Site Visit Questions and Answers.docx

DOCX document 19 KB Posted

Attached to
H263--ANTI-LIGATURE DOOR ALARM INSTALLATION SERVICES
Solicitation number
36C26227Q0084
Issued by

About this file

This file is a Site Visit Questions and Answers document for solicitation 36C26227Q0084, addressing vendor inquiries regarding anti-ligature door alarm installation services at the San Diego VA Medical Center. The document clarifies that the project requires installation of a complete anti-ligature alarm system in all rooms, including switches, dome lights, and controllers. Subcontractors may be utilized if they meet the requirements outlined in the scope of work. Regarding existing equipment, no existing alarm or nurse-call equipment requires retention; however, any materials originating from the interstitial spaces or ceiling must be disposed of according to asbestos disposal regulations, while other waste may be disposed of in the facility's dumpsters.

View the file

Other files

File Type Posted
Corrected - 36C26227Q0084 0004.pdf PDF
36C26227Q0084 0004.pdf PDF
RFQ Amendment 0004.docx DOCX document
36C26227Q0084 0003.pdf PDF
36C26227Q0084 0002.pdf PDF
Site Visit - 2South Apod Anti-Ligature System.pdf PDF
36C26227Q0084 0001.pdf PDF
Vendor Questions - Anti-Ligature .pdf PDF
36C26227Q0084_2.docx DOCX document
P09 - FINAL SOW - Door Alarm.doc DOC document
W-9 Form.pdf PDF
FMS Vendor File Update Request Form.pdf PDF
VA10091.pdf PDF
S02 - 36C26227Q0084_1 - Door Alarm.pdf PDF
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Site Visit Vendor Questions 36C26227Q0084

ANTI-LIGATURE DOOR ALARM INSTALLATION SERVICE

Is this installation of a full anti-ligature alarm system (including switches, dome lights, controllers)?

Yes, all rooms will need a new anti-ligature alarm system which includes switches, dome lights, controllers, etc.

There was conversation about the use of subcontractors, not a question but we did tell the vendor that subcontractors could be used if they met requirements outlined in the scope of work.

Update to original (Amendment 0001) question #36

36. What existing alarm, nurse-call wiring or equipment must be removed or retained? Identify disposal and sensitive-data procedures and whether temporary coverage is required.

No existing equipment. If anything comes from the interstitial or ceiling then the waste has to be disposed of by asbestos disposal rules. Anything other waste can be disposed of in our dumpsters.