual cleaning by scraping, grinding, or scrubbing (2) Chemical cleaning with agents and water (3) Pressure washing with pressurized water, or pressurized water and agents (4) Steam cleaning with pressurized steam. Wastewater and solid waste used in the cleaning process are to be collected and disposed of by the contractor. Upon completion of the cleaning, the grease depth shall be measured and confirmed to be less than 0.002 inches (50 microns). Attachment B:
Deep Cleaning Instructions.
F. Service: CLC Cottage Kitchen Hood and Exhaust Systems Inspection and Cleaning
• Work: The entire exhaust system should be inspected for grease buildup once per year using a grease depth gauge. The entire exhaust system (to include hoods, grease removal devices, fans, ducts and other appurtenances) will be cleaned to remove contaminants. A frequency of 1x per year was selected from Table 12.4 for CLC Cottage.
• Schedule: Annual
• Quantity: 1 inspection/cleaning per contract year
• Location(s): CLC Cottage, Building 54
• Reporting requirements:
Kitchen Exhaust System Grease Build up Inspection Report:
• NFPA 96 12.6.13 – Labeling o Contractor shall include one NFPA 12.6.13.1 label affixed to hood system when hoods are both INSPECTED and CLEANED. Label includes:
▪ Date service was performed
▪ Name of person who performed work
▪ Name, address and phone number of service provider
• NFPA 96 12.6.14 and VA Specific Reporting Requirements:
o A written report will identify current condition of each kitchen hood, connected ductwork, and exhaust fans. Handwritten notes are not an acceptable format for final reports.
o Date inspection was performed o Name of Technician who performed work o Name, address and phone number of service provider o Photo of each kitchen hood and associated ductwork at inlet and outlet o Kitchen hood room number and location o Measurement of grease thickness on hood surface o Measurement of grease thickest grease found in ductwork o Measurement of grease thickness found in exhaust fan o Areas that are inaccessible and were not inspected o Areas that are accessible but were not inspected o Location of duct access panel(s) o Locations of visible leakage from ductwork o Locations of leaking access panels o Applicable codes o If any deficiencies are noted, notify the VATR in writing and submit a quote to correct as outlined in the parts for repair section of the SOW
Post Kitchen Exhaust System Cleaning Report:
• NFPA 96 12.6.13 – Labeling o Contractor shall include one NFPA 12.6.13.1 label affixed to hood system when hoods are both INSPECTED and CLEANED. Label includes:
▪ Date service was performed
▪ Name of person who performed work
▪ Name, address and phone number of service provider
• NFPA 96 12.6.15 and VA Specific Reporting Requirements:
o A written report will identify current condition of each kitchen hood, connected ductwork, and exhaust fans. Handwritten notes are not an acceptable format for final reports.
o Date Inspection was performed o Name of Technician who performed cleaning o Name, address and phone number of service provider o Photo of each kitchen hood and associated ductwork at inlet and outlet o Kitchen hood room number and location o Measurement of grease thickness on hood surface after cleaning, at the same location as inspection o Measurement of grease thickest grease found in ductwork after cleaning, at the same location as inspection o Measurement of grease thickness found in exhaust fan after cleaning, at the same location as inspection o Areas that are inaccessible and were not cleaned o Areas that are accessible but were not cleaned o Location(s) of duct access panel(s) o Location(s) of visible leakage from ductwork o Location(s) of leaking access panels o Applicable codes o If any deficiencies are noted, notify the VATR in writing and submit a quote to correct as outlined in the parts for repair section of the SOW
• Qualifications: NFPA 96 Certifications
• Procedure: Acceptable cleaning methods are (1) Manual cleaning by scraping, grinding, or scrubbing (2) Chemical cleaning with agents and water (3) Pressure washing with pressurized water, or pressurized water and agents (4) Steam cleaning with pressurized steam. Wastewater and solid waste used in the cleaning process are to be collected and disposed of by the contractor. Upon completion of the cleaning, the grease depth shall be measured and confirmed to be less than 0.002 inches (50 microns). Attachment B:
Deep Cleaning instructions.
G. Service: VCS, NFS, and CLC Cottage Kitchen Hood Fire Suppression – Inspections
• Work: NFPA 96 - Inspect kitchen hood fire suppression systems with Ansul R102 system
(1) Contractor shall recharge any hood suppression cylinders which have been determined by the contractor to be repairable
(2) Contractor shall dispose of any fire suppression cylinders as requested by the owner
• Schedule: Semiannually
• Quantity: 6 inspections per contract year (semiannually, x3 hoods)
• Location(s): 1 hood in Hospice Cottage, Building 54; 1 VCS hood and 1 NFS hood in main hospital, Building 5
• Reporting requirements: NFPA 96 12.3.4 A documentation tag shall include the year of manufacture and date of installation of the fusible links, signed by installer. A certificate of inspection and maintenance will be provided to the VATR. NFPA 17A Maintenance report, including any recommendations. If any deficiencies are noted, notify the VATR in writing and submit a quote to correct as outlined in the parts for repair section of the SOW.
• Qualifications: Must be trained and hold an ANSUL certificate in an R-102 program
• Procedure: Fusible links (metal alloy type--date of manufacture marked on inspection tag) and automatic sprinklers (metal alloy type-same temperature rating) shall be replaced. NFPA 17A--Maintenance shall be conducted in accordance with the manufacturer's design, installation, and maintenance manual to include (1) The hazard has not changed (2) Examination of all detectors, expellant gas containers, agent containers, releasing devices, piping, hose assemblies, nozzles, signals, auxiliary equipment and liquid level (non-pressurized) (3) Test to verify that the agent distribution piping is not obstructed using nitrogen or dry air at a pressure not to exceed normal operating pressure of the extinguishing system and to ensure that nitrogen or dry air has discharged out of each nozzle in the system. Where maintenance of the wet chemical containers reveals conditions (corrosion or pitting in excess of manufacturers limits, structural damage, fire damage, repairs by soldering welding or brazing) the container shall be replaced. Where maintenance of the wet chemical system reveals corrosion or pitting in excess of manufacturers limits, structural damage, or fire damage the affected parts shall be replaced. Testing shall include operation of the detection system signals and releasing devices including manual station and other associated equipment.
H. Service: VCS, NFS, and CLC Cottage Kitchen Hood Fire Suppression – Inspections and
Tag Signing
• Work: NFPA 96 and NFPA 17A 8.2.2
• Schedule: Monthly
• Quantity: 36 inspections per contract year (monthly, x3 hoods)
• Location(s): 1 hood in Hospice Cottage, Building 54; 1 VCS hood and 1 NFS hood in main hospital, Building 5
• Reporting requirements: NFPA 96 and NFPA 17A 8.2.2 Must sign tag that is affixed to equipment. If any deficiencies are noted, notify the VATR in writing and submit a quote to correct as outlined in the parts for repair section of the SOW.
• Qualifications: Must be trained and hold an ANSUL certificate in an R-102 program
• Procedure: Visual inspection shall be conducted in accordance with the manufacturers’ listed maintenance manual and shall include, at a minimum (1) The extinguishing system is in its proper location (2) Manual actuators are unobstructed (3) Tamper indicators and seals are intact (4) The maintenance tag and certificate are in place (5) No obvious physical damage or conditions exist that would prevent operation (6) The pressure gauges have been inspected physically or electronically to ensure it is in operable range
(7) The nozzle blowoff caps are intact and undamaged (8) The hazard has not changed, including replacement, modification and relocation of protected equipment
I. Service: VCS, NFS, and CLC Cottage Kitchen Hood Fire Suppression Nozzle – Inspections and Maintenance
• Work: Suppression nozzle maintenance
• Schedule: Annual and per R102 systems manufacturer recommendations
• Quantity: 3 inspections per contract year (annually, x3 hoods)
• Location(s): 1 hood in Hospice Cottage, Building 54; 1 VCS hood and 1 NFS hood in main hospital, Building 5
• Reporting requirements: No explicit reporting requirement in NFPA or manual
• Qualifications: Must be trained and hold an ANSUL certificate in an R-102 program
• Procedure: At least annually, use dry air or nitrogen and blow through the agent distribution piping with the nozzle blow-off caps, verify that dry air or nitrogen is discharging at each nozzle station. Replace all as required per NFPA 96 12.2.4 through 12.2.8.
J. Service: Portable Fire Extinguisher Inspections for all types
• Work:
(1) All inspections, maintenance, and testing criteria used will be in compliance with manufacturers established operating standards and the most current edition of National Fire Protection Association (NFPA) 10/ Standard for Portable Fire Extinguishers.
(2) Any FE found unserviceable during an inspection will be exchanged with like-type of extinguisher from the spare inventory located on the main Sioux Falls campus.
Contractor shall provide quote for any new extinguisher not available in owner stock.
New/replacement FE should be given a sticker number, using the EFEIL to find a number that is not already being used.
(3) Any new FE that is brought into the SFVAHCS inventory will have an inventory number established by the contractor and will be placed on the EFEIL maintained by the contractor. All information from the new extinguisher will be provided to the SFVAHCS Safety Office by the contractor as part of the EFEIL. Each extinguisher shall have a unique number. The electronic record includes filters to identify duplicates.
(4) Contractor shall recharge FEs which have been determined by the contractor to be repairable.
(5) Contractor will locate each fire extinguisher and note month, date, and initials of inspector on each extinguisher tag. NFPA 7.2.2 process.
• Schedule: Monthly
• Quantity: 4,800 FE inspections per contract year, in support of 400 individual devices (12 months x 400 FE)
• Location(s): Main Sioux Falls campus
• Reporting requirements: All records will be maintained by the contractor in the owner provided EFEIL. The EFEIL includes: serial #, manufacturer, type, weight/volume, number, manufacture date, annual maintenance date, next scheduled maintenance action, building, floor, room data point, and applicable service technician. The EFEIL provided by the SFVAHCS to the contractor shall be updated and delivered to the VATR.
Contractor is responsible for accurately maintaining the location of all extinguishers throughout the contract. The EFEIL will be turned into the SFVAHCS Safety Office in Excel and PDF formats. NFPA 10 7.2.2 Contractor to perform monthly inspections and document the date, result, and technician completing the work in the EFEIL.
• Qualifications: NFPA 10 Certifications
• Procedure: NFPA 7.2.2 (1) Locate in designated place (2) Visibility of extinguisher or means of indicating extinguisher location (if sign is missing, note on EFEIL spreadsheet)
(3) Access to extinguisher (if blocked by equipment, tables, etc note on EFEIL spreadsheet) (4) Pressure gauge indicator in operable range (5) Fullness determined by weighing or hefting (6) Tamper band in place (7) No physical damage
K. Service: Portable Fire Extinguisher Inspections for all types
(1) All inspections, maintenance, and testing criteria used will be in compliance with manufacturers established operating standards and the most current edition of National Fire Protection Association (NFPA) 10/ Standard for Portable Fire Extinguishers
(2) Any FE found unserviceable during an inspection will be exchanged with like-type of extinguisher from the spare inventory located on the main Sioux Falls campus.
Contractor shall provide quote for any new extinguisher not available in owner stock.
New/replacement FE should be given a sticker number, using the EFEIL to find a number that is not already being used.
(3) Any new FE that is brought into the SFVAHCS inventory will have an inventory number established by the contractor and will be placed on the EFEIL maintained by the contractor. All information from the new extinguisher will be provided to the SFVAHCS Safety Office by the contractor as part of the EFEIL. Each extinguisher shall have a unique number. The electronic record includes filters to identify duplicates.
(4) Contractor shall recharge FEs which have been determined by the contractor to be repairable.
(5) Contractor shall dispose of any portable fire extinguisher. Including those listed in the owner provided EFEIL, any unserviceable fire extinguisher, and any requested by the owner.
(6) Contractor shall perform a campus-wide audit of the FE inventory each January with the maintenance inspections, including contractor or owner provided devices. An audit requires verifying that all data on the EFEIL matches the extinguisher data in the field.
Refer to overall reporting requirements for each data point.
• Schedule: Annual. Inspection and maintenance shall be completed by January 31 of each year.
• Quantity: 400 inspections per year for Base, OY 1, OY 2, OY 3, and OY 4
• Location(s): Main Sioux Falls campus
• Reporting requirements: All records will be maintained by the contractor in the owner provided EFEIL. The EFEIL Includes: serial #, manufacturer, type, weight/volume, number, manufacture date, annual maintenance date, next scheduled maintenance action, building, floor, room data point, and applicable service technician. The EFEIL provided by the SFVAHCS to the contractor shall be updated and delivered to the VATR.
Contractor is responsible for accurately maintaining the location of all extinguishers throughout the contract. The EFEIL will be turned into the SFVAHCS Safety Office in Excel and PDF formats. Contractor shall provide annual report of discrepancies found in EFEIL and make corrections to the spreadsheet.
• Qualifications: NFPA 10 Certifications
• Procedure: NFPA 10 7.3.2. Each individual FE must have maintenance performed in accordance with NFPA 10, including recharging where necessary. The maintenance shall include, at a minimum, the following: (1) Locate in designated place (2) No obstruction to access or visibility to the extinguisher. Any access or visibility issues that cannot be immediately corrected shall be documented on the EFEIL (3) Operating instructions on nameplate are legible and facing outward (4) Safety seals and tamper indicators are not broken or missing (5) Fullness determined by weighing or “hefting” (6) Examination for obvious physical damage, corrosion, leakage, or clogged nozzle (7) Pressure gauge reading or indicator in the operable range or position (8) Contractor will supply a new inspection tag with the year and month documented. (9) Tamper indicators are to be completely removed and replaced. Contractor shall perform annual maintenance and document the date, result, and technician completing the work in the
EFEIL.
L. Service: Portable CO2 Fire Extinguisher Inspection
• Work: Hose conductivity test
(1) All inspections, maintenance, and testing criteria used will be in compliance with manufacturers established operating standards and the most current edition of National Fire Protection Association (NFPA) 10/ Standard for Portable Fire Extinguishers
(2) Any FE found unserviceable during an inspection will be exchanged with like-type of extinguisher from the spare inventory located on the main Sioux Falls campus.
Contractor shall provide quote for any new extinguisher not available in owner stock.
New/replacement FE should be given a sticker number, using the EFEIL to find a number that is not already being used.
(3) Any new FE that is brought into the SFVAHCS inventory will have an inventory number established by the contractor and will be placed on the EFEIL maintained by the contractor. All information from the new extinguisher will be provided to the SFVAHCS Safety Office by the contractor as part of the EFEIL. Each extinguisher shall have a unique number. The electronic record includes filters to identify duplicates.
(4) Contractor shall recharge FEs which have been determined by the contractor to be repairable.
• Schedule: Annual
• Quantity: 80 FE inspections per year for Base, OY 1, OY 2, OY 3, and OY 4
• Location(s): Main Sioux Falls campus
• Reporting requirements: All records will be maintained by the contractor in the owner provided EFEIL. The EFEIL includes: serial #, manufacturer, type, weight/volume, number, manufacture date, annual maintenance date, next scheduled maintenance action, building, floor, room data point, and applicable service technician. The EFEIL provided by the SFVAHCS to the contractor shall be updated and delivered to the VATR.
Contractor is responsible for accurately maintaining the location of all extinguishers throughout the contract. The EFEIL will be turned into the SFVAHCS Safety Office in Excel and PDF formats. Durable weatherproof label minimum of ½” x 3” affixed to hose with month and year test performed indicated by perforation, name or initials of person and agency conducting test. Tamper indicators are to be completely removed and replaced. Contractor shall perform annual maintenance and document the date, result, and technician completing the work in the EFEIL.
• Qualifications: NFPA 10 Certifications
• Procedure: NFPA 10 7.4
M. Service: Portable Water Mist, CO2, and Class K Fire Extinguisher Maintenance
(1) All inspections, maintenance, and testing criteria used will be in compliance with manufacturers established operating standards and the most current edition of National Fire Protection Association (NFPA) 10/ Standard for Portable Fire Extinguishers
(2) Any FE found unserviceable during an inspection will be exchanged with like-type of extinguisher from the spare inventory located on the main Sioux Falls campus.
Contractor shall provide quote for any new extinguisher not available in owner stock.
New/replacement FE should be given a sticker number, using the EFEIL to find a number that is not already being used.
(3) Any new FE that is brought into the SFVAHCS inventory will have an inventory number established by the contractor and will be placed on the EFEIL maintained by the contractor. All information from the new extinguisher will be provided to the SFVAHCS Safety Office by the contractor as part of the EFEIL. Each extinguisher shall have a unique number. The electronic record includes filters to identify duplicates.
(4) Contractor shall recharge FEs which have been determined by the contractor to be repairable.
(5) Hydrostatic testing of all portable FEs shall be done by January 31 of the year they are to expire as defined by the interval in NFPA 10 Table 8.3.1
• Schedule: 5 year
• Quantity: Base year = 7 FE, OY 1 = 12, OY 2 = 35, OY 3 = 10, and OY 4 = 18
• Location(s): Main Sioux Falls campus
• Reporting requirements: All records will be maintained by the contractor in the owner provided EFEIL. The EFEIL includes: serial #, manufacturer, type, weight/volume, number, manufacture date, annual maintenance date, next scheduled maintenance action, building, floor, room data point, and applicable service technician. The EFEIL provided by the SFVAHCS to the contractor shall be updated and delivered to the VATR.
Contractor is responsible for accurately maintaining the location of all extinguishers throughout the contract. The EFEIL will be turned into the SFVAHCS Safety Office in Excel and PDF formats. The record is to be maintained by the organization that performed the test until either the expiration of the test period or the cylinder is next tested, whichever occurs first. Label should be 2’ x 3 ½”, affixed by heatless process, self-destructs when removed from shell and made of a durable weatherproof material with pressure sensitive. Contractor shall update EFEIL with next scheduled maintenance due date and planned action.
• Qualifications: NFPA 10 Certifications
• Procedure: NFPA 8.5
N. Service: Portable ABC, halogenated agents, and Purple K Fire Extinguisher Maintenance
• Work:
(1) All inspections, maintenance, and testing criteria used will be in compliance with manufacturers’ established operating standards and the most current edition of National Fire Protection Association (NFPA) 10/ Standard for Portable Fire Extinguishers
(2) Any FE found unserviceable during an inspection will be exchanged with like-type of extinguisher from the spare inventory located on the main Sioux Falls campus.
Contractor shall provide quote for any extinguisher not available in owner stock.
New/replacement FE should be given a sticker number that is unused on the EFEIL.
(3) Contractor shall recharge FEs which have been determined by the contractor to be repairable.
(4) NFPA 10 - 6 year maintenance NFPA 10 7.3.6 (all extinguishers with 12-year hydrostatic test defined by Table 8.3.1) i.e. ABC, clean agent
• Schedule: 6 year
• Quantity: Base year = 10 FE, OY 1 = 28, OY 2 = 45, OY 3 = 16, and OY 4 = 45
• Location(s): Main Sioux Falls campus
• Reporting requirements: All records will be maintained by the contractor in the owner provided EFEIL. The EFEIL includes: serial #, manufacturer, type, weight/volume, number, manufacture date, annual maintenance date, next scheduled maintenance action, building, floor, room data point, and applicable service technician. The EFEIL provided by the SFVAHCS to the contractor shall be updated and delivered to the VATR.
Contractor is responsible for accurately maintaining the location of all extinguishers throughout the contract. The EFEIL will be turned into the SFVAHCS Safety Office in Excel and PDF formats. Durable weatherproof label minimum of 2” x 3 ½” affixed to shell, self-destructive type when removal is attempted, at minimum has month and year, person and agency performing test. Contractor shall update EFEIL with next scheduled maintenance due date and planned action.
• Qualifications: NFPA 10 Certifications
• Procedure: NFPA 7.3.6
O. Service: Portable ABC, Halogenated Agents, and Purple K Fire Extinguisher Maintenance
• Work:
(1) All inspections, maintenance, and testing criteria used will be in compliance with manufacturers established operating standards and the most current edition of National Fire Protection Association (NFPA) 10/ Standard for Portable Fire Extinguishers
(2) Any FE found unserviceable during an inspection will be exchanged with like-type of extinguisher from the spare inventory located on the main Sioux Falls campus.
Contractor shall provide quote for any new extinguisher not available in owner stock.
New/replacement FE should be given a sticker number that is unused on the EFEIL.
(3) Any new FE that is brought into the SFVAHCS inventory will have an inventory number established by the contractor and will be placed on the EFEIL maintained by the contractor. All information from the new extinguisher will be provided to the SFVAHCS Safety Office by the contractor as part of the EFEIL. Each extinguisher shall have a unique number. The electronic record includes filters to identify duplicates.
(4) Contractor shall recharge FEs which have been determined by the contractor to be repairable
(5) Hydrostatic testing of all portable FEs shall be done by January 31 of the year they are to expire as defined by the interval in NFPA 10 Table 8.3.1
• Schedule: 12 year
• Quantity: Base year = 16 FE, OY 1 = 18, OY 2 = 30, OY 3 = 12, and OY 4 = 10
• Location(s): Main Sioux Falls campus
• Reporting requirements: All records will be maintained by the contractor in the owner provided EFEIL. The EFEIL includes: serial #, manufacturer, type, weight/volume, number, manufacture date, annual maintenance date, next scheduled maintenance action, building, floor, room data point, and applicable service technician. The EFEIL provided by the SFVAHCS to the contractor shall be updated and delivered to the VATR.
Contractor is responsible for accurately maintaining the location of all extinguishers throughout the contract. The EFEIL will be turned into the SFVAHCS Safety Office in Excel and PDF formats.