1728 Orbit Way - Minden, Nevada 89423 P: 775-782-1700 F: 775-782-1701 info@maxtonvalve.com www.maxtonvalve.com
\\DCFS\CATALOG 2022\2022 Catalog Rev 1
ADJUSTMENT PROCEDURE UC4MR B44
THE INFORMATION PRESENTED HEREIN IS FOR USE BY SKILLED HYDRAULIC ELEVATOR PROFESSIONALS
SPECIAL CONSIDERATIONS:
Make all adjustments at minimum pressure (no load on elevator) except where noted. “IN” is ALWAYS (CW) clockwise. “OUT” is ALWAYS (CCW) counterclockwise. THE CONTROL PLATE ADJUSTERS HAVE SEAL NUTS, NOT LOCK NUTS. Adjust nut only to set seal friction (friction will maintain adjustment). When adjustment procedure calls for coils to be disconnected, disconnect them electrically. Do not remove them physically.
Make adjustments with a minimum oil temperature of 80˚ F, not to exceed 100˚ F maximum. Maxton recommends the use of a 5 micron filtration system. With the presence of at least some adverse conditions in most installations, serious consideration should be given to overhaul or replacement of a control valve on a five year cycle.
GAUGE PORTS:
Gauge ports - 1/8” NPT provided at points A, B and S.
A Port: Pump pressure (RELIEF, WORKING PRESSURE).
B Port: Jack pressure (STATIC, DOWN RUNNING).
S Port: Low pressure switch port.
Note: The minimum operating pressure at port B should be at least 175 psi (12 bar) as car is moving down full speed with no load. See flow chart.
OPERATIONAL DATA:
Min. / Max. Pressure:
Max. Rated Flow:
Operating Temperature:
Optimal Temp. Range.
Oil Type:
175-800 psi (3.4-55 bar) 185 gpm (700 l / min.)
80˚-150˚ F (26˚- 65˚ C) 100˚-130˚ F (38˚- 54˚ C) Hyd. ISO VG 32
150 SUS @ 100˚ F (38˚ C)
* SAFETACH2 performance meter validates valve adjustment by providing direct speed and acceleration (g-force) readouts.
Questions: Call Tech Support (775) 782-1700 (7am-4pm PST), use
Maxtonvalve.com or download Maxton Mobile Mechanic from your APP Store
1 BPS Disconnect the US coil, turn UA IN (CW) register an up call and turn BPS IN (CW) until the car just moves. Next, turn the BPS adjuster OUT (CCW) until it stops the movement of the car, then OUT 1/ 2 turn more. Snug lock nut on BPS adjuster and stop pump. NOTE: If car does not move with BPS fully IN (CW), the valve may be oversized for the job (consult factory for proper valve sizing). Reconnect the US coil.
2 UA Register an up call (pump running, U & US coils energized, car should not move), slowly turn UA OUT (CCW) to attain full up speed within 24 to 36 inches. * (Accel 0.04g-0.09g).
3 UL Disconnect the U coil. Turn UL adjuster IN (CW) to stop and register an up call. Leveling speed should be 3 to 5 fpm. (If not, readjust LS*). Turn UL adjuster OUT (CCW) to attain 9 to 12 fpm leveling speed. Reconnect the U coil and lower the car to lowest landing. *(Read leveling speed).
4 UT Register an up call and turn UT IN (CW) so that the car slows to provide 4 to 6 inches of stabilized up leveling. Repeat steps 3 and 4 as necessary. *(Decel 0.04g-0.09g).
5 US With US adjuster fully OUT (CCW), car should stop 1/4" to 3/8" below floor. After a normal up run, turn US IN (CW) as needed to bring car to floor level. The pump must be timed to run ½ second after the car has reached the floor.
6 With empty car at bottom floor, disconnect U & US coils and register a call. The car must not move. If movement occurs, check BPS and US.
LS* Dot on the LS adjuster should be referenced to the line between F / S. When necessary, disconnect the U coil and turn the UL adjuster IN (CW) to stop. Unlock the LS adjuster by loosening the screw next to the symbol 1 turn. Move the LS adjuster slightly toward S for slower or F for faster leveling speeds. Set adjustment from 3 to 5 fpm with the LS adjuster, tighten locking screw down, verify LS speed after tightening screw, then repeat step 3.
* (Level Speed Test 3 to 5 fpm).
7 DSR Register a down call and turn DSR OUT (CCW) until the car reaches approx. 5% above contract speed. NOTE: You may need to turn DT IN (CW) until the car begins down acceleration.
In order to achieve desired speed, D may need to be turn OUT
(CCW).
8 D Register a down call to set your actual contract speed with D adjuster (CW slower). Tighten the lock nut (snug) & send car to upper landing. *(Read high speed).
9 DL Disconnect D coil. Register a down call and set down leveling speed at 6 to 9 fpm with the DL adjuster. Tighten the lock nut (snug tight). Reconnect D coil. * (leveling speed 6 to 9 fpm).
10 DT Register a down call and turn DT IN (CW) so that the car slows to provide 4 to 6 inches of stabilized down leveling. NOTE: A minor re-adjustment of DL may be necessary. Send car to upper landing. * (Decel 0.04g-0.09g).
11 DA Turn DA IN (CW) until desired rate of acceleration is achieved.
Full down speed should be attained within 24 to 36 inches. * (Accel 0.04-0.09g).
ML MANUAL LOWERING: Push ML button to lower car downward at leveling speed when necessary
R RELIEF:
A. Land car in pit and install pressure gauge in A port.
B. Register an up call with a fully loaded car, making note of
Maximum operating pressure.
C. Turn UA and RELIEF adjuster OUT (CCW) to stop.
D. Close the manual shut off valve to the jack.
E. Register an up call, observe pressure gauge and turn
RELIEF IN (CW) to increase pressure. Final setting should be in accordance with local code requirement not to exceed 150% of maximum operating pressure.
F. Tighten the lock nut (snug).
G. Restart to check the pressure relief setting. Seal as required .
H. Open the manual shut off valve to the jack.
I. Readjust UA for proper Up Acceleration.
*(Accel 0.04g-0.09g). DEFAULT SETTINGS If valve is received from Maxton, only minor adjustments may be required.
CONTROL PLATE
US UP STOP OUT (CCW) to stop (faster rate)
UL UP LEVEL IN (CW) to stop (slower rate)
UA UP ACCELERATION IN (CW) to stop (slower rate)
UT UP TRANSITION OUT (CCW) to stop (faster rate)
VALVE BODY
BPS BY-PASS SIZING OUT (CCW) to stop (delays up start)
LS LEVEL SPEED (factory set) DOT ON LINE (set 3-5 fpm)
R RELIEF APPROX 450 psi (CW increases pressure)
DEFAULT SETTINGS
If valve is received from Maxton, only minor adjustments may be required.
CONTROL PLATE
DT DOWN TRANSITION OUT (CCW) to stop (faster rate)
DA DOWN ACCELERATION OUT (CCW) to stop (faster rate)
ML MANUAL LOWERING
VALVE BODY
D DOWN SPEED Turn OUT (CCW) 9 threads above lock nut. (faster speed)
DL DOWN LEVEL Turn OUT (CCW) 2 threads above lock nut. (faster speed)
Push Button
DSR DOWN SPEED REGULATOR Turn IN (CW) 1 thread above jam nut
1728 Orbit Way - Minden, Nevada 89423 P: 775-782-1700 F: 775-782-1701 info@maxtonvalve.com www.maxtonvalve.com
\\DCFS\CATALOG 2022\2022 Catalog Rev 1
DL
D B
A
BPS
R
DSR
PUMP
PRESSURE
“A” PORT
COIL
COVER
SYSTEM
PRESSURE
(JACK)
“B” PORT PUMP
Front View
US D
DL U
SERIAL #
*DOWN STRAINER
*UP STRAINER
SOLENOIDS
(UNDER)
COVER
Top View
* Strainer access is provided from the top of the control plate.
Prior to 2012 the sleeve and baseplate were an integral part of coil operation.
2012 to current the C-Frame is an integral part of coil operation.
ELECTRO-MAGNETIC COILS
U = UP COIL D = DOWN COIL
US = UP STOP COIL DL = DOWN LEVEL COIL
ATTENTION: All Maxton Valves MUST be installed with the solenoids in the upright (vertical) position.
When replacing a Maxton UC3 / UC3AM or UC4 / UC4M series valve, pump flange assembly must also be replaced. It is subject to the same wear and tear as the valve.
COIL OPERATING SEQUENCE
US For up travel, energize when pump starts and de-energize to stop. With US energized and pump running, car will move up at leveling speed. For “soft stop”, pump should run ½ second after US de-energizes.
U Energize with US coil to run up at contract speed. De-energize at slowdown distance from floor. Slowdown distance = 2 inches for each 10 fpm of car speed NOT to exceed 6 inches for every 25 fpm of car speed. If necessary increase slowdown distance to achieve 4-6 inches of stabilized up leveling.
DL Energize to move car at leveling speed. De-energize to stop.
D Energize with DL coil to run down at contract speed. De-energize at slowdown distance from floor. Slowdown distance = 2 inches for each 10 fpm NOT to exceed 6 inches for every 25 fpm of car speed. If necessary increase slowdown distance to achieve 4-6 inches of stabilized down leveling.
CAUTION: On Wye - Delta Up Start do not energize U and US Coils until motor is running on Delta.
With soft starter, energize US coil with motor up to speed signal.
ADJUSTMENT PROCEDURE UC4MR B44
J T
LOW
PRESSURE
SWITCH
“S” PORT
SERIAL #
ML