Uninterruptible Power Supply Semi-Annual Maintenance SAVAHCS
Solicitation number
36C26226Q1401
Issued by

About this file

This document is a technical status report detailing operational parameters and battery performance data for six uninterruptible power supply (UPS) systems across two federal buildings.

The report covers six UPS installations: BLDG 38 RM A17 (Eaton 9355-30, 208V/3/100A), BLDG 38 RM A186 (Eaton 9355-15, 480V/3/24A), BLDG 57 RM 290 (Eaton 93PM-150-3, 480V/3/218A), BLDG 57 RM A106 (APC Symmetra PX 100KVA/100KW, 208V/3/332A), BLDG 57 RM B106 (APC Symmetra PX 100KVA/100KW, 208V/3/332A), and BLDG 57 RM A192 (Eaton 9355-30, 208V/3/100A). Each section provides comprehensive electrical performance data including input/output voltage and amperage by phase, bypass specifications, current load percentages (ranging from 0-24%), and battery status. Battery runtime varies significantly across systems, from 37 minutes for BLDG 38 RM A17 to 466 minutes for BLDG 57 RM A192, with all systems showing 100% charge status at time of reporting. Additional battery string data documents individual cell voltages for external and internal battery packs, with readings from November 2022 through February 2025, indicating ongoing monitoring and maintenance of critical backup power infrastructure across the two facilities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BLDG 38 RM A17 – Eaton 9355-30, 208V/3/100A/208V, S/N BG213KXX01

Building 38 RM A17

EATON POWERWARE 9355-30

INPUT

Phase L-L Volts L-N Volts Amps

A 198 114 61.8

B 198 115 61.9

C 199 116 62.1

BYPASS

Phase L-L Volts L-N Volts Amps

A 199 115 0

B 200 115 0

C 199 115 0

OUTPUT

Phase L-L Volts L-N Volts Amps

A 208 120 59.7

B 208 120 51.6

C 208 120 52.7

N

LOAD

Phase KW KVA %

A 6.9 7.2 24.0

B 6.1 6.1 20.3

C 6.1 6.3 21.0

BATTERY

Voltage Charge Runtime

231V(Rest) 100% 37min

Battery Information Bldg 38 RM A17

External String 1 Hitachi CSB HR 12120W

FR DC: 11-2022

JAR DC VOLTS JAR DC VOLTS

1 12.84 10 12.81

2 12.90 11 12.78

3 12.77 12 12.92

4 12.87 13 12.94

5 12.88 14 12.86

6 12.85 15 12.78

7 12.82 16 12.79

8 12.80 17 12.80

9 12.75 18 12.88

External String 2 Hitachi CSB HR 12120W

FR DC: 11-2022

JAR DC VOLTS JAR DC VOLTS

1 12.87 10 12.81

2 12.85 11 12.89

3 12.90 12 12.83

4 12.86 13 12.82

5 12.88 14 12.79

6 12.89 15 12.79

7 12.82 16 12.89

8 12.87 17 12.85

9 12.86 18 12.86

Internal Battery Packs

HITACHI CSB

HRL1234WF2FR DC: 11-2022

PACK DC VOLTS PACK DC VOLTS

1 231.24 4 231.24

2 231.24 5 231.24

3 231.24 6 231.24

BLDG 38 RM A186 – EATON 9355-15,

480V/3/24A/208V, S/N BG246JBA03

Building 38 RM A186

INPUT

Phase L-L Volts L-N Volts Amps

A 214 123 5.0

B 214 124 0.0

C 214 124 5.0

BYPASS

Phase L-L Volts L-N Volts Amps

A 215 125 0

B 216 124 0

C 216 125 0

OUTPUT

Phase L-L Volts L-N Volts Amps

A 210 122 5.2

B 209 121 0.0

C 210 121 5.9

N

LOAD

Phase KW KVA %

A 0.0 0.0 0

B 0.0 0.0 0

C 0.0 0.0 0

BATTERY

204v(Rest) 100% 333min

Bldg 38 RM A186

String 1

CSB HRL123WF2FR DC: 11-2022

JAR DC VOLTS JAR DC VOLTS

1 12.89 9 12.91

2 12.92 10 12.91

3 12.83 11 12.90

4 12.90 12 12.90

5 12.92 13 12.90

6 12.89 14 12.93

7 12.90 15 12.91

8 12.68 16 12.95

Bldg 38 RM A186

String 2

CSB HRL123WF2FR DC: 11-2022

JAR DC VOLTS JAR DC VOLTS

1 12.94 9 12.89

2 12.93 10 12.87

3 12.66 11 12.91

4 12.88 12 12.89

5 12.90 13 12.90

6 12.88 14 12.92

7 12.81 15 12.92

8 12.87 16 12.96

BLDG 57 RM 290 – EATON 93PM-150-3,

480V/3/218A/480V

S/N EN123UXX07

Building 57 RM 290

EATON POWERWARE 93 PM-150

INPUT

Phase L-L Volts L-N Volts Amps

A 477.6 277.0 17.6

B 480.5 276.5 16.3

C 481.4 278.4 17.2

BYPASS

Phase L-L Volts L-N Volts Amps

A 479.2 278.1 0

B 480.2 277.1 0

C 481.9 277.9 0

OUTPUT

Phase L-L Volts L-N Volts Amps

A 480.2 277.1 7.8

B 480.0 277.1 9.3

C 479.8 277.1 8.5

N

LOAD

Phase KW KVA %

A 1.2 2.2 0.0

B 1.7 2.5 0.0

C 1.6 2.3 0.0

BATTERY

514v(Rest) 100% 315.9Min

Bldg 57 RM 290

String 1

Enersys 12HX300-FR DC: 1-2023

514.5vdc .00vac 0.0a 66°F

JAR DC VOLTS JAR DC VOLTS

1 12.88 21 12.84

2 12.87 22 12.91

3 12.91 23 12.88

4 12.86 24 12.83

5 12.84 25 12.85

6 12.85 26 12.82

7 12.86 27 12.86

8 12.87 28 12.88

9 12.86 29 12.91

10 12.70 30 12.85

11 12.88 31 12.92

12 12.84 32 12.89

13 12.88 33 12.88

14 12.85 34 12.87

15 12.81 35 12.85

16 12.86 36 12.88

17 12.88 37 12.84

18 12.87 38 12.87

19 12.81 39 12.89

20 12.84 40 12.87

BLDG 57 RM A106 – APC SYMMETRA PX 100KVA/100KW,

208V/3/332A/208V, S/N QD1940140177

Building 57 RM A106

Symmetra 30 kV

INPUT

Phase L-L Volts L-N Volts Amps

A 205.9 117.9 34

B 207.9 119.0 35

C 207.3 119.2 34

BYPASS

Phase L-L Volts L-N Volts Amps

A 206.0 118.4 0

B 207.2 119.2 0

C 206.4 119.1 0

OUTPUT

Phase L-L Volts L-N Volts Amps

A 208.0 120.9 35

B 208.8 121.1 26

C 208.1 121.1 35

N --

LOAD

Phase KW KVA %

A 4.2 4.3 13.0

B 2.8 3.2 10.8

C 4.0 4.3 13.0

BATTERY

217.0 100% 1H35Min

BLDG 57 RM B106 – APC SYMMETRA PX 100KVA/100KW,

208V/3/332A/208V, S/N QD1946140506

Building 57 RM B106

Symmetra 40 kVA

INPUT

Phase L-L Volts L-N Volts Amps

A 205.9 118.3 34

B 207.4 119.1 34

C 206.3 118.9 34

BYPASS

Phase L-L Volts L-N Volts Amps

A 205.5 118.2 0

B 206.9 118.9 0

C 205.8 119.0 0

OUTPUT

Phase L-L Volts L-N Volts Amps

A 208.4 120.8 22

B 208.5 121.1 35

C 207.3 121.0 43

N --

LOAD

Phase KW KVA %

A 2.4 2.6 8.2

B 3.6 4.1 10.1

C 5.0 5.1 12.2

BATTERY

215.3 100% 1H32Min

BLDG 57 RM A192 – EATON 9355-30,

208V/3/100A/208V, S/N BG213KXX02

Building 57 RM A192

INPUT

Phase L-L Volts L-N Volts Amps

A 211 122 15.4

B 211 121 13.6

C 210 121 13.6

BYPASS

Phase L-L Volts L-N Volts Amps

A 209 120 0

B 208 121 0

C 207 119 0

OUTPUT

Phase L-L Volts L-N Volts Amps

A 208 120 5.8

B 210 120 8.7

C 208 120 6.8

N

LOAD

Phase KW KVA %

A 0.7 0.8 2.3

B 1.0 1.0 3.3

C 0.0 0.0 0.0

BATTERY

232v(Rest) 100% 466min

Bldg 57 RM A192

External String 1A

DATASAFE 12HX100R-

FR DC: 02-25

JAR DC VOLTS JAR DC VOLTS

1 12.94 10 12.93

2 12.98 11 12.99

3 12.99 12 12.99

4 12.97 13 12.96

5 12.92 14 12.98

6 12.98 15 12.97

7 12.89 16 12.97

8 12.98 17 12.99

9 12.99 18 12.99

Bldg 57 Rm A192

External String 1B

DATASAFE 12HX100R-

FR DC: 02-25

JAR DC VOLTS JAR DC VOLTS

1 12.99 10 12.87

2 12.96 11 12.99

3 12.99 12 12.98

4 12.99 13 12.99

5 12.98 14 12.99

6 12.99 15 12.99

7 12.99 16 12.87

8 12.99 17 12.70

9 12.84 18 12.99

Bldg 57 Rm A192

Internal Battery Packs

CSB 1234WF2FR DC: 12-24

PACK DC VOLTS PACK DC VOLTS

1 233.61 4 233.61

2 233.47 5 233.61

3 233.61 6 233.61

File details come from the government source that posted it. Updated .