S02 St Cloud VA West Side Tunnels- Lead Paint Testing Report.pdf

PDF 1 MB Posted

Attached to
Y1DA--St. Cloud VAHCS Replacement/Addition Steam Mains Solicitation Notice Federal contract opportunity
Solicitation number
36C26326B0010
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23

About this file

This is a lead-based paint testing report prepared by Landmark Environmental LLC for Anderson Engineering of Minnesota, LLC regarding the Replace/Add Steam Mains West Side Campus project at the St. Cloud VA Health Care System in Minnesota. Testing was conducted on December 22, 2023, in the western portion of the tunnel system and crawlspaces between manhole 21 and Building 51, covering approximately 20 feet on either side of main steam lines.

The testing identified lead-based paint on 15 painted surfaces, with 13 surfaces exceeding OSHA guidelines of 0.0 mg/cm². Eleven surfaces tested above the Minnesota Department of Health/EPA/HUD lead paint level of 1.0 mg/cm², with results ranging from 0.03 mg/cm² to 10.1 mg/cm². The highest concentrations (10.1 mg/cm²) were found on white paint applied to metal pipes and steam pipe hangers in crawlspaces 48, 49, and 51, as well as gray paint on metal steam pipe hangers in crawlspace 51. Testing used a NITON XL706A X-Ray Fluorescence analyzer operated in K+L+Spectra mode with calibration checks conducted at the beginning, end, and every four hours of work. The report notes that OSHA standards require contractors to evaluate potential for lead dust or fume generation from activities disturbing paint containing any detectable quantity of lead and to demonstrate that operations will not exceed the OSHA Action Level of 30 µg/m³ or Permissible Exposure limit of 50 µg/m³. Landmark Environmental is a Certified Lead Firm licensed by the Minnesota Department of Health with License No. LF5321.

View the file

Other files for this federal contract opportunity

Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CLIENT: Anderson Engineering of Minnesota, L.L.C. PROJECT NUMBER: 21175.12

DATE OF SAMPLING: 12/22/2023 DATE OF REPORT: 1/5/2024

PROJECT: Lead Paint Testing at the St. Cloud VA Health Care System – West Main Steam Line Project

Landmark Environmental LLC (Landmark) was retained by Anderson Engineering of Minnesota, L.L.C.

(the Client) to perform lead-based paint testing (Testing) as part of a project at the St. Cloud Veterans

Affairs (VA) Health Care System (VAHCS) located in St. Cloud, Minnesota (the Property). The Testing was conducted in the western portion of the tunnel system as part of the Replace/Add Steam Mains West

Side Campus – St. Cloud VAHCS project (the Project). Tunnels and crawlspaces between manhole 21 and Building 51 were included in the Testing. In the crawlspaces of the buildings, approximately 20 feet on either side of the main steam lines were included in the Testing. A diagram of the locations included in the Testing has been included in this report.

Landmark conducted the Testing on December 22, 2023. All test results are included in the attached sheets. Results that exceeded the OSHA Standards have been transferred to the following table:

Testing Conducted by Landmark Environmental on December 22, 2023

Sample Number

Sample Location Sample Description Lead Result (mg/cm2)

5 Crawlspace 48 White paint on metal pipe 10.1

6 Crawlspace 48 White paint on metal steam pipe hanger 10.1

7 Crawlspace 48 White paint on metal pipe 10.1

8 Tunnel between Buildings 48 & 49 White paint on metal steam pipe hanger 10.1

9 Crawlspace 49 White paint on metal pipe 10.1

10 Crawlspace 49 White paint on metal steam pipe hanger 7.2

13 Tunnel between Buildings 49 & 50 Gray paint on metal steam pipe hanger 3.2

16 Crawlspace 50 by ladder White paint on metal electric conduit 0.4

18 Tunnel between Buildings 50 & 51 Gray paint on metal steam pipe hanger 7.6

19 Tunnel between Buildings 50 & 51 Gray paint on metal steam pipe hanger beam

0.03

20 Tunnel between Buildings 50 & 51 Gray paint on metal steam pipe hanger 5.0

21 Tunnel between Buildings 50 & 51 Gray paint on metal steam pipe hanger 5.7

23 Crawlspace 51 Gray paint on metal steam pipe hanger 10.1

Landmark Environmental, LLC

9555 James Avenue South – Suite 262

Bloomington, MN 55431

Phone: 952-295-9400 www.landmarkenv.com http://www.landmarkenv.com/

January 5, 2024

9555 James Avenue South – Suite 262 | Bloomington, MN 55431 | Phone: 952-295-9400 | www.landmarkenv.com

INTERPRETING PAINT SAMPLING RESULTS

Minnesota Occupational Safety and Health Administration (MNOSHA) has adopted the federal

Occupational Safety and Health Administration (OSHA) standards and operates an OSHA approved state plan. This Testing does not meet the Department of Housing and Urban Development (HUD) or

Minnesota Department of Health (MDH) definition of a lead paint inspection.

Testing surfaces for lead and establishing "safe" levels of lead content is difficult. The OSHA standard does not identify a lower level of lead content in paint that will eliminate the initial air monitoring requirement. Landmark tested a total of fifteen (15) painted surfaces for lead. Thirteen (13) of these surfaces tested above the Occupational Safety and Health Administration (OSHA) guideline of 0.0 milligrams per square centimeter (mg/cm2). Eleven (11) of these surfaces also tested above the

Minnesota Department of Health (MDH)/Environmental Protection Agency (EPA)/ and the Housing and urban Development (HUD) lead paint level of 1.0 mg/cm2. Two (2) surfaces tested at this OSHA guideline. Additionally, 2 quality control tests were performed during the Testing, and 2 tests were found to be inconclusive (Null). When a Null reading was given, a retest was performed immediately after with a result obtained. If these results are used by a contractor to comply with the OSHA interim lead in construction standard (29 CFR 1926.62), the contractor must evaluate the potential for lead dust or fume generation from all activities which will disturb paint containing any detectable quantity of lead.

OSHA Standards apply to any employee disturbing (creating dust or fumes) materials covered with lead-based paint. OSHA regulates lead as an airborne contaminant. Airborne concentrations during disturbance will vary with both the concentration of lead paint and with the operation (manual demolition, sanding, etc.). OSHA requires the contractor to show proof that the operations disturbing lead-based paint in any concentration will not exceed the OSHA Action Level of 30 micrograms of lead per cubic meter of air (µg/m3) or the OSHA Permissible Exposure limit of 50 µg/m3.

This information is provided as a general approach to compliance with OSHA 29CFR 1926.62. It is not the intent of Landmark that this information applies to all situations involving the standard. The standard should be consulted in all cases, and interpretations verified with OSHA prior to construction.

Landmark is a Certified Lead Firm with the Minnesota Department of Health (License No. LF5321).

A NITON 706A X-Ray Fluorescence field portable analyzer (XRF) was used to conduct lead paint testing in the Project work area where paint was observed. The Performance Characteristic Sheet for this instrument is included in the Appendix. The following information details information on the specific

XRF used in this inspection.

January 5, 2024

9555 James Avenue South – Suite 262 | Bloomington, MN 55431 | Phone: 952-295-9400 | www.landmarkenv.com

XRF Manufacturer Niton

XRF Model Number XL706A

XRF Serial Number 89147

XRF Mode of Operation K + L + Spectra Mode

XRF Source Date 08/26/20

XRF Source Activity Cadmium 109

The XRF was set on the mode of operation “K+L+Spectra” during the inspection phase of the work. The equipment does not need substrate corrections for brick, concrete drywall, plaster, and wood. Calibration checks were conducted at the beginning, end, and every 4 hours of work.

Conditions

Landmark conducted the Testing and the Report in a manner consistent with the care and skill ordinarily exercised by members of the environmental profession in the community under similar budget and time constraints.

If you have any questions or comments, please contact me at mmeier@landmarkenv.com or at 952-295- 9400. Thank you for the opportunity to assist you.

Sincerely, Mark Meier Sarah Anderson

MDH Lead Risk Assessor (LR753) MDH Lead Risk Assessor (LR5769)

Attachments

LEAD PAINT TESTING RESULTS

WEST MAIN STEAM LINE PROJECT

ST. CLOUD VAHCS

TEST # TIME FLOOR BUILDING COMPONENT SUBSTRATE CONDITION COLOR RESULT

Action

Level PbC PbC Error PbL PbL Error PbK PbK Error Units QC

1 12/22/2023 11:07 Calibration 1.52 0 0.25 0 0 0 cps

2 12/22/2023 11:12 Calibration Positive 0.0 1 0.1 1 0.1 0.5 0.3 mg/cm2

3 12/22/2023 11:14 Calibration Positive 0.0 1 0.1 1 0.1 0.5 0.3 mg/cm2

4 12/22/2023 11:16 Calibration Positive 0.0 1 0.1 1 0.1 < LOD 0.45 mg/cm2

5 12/22/2023 11:26 Crawlspace 48 Pipe Metal Solid White Positive 0.0 14.3 3.6 10.1 2.1 14.3 3.6 mg/cm2

6 12/22/2023 11:27 Crawlspace 48 Steam Pipe Hanger Metal Solid White Positive 0.0 21.4 5.2 10.1 5.1 21.4 5.2 mg/cm2

7 12/22/2023 11:34 Crawlspace 48 Pipe Metal Solid White Positive 0.0 12.5 3.2 10.1 2.2 12.5 3.2 mg/cm2

8 12/22/2023 11:39 Tunnel 48 to 49 Steam Pipe Hanger Metal Solid White Positive 0.0 11.3 3.8 10 1.8 11.3 3.8 mg/cm2

9 12/22/2023 11:46 Crawlspace 49 Pipe Metal Solid White Positive 0.0 14.4 4.4 10.1 2.5 14.4 4.4 mg/cm2

10 12/22/2023 11:55 Crawlspace 49 Steam Pipe Hanger Metal Solid White Positive 0.0 6.4 2.8 7.2 1.1 6.4 2.8 mg/cm2

11 12/22/2023 11:56 Crawlspace 49 Steam Pipe Beam Hanger Metal Solid Gray Null 0.0 < LOD 0.03 < LOD 0.03 < LOD 5.39 mg/cm2 Null

12 12/22/2023 11:56 Crawlspace 49 Steam Pipe Hanger Metal Solid Gray Negative 0.0 < LOD 0.03 < LOD 0.03 < LOD 2.7 mg/cm2

13 12/22/2023 12:08 Tunnel 49 to 50 Steam Pipe Hanger Metal Solid Gray Positive 0.0 3.2 0.7 3.2 0.7 < LOD 3.6 mg/cm2

14 12/22/2023 12:18 Crawlspace 50 Steam Pipe Beam Hanger Metal Solid Gray Negative 0.0 < LOD 0.03 < LOD 0.03 < LOD 1.35 mg/cm2

15 12/22/2023 12:22 Crawlspace 50

Electrical Conduit (by ladder) Metal Peeling White Null 0.0 < LOD 0.06 < LOD 0.06 < LOD 2.22 mg/cm2 Null

16 12/22/2023 12:27 Crawlspace 50

Electrical Conduit (by ladder) Metal Peeling White Positive 0.0 0.4 0.1 0.4 0.1 < LOD 2.4 mg/cm2

17 12/22/2023 12:28 Crawlspace 50

Electrical Conduit (by ladder) Metal Peeling White Positive 0.0 0.3 0.08 0.3 0.08 < LOD 1.35 mg/cm2 QC

18 12/22/2023 12:40 Tunnel 50 to 51 Steam Pipe Hanger Metal Solid Gray Positive 0.0 8 3.3 7.6 1.9 8 3.3 mg/cm2

19 12/22/2023 12:44 Tunnel 50 to 51 Steam Pipe Beam Hanger Metal Solid Gray Positive 0.0 0.03 0.02 0.03 0.02 < LOD 1.05 mg/cm2

20 12/22/2023 12:46 Tunnel 50 to 51 Steam Pipe Hanger Metal Solid Gray Positive 0.0 4.6 2.7 5 1 4.6 2.7 mg/cm2

21 12/22/2023 12:47 Tunnel 50 to 51 Steam Pipe Hanger Metal Solid Gray Positive 0.0 5.7 2.6 5.7 2.6 < LOD 9.6 mg/cm2

22 12/22/2023 12:47 Tunnel 50 to 51 Steam Pipe Hanger Metal Solid Gray Positive 0.0 4.5 2.5 5.5 1.1 4.5 2.5 mg/cm2 QC

23 12/22/2023 12:57 Crawlspace 51 Steam Pipe Hanger Metal Solid Gray Positive 0.0 14.5 3.3 10.1 2.3 14.5 3.3 mg/cm2

24 12/22/2023 13:25 Calibration Positive 0.0 1 0.1 1 0.1 0.9 0.2 mg/cm2

LEAD PAINT TESTING RESULTS

WEST MAIN STEAM LINE PROJECT

ST. CLOUD VAHCS

TEST # TIME FLOOR BUILDING COMPONENT SUBSTRATE CONDITION COLOR RESULT

Action

Level PbC PbC Error PbL PbL Error PbK PbK Error Units QC

25 12/22/2023 13:26 Calibration Null 0.0 1 0.1 1 0.1 0.8 0.3 mg/cm2

26 12/22/2023 13:27 Calibration Null 0.0 1 0.1 1 0.1 0.9 0.4 mg/cm2

27 12/22/2023 13:28 Calibration Negative 0.0 < LOD 0.03 < LOD 0.03 < LOD 0.62 mg/cm2

Lead Test LocationX

56 7

File details come from the government source that posted it. Updated .