36C26319R0036-007.pdf
PDF 22 MB Posted
- Solicitation number
- 36C26319R0036
About this file
36C26319R0036 S02_Atch_Drawings_(30 Pages).pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26319R0036-0001003.pdf | ||
| 36C26319R0036-0001000.docx | DOCX document | |
| 36C26319R0036-0001001.pdf | ||
| 36C26319R0036-0001004.pdf | ||
| 36C26319R0036-0001002.pdf | ||
| 36C26319R0036-003.docx | DOCX document | |
| 36C26319R0036-001.docx | DOCX document | |
| 36C26319R0036-005.docx | DOCX document | |
| 36C26319R0036-002.docx | DOCX document | |
| 36C26319R0036-004.docx | DOCX document | |
| 36C26319R0036-006.pdf | ||
| 36C26319R0036-000.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W8x24
W x
W x
W8x24
W8x24
3'-1" 7'-10" 3'-1"
M C x
M C x
1" GALV. BAR GRATE
CHILLER
HSS 12x6x5/16
HSS 12x6x5/16
H S
S x x
6" Ø STD. PIPE
6-PLACES
W8x24
W8x24
W x
W x
W x
W x
W x
W x
W x
W x
6" Ø STD PIPE
4-PLACES
2-L3 x 2 x
DIAG. BRACE
2-L3 x 2 x
DIAG. BRACE
2-L3 x 2 x
DIAG. BRACE,
2-L3 x 2 x
DIAG. BRACE,
W x
W14x30
W14x30
W x
W x
W x
5'-9"7'-4" 7'-4" 7'-4"
3" Ø STD. PIPE
MC12x10.6
MC12x10.6
3" Ø STD. PIPE
W x
RTU
D
5,000#
RTU
16000#
FRAME BEAM OVER
COLUMN W/
" BOLTED
CAP PL, SIM. TO DET. 5/S101
PLAN NOTES:
1. ALL NEW PLATFORM FRAMING MUST BE A MINIMUM OF
3'-0" ABOVE THE TOP OF ROOF, TYP.
GUARDRAIL,
EA. SIDE
2-L3 x2 x
HORIZ. BRACE
GUARDRAIL, BOTH
SIDES OF STAIR
GUARDRAIL,
4-SIDES
2-L3 x 2 x
DIAG. BRACE,
EA. SIDE
CONTRACTOR FIELD VERIFY
LOCATION OF 4-6" Ø PIPE
COLUMNS OVER EXISTING
COLUMNS BELOW.
SEE MECH. EQUIP. DRAWINGS
FOR ATTACHMENT OF
EQUIP. TO SUPPORT BEAMS
CONTRACTOR FIELD VERIFY
LOCATION OF 4-6" Ø PIPE
COLUMNS OVER EXISTING
COLUMNS BELOW.
SEE MECH. EQUIP.
DRAWINGS FOR
ATTACHMENT OF
EQUIP. TO
SUPPORT BEAMS
HSS 3x3x
, W/
CURVED HSS 4x2, TYP.
HSS 4x4x
HANGER
BOLT FRAME TO WALL
BOLT FRAME TO WALL
BOLT FRAME TO WALL
BOLT FRAME TO WALL
BOLT FRAME TO WALL
HSS 12x6
PERFORATED STAINLESS
STEEL PANEL
HSS 3x3x
FACE OF (E) BLDG
" END PL
CURVED
HSS 4x2x
L 4x3x x 4
4'-8"
8'-8"
PERFORATED
STAINLESS
STEEL PANEL
8"
HSS 4x4x
HANGER
HSS 4x4x
HANGER
HSS 3x3x
@ EA. FLOOR TYP.
CURVED HSS 4x2x
L 4x3x x 4
HSS 4x4x
HANGER
PERFORATED
STAINLESS
STEEL PANEL
FACE OF (E) BRICK
PL 1/2x4x11 W/ 2-
" Ø
HAS SUPER THREADED
RODS W/ 11
" EMBED
W/ HIT-HY 70
ADHESIVE BY HILTI
1" NON-SHRINK
GROUT
HSS 3x3x1/4
8"
LOCATE SCREW
WITHIN 2" OF EA.
END OF EA. PANEL
1/4
3 SIDES
(1/4)
1/4
(1/4)
HSS 3x3 TO
HSS 4x4
1/4
3 SIDES
1/4
TYP.
1/4
TYP.
#10 STAINLESS STEEL
SCREWS @ 12" O.C.
CONC.
BEAM
#10 STAINLESS STEEL
SCREWS @ 12" O.C., TYP.
(DO NOT SCREW AT
PERFERATION)
(1/4)
3'-1"
W8
W8
CHILLER
L4x3 1/2x1/4x6"
W/ 2-
" Ø BOLTS
GUARD RAIL
x 4" KICK PL
1" GALV. BAR GRATING
SEE MECH.
FOR BOLTING
REQUIREMENTS
" X-STRG PIPE POSTS
@ 8"-0" MAX. W/ 1
" STD
PIPE HORIZONTALS,
TYP. ALL GUARDRAILS
6" Ø STD PIPE
BASE PL
x12x12 W/ 4-
" Ø
HIT-HY200 ADHESIVE ANCHORS BY
HILTI W/ HIT-Z RODS & 3
" EMBED
" NON-SHRINK
GROUT
PL 5/16x4x"L"
3/4" Ø A325
SCHEDULE
BEAM
DEPTH
LESS THAN
12 or 14
"L"
3"
5 1/2"
8 1/2"
11 1/2"
1'-2 1/2"
1'-5 1/2"
1'-8 1/2"
8 or 10
1/4"
T Y
P
T Y
P
L
MC 12x10.6
" CLOSURE PL
3" Ø STD. PIPE
HSS 8x6x
L3x3x x 1'-0", EA. SIDE
L3x3x x 1-0"
EA. SIDE
4-
" Ø A325 BOLTS
HSS 12x6x
" CAP PL W/
4-
" Ø A325
BOLTS
PL
x 6
W/
4-
" Ø A325 BOLTS
" GUSSET PL
" GUSSET PL
1/4
W8W8
TYP. SHEAR PL
CONN, DET. 6/S101
(3/16) 3"
ROOFING
BASE PL
x 4x9 W/
2-
" Ø HLC SLEEVE ANCHORS
BY HILTI W/ 1
" EMBED
" NON-SHRINK GROUT
" CLOSURE PL
1" BAR GRATING
TYP. SHEAR PL
CONN. 6/S1.1
W8
1 1/2" TYP.
EDGE
DISTANCE
L3 x 2 x
LL/BB
W/ 2-
" Ø A325 BOLTS, EA. END
W.P.
1" BAR GRATING TREADS
GUARDRAIL
2-L3 x2 x
HORIZ. BRACE
2-
" Ø A325 BOLTS
M
I N
T
O
B
O T
O
F
S
T R
U C
T U
R E
A D
J U
S T
A
N G
L E
O
F
B R
A C
E
T
O
M A
I N
T A
I
M
I N
DOWN
UU
BRACING,
NOTE 1, TYP.
BRACING
BRACING
PENDANT BY LIKO
PENDANT BY LIKO
PENDANT BY LIKO
BOLT UNISTRUT
TO CONC. JOIST
BOLT UNISTRUT
TO CONC. JOIST
BOLT UNISTRUT
TO CONC. JOIST
EXIST. CONC. PAN JOISTS, TYP.
BRACING NOTES:
1. EACH PENDANT SHALL BE BRACED IN 2 DIRECTIONS
TO PREVENT LATERAL MOVEMENT, BRACES MAY BE
INSTALLED ON EITHER SIDE OF PENDANT. DIAGONAL
UNISTRUT BRACES (P1000) SHALL BE USED
PERPENDICULAR TO THE PRIMARY RAILS AT EACH
PENDANT.
2. THE PRIMARY RAILS MAY BE USED TO TRANSFER
BRACE FORCES PARALLEL TO THE RAILS. ONE
DIAGONAL UNISTRUT BRACE IS REQUIRED PARALLEL
TO EACH PRIMARY RAIL.
3. BRACES SHALL BE INSTALLED ±15 DEGREES
RELATIVE TO EACH AXIS. SEE LIKO TYPICAL DETAILS.
4. PENDANT SUPPORT DETAILS ARE DESIGNED FOR A
LIFTING CAPACITY OF 1,100#
LIKO RAIL
LIKO RAIL
GENERAL STRUCTURAL NOTES
DESIGN CRITERIA:
DESIGN CODE: 2015 IBC
WIND LOAD:
BASIC WIND SPEED V = 120 MPH
EXPOSURE CATEGORY B
SEISMIC LOAD:
Ss = 0.097 S1 = 0.045
IMPORTANCE FACTOR I = 1.5
SOIL PROFILE TYPE = SD
FLOOR LIVE LOAD:
CATWALKS = 40 PSF
GENERAL PROJECT NOTES
1. ALL DIMENSIONS AND CONDITIONS SHOWN ON THE DRAWINGS SHALL BE VERIFIED BY
THE CONTRACTOR PRIOR TO FABRICATION OR CONSTRUCTION.
2. THE ARCHITECT SHALL BE NOTIFIED IN WRITING OF ANY EXISTING CONDITIONS WHICH
DIFFER FROM THOSE SHOWN ON THE CONTRACT DOCUMENTS.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF THE EXISTING
BUILDING DURING THE EXECUTION OF THE CONTRACT.
4. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN ADEQUATE SHORING AND BRACING
TO PROTECT THE EXISTING STRUCTURE AND UNFINISHED NEW CONSTRUCTION.
SPECIAL INSPECTIONS:
1. PROVIDE SPECIAL INSPECTIONS AS REQUIRED IN ACCORDANCE WITH THE
INTERNATIONAL BUILDING CODE FOR THE FOLLOWING: STRUCTURAL STEEL (IN
ACCORDANCE WITH AISC 360).
2. PROVIDE THE SPECIAL INSPECTOR 48 HOURS PRIOR NOTICE FOR THE SPECIAL
INSPECTIONS.
STRUCTURAL STEEL:
1. STRUCTURAL STEEL SHALL BE DESIGNED, FABRICATED AND ERECTED IN ACCORDANCE
WITH THE AISC "SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF
STRUCTURAL STEEL BUILDINGS" AND THE "CODE OF STANDARD PRACTICE", LATEST
EDITIONS.
2. ALL WIDE FLANGES SHALL BE ASTM A992, GRADE 50, UNLESS NOTED OTHERWISE.
CHANNELS, ANGLES AND PLATE MATERIAL SHALL BE ASTM A36.
3. ALL STRUCTURAL PIPES SHALL BE ASTM A53, GRADE B, FY = 35 KSI.
4. ALL RECTANGULAR HOLLOW STRUCTURAL SECTIONS (HSS) SHALL BE ASTM A500, GRADE
B, FY = 46 KSI.
5. ALL STRUCTURAL STEEL BOLTS SHALL BE 3/4" DIAMETER ASTM A325N IN SNUG TIGHT
CONNECTIONS.
6. ALL WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS IN ACCORDANCE WITH
AWS D.1.1, LATEST EDITION.
7. ALL WELDS SHALL BE MADE WITH E70 ELECTRODES.
8. ALL STEEL SHALL HOT DIP GALVANIZED.
9. STANDARD AISC CONNECTIONS SHALL BE USED UNLESS SHOWN OTHERWISE. NO
CONNECTION SHALL HAVE LESS THAN TWO BOLTS OR AN EQUIVALENT WELD.
10. BRACING MEMBERS SHALL BE FRAMED TO THE CENTERLINE OF THE BEAMS AND
COLUMNS AT THE CONNECTION UNLESS NOTED OTHERWISE.
11. GALVANIZED STEEL SHALL BE SURFACE PREPARED BY CAUSTIC CLEANING, ACID
PICKLING, AND FLUXING, AND SHALL BE HOT DIP GALVANIZED ACCORDING TO ASTM
A123, "STANDARD SPECIFICATION FOR ZINC (HOT DIP GALVANIZED) COATINGS ON IRON
AND STEEL PRODUCTS".
12. ALL STRUCTURAL STEEL SHALL BE HOT DIP GALVANIZED.
13. THE CONTRACTOR SHALL SUBMIT STRUCTURAL STEEL SHOP DRAWINGS TO THE
ARCHITECT.
STEEL STAIRS AND GRATING:
1. STRUCTURAL STEEL SHALL BE DESIGNED, FABRICATED AND ERECTED IN ACCORDANCE
WITH THE AISC "SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF
STRUCTURAL STEEL BUILDINGS" AND THE "CODE OF STANDARD PRACTICE", LATEST
EDITIONS.
2. ALL WIDE FLANGES SHALL BE ASTM A992, GRADE 50, UNLESS NOTED OTHERWISE.
CHANNELS, ANGLES AND PLATE MATERIAL SHALL BE ASTM A36.
3. ALL STAIR STRINGERS SHALL BE MC12X10.6 UNLESS NOTED OTHERWISE.
4. STAIR TREADS SHALL BE 1" BAR GRATING WITH CHECKER PLATE NOSING.
5. PROVIDE SAFETY NOSING AT THE TOP OF ALL STAIRS AND AT OTHER EXPOSED EDGES OF
THE FLOOR.
6. ALL LADDERS AND STAIRS SHALL BE BOLTED TO FRAMING MEMBERS, OR ANCHORED TO
CONCRETE WITH 5/8" DIAMETER EXPANSION ANCHORS EMBEDDED 4" INTO THE
CONCRETE.
7. ALL METAL GRATING AND GRATING TREADS SHALL COMPLY WITH THE SPECIFICATIONS
OF THE NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS.
8. WELDED STEEL GRATING SHALL HAVE 1" X 3/16" BEARING BARS AT 1 3/16" O.C., AND
CROSS BARS AT 4" O.C. UNLESS NOTED OTHERWISE.
9. ALL GRATING BEARING AND CROSS BARS SHALL BE IN LINE.
10. BAND ALL EXPOSED EDGES OF GRATING, EXCEPT AT SUPPORTS WHERE GRATING ABUTS
CONCRETE, STEEL OR ADJACENT GRATING PANEL. BAND EDGES AT ALL BLOCKOUTS. ALL
REMOVABLE GRATING PANELS SHALL BE BANDED.
11. ALL STAIR FRAMING SHALL BE HOT DIP GALVANIZED.
12. THE CONTRACTOR SHALL SUBMIT STRUCTURAL STEEL STAIR AND GRATING SHOP
DRAWINGS TO THE ARCHITECT.
FASTENERS:
1. ALL EXPANSION ANCHORS SHALL BE THE SIZE AND EMBEDMENT AS SHOWN ON THE
DRAWINGS. WHEN EMBEDMENT IS NOT SHOWN ON THE DRAWINGS, THE EMBEDMENT
SHALL BE THE STANDARD EMBEDMENT AS RECOMMENDED BY THE MANUFACTURER.
2. THE PLACEMENT OF EXPANSION BOLTS IN MASONRY HEAD JOINTS OR 'T' JOINTS SHALL BE
AVOIDED IF POSSIBLE.
3. APPROVED EXPANSION ANCHORS SHALL BE:
a. KWIK BOLT 3 EXPANSION ANCHOR BY HILTI,
b. TRUBOLT WEDGE ANCHOR BY ITW RAMSET / REDHEAD,
c. OR AN APPROVED EQUAL.
4. ALL ADHESIVE ANCHORS SHALL BE THE SIZE AND EMBEDMENT AS SHOWN ON THE
DRAWINGS. WHEN EMBEDMENT IS NOT SHOWN ON THE DRAWINGS, THE EMBEDMENT
SHALL BE THE STANDARD EMBEDMENT AS RECOMMENDED BY THE MANUFACTURER.
5. APPROVED ADHESIVE ANCHORS SHALL BE:
a. HY-200 INJECTION ADHESIVE ANCHOR INTO SOLID CONCRETE OR SOLID MASONRY
BLOCK, BY HILTI,
b. HY-70 INJECTION ADHESIVE ANCHOR WITH SCREEN TUBE INTO HOLLOW MASONRY
BLOCK OR SOLID BRICK WITH VOIDS, BY HILTI,
c. OR AN APPROVED EQUAL.
HSS 12x6
L5x3x x8
L4x4x x8
3-
" Ø A325 BOLTS
HSS 4x4x
HANGER
6" Ø STD. PIPE
BASE PL
x12x12
W/ 4-
" Ø HIT-HY 200
ADHESIVE ANCHORS BY HILTI
W/ HIT-Z RODS & 3
" EMBED
" NON-SHRINK
GROUT
" CAP PL W/
4-
" Ø A325
BOLTS
PL
" W/
4-
" Ø A325 BOLTS
" GUSSET PL
" GUSSET PL
L3 x 2 x
LL/BB
W/ 2-
" Ø A325 BOLTS,
EA. END
1/4
3'-0"
3"
1 1/2" TYP.
EDGE DISTANCE
W14
" STIFF PL,
EA. SIDE
" END PL
M
I N
B
T
O
F
N
W
R
U C
T U
R E
HSS 4x4
HANGER
6" Ø STD PIPE
" NON-SHRINK
GROUT
HSS 12x6
W8
W8
" GUSSET,
EA. END
2-L3 x2 x
LL/BB W/
2-
" Ø A325 BOLT, EA. END
2-L3 x2 x
LL/BB
L3 x3 x
STIFF.
HSS 12x6x
PL
x12x12 W/
3-
" Ø A325 BOLTS,
EA. SIDE
W14
HSS 12x6
W14
L3 x3
PL
" Ø HILTI KWIK BOLT
TZ EXPANSION ANCHOR
(CARBON STEEL)
W/ 2
" EMBEDMENT
(E) CONC. JOISTS
P1000 BRACE
P1546 BY UNISTRUT
EA. END, TYP.
" Ø BOLT
" Ø BOLT
LIKO PENDANT
M
I N
M A
X
P1000 BRACE
LIKO RAIL
" Ø HILTI KWIK BOLT
TZ EXPANSION ANCHOR
(CARBON STEEL)
W/ 2
" EMBEDMENT
IN SIDE OF JOIST
P1000 H3, 8" LONG
(E) CONC. JOIST
M
I N
P1001
LIKO PENDANT
SIDE OF JOIST
P1000 H3 BOLTED
TO JOIST
" Ø BOLT
P1000 DIAGONAL BRACE
M A
X
LIKO RAIL
3 SIDES
1/4
3 SIDES
1/4
A D
J U
G
L
F
B R
A C
E
A
S
R
E Q
D
M
I N
T A
I
M
I N
BASE PL
x12x12
W/ 4-
" Ø HIT-HY 200
ADHESIVE ANCHORS BY HILTI
W/ HIT-Z RODS & 3
" EMBED
P1325 BY UNISTRUT
W/ 2-
" Ø BOLTS W/
P1010 NUT, EA. LEG, TYP.
LIKO
PENDANT
P1000 (12 GA.) BY UNISTRUT W/
" Ø HILTI KWIK BOLT TZ EXPANSION ANCHOR
(CARBON STEEL) W/ 3
" EMBEDMENT, TYP.
M
I N
P1001 (12 GA.)
BY UNISTRUT
SHIM BTWN
ANGLE &
UNISTRUT
AS REQ'D
EXISTING
CONCRETE
JOISTS
| 201514G0 |
| 201514AD101 |
| 201514AD102 |
| 201514A101 |
| 201514A102 |
| 201514A103 |
| 201514A201 |
| 201514A301 |
| 201514A501 |
| 201514VL101 |
| 15052-100%.pdf |
| Sheets and Views |
| 15052-PLAN-S101 |
| 15052-PLAN-S102 |
| 15052-100%.pdf |
| Sheets and Views |
| 15052-PLAN-S101 |
| 15052-PLAN-S102 |