36C26318B0004-A00002001.pdf
PDF 143 KB Posted
- Attached to
- PN: 636-16-882, Upgrade Physical Security Deficiencies (GI) Federal contract opportunity
- Solicitation number
- 36C26318B0004
About this file
36C26318B0004 A00002 Addendum No. 1.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26318B0004-A00002000.docx | DOCX document | |
| 36C26318B0004-A00001001.docx | DOCX document | |
| 36C26318B0004-A00001005.pdf | ||
| 36C26318B0004-A00001004.pdf | ||
| 36C26318B0004-A00001002.pdf | ||
| 36C26318B0004-A00001000.docx | DOCX document | |
| 36C26318B0004-A00001003.pdf | ||
| 36C26318B0004-004.pdf | ||
| 36C26318B0004-002.pdf | ||
| 36C26318B0004-003.pdf | ||
| 36C26318B0004-001.docx | DOCX document | |
| 36C26318B0004-005.pdf | ||
| 36C26318B0004-000.docx | DOCX document |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum 1 .
ADDENDUM NUMBER ONE
Veterans Affairs Medical Center Correct Physical Security Deficiencies Grand Island VA Medical Center, Holdrege CBOC, North Platte CBOC, and O'Neill CBOC Project Number 636-16-203
2201 Broadwell Avenue Grand Island, Nebraska
CLH Project #: 2017-01
DATE OF ISSUE: January 17, 2018
NOTICE
THIS ADDENDUM IS ISSUED BY THE ARCHITECT TO ALL KNOWN
INDIVIDUALS, FIRMS OR CORPORATIONS WHO HAVE OBTAINED OR
RECEIVED DOCUMENTS FOR THE ABOVE LISTED PROJECT. THIS
ADDENDUM SHALL BECOME PART OF THE CONTRACT DOCUMENTS AS
A REVISION TO THE ORIGINAL DOCUMENTS.
CHANGES TO SPECIFICATIONS
None.
CHANGES TO DRAWINGS
1. Sheet M-301 Mechanical Details and Schedules
a. Delete the Split System Schedule on this sheet and replace with the attached Split System Schedule.
b. Add the attached Mechanical and Electrical Coordination schedule to this sheet.
THIS ADDENDUM IS HEREBY MADE A PORTION OF THE CONTRACT
DOCUMENTS. GENERAL CONTRACTOR IS REQUIRED TO
ACKNOWLEDGE RECEIPT OF THIS ADDENDUM.
By: __________________________________ Calvin L. Hinz, Principal
Attachments:
Sketch M-301.1.
OUTDOOR CLG (MBH) INDOOR UNIT OUTDOOR UNIT
UNIT MARK TOTAL CAPACITY BACKUP KW MODEL NO. MODEL NO.
CU-1 530 18.7 23.7 N/A LENNOX MWMA018 MLA018 1, 2, 3, 4, 5, 6
1.
2.
3. PROVIDE INTEGRAL CONDENSATE PUMP, MOUNTING BRACKET, AND OUTDOOR MOUNTING BRACKET AND INSULATED LINE SETS.
4.
5. UNIT SHALL BE MINIMUM 13.0 SEER.
6. PROVIDE THERMOSTAT AND A SENSOR IN THE SPACE TO CONNECT TO EXISTING BAS.
UNIT SHALL BE ABLE TO COOL WITH AMBIENT TEMPERATURES AS HIGH AS 100 DEG F AND AS LOW AS -20 DEG F.
SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.
REMARKS:
REFRIGERANT SHALL BE R-410A.
SS-1
SPLIT SYSTEM UNIT SCHEDULE
MANUFACTURER REMARKS
INDOOR
UNIT MARK
CFM
HEATING DATA
E HP 4X V
M KW PH VFD
I MR RE
C RV 2S
NF SF 3S
CB NR SS
FV N1 SH
FLA 3R STE
NAMEPLATE
CU-1 /
SS-1
OUTDOOR DUCTLESS
SPLIT UNIT
18 MCA 208 1 E/E SS 30 MR N1 - - - -
A.
B.
C.
D.
E.
F.
1.
2.
3.
4.
VARIABLE FREQUENCY
DRIVE
PHASE
REVERSING
NON-FUSED
NON-REVERSING
REDUCED VOLTAGE
THREE SPEED
PER MANUFACTURER'S
RECOMMENDATION
HORSEPOWER
KILOWATTSMECHANICAL CONTRACTOR
INTEGRAL WITH EQUIPMENT
CIRCUIT BREAKER
FULL VOLTAGE
COMBINATION STARTER AND
SAFETY SWITCH
FULL LOAD AMPS
LOAD
REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
DISCONNECT
MARK DESCRIPTION REMARKS
ENCL.
MOTOR STARTER
V
ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT AND STARTER INTEGRAL WITH MOTOR CONTROL CENTER.
PROVIDE LOCKABLE DISCONNECT INTEGRAL WITH VFD.
TYPE
RATING
(AMPS)
INDUSTRIAL CONTROL PANELS AS DEFINED BY NEC ARTICLE 409, MOTOR CONTROLLERS, HERMETIC REFRIGERANT MOTOR COMPRESSORS AND EQUIPMENT
SHALL BE MARKED WITH INFORMATION AS REQUIRED BY THE NATIONAL ELECTRICAL CODE (NEC). MARK IN ACCORDANCE WITH NEC ARTICLE 409.110 FOR
INDUSTRIAL CONTROL PANELS, NEC ARTICLE 430.8 FOR CONTROLLERS AND NEC ARTICLE 440.4(B) FOR HERMETIC REFRIGERANT MOTOR COMPRESSORS AND
EQUIPMENT. THE MARKED SHORT CIRCUIT CURRENT RATING (SCCR) SHALL BE NO LESS THAN THE VALUE INDICATED ABOVE.
PH
RATING
VERIFY/COORDINATE ALL RATINGS FOR EQUIPMENT. WHERE SUCH RATINGS ARE OTHER THAN THAT INDICATED ON MECHANICAL/ELECTRICAL COORDINATION
SCHEDULE, PROVIDE DISCONNECTS, MOTOR STARTERS, OVERCURRENT DEVICES AND RELATED REVISIONS ACCORDINGLY. WHERE EQUIPMENT IS PROVIDED
WITH RATINGS OTHER THAN THAT INDICATED, CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION AND ASSOCIATED COSTS FOR REVISIONS.
EQUIPMENT LISTED IN SCHEDULE MAY APPEAR IN NUMEROUS LOCATIONS. EQUIPMENT MARKS ARE DESIGNATED BY UNIQUE IDENTIFIERS ON THE PLANS; I.E., HP-
1.1, HP-1.2. IN THESE INSTANCES, THE ELECTRICAL REQUIREMENTS DO NOT CHANGE FROM ONE MARK TO THE NEXT, ONLY THE UNIQUE IDENTIFIER CHANGES.
HORSEPOWER RATED SWITCHES (SH): FOR 120 V MOTORS LESS THAN 1/2 HP, PROVIDE FUSEHOLDER WITH SWITCH, FUSED PER MANUFACTURER'S
RECOMMENDATION AND NEC REQUIREMENTS. FOR 120 V MOTORS RATED 1/2 HP OR 3/4 HP, PROVIDE HP RATED TOGGLE SWITCH (WHERE BRANCH CIRCUIT
OVERCURRENT DEVICE MEETS NEC REQUIREMENTS FOR SHORT-CIRCUIT PROTECTION) OR FUSED SAFETY SWITCH.
GENERAL NOTES:
REMARKS:
PROVIDE FRACTIONAL HORSEPOWER MOTORS WITH INTEGRAL OVERLOAD PROTECTION.
FOR MOTORS CONTROLLED BY VARIABLE FREQUENCY DRIVES, PROVIDE FACTORY INSTALLED SHAFT GROUNDING THAT REQUIRES NO MAINTENANCE FOR THE
SERVICE LIFE OF THE MOTOR.
MECHANICAL / ELECTRICAL COORDINATION SCHEDULE
VOLTAGE
TWO SPEED
NEMA 4X
ABBREVIATION:
ELECTRICAL CONTRACTOR
FUSE HOLDER WITH SWITCH
SAFETY SWITCH
HP RATED SWITCHNEMA 1
NEMA 3R
FURNISH/
INSTALL
BY
MINIMUM
SCCR
(AMPS)
ENCL.
FUSE
SIZE
TYPE/
NEMA
SIZE
FURNISH/
INSTALL
BY
THERMAL ELEM. SWITCH
VFD PROVIDED BY MECHANICAL.
PROVIDE EXHAUST FAN MOTOR FACTORY-WIRED TO WEATHERPROOF JUNCTION BOX INTEGRAL WITH FAN. ELECTRICAL CONTRACTOR TO PROVIDE
WEATHERPROOF HORSEPOWER RATED SWITCH (SEE GENERAL NOTES ABOVE).