VA Prescott PV System.pdf
PDF 4 MB Posted
- Solicitation number
- 36C26225Q0005
About this file
This file contains detailed electrical engineering drawings and specifications for a solar photovoltaic (PV) system installation at the Prescott Health Care Center VA facility located at 500 N US Highway 89, Prescott, AZ 86313. The drawings were prepared by REC Solar, Inc. in coordination with GLHN Architects and Engineers.
The technical drawings include single-line diagrams for three inverters, electrical site plans showing PV array layouts, metering/combiner sections, grounding details, conduit schedules, and comprehensive signage requirements. Key specifications include monitoring of circuit breaker trip status, providing visual open and lockable disconnect switches accessible from ground level, coordination with local utility requirements, and detailed conduit/wiring schedules listing conductor sizes, types, and voltage drop calculations. The system utilizes REC 240 PE (BLK) solar modules arranged in multiple strings of 14 modules each, connected through combiner boxes to three main inverters. The drawings provide comprehensive details for electrical contractors to properly install and interconnect the PV system components while meeting all relevant codes and safety requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26225Q0005 0002.docx | DOCX document | |
| 36C26225Q0005 0001.docx | DOCX document | |
| 36C26225Q0005.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
REC SOLAR, INC. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE
WRITTEN PERMISSION OF REC SOLAR, INC IS PROHIBITED, 2011.
REC SOLAR, INC.
ROCAZ LIC. #252827
775 FIERO LANE, SUITE 200
SAN LUIS OBISPO, CA 93401
USA
PHONE (805) 528-9705
FAX (805) 528-9701
(888) OK SOLAR
DATEREV #
DATE
ENGINEERING MANAGER
SHEET
PROJECT ENGINEER
PV SYSTEM DESIGNER PROJECT MANAGER
DRAFTER
DWG TITLE
APPROVED: PROJECT
DIRECTOR
VA PROJECT NUMBER
Office of Construction and
Facilities Management
E D C B A
DESCRIPTION
PRESCOTT HEALTH CARE CENTER
SOLAR PHOTOVOLTAIC (PV) SYSTEM
CONTRACTING OFFICER (CO) - JOHN YALLECH
CONTRACT SPECIALIST (CS) - SHON JOHNSON
CONTRACTING OFFICER'S TECHNICAL
REPRESENTATIVE (COTR) - JAMES LARSON
06/19/12
PVE-1.1
E D C B A
50% SUBMITTAL 9/9/11
100% SUBMITTAL
FINAL SUBMITTAL
REC SOLAR STRUCTURAL COMMENTS 11/17/11
REC SOLAR ARRAY SHIFT FOR GUY WIRE 12/5/11
12/8/11 6/4/12
SINGLE LINE DIAGRAM
INVERTER 1
POWER
ELECTRONICS
SECTION
AC
INTERFACE
SECTION
DC
INTERFACE
SECTION
AC CONTACTOR
EMI FILTER
AC DISCONNECT
DC CONTACTOR
NEG GROUND
TERMINALS
POS GROUND
TERMINALS
"AC1"
PHOTOVOLTAIC SYSTEM
UTILITY AC DISCONNECT
SWITCH SQUARE D
H367NR 3 POLE 800A,
600V, NEMA 3R WITH (3)
600V CLASS L FUSES:
800A
"INV1"
ADVANCED ENERGY
SOLARON 500kW
480V 3-PHASE INVERTER
UL LISTED ASSEMBLY
GROUND
1.6
1.8
INVERTER 1
TRANSFORMER, 1500kVA
1.7
GROUND
GROUND
GROUND
GROUND
"ARC1"
AMTEC EQUINOX 2000 NEMA 4
36"x36"x10"(FS) WITH (8) 600V
CLASS R FUSES: (7) 175A, (1)
110A, 75°F RATED INPUT LUGS
90°F RATED OUTPUT LUGS
"ARC2"
AMTEC EQUINOX 2000 NEMA 4
36"x36"x10"(FS) WITH (8) 600V
CLASS R FUSES: (7) 175A, (1)
110A, 75°F RATED INPUT LUGS
90°F RATED OUTPUT LUGS
1.4B
1.5A 175A 175A 110A 175A
POSITIVELY GROUNDED
(POS POL)
1.5A
"DC1"
PHOTOVOLTAIC ARRAY
DC DISCONNECT SWITCH,
SQUARE D H268R 2P, 1200A,
600V, NEMA 3R WITH (2) 600V
CLASS L FUSES: 1200A
175A 175A
175A 175A
175A 175A 175A 175A
(A39.C12)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A40.C14)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A36.C9)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (8) 600V FUSES: 15A
(A37.C10)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
"DC2"
PHOTOVOLTAIC ARRAY
DC DISCONNECT SWITCH,
SQUARE D H268R 2P, 1200A,
600V, NEMA 3R WITH (2) 600V
CLASS L FUSES: 1200A
"PVT1"
AE SOLARON
REMOTE
PV TIE
1.4B
1.4A
1.4A
GROUND
GROUND
GROUND
GROUND
(A38.C11)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A39.C13)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A40.C15)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A41.C16)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
1.2B 1.1
1.1
1.1
1.1
1.2B 1.1
1.1
1.1
1.1
(A39)
(140) REC 240 PE (BLK) MODULES
IN (10) STRINGS OF 14 MODULES EACH
(A40)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A37)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A38)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A39)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A40)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A41)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
1.2B
1.2B
1.2B
1.2C
1.2B
1.2B
175A 175A
110A 175A
GROUND
GROUND
GROUND
GROUND
(A31.C1)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A33.C2)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A34.C3)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A35.C4)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (8) 600V FUSES: 15A
GROUND
GROUND
GROUND
GROUND
(A36.C5)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A37.C6)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A38.C8)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A37.C7)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED,
NEMA 4X
WITH (12) 600V
FUSES: 15A
1.2B 1.1
1.1
1.1
1.1 1.2B 1.1
1.1
1.1
1.1
(A31)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A33)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A35)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A36)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A37)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A38)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A34)
(28) REC 240 PE (BLK) MODULES
IN (2) STRINGS OF 14 MODULES EACH
1.2B
1.2B
1.2B 1.2C
1.2A
1.2B
NEGATIVELY GROUNDED
(NEG POL)
(A36)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A34)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
GROUND
1.1 (A32)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB1
GROUND
1.1 (A34)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB2
GROUND
1.1 (A36)
(28) REC 240 PE (BLK) MODULES
IN (2) STRINGS OF 14 MODULES EACH
PB4
GROUND
(A37)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
GROUND
(A36)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
1.1
PB5
1.1
PB3
GROUND
(A41)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
1.1
PB7
GROUND
(A38)
(28) REC 240 PE (BLK) MODULES
IN (2) STRINGS OF 14 MODULES EACH
1.1
PB6
GROUND
(A42)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
1.1
PB8
PB-L
PB-B
PB-C
PB-A
1.3A
1.3C
1.3D
1.3B
1.5B
1.3B
INVERTER 2
INVERTER 3
SEE ELECTRICAL
SHEETS E1 THRU E5
MONITORING, SEE SHEET PVE-3.1
ELECTRICAL ENGINEER
GLHN ARCHITECTS AND
ENGINEERS, INC.
2939 EAST BROADWAY BLVD.
TUCSON, AZ 85716
CONTACT: DENISE PAPE, PE
(820) 881-4546
DC CONDUIT SCHEDULE - INVERTER 1
DC SYSTEM ADJUSTMENT FACTORS CONDUCTORS CONDUITS FUSES VOLTAGE DROP
ITEM CONDUCTOR RUN SUMMARY # STRINGS PER
CONDUCTOR
# CURRENT
CARRYING
CONDUCTORS
# OF CONDUITS
MAX POWER LOAD
[A]
SHORT CIRCUIT
LOAD [A] DUTY Tamb RACEWAY FILL
MIN. CALCULATED
CONDUCTOR
AMPACITY [A]
CONDUCTOR AMPACITY
VALUE NEC 310.16 WIRE TYPE MAIN CONDUCTOR
SIZE
MAIN CONDUCTOR
MATERIAL
WIRE AMPACITY
310.16 NEUTRAL SIZE EGC SIZE TYPE SIZE (IN)
PROTECTION
(FUSES OR
BREAKERS)
CONDUIT RUN
DISTANCE [FT] 0.00%
75°C 90°C
1.1 STRING TO FUSED DC
COMBINER BOX
2" PVC CONDUIT: MAX (20) 10 AWG PV RHW/USE-2
CONDUCTORS + (1) 8 AWG BARE CU GROUND 1 20 AS NEEDED 7.9 8.4 0.64 0.76 0.5 34.5 35 40 PV RHW/USE-2 10 Cu 40 -- 8 PVC 2" 15 125 0.60%
1.2A FUSED COMBINER BOX TO
FUSED ARRAY COMBINER
(1) 1-1/2" PVC CONDUIT: (2) 4/0 AWG THHN/THWN-2
CONDUCTORS + (1) 6 AWG THHN/THWN-2 GROUND 12 2 1 94.8 100.8 0.64 0.91 1 173.1 230 260 THHN/THWN-2 4/0 Cu 260 -- 6 PVC 1-1/2" 175 125 0.35%
1.2B FUSED COMBINER BOX TO
UNDERGROUND PULL BOX
(1) 1-1/2" PVC CONDUIT: (2) 4/0 AWG THHN/THWN-2
CONDUCTORS + (1) 6 AWG THHN/THWN-2 GROUND 12 2 1 94.8 100.8 0.64 0.91 1 173.1 230 260 THHN/THWN-2 4/0 Cu 260 -- 6 PVC 1-1/2" 175 75 0.21%
1.2C FUSED COMBINER BOX TO
UNDERGROUND PULL BOX
(1) 1-1/2" PVC CONDUIT: (2) 2/0 AWG THHN/THWN-2
CONDUCTORS + (1) 6 AWG THHN/THWN-2 GROUND 8 2 1 63.2 67.2 0.64 0.91 1 115.4 175 195 THHN/THWN-2 2/0 Cu 195 -- 6 PVC 1-1/2" 110 85 0.25%
1.3A UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 3" PVC CONDUIT: (6) 4/0 AWG THHN/THWN-2
CONDUCTORS + (3) 6 AWG THHN/THWN-2 GROUND 12 6 1 94.8 100.8 0.64 0.91 0.8 216.3 230 260 THHN/THWN-2 4/0 Cu 260 -- 6 PVC 3" 175 275 0.77%
1.3B UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 3" PVC CONDUIT: (4) 4/0 AWG THHN/THWN-2
CONDUCTORS + (2) 2/0 AWG THHN/THWN-2
CONDUCTORS + (3) 6 AWG THHN/THWN-2 GROUND
12 4
94.8 100.8 0.64 0.91 0.8 216.3 230 260 THHN/THWN-2 4/0 Cu 260 -- 6
PVC 3"
0.77%
8 2 63.2 67.2 0.64 0.91 0.8 144.2 175 195 THHN/THWN-2 2/0 Cu 195 -- 6 110 0.82%
1.3C UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 2-1/2" PVC CONDUIT: (4) 4/0 AWG THHN/THWN-2
CONDUCTORS + (2) 6 AWG THHN/THWN-2 GROUND 12 4 1 94.8 100.8 0.64 0.91 0.8 216.3 230 260 THHN/THWN-2 4/0 Cu 260 -- 6 PVC 2-1/2" 175 155 0.43%
1.3D UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(2) 2-1/2" PVC CONDUIT: (4) 4/0 AWG THHN/THWN-2
CONDUCTORS + (2) 6 AWG THHN/THWN-2 GROUND 12 8 2 94.8 100.8 0.64 0.91 0.8 216.3 230 260 THHN/THWN-2 4/0 Cu 260 -- 6 PVC 2-1/2" 175 95 0.26%
1.4A ARRAY COMBINER BOX TO
FUSED DC DISCONNECT
(2) 2-1/2" PVC CONDUIT: (2) 350 AWG THHN/THWN-2
CONDUCTORS + (1) 3/0 THHN/THWN-2 GROUND EACH 23 4 2 181.7 193.2 0.64 0.91 1 331.7 310 350 THHN/THWN-2 350 Cu 350 -- 3/0 PVC 2-1/2" 1200 110 0.18%
1.4B ARRAY COMBINER BOX TO
REMOTE PV TIE
(2) 2-1/2" PVC CONDUIT: (2) 350 AWG THHN/THWN-2
CONDUCTORS + (1) 3/0 THHN/THWN-2 GROUND EACH 23 4 2 181.7 193.2 0.64 0.91 1 331.7 310 350 THHN/THWN-2 350 Cu 350 -- 3/0 PVC 2-1/2" 1200 20 0.03%
1.5A DC DISCONNECT TO INVERTER
(2) 2-1/2" PVC CONDUIT: (2) 350 AWG THHN/THWN-2
CONDUCTORS + (1) 3/0 THHN/THWN-2 GROUND EACH 23 4 2 181.7 193.2 0.64 0.91 1 331.7 310 350 THHN/THWN-2 350 Cu 350 -- 3/0 PVC 2-1/2" 1200 20 0.03%
1.5B REMOTE PV TIE TO INVERTER
(1) 1" PVC CONDUIT: (1) 16 AWG 'TYPE TC' 6
CONDUCTOR DATA CABLE (BELDEN 1527A, GENERAL
CABLE 239200, OR EQUIVALENT)
-- -- 1 -- -- -- 0.91 1 -- -- -- DATA CABLE -- Cu 0 -- 16 PVC 1" -- 110 0.00%
Calculations shown using the worst case derations per NEC 310.15(A)(2) CALCULATED WORST CASE TOTAL: 1.98%
AC CONDUIT SCHEDULE - INVERTER 1
AC SYSTEM ADJUSTMENT FACTORS CONDUCTORS CONDUITS FUSES VOLTAGE DROP
ITEM CONDUCTOR SUMMARY
# CURRENT
CARRYING
CONDUCTORS
# OF CONDUITS NEUTRAL
CIRCUIT LOAD PER
CONDUCTOR [A] AC VOLTAGE [V] DUTY Tamb RACEWAY FILL
MIN. CALCULATED
CONDUCTOR
AMPACITY [A]
CONDUCTOR AMPACITY
VALUE NEC 310.16 WIRE TYPE MAIN CONDUCTOR
SIZE
MAIN CONDUCTOR
MATERIAL
WIRE AMPACITY
310.16 NEUTRAL SIZE GEC SIZE TYPE SIZE (IN) PROTECTION (FUSE
OR BREAKER)
CONDUIT RUN
DISTANCE (FT) 0.00%
75°C 90°C
1.6 INVERTER GEC 1/0 AWG THHN/THWN-2 GROUNDING ELECTRODE
CONDUCTOR -- -- -- -- -- -- -- -- -- 150 170 THHN/THWN-2 1/0 Cu 170 -- -- -- -- -- -- 0.00%
1.7 INVERTER TO FUSED AC
DISCONNECT
(3) 3" PVC CONDUIT: (3) 300 KCMIL THHN/THWN-2
CONDUCTORS + (1) 1/0 AWG THHN/THWN-2 GROUND
EACH
9 3 -- 222.33 480 3-phase 0.8 0.91 1 305.40 285 320 THHN/THWN-2 300 Cu 320 -- 1/0 PVC 3" 800 20 0.07%
1.8 AC DISCONNECT TO
TRANSFORMER
(3) 3" PVC CONDUIT: (3) 300 KCMIL THHN/THWN-2
CONDUCTORS + (1) 2/0 AWG THHN/THWN-2 NEUTRAL +
(1) 1/0 AWG THHN/THWN-2 GROUND EACH
9 3 3 222.33 480 3-phase 0.8 0.91 1 305.40 285 320 THHN/THWN-2 300 Cu 320 -- 1/0 PVC 3" 800 15 0.05%
Calculations shown using the worst case derations per NEC 310.15(A)(2) CALCULATED WORST CASE TOTAL: 0.12%
WRITTEN PERMISSION OF REC SOLAR, INC IS PROHIBITED, 2011.
REC SOLAR, INC.
ROCAZ LIC. #252827
775 FIERO LANE, SUITE 200
SAN LUIS OBISPO, CA 93401
USA
PHONE (805) 528-9705
FAX (805) 528-9701
(888) OK SOLAR
DATEREV #
DATE
ENGINEERING MANAGER
SHEET
PROJECT ENGINEER
PV SYSTEM DESIGNER PROJECT MANAGER
DRAFTER
DWG TITLE
APPROVED: PROJECT
DIRECTOR
VA PROJECT NUMBER
Office of Construction and
Facilities Management
E D C B A
DESCRIPTION
PRESCOTT HEALTH CARE CENTER
SOLAR PHOTOVOLTAIC (PV) SYSTEM
CONTRACTING OFFICER (CO) - JOHN YALLECH
CONTRACT SPECIALIST (CS) - SHON JOHNSON
CONTRACTING OFFICER'S TECHNICAL
REPRESENTATIVE (COTR) - JAMES LARSON
06/19/12
PVE-1.2
E D C B A
50% SUBMITTAL 9/9/11
100% SUBMITTAL
FINAL SUBMITTAL
REC SOLAR STRUCTURAL COMMENTS 11/17/11
REC SOLAR ARRAY SHIFT FOR GUY WIRE 12/5/11
12/8/11 6/4/12
SINGLE LINE DIAGRAM
INVERTER 2
POWER
ELECTRONICS
SECTION
AC
INTERFACE
SECTION
DC
INTERFACE
SECTION
AC CONTACTOR
EMI FILTER
AC DISCONNECT
DC CONTACTOR
NEG GROUND
TERMINALS
POS GROUND
TERMINALS
"AC2"
PHOTOVOLTAIC SYSTEM
UTILITY AC DISCONNECT
SWITCH SQUARE D
H367NR 3 POLE 800A,
600V, NEMA 3R WITH (3)
600V CLASS L FUSES:
800A
"INV2"
ADVANCED ENERGY
SOLARON 500kW
480V 3-PHASE INVERTER
UL LISTED ASSEMBLY
GROUND
2.6
2.8
INVERTER 2
GROUND
GROUND
GROUND
GROUND
"ARC3"
AMTEC EQUINOX 2000 NEMA 4
36"X36"X10"(FS) WITH (8) 600V
CLASS R FUSES: (7) 175A, (1)
110A, 75°F RATED INPUT LUGS
90°F RATED OUTPUT LUGS
"ARC4"
AMTEC EQUINOX 2000 NEMA 4
36"X36"X10"(FS) WITH (8) 600V
CLASS R FUSES: (6) 175A, (2)
150A, 75°F RATED INPUT LUGS
90°F RATED OUTPUT LUGS
2.4B
2.5A 175A 175A 175A 175A
POSITIVELY GROUNDED
(POS POL)
2.5A
"DC3"
PHOTOVOLTAIC ARRAY
DC DISCONNECT SWITCH,
SQUARE D H268R 2P, 1200A,
600V, NEMA 3R WITH (2) 600V
CLASS L FUSES: 1200A
175A 175A
175A 150A
175A 175A 150A 175A
(A24.C9)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A25.C10)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A26.C11)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A27.C12)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
"DC4"
PHOTOVOLTAIC ARRAY
DC DISCONNECT SWITCH,
SQUARE D H268R 2P, 1200A,
600V, NEMA 3R WITH (2) 600V
CLASS L FUSES: 1200A
TRANSFORMER, 1500kVA
2.7
2.4B
2.4A
2.4A
GROUND
GROUND
GROUND
GROUND
(A27.C13)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (8) 600V FUSES: 15A
(A28.C14)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A29.C15)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A30.C16)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
2.2D 2.1
2.1
2.1
2.1
2.2B 2.1
2.1
2.1
2.1
(A24)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A25)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A26)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A27)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A27)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A28)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A29)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A30)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
2.2B 2.2B
2.2B 2.2B
2.2B 2.2B
175A 110A
175A 175A
GROUND
GROUNDGROUND
GROUND
(A16.C1)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A18.C2)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A18.C3)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (10) 600V FUSES: 15A
(A19.C4)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
GROUND
GROUND GROUND
GROUND
(A20.C5)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A20.C6)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (10) 600V FUSES: 15A
(A21.C7)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A27.C8)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
2.2B 2.1
2.1 2.1
2.1 2.2B 2.1
2.12.1
2.1
(A16)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A18)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A18)
(70) REC 240 PE (BLK) MODULES
IN (5) STRINGS OF 14 MODULES EACH
(A19)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A20)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A20)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A21)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A27)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
2.2C
2.2B
2.2B
2.2C
2.2A
2.2B
NEGATIVELY GROUNDED
(NEG POL)
"PVT2"
AE SOLARON
REMOTE
PV TIE
GROUND
(A23)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
2.1
PB17
GROUND
(A28)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
2.1
PB19
GROUND
(A29)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
2.1
PB20
GROUND
2.1 (A15)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB9
GROUND
2.1 (A17)
(70) REC 240 PE (BLK) MODULES
IN (5) STRINGS OF 14 MODULES EACH
PB11
GROUND
2.1 (A18)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB12
GROUND
2.1 (A19)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
PB13
GROUND
2.1 (A21)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB14
GROUND
2.1 (A22)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
PB15
GROUND
2.1 (A22)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB16
GROUND
(A26)
(28) REC 240 PE (BLK) MODULES
IN (2) STRINGS OF 14 MODULES EACH
2.1
PB18
GROUND
2.1 (A17)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
PB10
PB-G
PB-F
PB-E
PB-D
2.3A
2.3C
2.3D
2.3C
2.3B
2.5B
INVERTER 1
INVERTER 3
MONITORING, SEE SHEET PVE-3.1
SEE ELECTRICAL
SHEETS E1 THRU E5
ELECTRICAL ENGINEER
GLHN ARCHITECTS AND
ENGINEERS, INC.
2939 EAST BROADWAY BLVD.
TUCSON, AZ 85716
CONTACT: DENISE PAPE, PE
(820) 881-4546
DC CONDUIT SCHEDULE - INVERTER 2
DC SYSTEM ADJUSTMENT FACTORS CONDUCTORS CONDUITS FUSES VOLTAGE DROP
ITEM CONDUCTOR RUN SUMMARY # STRINGS PER
CONDUCTOR
# CURRENT
CARRYING
CONDUCTORS
# OF CONDUITS
MAX POWER LOAD
[A]
SHORT CIRCUIT
LOAD [A] DUTY Tamb RACEWAY FILL
MIN. CALCULATED
CONDUCTOR
AMPACITY [A]
CONDUCTOR AMPACITY
VALUE NEC 310.16 WIRE TYPE MAIN CONDUCTOR
SIZE
MAIN CONDUCTOR
MATERIAL
WIRE AMPACITY
310.16 NEUTRAL SIZE EGC SIZE TYPE SIZE (IN)
PROTECTION
(FUSES OR
BREAKERS)
CONDUIT RUN
DISTANCE [FT] 0.00%
75°C 90°C
2.1 STRING TO FUSED DC
COMBINER BOX
2" PVC CONDUIT: MAX (20) 10 AWG PV RHW/USE-2
CONDUCTORS + (1) 8 AWG BARE CU GROUND 1 20 AS NEEDED 7.9 8.4 0.64 0.76 0.50 34.5 35 40 PV RHW/USE-2 10 Cu 40 -- 8 PVC 2" 15 125 0.60%
2.2A FUSED COMBINER BOX TO
FUSED ARRAY COMBINER
(1) 1-1/2" PVC CONDUIT: (2) 4/0 AWG THHN/THWN-2
CONDUCTORS + (1) 4 AWG THHN/THWN-2 GROUND 12 2 1 94.8 100.8 0.64 0.91 1.00 173.1 230 260 THHN/THWN-2 4/0 Cu 260 -- 4 PVC 1-1/2" 175 35 0.10%
2.2B FUSED COMBINER BOX TO
UNDERGROUND PULL BOX
(1) 2" PVC CONDUIT: (2) 250 AWG THHN/THWN-2
CONDUCTORS + (1) 4 AWG THHN/THWN-2 GROUND 12 2 1 94.8 100.8 0.64 0.91 1.00 173.1 255 290 THHN/THWN-2 250 Cu 290 -- 4 PVC 2" 175 175 0.42%
2.2C FUSED COMBINER BOX TO
UNDERGROUND PULL BOX
(1) 1-1/2" PVC CONDUIT: (2) 4/0 AWG THHN/THWN-2
CONDUCTORS + (1) 4 AWG THHN/THWN-2 GROUND 10 2 1 79.0 84.0 0.64 0.91 1.00 144.2 230 260 THHN/THWN-2 4/0 Cu 260 -- 4 PVC 1-1/2" 150 100 0.23%
2.2D FUSED COMBINER BOX TO
UNDERGROUND PULL BOX
(1) 1-1/2" PVC CONDUIT: (2) 3/0 AWG THHN/THWN-2
CONDUCTORS + (1) 6 AWG THHN/THWN-2 GROUND 8 2 1 63.2 67.2 0.64 0.91 1.00 115.4 200 225 THHN/THWN-2 3/0 Cu 225 -- 6 PVC 1-1/2" 110 10 0.02%
2.3A UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 2-1/2" PVC CONDUIT: (2) 250 AWG THHN/THWN-2
CONDUCTORS + (2) 3/0 AWG THHN/THWN-2
CONDUCTORS + (1) 4 AWG THHN/THWN-2 GROUND +
(1) 6 AWG THHN/THWN-2 GROUND
12 2
94.8 100.8 0.64 0.91 0.80 216.3 255 290 THHN/THWN-2 250 Cu 290 -- 4
PVC 2-1/2"
0.68%
8 2 63.2 67.2 0.64 0.91 0.80 144.2 200 225 THHN/THWN-2 3/0 Cu 225 -- 6 110 0.67%
2.3B UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 2-1/2" PVC CONDUIT: (4) 250 AWG THHN/THWN-2
CONDUCTORS + (2) 4 AWG THHN/THWN-2 GROUND 12 4 1 94.8 100.8 0.64 0.91 0.80 216.3 255 290 THHN/THWN-2 250 Cu 290 -- 4 PVC 2-1/2" 175 285 0.68%
2.3C UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(2) 2-1/2" PVC CONDUIT: (4) 250 AWG THHN/THWN-2
CONDUCTORS + (2) 4 AWG THHN/THWN-2 GROUND 12 8 2 94.8 100.8 0.64 0.91 0.80 216.3 255 290 THHN/THWN-2 250 Cu 290 -- 4 PVC 2-1/2" 175 190 0.45%
2.3D UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 3" PVC CONDUIT: (2) 250 AWG THHN/THWN-2
CONDUCTORS + (4) 4/0 AWG THHN/THWN-2
CONDUCTORS + (3) 4 AWG THHN/THWN-2 GROUND
12 2
94.8 100.8 0.64 0.91 0.80 216.3 255 290 THHN/THWN-2 250 Cu 290 --
4 PVC 3"
0.18%
10 4 79.0 84.0 0.64 0.91 0.80 180.3 230 260 THHN/THWN-2 4/0 Cu 260 -- 110 0.17%
2.4A ARRAY COMBINER BOX TO
FUSED DC DISCONNECT
(2) 2-1/2" PVC CONDUIT: (2) 350 AWG THHN/THWN-2
CONDUCTORS + (1) 3/0 THHN/THWN-2 GROUND EACH 23 4 2 181.7 193.2 0.64 0.91 1.00 331.7 310 350 THHN/THWN-2 350 Cu 350 -- 3/0 PVC 2-1/2" 1200 135 0.22%
2.4B ARRAY COMBINER BOX TO
REMOTE PV TIE
(2) 2-1/2" PVC CONDUIT: (2) 350 AWG THHN/THWN-2
CONDUCTORS + (1) 3/0 THHN/THWN-2 GROUND EACH 23 4 2 181.7 193.2 0.64 0.91 1.00 331.7 310 350 THHN/THWN-2 350 Cu 350 -- 3/0 PVC 2-1/2" 1200 20 0.03%
2.5A DC DISCONNECT TO INVERTER
(2) 2-1/2" PVC CONDUIT: (2) 350 AWG THHN/THWN-2
CONDUCTORS + (1) 3/0 THHN/THWN-2 GROUND EACH 23 4 2 181.7 193.2 0.64 0.91 1.00 331.7 310 350 THHN/THWN-2 350 Cu 350 -- 3/0 PVC 2-1/2" 1200 20 0.03%
2.5B REMOTE PV TIE TO INVERTER
(1) 1" PVC CONDUIT: (1) 16 AWG 'TYPE TC' 6
CONDUCTOR DATA CABLE (BELDEN 1527A, GENERAL
CABLE 239200, OR EQUIVALENT)
-- -- 1 -- -- -- 0.91 1.00 -- -- -- DATA CABLE -- Cu 0 -- 16 PVC 1" -- 135 0.00%
Calculations shown using the worst case derations per NEC 310.15(A)(2) CALCULATED WORST CASE TOTAL: 1.95%
AC CONDUIT SCHEDULE - INVERTER 2
AC SYSTEM ADJUSTMENT FACTORS CONDUCTORS CONDUITS FUSES VOLTAGE DROP
ITEM CONDUCTOR SUMMARY
# CURRENT
CARRYING
CONDUCTORS
# OF CONDUITS NEUTRAL
CIRCUIT LOAD PER
CONDUCTOR [A] AC VOLTAGE [V] DUTY Tamb RACEWAY FILL
MIN. CALCULATED
CONDUCTOR
AMPACITY [A]
CONDUCTOR AMPACITY
VALUE NEC 310.16 WIRE TYPE MAIN CONDUCTOR
SIZE
MAIN CONDUCTOR
MATERIAL
WIRE AMPACITY
310.16 NEUTRAL SIZE GEC SIZE TYPE SIZE (IN) PROTECTION (FUSE
OR BREAKER)
CONDUIT RUN
DISTANCE (FT) 0.00%
75°C 90°C
2.6 INVERTER GEC 1/0 AWG THHN/THWN-2 GROUNDING ELECTRODE
CONDUCTOR -- -- -- -- -- -- -- -- -- 150 170 THHN/THWN-2 1/0 Cu 170 -- -- -- -- -- -- 0.00%
2.7 INVERTER TO FUSED AC
DISCONNECT
(3) 3" PVC CONDUIT: (3) 300 KCMIL THHN/THWN-2
CONDUCTORS + (1) 1/0 AWG THHN/THWN-2 GROUND
EACH
9 3 -- 222.33 480 3-phase 0.80 0.91 1.00 305.40 285 320 THHN/THWN-2 300 Cu 320 -- 1/0 PVC 3" 800 20 0.07%
2.8 AC DISCONNECT TO
TRANSFORMER
(3) 3" PVC CONDUIT: (3) 300 KCMIL THHN/THWN-2
CONDUCTORS + (1) 2/0 AWG THHN/THWN-2 NEUTRAL +
(1) 1/0 AWG THHN/THWN-2 GROUND EACH
9 3 3 222.33 480 3-phase 0.80 0.91 1.00 305.40 285 320 THHN/THWN-2 300 Cu 320 -- 1/0 PVC 3" 800 25 0.09%
Calculations shown using the worst case derations per NEC 310.15(A)(2) CALCULATED WORST CASE TOTAL: 0.16%
WRITTEN PERMISSION OF REC SOLAR, INC IS PROHIBITED, 2011.
REC SOLAR, INC.
ROCAZ LIC. #252827
775 FIERO LANE, SUITE 200
SAN LUIS OBISPO, CA 93401
USA
PHONE (805) 528-9705
FAX (805) 528-9701
(888) OK SOLAR
DATEREV #
DATE
ENGINEERING MANAGER
SHEET
PROJECT ENGINEER
PV SYSTEM DESIGNER PROJECT MANAGER
DRAFTER
DWG TITLE
APPROVED: PROJECT
DIRECTOR
VA PROJECT NUMBER
Office of Construction and
Facilities Management
E D C B A
DESCRIPTION
PRESCOTT HEALTH CARE CENTER
SOLAR PHOTOVOLTAIC (PV) SYSTEM
CONTRACTING OFFICER (CO) - JOHN YALLECH
CONTRACT SPECIALIST (CS) - SHON JOHNSON
CONTRACTING OFFICER'S TECHNICAL
REPRESENTATIVE (COTR) - JAMES LARSON
06/19/12
PVE-1.3
E D C B A
50% SUBMITTAL 9/9/11
100% SUBMITTAL
FINAL SUBMITTAL
REC SOLAR STRUCTURAL COMMENTS 11/17/11
REC SOLAR ARRAY SHIFT FOR GUY WIRE 12/5/11
12/8/11 6/4/12
SINGLE LINE DIAGRAM
INVERTER 3
POWER
ELECTRONICS
SECTION
AC
INTERFACE
SECTION
DC
INTERFACE
SECTION
AC CONTACTOR
EMI FILTER
AC DISCONNECT
DC CONTACTOR
NEG GROUND
TERMINALS
POS GROUND
TERMINALS
"AC3"
PHOTOVOLTAIC SYSTEM
UTILITY AC DISCONNECT
SWITCH SQUARE D
H367NR 3 POLE 800A,
600V, NEMA 3R WITH (3)
600V CLASS L FUSES:
800A
"INV3"
ADVANCED ENERGY
SOLARON 500kW
480V 3-PHASE INVERTER
UL LISTED ASSEMBLY
GROUND
3.6
3.8
INVERTER 3
TRANSFORMER 1500kVA
3.7
GROUND GROUND
GROUND
GROUND
"ARC5"
AMTEC EQUINOX 2000 NEMA 4
36"X36"X10"(FS) WITH (8) 600V
CLASS R FUSES: (6) 175A, (2)
150A, 75°F RATED INPUT LUGS
90°F RATED OUTPUT LUGS
"ARC6"
AMTEC EQUINOX 2000 NEMA 4
36"X36"X10"(FS) WITH (8) 600V
CLASS R FUSES: (6) 175A, (2)
150A, 75°F RATED INPUT LUGS
90°F RATED OUTPUT LUGS
3.4B
3.5A 150A 150A 175A 175A
POSITIVELY GROUNDED
(POS POL)
3.5A
"DC5"
PHOTOVOLTAIC ARRAY
DC DISCONNECT SWITCH,
SQUARE D H268R 2P, 1200A,
600V, NEMA 3R WITH (2) 600V
CLASS L FUSES: 1200A
175A 175A
175A 150A
175A 175A 150A 175A
(A4.C9)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A4.C10)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A6.C11)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A7.C12)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED,
NEMA 4X
WITH (12) 600V
FUSES: 15A
"DC6"
PHOTOVOLTAIC ARRAY
DC DISCONNECT SWITCH,
SQUARE D H268R 2P, 1200A,
600V, NEMA 3R WITH (2) 600V
CLASS L FUSES: 1200A
3.4B
3.4A
3.4A
GROUND
GROUND
GROUND
GROUND
(A9.C13)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A11.C14)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A12.C15)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (10) 600V FUSES: 15A
(A13.C16)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (10) 600V FUSES: 15A
3.2B 3.1
3.1
3.1
3.1
3.2A 3.1 3.1
3.1
3.1
(A4)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A4)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A6)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A7)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A9)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
(A11)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A12)
(140) REC 240 PE (BLK) MODULES
IN (10) STRINGS OF 14 MODULES EACH
(A13)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
3.2B
3.2B
3.2C
3.2B
3.2C 3.2B
175A 175A
175A 175A
GROUND
GROUND
GROUND
GROUND(A1.C1)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A2.C2)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A5.C3)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A6.C4)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
GROUND
GROUND
GROUND
GROUND
(A7.C5)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A8.C6)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (10) 600V FUSES: 15A
(A10.C7)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (12) 600V FUSES: 15A
(A11.C8)
PV COMBINER BOX
AMTEC PROM12
600VDC RATED, NEMA 4X
WITH (10) 600V FUSES: 15A
3.2B 3.1
3.1
3.1
3.1
3.2B 3.1
3.1
3.1
3.1
(A1)
(98) REC 240 PE (BLK) MODULES
IN (7) STRINGS OF 14 MODULES EACH
(A2)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A5)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A6)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A7)
(168) REC 240 PE (BLK) MODULES
IN (12) STRINGS OF 14 MODULES EACH
(A8)
(70) REC 240 PE (BLK) MODULES
IN (5) STRINGS OF 14 MODULES EACH
(A10)
(112) REC 240 PE (BLK) MODULES
IN (8) STRINGS OF 14 MODULES EACH
(A11)
(85) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
3.2C
3.2B3.2B
3.2B3.2C
3.2B
NEGATIVELY GROUNDED
(NEG POL)
"PVT3"
AE SOLARON
REMOTE
PV TIE
GROUND
3.1 (A0)
(70) REC 240 PE (BLK) MODULES
IN (5) STRINGS OF 14 MODULES EACH
PB21
GROUND
3.1 (A12)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB25
GROUND
3.1 (A11)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB24
GROUND
3.1 (A9)
(70) REC 240 PE (BLK) MODULES
IN (5) STRINGS OF 14 MODULES EACH
PB23
3.1 (A9)
(28) REC 240 PE (BLK) MODULES
IN (2) STRINGS OF 14 MODULES EACH
PB30
GROUND
3.1 (A10)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
PB31
GROUND
3.1 (A10)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB32
GROUND
GROUND
(A14)
(28) REC 240 PE (BLK) MODULES
IN (2) STRINGS OF 14 MODULES EACH
3.1
PB33
GROUND
3.1 (A4)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB22
GROUND
3.1 (A3)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB26
GROUND
3.1 (A5)
(56) REC 240 PE (BLK) MODULES
IN (4) STRINGS OF 14 MODULES EACH
PB27
GROUND
3.1 (A5)
(84) REC 240 PE (BLK) MODULES
IN (6) STRINGS OF 14 MODULES EACH
PB28
3.1 (A6)
(28) REC 240 PE (BLK) MODULES
IN (2) STRINGS OF 14 MODULES EACH
PB29
GROUND
PB-I
PB-J
PB-K
PB-H
3.3C
3.3E
3.3B
3.3A
3.5B
3.3D
INVERTER 1
INVERTER 2
MONITORING, SEE SHEET PVE-3.1
SEE ELECTRICAL
SHEETS E1 THRU E5
ELECTRICAL ENGINEER
GLHN ARCHITECTS AND
ENGINEERS, INC.
2939 EAST BROADWAY BLVD.
TUCSON, AZ 85716
CONTACT: DENISE PAPE, PE
(820) 881-4546
DC CONDUIT SCHEDULE - INVERTER 3
DC SYSTEM ADJUSTMENT FACTORS CONDUCTORS CONDUITS FUSES VOLTAGE DROP
ITEM CONDUCTOR RUN SUMMARY # STRINGS PER
CONDUCTOR
# CURRENT
CARRYING
CONDUCTORS
# OF CONDUITS
MAX POWER LOAD
[A]
SHORT CIRCUIT
LOAD [A] DUTY Tamb RACEWAY FILL
MIN. CALCULATED
CONDUCTOR
AMPACITY [A]
CONDUCTOR AMPACITY
VALUE NEC 310.16 WIRE TYPE MAIN CONDUCTOR
SIZE
MAIN CONDUCTOR
MATERIAL
WIRE AMPACITY
310.16 NEUTRAL SIZE EGC SIZE TYPE SIZE (IN)
PROTECTION
(FUSES OR
BREAKERS)
CONDUIT RUN
DISTANCE [FT] 0.00%
75°C 90°C
3.1 STRING TO FUSED DC
COMBINER BOX
2" PVC CONDUIT: MAX (20) 10 AWG PV RHW/USE-2
CONDUCTORS + (1) 8 AWG BARE CU GROUND 1 20 AS NEEDED 7.9 8.4 0.64 0.76 0.50 34.5 35 40 PV RHW/USE-2 10 Cu 40 -- 8 PVC 2" 15 125 0.60%
3.2A FUSED COMBINER BOX TO
FUSED ARRAY COMBINER
(1) 1-1/2" PVC CONDUIT: (2) 4/0 AWG THHN/THWN-2
CONDUCTORS + (1) 4 AWG THHN/THWN-2 GROUND 12 2 1 94.8 100.8 0.64 0.91 1.00 173.1 230 260 THHN/THWN-2 4/0 Cu 260 -- 4 PVC 1-1/2" 175 110 0.31%
3.2B FUSED COMBINER BOX TO
UNDERGROUND PULL BOX
(1) 2" PVC CONDUIT: (2) 250 AWG THHN/THWN-2
CONDUCTORS + (1) 4 AWG THHN/THWN-2 GROUND 12 2 1 94.8 100.8 0.64 0.91 1.00 173.1 255 290 THHN/THWN-2 250 Cu 290 -- 4 PVC 2" 175 215 0.51%
3.2C FUSED COMBINER BOX TO
UNDERGROUND PULL BOX
(1) 2" PVC CONDUIT: (2) 3/0 AWG THHN/THWN-2
CONDUCTORS + (1) 4 AWG THHN/THWN-2 GROUND 10 2 1 79.0 84.0 0.64 0.91 1.00 144.2 200 225 THHN/THWN-2 3/0 Cu 225 -- 4 PVC 2" 150 65 0.19%
3.3A UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 3" PVC CONDUIT: (2) 250 AWG THHN/THWN-2
CONDUCTORS + (4) 3/0 AWG THHN/THWN-2
CONDUCTORS + (3) 4 AWG THHN/THWN-2 GROUND
12 2
94.8 100.8 0.64 0.91 0.80 216.3 255 290 THHN/THWN-2 250 Cu 290 -- 4
PVC 3"
0.41%
10 4 79.0 84.0 0.64 0.91 0.80 180.3 200 225 THHN/THWN-2 3/0 Cu 225 -- 4 110 0.50%
3.3B UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(2) 2-1/2" PVC CONDUIT: (4) 250 AWG THHN/THWN-2
CONDUCTORS + (2) 4 AWG THHN/THWN-2 GROUND 12 8 2 94.8 100.8 0.64 0.91 0.80 216.3 255 290 THHN/THWN-2 250 Cu 290 -- 4 PVC 2-1/2" 175 165 0.39%
3.3C UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 3" PVC CONDUIT: (4) 250 AWG THHN/THWN-2
CONDUCTORS + (2) 3/0 AWG THHN/THWN-2
CONDUCTORS + (3) 4 AWG THHN/THWN-2 GROUND
12 4
94.8 100.8 0.64 0.91 0.80 216.3 255 290 THHN/THWN-2 250 Cu 290 -- 4
PVC 3"
0.05%
10 2 79.0 84.0 0.64 0.91 0.80 180.3 200 225 THHN/THWN-2 3/0 Cu 225 -- 4 110 0.06%
3.3D UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 2-1/2" PVC CONDUIT: (2) 250 AWG THHN/THWN-2
CONDUCTORS + (2) 3/0 AWG THHN/THWN-2
CONDUCTORS + (2) 4 AWG THHN/THWN-2 GROUND
12 2
94.8 100.8 0.64 0.91 0.80 216.3 255 290 THHN/THWN-2 250 Cu 290 -- 4
PVC 2-1/2"
0.05%
10 2 79.0 84.0 0.64 0.91 0.80 180.3 200 225 THHN/THWN-2 3/0 Cu 225 -- 4 110 0.06%
3.3E UNDERGROUND PULL BOX TO
FUSED ARRAY COMBINER
(1) 3" PVC CONDUIT: (6) 250 AWG THHN/THWN-2
CONDUCTORS + (3) 4 AWG THHN/THWN-2 GROUND 12 6 1 94.8 100.8 0.64 0.91 0.80 216.3 255 290 THHN/THWN-2 250 Cu 290 -- 4 PVC 3" 175 90 0.21%
3.4A ARRAY COMBINER BOX TO
FUSED DC DISCONNECT
(2) 3" PVC CONDUIT: (2) 500 AWG THHN/THWN-2
CONDUCTORS + (1) 3/0 THHN/THWN-2 GROUND EACH 23 4 2 181.7 193.2 0.64 0.91 1.00 331.7 380 430 THHN/THWN-2 500 Cu 430 -- 3/0 PVC 3" 1200 540 0.61%
3.4B ARRAY COMBINER BOX TO
REMOTE PV TIE
(2) 3" PVC CONDUIT: (2) 500 AWG THHN/THWN-2
CONDUCTORS + (1) 3/0 THHN/THWN-2 GROUND EACH 23 4 2 181.7 193.2 0.64 0.91 1.00 331.7 380 430 THHN/THWN-2 500 Cu 430 -- 3/0 PVC 3" 1200 20 0.02%
3.5A DC DISCONNECT TO INVERTER
(2) 3" PVC CONDUIT: (2) 500 AWG THHN/THWN-2
CONDUCTORS + (1) 3/0 THHN/THWN-2 GROUND EACH 23 4 2 181.7 193.2 0.64 0.91 1.00 331.7 380 430 THHN/THWN-2 500 Cu 430 -- 3/0 PVC 3" 1200 20 0.02%
3.5B REMOTE PV TIE TO INVERTER
(1) 1" PVC CONDUIT: (1) 16 AWG 'TYPE TC' 6
CONDUCTOR DATA CABLE (BELDEN 1527A, GENERAL
CABLE 239200, OR EQUIVALENT)
-- -- 1 -- -- -- 0.91 1.00 -- -- -- DATA CABLE -- Cu 0 -- 16 PVC 1" -- 540 0.00%
Calculations shown using the worst case derations per NEC 310.15(A)(2) CALCULATED WORST CASE TOTAL: 2.25%
AC CONDUIT SCHEDULE - INVERTER 3
AC SYSTEM ADJUSTMENT FACTORS CONDUCTORS CONDUITS FUSES VOLTAGE DROP
ITEM CONDUCTOR SUMMARY
# CURRENT
CARRYING
CONDUCTORS
# OF CONDUITS NEUTRAL
CIRCUIT LOAD PER
CONDUCTOR [A] AC VOLTAGE [V] DUTY Tamb RACEWAY FILL
MIN. CALCULATED
CONDUCTOR
AMPACITY [A]
CONDUCTOR AMPACITY
VALUE NEC 310.16 WIRE TYPE MAIN CONDUCTOR
SIZE
MAIN CONDUCTOR
MATERIAL
WIRE AMPACITY
310.16 NEUTRAL SIZE GEC SIZE TYPE SIZE (IN) PROTECTION (FUSE
OR BREAKER)
CONDUIT RUN
DISTANCE (FT) 0.00%
75°C 90°C
3.6 INVERTER GEC 1/0 AWG THHN/THWN-2 GROUNDING ELECTRODE
CONDUCTOR -- -- -- -- -- -- -- -- -- 150 170 THHN/THWN-2 1/0 Cu 170 -- -- -- -- -- -- 0.00%
3.7 INVERTER TO FUSED AC
DISCONNECT
(3) 3" PVC CONDUIT: (3) 300 KCMIL THHN/THWN-2
CONDUCTORS + (1) 1/0 AWG THHN/THWN-2 GROUND
EACH
9 3 -- 222.33 480 3-phase 0.80 0.91 1.00 305.40 285 320 THHN/THWN-2 300 Cu 320 -- 1/0 PVC 3" 800 20 0.07%
3.8 AC DISCONNECT TO
TRANSFORMER
(3) 3" PVC CONDUIT: (3) 300 KCMIL THHN/THWN-2
CONDUCTORS + (1) 2/0 AWG THHN/THWN-2 NEUTRAL +
(1) 1/0 AWG THHN/THWN-2 GROUND EACH
9 3 3 222.33 480 3-phase 0.80 0.91 1.00 305.40 285 320 THHN/THWN-2 300 Cu 320 -- 1/0 PVC 3" 800 35 0.12%
Calculations shown using the worst case derations per NEC 310.15(A)(2) CALCULATED WORST CASE TOTAL: 0.19%
GENERAL NOTES FOR SIGNAGE
1. PLACARD LOCATIONS ARE SPECIFIED ON OTHER PLAN SHEETS THAT
CONTAIN DETAIL INFORMATION FOR EACH ENCLOSURE.
2. EXACT PLACEMENT SHALL BE DETERMINED BY THE CONTRACTOR IN THE
FIELD.
3. PLACARD PLACEMENT SHALL BE CENTERED ON THE ENCLOSURE AND
VISIBLE FOR EQUIPMENT IDENTIFICATION.
4. PLACARDS SHALL BE PLACED ON EACH ENCLOSURE IN ACCORDANCE WITH
THE NATIONAL ELECTRIC CODE.
5. SECURE PLACARDS WITH ADHESIVE BACKING, THEN NEATLY CAULK WITH
CLEAR SILICONE AROUND ALL EDGES.
6. ALL PLACARDS SHALL BE LAMINATED BLACK PHENOLIC RESIN WITH WHITE
CORE ENGRAVED LETTERING, IN ACCORDANCE WITH VA SPECIFICATIONS.
QUANTITY= 4
6"L x 3"H www.recsolar.com
DANGER
NEGATIVELY GROUNDED COMPONENTS
AUTHORIZED PERSONNEL ONLY
HIGH VOLTAGE - KEEP AWAY
WARNING!! BIPOLAR PHOTOVOLTAIC ARRAY
DISCONNECTION OF NEUTRAL OR GROUNDED
CONDUCTORS MAY RESULT IN OVER VOLTAGE ON
ARRAY OR INVERTER.
www.recsolar.com
DANGER
POSITIVELY GROUNDED COMPONENTS
AUTHORIZED PERSONNEL ONLY
HIGH VOLTAGE - KEEP AWAY
WARNING!! BIPOLAR PHOTOVOLTAIC ARRAY
DISCONNECTION OF NEUTRAL OR GROUNDED
CONDUCTORS MAY RESULT IN OVER VOLTAGE ON
ARRAY OR INVERTER.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16 17 18 A B C D E
CAUTION:
PHOTOVOLTAIC POWER TO THIS
BUILDING IS SUPPLIED FROM
THE FOLLOWING SOURCE WITH
DISCONNECTS AS SHOWN
www.recsolar.com R
CAUTION:
SOLAR CIRCUIT
MARKING IS REQUIRED ON ALL
INTERIOR AND EXTERIOR DC
CONDUIT, RACEWAYS,
ENCLOSURES, JUNCTION BOXES,
CABLE ASSEMBLIES, EVERY 10', AT
TURNS AND ABOVE AND/OR BELOW
PENETRATIONS AND ALL DC
COMBINER BOXES PER CALFIRE
www.recsolar.com
DANGER
PHOTOVOLTAIC SYSTEM
ARRAY PULL BOX
AUTHORIZED PERSONNEL ONLY
HIGH VOLTAGE - KEEP AWAY
R
QUANTITY= ?
4-1/2" x 1-1/2" STICKER
QUANTITY= 48
6"L x 3"H
QUANTITY= 33
6"L x 3"H
QUANTITY= 3
6"L x 3"H
QUANTITY= 3
6"L x 3"H
QUANTITY= 2
6"L x 3"H
QUANTITY= 6
6"L x 3"H
QUANTITY= 4
6"L x 3"H
QUANTITY= 6
6"L x 3"H
QUANTITY= 1
6"L x 3"H
QUANTITY= 1
6"L x 3"H
QUANTITY= 1
6"L x 3"H
QUANTITY= 5
6"L x 10"H
AC DISCONNECT
INVERTER
SOLAR PHOTOVOLTAIC
PANELS GROUND MOUNT
(E) SWITCHGEAR
AND POC
QUANTITY= 51
6"L x 3"H
QUANTITY= 48
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC SOURCE CIRCUIT
COMBINER BOX
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R www.recsolar.com
DANGER
PHOTOVOLTAIC ARRAY
COMBINER BOX
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R www.recsolar.com
DANGER
PHOTOVOLTAIC SYSTEM UTILITY
LOCKABLE AC DISCONNECT
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R www.recsolar.com
DANGER
PHOTOVOLTAIC SYSTEM
COMMUNICATION EQUIPMENT
AUTHORIZED PERSONNEL ONLY
HIGH VOLTAGE - KEEP AWAY
R www.recsolar.com
DANGER
PHOTOVOLTAIC SYSTEM
TRANSFORMER
AUTHORIZED PERSONNEL ONLY
HIGH VOLTAGE - KEEP AWAY
R www.recsolar.com
DANGER
PHOTOVOLTAIC SYSTEM
INVERTER
AUTHORIZED PERSONNEL ONLY
HIGH VOLTAGE - KEEP AWAY
R www.recsolar.com
DANGER
PHOTOVOLTAIC INVERTER OUTPUT
COMBINER BOX
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R www.recsolar.com
DANGER
FUSE BOX
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
FOR SERVICE OR
IN CASE OF EMERGENCY
www.recsolar.com
CONTACT REC SOLAR
888 OK SOLAR
(888) 657-6527
R
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF
REC SOLAR, INC. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE
WRITTEN PERMISSION OF REC SOLAR, INC IS PROHIBITED, 2011.
REC SOLAR, INC.
ROCAZ LIC. #252827
775 FIERO LANE, SUITE 200
SAN LUIS OBISPO, CA 93401
USA
PHONE (805) 528-9705
FAX (805) 528-9701
(888) OK SOLAR
DATEREV #
DATE
ENGINEERING MANAGER
SHEET
PROJECT ENGINEER
PV SYSTEM DESIGNER PROJECT MANAGER
DRAFTER
DWG TITLE
APPROVED: PROJECT
DIRECTOR
VA PROJECT NUMBER
Office of Construction and
Facilities Management
E D C B A
DESCRIPTION
PRESCOTT HEALTH CARE CENTER
SOLAR PHOTOVOLTAIC (PV) SYSTEM
CONTRACTING OFFICER (CO) - JOHN YALLECH
CONTRACT SPECIALIST (CS) - SHON JOHNSON
CONTRACTING OFFICER'S TECHNICAL
REPRESENTATIVE (COTR) - JAMES LARSON
06/19/12
PVE-2.1
E D C B A
50% SUBMITTAL 9/9/11
100% SUBMITTAL
FINAL SUBMITTAL
REC SOLAR STRUCTURAL COMMENTS 11/17/11
REC SOLAR ARRAY SHIFT FOR GUY WIRE 12/5/11
12/8/11 6/4/12
SIGNAGE DETAILS
www.recsolar.com
DANGER
MAXIMUM AC OUTPUT OPERATING CURRENT:
MAXIMUM AC OPERATING VOLTAGE:
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
ORDER AS
INDIVIDUAL 2" x 2"
PLACARDS
QUANTITY =
A = ?
B = ?
C = ?
D = ?
QUANTITY= 3
6"L x 3"H www.recsolar.com
DANGER
IF GROUND FAULT IS INDICATED, NORMALLY GROUNDED
CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
QUANTITY= 3
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC SYSTEM
INVERTER PV TIE
AUTHORIZED PERSONNEL ONLY
HIGH VOLTAGE - KEEP AWAY
R
ELECTRICAL ENGINEER
GLHN ARCHITECTS AND
ENGINEERS, INC.
2939 EAST BROADWAY BLVD.
TUCSON, AZ 85716
CONTACT: DENISE PAPE, PE
(820) 881-4546
QUANTITY= 1
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC ARRAY
DC DISCONNECT DEVICE 1 OF 6
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
QUANTITY= 1
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC ARRAY
DC DISCONNECT DEVICE 2 OF 6
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
QUANTITY= 1
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC ARRAY
DC DISCONNECT DEVICE 3 OF 6
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
QUANTITY= 1
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC ARRAY
DC DISCONNECT DEVICE 4 OF 6
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
QUANTITY= 1
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC ARRAY
DC DISCONNECT DEVICE 5 OF 6
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
QUANTITY= 1
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC ARRAY
DC DISCONNECT DEVICE 6 OF 6
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
QUANTITY= 1
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC SYSTEM
METER
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
QUANTITY= 1
6"L x 3"H www.recsolar.com
DANGER
PHOTOVOLTAIC SYSTEM
UTILITY DISCONNECT SWITCH
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
-WARNING-
INVERTER OUTPUT
CONNECTION, DO NOT
RELOCATE THIS
OVERCURRENT DEVICE
LOCATE BREAKER AT OPPOSITE END OF BUS FROM MAIN BREAKER
LOCATION PER NEC 690.64(B)(7)
QUANTITY= 3
6"L x 3"H
PRIOR TO WORKING ON
THIS METER SECTION,
VERIFY UTILITY ISOLATION
SWITCH AND APS SWITCH
ARE OPEN
QUANTITY= 1
6"L x 3"H
QUANTITY= 2
6"L x 3"H www.recsolar.com
DANGER
REVERSE FED PHOTOVOLTAIC
METER SECTION
AUTHORIZED PERSONNEL ONLY
- WARNING -
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS. TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN OPEN POSITION
R
-WARNING-
DO NOT OPEN FUSES
UNDER LOAD
QUANTITY= 6
6"L x 3"H
PRIOR TO WORKING ON
THIS METER SECTION,
VERIFY UTILITY
DISCONNECT DEVICE AND
INVERTER DISCONNECT
SWITCH(ES) ARE OPEN
QUANTITY= 1
6"L x 3"H
PHOTOVOLTAIC ARRAY
CHARACTERISTICS
SYSTEM SIZE:
SYSTEM OPEN CIRCUIT VOLTAGE:
SYSTEM OPERATING VOLTAGE:
MAXIMUM ALLOWABLE DC VOLTAGE:
SYSTEM OPERATING CURRENT:
SYSTEM SHORT CIRCUIT CURRENT:
www.recsolar.com
| 1151.00 E-1 |
| 1151.00 E-2 Electrical Site Plan |
| 1151.00 E-3 |
| 1151.00 E-4 |
| 1151.00 E-5 |
| VA Prescott - Final Electrical Sheets - REC Solar |