SOL 6 11 004 RECORD DRAWINGS 5 23 2013.pdf
PDF 13 MB Posted
- Solicitation number
- 36C26224Q0956
About this file
This document is a Combined Synopsis/Solicitation for a Solar Photovoltaic Power Monitoring System Replacement requirement at the Jennifer Moreno VA Medical Center in San Diego, CA. The solicitation is issued as a Request for Quotations (RFQ) under NAICS code 221114 with a small business size standard of 500 employees. The Department of Veterans Affairs, Network Contracting Office 22 is seeking these services. Offers are due by May 22, 2024 at 12:00 PM PDT. Questions must be received by May 14, 2024 at 2:00 PM AZ Time. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBs). Offerors are instructed not to contact VA Medical Center employees directly during the solicitation process.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Questions and Answers Solar PEV VA.pdf | ||
| 36C26224Q0956 0002.pdf | ||
| 36C26224Q0956 0002_1.docx | DOCX document | |
| 12818 San Diego VA O and M.pdf | ||
| 36C26224Q0956 0001_1.docx | DOCX document | |
| 36C26224Q0956 0001.pdf | ||
| FMS Vendor File Update Request Form.pdf | ||
| 36C26224Q0956_1.docx | DOCX document | |
| VA Form 10091.pdf | ||
| RFQ - 36C26224Q0956 - Solar PEV Replacement.pdf | ||
| W-9 Form.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SACRAMENTO
BERKELEY
OAKLAND
SAN JOSE
FRESNO
SAN FRANCISCO
SANTA CRUZ
MONTEREY
CHICO
SAN LUIS OBISPO
SANTA BARBARA
LOS ANGELES
LONG BEACH
SAN DIEGO
EUREKA
SAN BERNARDINO
PALM SPRINGS
CALIFORNIA
DESIGN ENGINEERING FIRM:
BLUE OAK ENERGY, INC.
1560 DREW AVENUE
DAVIS, CA 95618
CONTACT: RYAN ZAHNER, PE
TEL: 530.747.2026
EMAIL: RYAN@BLUEOAKENERGY.COM
CA STATE PE LIC. #19544
SITE CONTACT:
JON COGER
DEPARTMENT OF VETRANS AFFAIRS
3350 LA JOLLA VILLAGE DRIVE
SAN DIEGO, CA 92161
TEL: 858-552-7480
EMAIL: JON.COGER@VA.GOV
PROJECT MANAGER:
SOLAR POWER INTEGRATORS
735 SUNRISE AVENUE, SUITE 200
ROSEVILLE, CA 95661
CONTACT: PAMELA STEVENS
TEL: 916.783.3585
EMAIL: PSTEVENS@SOLARPOWERINTEGRATORS.COM
SOLAR ELECTRIC SYSTEM
THIS PROJECT ENTAILS THE INSTALLATION OF A SOLAR PHOTOVOLTAIC SYSTEM AT THE SAN DIEGO VA MEDICAL CENTER. THE SYSTEM
WILL NOT BE A NET ELECTRICITY EXPORTER TO THE UTILITY GRID.
THIS INSTALLATION CONSISTS OF FIXED TILT PHOTOVOLTAIC MODULES MOUNTED TO THE MAIN HOSPITAL ROOFTOP. THE SYSTEM WILL
INCLUDE MULTIPLE INVERTERS AND A UTILITY AC DISCONNECT TO ISOLATE IT FROM THE UTILITY GRID. THE PROPOSED INVERTER IS
UL1741 LISTED FOR POWER QUALITY AND SAFETY.
THE SYSTEM WILL BE INTERCONNECTED TO, AND OPERATED IN PARALLEL WITH, THE LOCAL ENERGY PROVIDER'S ELECTRIC GRID PER
THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE.
PROJECT SCOPE:
PROJECT TEAM:
VICINITY MAP:
STREET MAP:
PERMITTING/PLANNING NOTES:DRAWING INDEX:
AERIAL VIEW:
PROJECT SITE
PROJECT SITE
ARRAY LOCATION
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
G-001
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
G-001 TITLE SHEET
G-002 SYMBOLS & NOTES
E-101 EXISTING SITE PLAN - ROOF TOP
E-111 ARRAY PLAN - WEST
E-112 ARRAY PLAN - NORTH
E-113 ARRAY PLAN - EAST
E-114 ARRAY PLAN - SOUTH
E-121 EQUIPMENT LOCATION AND DC WIRING PLAN - WEST
E-122 EQUIPMENT LOCATION AND DC WIRING PLAN PLAN - NORTH
E-123 EQUIPMENT LOCATION AND DC WIRING PLAN PLAN - EAST
E-124 EQUIPMENT LOCATION AND DC WIRING PLAN PLAN - SOUTH
E-125 EQUIPMENT LOCATION PLAN & AC CONDUIT ROUTING
E-401 EQUIPMENT ELEVATIONS
E-501 ELECTRICAL DETAILS 1 OF 3
E-502 ELECTRICAL DETAILS 2 OF 3
E-503 ELECTRICAL DETAILS 3 OF 3
E-601 ELECTRICAL WIRING DIAGRAM
E-602 DAS SCHEMATIC
E-701 EQUIPMENT SPECIFICATIONS
E-711 LABELS & MARKINGS - MAIN BUILDING
E-801 ONE LINE DIAGRAM
S-001 GENERAL STRUCTURAL NOTES
S-111 ROOF FRAMING PLAN - WEST
S-112 ROOF FRAMING PLAN - NORTH
S-113 ROOF FRAMING PLAN - EAST
S-114 ROOF FRAMING PLAN - SOUTH
S-501 STRUCTURAL DETAILS 1 OF 2
S-502 STRUCTURAL DETAILS 2 OF 2
A-101 WALK PATH LOCATION PLAN - WEST
A-102 WALK PATH LOCATION PLAN - NORTH
A-103 WALK PATH LOCATION PLAN - EAST
A-104 WALK PATH LOCATION PLAN - SOUTH
1. THIS PV SYSTEM INSTALLATION IS SUBJECT TO INSPECTION BY THE VA AND THEIR THIRD PARTY COMMISSIONING
AGENT, SOLAR POWER INTEGRATORS, AND BLUE OAK ENERGY.
2. THIS PROJECT SHALL MEET SAN DIEGO GAS & ELECTRIC INTERCONNECTION REQUIREMENTS.
3. THIS PROJECT SHALL CONFORM TO THE FOLLOWING CODE VERSIONS:
2010 INTERNATIONAL BUILDING CODE
2008 NATIONAL ELECTRICAL CODE
SAN DIEGO VA MEDICAL CENTER
3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161
SOLAR ELECTRIC SYSTEM PROJECT - 210.2 kW DC RATING
STRUCTURAL ENGINEERING FIRM:
ATM ENGINEERING
8950 CAL CENTER DRIVE
SACRAMENTO, CA 95826
CONTACT: TIM McPARTLAND, SE
TEL: 916.859.7300
EMAIL: TIMM@ATMENGINEERING.COM
CA STATE SE LIC. # 3826
AC ALTERNATING CURRENT
AHJ AUTHORITY HAVING
JURISDICTION
APPROX APPROXIMATE
AWG AMERICAN WIRE GAUGE
C/L CENTER LINE
CB COMBINER BOX
CEC CALIFORNIA ENERGY
COMMISSION
DC DIRECT CURRENT
DCD DC DISCONNECT
DI DROP INLET
DISC DISCONNECT
(E) EXISTING
EGC EQUIPMENT GROUNDING
CONDUCTOR
EL ELEVATION
EMT ELECTRICAL METALLIC TUBING
EQ EQUAL
GEC GROUNDING ELECTRODE
CONDUCTOR
ID INSIDE DIAMETER
IMC INTERMEDIATE METAL CONDUIT
JB JUNCTION BOX
LFNC LIQUID TIGHT FLEXIBLE
NON-METALLIC CONDUIT
MCB MAIN COMBINER BOX
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
(N) NEW
OAE OR APPROVED EQUAL
OC ON CENTER
OD OUTSIDE DIAMETER
POCC POINT OF COMMON
COUPLING
PTC PVUSA TEST CONDITIONS
PV PHOTOVOLTAIC
RMC RIGID METAL CONDUIT
SD STORM DRAIN
SF SQUARE FOOT/FEET
SIM SIMILAR
STC STANDARD TEST CONDITIONS
TBD TO BE DETERMINED
TOF TOP OF FOOTING
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VIF VERIFY IN FIELD
XFMR TRANSFORMER
KEYED NOTES
REVISIONS
DETAIL
DETAIL
(ENLARGED PLAN)
G
GROUND TERMINAL
GROUNDING POINT/ROD . . .
MALE/FEMALE
CONNECTIONS
SOLAR PANEL
MODULE FRAME
DISCONNECTING BLADE
OVERCURRENT BREAKER . .
BREAKER
RATING
400A
COMBINER BOX
AND CONDUIT
COMBINER BOX #
FUSE BOX #
FUSE BOX
COMBINER BOX
F1
SOURCE CIRCUIT
SERIES INTERCONNECTION
FUSE
FUSE RATING
DISCONNECTING
BLADE
FUSIBLE DISCONNECT . .
DISCONNECTING BLADE
CURRENT
RATING
10A
FUSE RATING
BLADE DISCONNECT . . .
DISCONNECTING FUSE
10A
FUSED DISCONNECT . . .
400A
DC TO AC INVERTER
AC
DC
NEUTRAL BAR
TERMINATION
POINTS
SECONDARY SIDE
PRIMARY SIDE
ISOLATION TRANSFORMER . .
N
X0
X3
X2
X1
H0
H3
H2
H1
G G
REVISED AREA
CLOUDED
ADDENDUM NUMBER
ON APPLICABLE SHEET
KEYED NOTE DESIGNATION
SHEET WHERE
DETAIL IS LOCATED
DETAIL I.D. LETTER
AREA TO BE ENLARGED
ELEVATION
X-XX
X
DETAIL I.D. LETTER
X-XX
X
DETAIL I.D. LETTER
SHEET WHERE
DETAIL IS LOCATED
X-XX
X
1.
DC DISCONNECT
AND CONDUIT
DC DISCONNECT #
DC DISCONNECT
DCD-X
CB-0X
STRING I.D. NUMBER
STRING I.D. NUMBER
INVERTER
STRING #
COMBINER #
FRAME GROUND POINT
LOCATION IN STRING
NOTES:ABBREVIATIONS:SYMBOLS:
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
G-002
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
PROCEDURAL NOTES:
P1. PRIOR TO COMMENCEMENT OF ANY WORK, THE CONTRACTOR SHALL NOTIFY THE
ENGINEER OF RECORD OF ANY DISCREPANCIES NOTED TO EXISTING CONDITIONS, STRUCTURES, ELECTRICAL RUNS (SPECIFY EXISTING ITEMS), WALLS, PARAPETS, FLASHINGS, ETC. AMONG SITE
CONDITIONS, MANUFACTURER RECOMMENDATIONS OR CODES, REGULATIONS OR RULES OF
JURISDICTIONS HAVING AUTHORITY.
P2. ALL DIMENSIONS OF EXISTING CONDITIONS MUST BE VERIFIED PRIOR TO COMMENCING WORK.
P3. THE CONTRACTOR IS RESPONSIBLE FOR ALL BRACING AND SHORING OF EQUIPMENT DURING
INSTALLATION.
P4. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS, OSHA REQUIREMENTS, AND SAFETY MEASURES ON SITE. THE ENGINEER HAS NO OVERALL SUPERVISORY AUTHORITY
AND NO DIRECT RESPONSIBILITY FOR THE SPECIFIC WORKING CONDITIONS OR FOR POSSIBLE
EXISTING HAZARDS.
P5. CONTRACTOR INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE ENGINEER OF
RECORD FOR APPROVAL PRIOR TO MAKING ANY CHANGES. APPROVED CHANGES SHALL
REQUIRE A DRAWING REVISION TO MAINTAIN CONTROL OVER THE ENGINEER APPROVED DESIGN.
DEVIATION FROM THESE PLANS PRIOR TO ENGINEER APPROVAL PLACES ALL LIABILITY ON THE
CONTRACTOR.
GENERAL NOTES:
G1. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR INSTALLING ALL EQUIPMENT AND
FOLLOWING ALL MANUFACTURER'S OR ENGINEER'S DIRECTIONS AND INSTRUCTIONS SHOWN
HERE.
G2. THE ELECTRICAL CONTRACTOR IS ADVISED ALL DRAWINGS, COMPONENT MANUALS, ESPECIALLY
THE INVERTER MANUALS, ARE TO BE READ AND UNDERSTOOD PRIOR TO INSTALLATION OR
ENERGIZING OF ANY EQUIPMENT. THE CONTRACTOR IS ALSO ADVISED TO HAVE ALL COMPONENT
SWITCHES IN THE OFF (OPEN) POSITION AND FUSES REMOVED PRIOR TO INSTALLATION OF
FUSE-BEARING COMPONENTS.
G3. THE INSTALLATION CREW IS TO HAVE A MINIMUM OF ONE JOURNEYMAN LEVEL ELECTRICIAN ON
SITE AT ALL TIMES WHEN ELECTRICAL WORK IS BEING PERFORMED.
G4. FOR SAFETY IT IS RECOMMENDED THE INSTALLATION CREW ALWAYS HAVE A MINIMUM OF TWO
PEOPLE WORKING TOGETHER.
G5. THIS SOLAR PHOTOVOLTAIC SYSTEM IS TO BE INSTALLED FOLLOWING THE CONVENTIONS OF THE
NATIONAL ELECTRIC CODE. ANY LOCAL CODE WHICH MAY SUPERSEDE THE NEC SHALL GOVERN.
G6. ALL COMPONENTS TO BE INSTALLED WITH THIS SYSTEM ARE TO BE LISTED BY A THIRD PARTY
TESTING AGENCY (UL, ETL, ETC.). EQUIPMENT SHALL BE NEMA 3R OUTDOOR RATED OR BETTER, UNLESS LOCATED INDOORS OR EXPRESSLY SPECIFIED OTHERWISE.
G7. THE CONTRACTOR IS RESPONSIBLE FOR SELECTING AND PURCHASING EQUIPMENT THAT WILL
LAST THE LIFETIME OF THE PV SYSTEM. ALL ENCLOSURES, CONDUIT, STRAPS, PAINTED METAL
SURFACES, CONCRETE, GROUNDING EQUIPMENT, AND OTHER PRODUCTS SHALL BE SELECTED
TO LAST THE LIFETIME OF THE PV SYSTEM. THE ENGINEER SPECIFIES THE MINIMUM REQUIRED
EQUIPMENT AND SPECIFICATIONS TO ACCOMPLISH THE PROJECT AND THE ELECTRICAL
CONTRACTOR IS RESPONSIBLE TO ENSURE THESE SPECIFICATIONS ARE MET OR EXCEEDED WITH
GOOD QUALITY EQUIPMENT, WORKMANSHIP, AND SKILL.
G8. DC VOLTAGE FROM THE ARRAY IS ALWAYS PRESENT AT THE DC DISCONNECT ENCLOSURE AND
THE DC TERMINALS OF THE INVERTER DURING DAYLIGHT HOURS. ALL PERSONS WORKING ON
OR INVOLVED WITH THIS PHOTOVOLTAIC SYSTEM MUST BE WARNED SOLAR MODULES ARE
ENERGIZED WHEN EXPOSED TO DAYLIGHT. THE LINE AND LOAD TERMINALS ON THE DC
DISCONNECTS MAY BE ENERGIZED IN THE OPEN POSITION AND THE SWITCH IS TO BE LABELED
TO COMPLY WITH ARTICLE 690.17 OF THE NEC REFLECTING THIS CONDITION.
G9. ALL PORTIONS OF THIS SOLAR ELECTRIC SYSTEM SHALL BE CLEARLY MARKED IN ACCORDANCE
WITH THE NEC ARTICLE 690.
G10. THE ELECTRICAL CONTRACTOR SHALL PERFORM INITIAL HARDWARE CHECKS AND PV/WIRING
CONDUCTIVITY CHECKS PRIOR TO TERMINATING ANY WIRES. ALL AC AND DC WIRE RUNS SHALL
BE MEGGER TESTED AT 1,000 VDC TO DEMONSTRATE A MINIMUM OF 5 MEGAOHMS RESISTANCE
TO GROUND.
THIS POINT IS REITERATED SEVERAL TIMES IN THESE DRAWINGS BECAUSE IT IS VERY
IMPORTANT TO PREVENT EQUIPMENT DAMAGE!
DO NOT MEGGER THE SOLAR MODULES AS THIS WILL LIKELY DAMAGE THEIR INTERNAL DIODES.
MEGGERING IS INTENDED FOR ALL CONDUCTORS INSTALLED BY THE ELECTRICAL CONTRACTOR.
G11. FOR PROPER MAINTENANCE AND ISOLATION OF INVERTERS, REFER TO ISOLATION PROCEDURE IN
INVERTER OPERATION MANUAL. CONTRACTOR PERFORMING THE MAINTENANCE IS RESPONSIBLE
FOR FOLLOWING ALL LOCKOUT/TAGOUT PROCEDURES.
G12. THIS PHOTOVOLTAIC SYSTEM'S UTILITY INTERCONNECTION POINT SHALL MEET THE SPECIFIC
REQUIREMENTS OF NEC ARTICLE 690.64. FOLLOW THE SPECIFIC INSTRUCTIONS IN THIS DRAWING
SET TO MEET THIS CODE REQUIREMENT.
G13. THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH NEC 690.45 AND NEC
690.47. IF THE REQUIREMENTS DESCRIBED IN THIS DRAWING SET ARE CLOSELY FOLLOWED, THE
GROUNDING REQUIREMENT WILL BE MET. ANY CHANGES WILL NEED TO BE REVIEWED AND
DEEMED ACCEPTABLE BY THE ENGINEER, MANUFACTURER AND LISTING AGENCY FOR PRODUCT
SAFETY.
G14. THE ELECTRICAL CONTRACTOR SHALL COORDINATE COMMISSIONING THE PV AND INVERTER
SYSTEMS WITH SOLAR POWER INTEGRATORS.
G15. THE CONTRACTOR IS RESPONSIBLE FOR MOUNTING ALL EQUIPMENT PER THE ENGINEER'S
REPORT OR MANUFACTURER'S SPECIFICATIONS. IF SPECIFICATIONS ARE NOT APPARENT, THE
CONTRACTOR SHALL USE DILIGENT EFFORTS TO MOUNT EQUIPMENT SUCH THAT IT WILL BE
CLEAN, LEVEL, AND SOLID IN ORDER TO LAST THE LIFETIME OF THIS SOLAR ELECTRIC SYSTEM.
G16. ANY METAL SHAVINGS RESULTING FROM SITE WORK SHALL BE CLEANED FROM ENCLOSURE
INTERIORS, TOP SURFACES OF ENCLOSURES, ROOF SURFACE, GROUND SURFACE, AND ANY
ADDITIONAL AREAS WHERE OXIDIZED OR CONDUCTIVE METAL SHAVINGS MAY CAUSE RUST,
ELECTRICAL SHORT CIRCUITS, OR OTHER DAMAGE.
G17. THE ELECTRICAL CONTRACTOR SHALL CONSIDER THE WEATHERING OF EQUIPMENT OVER TIME
AND ELIMINATE THE POSSIBILITY OF DEGRADATION DUE TO WATER ENTRY AND UV EXPOSURE.
AS A RESULT, THE USE OF UNISTRUT OR SIMILAR MOUNTING SYSTEMS IS REQUIRED TO MOUNT
ENCLOSURES, PULL BOXES, LOAD CENTERS, FUSE BOXES, OR OTHER EQUIPMENT TO ROOFTOPS
AND WALLS TO PREVENT WATER BUILD-UP. WEEP HOLES SHALL BE PROVIDED IN ENCLOSURES
WHERE CONDENSATION OR WATER BUILD-UP MAY OCCUR. SEALING CONDUIT WITH A FIRE
RETARDANT FOAM OR CAULK AT ENCLOSURE ENTRY POINTS IS RECOMMENDED TO MINIMIZE
CONDENSATION AND PESTS IN ENCLOSURES. FOR CONDUIT LOCATIONS RUNNING THROUGH
WALLS FIRE RETARDANT FOAM OR CAULK MUST BE USED TO MAINTAIN THE CURRENT FIRE
RATING OF THE WALL AND MUST COMPLY WITH UL 1479 & UL 723 STANDARDS FOR THROUGH
PENETRATIONS.
ELECTRICAL NOTES:
E1. THE ELECTRICAL CONTRACTOR IS REQUIRED TO USE PERMANENTLY COLOR CODED INSULATION PER THE WIRE
COLOR TABLE SHOWN IN FIGURE 1. PHASE TAPING BLACK CONDUCTORS DOES NOT MEET THIS REQUIREMENT.
THE CONTRACTOR ACCEPTS ALL RISK AND LIABILITY IF THESE INSTRUCTIONS ARE NOT FOLLOWED.
E2. IN EVERY PULL BOX, TERMINAL BOX, AND AT ALL PLACES WHERE WIRES MAY NOT BE READILY IDENTIFIED BY
NAMEPLATE MARKINGS ON THE EQUIPMENT TO WHICH THEY CONNECT, IDENTIFY EACH CIRCUIT WITH A
PLASTIC LABEL OR TAG FOR NUMBER, POLARITY, OR PHASE.
E3. THE LAYOUT OF CONDUIT SHOWN IN THESE PLANS IS INDICATIVE ONLY. CONTRACTOR SHALL ROUTE AND
LOCATE THE CONDUITS TO SUIT SITE CONDITIONS BUT SHALL NOT EXCEED THE MAXIMUM CONDUCTOR
LENGTHS IDENTIFIED ON THE WIRE SCHEDULE. CONTRACTOR WILL COORDINATE ALL CHANGES IN WIRING AND
CONDUIT WITH THE ENGINEER.
E4. WHERE WIRE AND CABLE ROUTING IS NOT SHOWN AND DESTINATION ONLY IS INDICATED, CONTRACTOR SHALL
DETERMINE EXACT ROUTING AND LENGTHS REQUIRED. THE ENGINEER OF RECORD SHALL BE NOTIFIED OF
CHANGES PRIOR TO INSTALLATION.
E5. BENDS SHALL NOT DAMAGE THE RACEWAY OR SIGNIFICANTLY CHANGE THE INTERNAL DIAMETER OF
RACEWAYS (NO KINKS).
E6. SUPPORT CONDUCTORS IN VERTICAL CONDUITS IN ACCORDANCE WITH REQUIREMENTS IN NEC 300.19.
E7. INSTALL ALL WIRING MATERIALS IN A NEAT WORKMANLIKE MANNER. USE GOOD TRADE PRACTICES AS
REQUIRED BY CHAPTER 3 OF THE NEC.
E8. INSTALL CONDUIT TO MAINTAIN PROPER CLEARANCES AND IN A NEAT INCONSPICUOUS MANNER. RUN
PARALLEL AND AT RIGHT ANGLES TO STRUCTURAL MEMBERS OR OTHER CONDUITS. PROVIDE BOXES, FITTINGS, AND BENDS FOR CHANGES IN DIRECTION. FASTEN CONDUIT SECURELY IN PLACE.
E9. SUPPORT CONDUIT USING STEEL PIPE STRAPS OAE, LAY-IN ADJUSTABLE HANGERS, CLEVIS HANGERS, OR
SPLIT-HANGERS. HANGER SPACING SHALL BE INSTALLED PER NEC REQUIREMENTS FOR THE TYPE OF CONDUIT
BEING INSTALLED. USE APPROVED BEAM CLAMPS FOR CONNECTION TO STRUCTURAL MEMBERS.
E10. PROVIDE PULL, JUNCTION, OR CHRISTY BOXES WHERE REQUIRED TO FACILITATE THE INSTALLATION OF WIRING
IN ADDITION TO THOSE SHOWN ON THE DRAWINGS. BENDS IN CONDUITS BETWEEN PULL BOXES SHALL NOT
EXCEED THE EQUIVALENT OF FOUR 90 DEGREE BENDS.
E11. WHEN FIELD CUTTING IS REQUIRED, THE CONDUIT SHALL BE CUT SQUARE AND DEBURRED.
E12. CONDUIT SIZES NOT SPECIFIED SHOULD CONFORM TO NEC SPECIFICATIONS, TO INCLUDE FILL FACTOR AND
DERATING FOR NUMBER OF CONDUCTORS WITH A MINIMUM CONDUIT SIZE BEING 3/4".
E13. THE MINIMUM DC WIRE SIZE ALLOWED SHALL BE #12 AWG COPPER CONDUCTOR.
E14. SAFETY REGULATIONS (LOCK OUT - TAG OUT, ETC..) IS THE FULL RESPONSIBILITY OF THE CONTRACTOR
DURING CONSTRUCTION.
E15. THE WIRING SIZE IS BASED ON THE ESTIMATED CONDUIT ROUTING AS SHOWN IN THIS DRAWING PACKAGE.
SHOULD THE CONDUIT'S LENGTH INCREASE DUE TO RELOCATION OF SOURCE AND/OR ROUTING, THE
CONDUITS AND THE CONDUCTORS MAY NEED TO BE RESIZED. CONTACT THE ENGINEER PRIOR TO MAKING
ANY FIELD CHANGES.
E16. ALL WIRING IN CONDUIT SHALL BE RHW2 ORTHWN-2 FOR 90°C APPLICATIONS. USE BARE COPPER FOR GROUND
FOR ALL EXTERNAL GROUNDING. USE-2 OR APPROVED EQUIVALENT SHALL BE USED FOR ALL EXPOSED OR
HOMERUN WIRING.
E17. FOR INTERCONNECTION VIA BUS TAP:
A. OVERCURRENT PROTECTION (SWITCHING DEVICE AND MEANS OF DISCONNECT) MUST BE LOCATED PER NEC
240.21.
B. THE CONDUCTORS SHALL BE CRIMPED WITH A CRIMP-ON TERMINAL LUG, MANUFACTURED BY ILSCO, BURNDY, OAE. THE TERMINAL LUG SHALL HAVE IDENTIFICATION OR COLOR CODING TO MATCH THE
CONDUCTOR SIZE. TERMINAL LUGS SHALL HAVE LONG BARRELS TO PROVIDE 2 CRIMPS PER TERMINAL LUG
PER CONDUCTOR.
C. CRIMPED TERMINAL LUGS SHALL BE CONSTRUCTED OF PURE COPPER AND TIN PLATED FOR HIGH
CONDUCTIVITY AND RATED FOR 600V AT 90°C.
D. THE CRIMP MUST BE MADE WITH THE MANUFACTURER'S APPROVED TOOL DEVICE TO ACHIEVE THE PROPER
CRIMP CONNECTION.
E. USE STAINLESS STEEL HARDWARE WITH THE FASTENER TORQUED TO MANUFACTURER'S
RECOMMENDATIONS ON ALL THREE PHASES TO COMPLY WITH NEC ARTICLE 110.14.
F. MINIMUM BEND RADIUS SHALL BE OBSERVED TO MAINTAIN GOOD CONDUCTOR QUALITY AND WIRE
MANAGEMENT IN THE LOAD CENTER OR TRANSFORMER. IF THIS BEND RADIUS IS TOO CONSTRICTING, USE
A 90° CRIMP-ON LUG MANUFACTURED BY ILSCO, BURNDY, OAE. 90° CRIMP-ON LUG MUST BE INSTALLED WITH
RATED INSULATION THAT MEETS OR EXCEEDS THE CONDUCTOR INSULATION IT IS BEING USED WITH. IT IS
RECOMMENDED ACCEPTABLE CLEARANCES ARE MAINTAINED WITH THIS BUS TAP FOR SAFE, CONTINUOUS
OPERATION .
G. FOLLOW MANUFACTURER'S GUIDELINES, OR THE APPLICABLE AHJ GUIDELINES, FOR MODIFICATION OF BUS
BAR(S).
E18. ALL CONDUITS SHALL BE FREE OF ANY OBSTRUCTIONS AND PROPERLY SECURED BEFORE WIRE IS PULLED.
E19. ELECTRICAL CONTRACTOR SHALL PROVIDE SIGNAGE TO ALL ELECTRICAL BOXES, JUNCTION BOXES, PULL
BOXES, DC DISCONNECTS, CONDUIT RUNS, AC DISCONNECTS, SUB PANELS, AND MAIN SERVICES PER NEC
ARTICLE 690.
E20. MEGGER TESTING: MEGGER (INSULATION) TEST ALL CONDUCTORS AT 1,000 VDC TO 5 MEGAOHMS BETWEEN
THE CONDUCTOR UNDER TEST AND GROUND WIRE. CONDUCT TEST AFTER WIRE IS PULLED THROUGH THE
CONDUIT BUT BEFORE TERMINATING TO THE MODULES, COMBINERS, DISCONNECTS OR INVERTER. DO NOT
MEGGER TEST THE MODULES AS THEY MAY BE DESIGN LIMITED TO 600 VDC AND MAY DAMAGE THE DEVICE.
E21. AC INTERCONNECTION CONDUCTORS: ALL AC INTERCONNECTION CONDUCTORS SHALL HAVE PERMANENTLY
COLOR CODED INSULATION PER COLOR CODING CHART PROVIDED. PHASE TAPING BLACK CONDUCTORS IS
NOT ACCEPTABLE.
E22. AC INTERCONNECTION CONDUIT SHALL BE UNINTERRUPTED AND CONDUCTORS SHALL BE NON- ACCESSIBLE.
USE OF LB'S, PULL BOXES, OR ANY OTHER CONDUIT BODIES WHICH ALLOW ACCESS TO INTERCONNECTING
CONDUCTORS WHICH TAP ON TO A LIVE BUS SHALL NOT BE PERMITTED.
E23. RACEWAY EXPANSION FITTINGS SHALL BE INSTALLED TO ALLOW FOR THERMAL EXPANSION AND CONTRACTION
WHERE NECESSARY, PER NEC ARTICLE 300.7(B). COMPONENT MANUFACTURER INSTRUCTIONS SHALL BE
FOLLOWED AND ALL ACCESSORIES SHALL BE INSTALLED TO ENSURE PROPER FUNCTIONING OF FITTINGS.
E24. ALL CONDUCTORS SHALL BE COPPER UNLESS SPECIFICALLY NOTED OTHERWISE.
E25. NONCONDUCTIVE COATINGS (SUCH AS PAINT, LACQUER, AND ENAMEL) ON EQUIPMENT TO BE GROUNDED
SHALL BE REMOVED FROM THREADS AND OTHER CONTACT SURFACES TO ENSURE GOOD ELECTRICAL
CONTINUITY OR BE CONNECTED BY MEANS OF FITTINGS DESIGNED SO AS TO MAKE SUCH REMOVAL
UNNECESSARY.
ROOFING AND SEALING NOTES:
R1. A POLYURETHANE BASED ADHESIVE SHALL BE APPLIED TO ANY DRILLED HOLE
FOR FASTENING.
R2. ALL STANDOFFS SHALL BE MADE WATERTIGHT USING APPROVED METHODS BY
THE ROOFING MATERIAL MANUFACTURER, DISTRIBUTOR, OR ENGINEER OF
RECORD.
R3. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY TRANSITION
MATERIAL WHERE THERE IS A DIFFERENCE OF 1/4 " OF HEIGHT OR MORE
BETWEEN THE ROOF AND STANDOFF BASE.
R4. CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLATION OF RIGID FOAM OR
SPRAY FOAM TO FILL ANY VOID AROUND THE STANDOFF, FROM THE BASE UP
TO 6" ABOVE THE ROOF.
R5. IN ORDER TO MAINTAIN THE EXISTING ROOF WARRANTIES ( MATERIALS AND
WORKMANSHIP) ANY REPAIR, MENDING, PATCHING, PENETRATIONS OR
ALTERATIONS OF ANY KIND TO THE EXISTING ROOF SURFACE SHALL BE MADE BY
AN APPROVED AND CERTIFIED (LOCAL) JOHNS MANVILLE ROOFING
SPECIALIST/CONTRACTOR (SEE ATTACHED WARRANTY DOCUMENTS
MODULE INSTALLATION NOTES:
M1. REFER TO THE MODULE MANUAL FOR MORE DETAILS ON RIGGING, UNPACKING,
HANDLING, PLANNING, AND INSTALLATION.
M2. THE MODULES MAY BE SHIPPED WITH SEVERAL MODULES PER BOX. TAKE CARE
WHEN OPENING THE BOX TO ENSURE ALL MODULES ARE SECURELY HANDLED.
M3. NEVER LEAVE A MODULE UNSUPPORTED OR UNSECURED. CONTRACTOR IS
RESPONSIBLE FOR ALL MATERIAL HANDLING ON THE JOB SITE.
SOLAR ARRAY COMMISSIONING:
C1. BEFORE CLOSING DISCONNECTS OR ATTEMPTING TO ENERGIZE THE INVERTERS,
THE FOLLOWING COMMISSIONING PROCEDURE SHALL BE COMPLETED:
A. CHECK THE OPEN CIRCUIT VOLTAGE (V_OC) AND POLARITY (+/-) OF EACH
SOURCE CIRCUIT. RECORD THE VALUES ON COMMISSIONING RECORD
DOCUMENTS.
B. CHECK THE SHORT CIRCUIT CURRENT (I_SC) FOR EACH SOURCE CIRCUIT.
RECORD THE VALUES ON COMMISSIONING RECORD DOCUMENTS.
C. CHECK ALL FUSES, DISCONNECTS, AND OTHER BALANCE OF SYSTEM
COMPONENTS ARE RATED FOR 600 VDC AND THE APPROPRIATE CURRENT
CAPACITY.
D. COMPLETE A VISUAL INSPECTION OF ALL MODULES TO CHECK FOR BROKEN
GLASS, FRAYED WIRES, EXPOSED CONDUCTORS, AND ANY OTHER PROBLEMS
THAT MAY CAUSE A FAULT.
INVERTER COMMISSIONING:
IC1. BEFORE TURNING THE INVERTER ON, OR CLOSING ANY OF THE INVERTER
DISCONNECTS, THE FOLLOWING COMMISSIONING PROCEDURE SHALL BE
COMPLETED:
A. CHECK THE INVERTER IS PROPERLY GROUNDED, AS DESCRIBED BY THE
MANUFACTURER AND THESE INSTRUCTIONS.
B. CHECK THE INVERTER DC INPUT VOLTAGE (V_OC) FROM THE SOLAR ARRAY
FOR PROPER POLARITY INSIDE THE INVERTER CABINET.
C. CHECK DC INPUT VOLTAGE (V_OC) IS WITHIN THE PROPER RANGE IN THE
INVERTER CABINET AS DEFINED BY THE INVERTER RATING LABEL AND
ACCOMPANIED MANUAL.
D. CHECK AC INPUT VOLTAGE IS IN THE PROPER PHASE SEQUENCE (CLOCKWISE)
IF APPLICABLE.
E. CHECK THE AC GRID VOLTAGE, AT THE INVERTER AC TERMINALS, IS WITHIN
THE PROPER RANGE AS DEFINED BY THE INVERTER RATING LABEL AND
ACCOMPANIED MANUAL
F. FOLLOW THE START-UP SEQUENCE IN THE MANUFACTURER'S OPERATION AND
MAINTENANCE MANUAL.
BROWN
PANEL WIRE COLOR
RED (ORG. IF HI LEG)
BLACK
YELLOW
ORANGE
PHASE A
240V OR 208V, 3Ø
PHASE C
PHASE B
DESCRIPTION
PHASE / CODE
FIGURE 1: WIRE COLOR TABLE
BROWN
YELLOW
ORANGE
LETTER
(INTERNAL)
FIELD WIRE
COLOR
480V, 3Ø
PHASE A
PHASE C
PHASE B RED (ORG. IF HI LEG)
BLUE
BLACK
BLUE
BLACK
240/120 1Ø
L2
L1 BLACK
RED RED
AC NEUTRAL N GRAY WHITE
GROUND G GREEN GREEN
BLACK
BLUE
RED
PHASE A
PHASE C
PHASE B
BLACK
BLUE
RED
12KV, 3Ø
VDC POS + BLACK BLACK
VDC NEG - WHITE / STRIPE WHITE / STRIPE
LIGHT SHAFT (TYP)
EQUIPMENT PIT WITH
42" HANDRAILS (TYP)
HVAC EQUIPMENT (TYP)
SAFETY RAILS (TYP)
HVAC LINES (TYP)
PENTHOUSE
FIRE HYDRANT (TYP)
MECHANICAL EQUIPMENT (TYP)
ROOF DRAIN (TYP)
VENT FANS (TYP)
VENTILATION EQUIPMENT (TYP)
ELECTRICAL CONDUIT
FOR SIGN LIGHTING
APPROX.
GEOGRAPHIC
NORTH
1. NOT USED.
NOTES:
1. NOT USED.
KEYED NOTES:
SCALE:
EXISTING SITE PLAN - ROOF TOP
1" = 20' - 0"
40'
GRAPHICAL SCALE
0 20'10'
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-101
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
KEY PLAN
APPROX.
GEOGRAPHIC
NORTH
AREA
ENLARGED
18' OFFSET FROM EDGE
OF BUILDING
MODULE RACKING TILT
BRACKETS
WALK PATH (TYP)
(N)WIND DEFLECTORS(TYP)
MODULE RACKING LATERAL LINKS
MODULE RACKING
LONGITUDINAL LINKS
6' INNER ROOF
EDGE OFFSET
1' OBJECT OFFSET
(RECOMMENDED)
A P
P R
O X
APPROX. 44'-4"
APPROX. 38'-10"
A P
P R
O X
9'-11"
4'-9"
12'-5"9'-10" 32'-2"
H
(E) CONDUIT FOR
SIGN LIGHTING
50'-1"
A P
P R
O X
APPROX. 33'-3"
26'-11"
A P
P R
O X
APPROX. 38'-10"
6'-10"9'-10"
29'-10"
APPROX.
GEOGRAPHIC
NORTH
SCALE:
ARRAY PLAN - WEST
1" = 7' - 0"
16'
GRAPHICAL SCALE
0 8'4'
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-111
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
KEY PLAN
APPROX.
GEOGRAPHIC
NORTH
NOTES:
1. NOT USED.
KEYED NOTES:
1. SHADING ON DECEMBER 21ST FROM 10AM
TO 2PM SHOWN FOR REFERENCE. SHADE IS
PROJECTED ONTO ROOF SURFACE. SHADE
IMPACT ON ELEVATED ARRAY WILL BE
REDUCED. SHADING FROM NEARBY TREES
WAS NOT CONSIDERED IN THIS LAYOUT.
2. DIMENSION IS TO THE CENTERLINE OF TILT
BRACKET.
3. EXISTING ROOF DRAIN. ARRAY SHALL BE
PLACED OVER DRAIN AND SHALL NOT BLOCK
OR OBSTRUCT DRAIN.
L E G E N D
PHOTOVOLTAIC MODULE
OMITTED MODULE
SHADE
AREA
ENLARGED
ROOF EDGE OFFSET
OBSTRUCTION OFFSET
N
0°
90°270°
180°
ARRAY
AZIMUTH
SYSTEM SUMMARY
LOCATION SAN DIEGO
SYSTEM MAIN ROOF
MODULE MODEL KYOCERA KD240GX-LPB
MODULE STC DC RATING 240 W
MODULE PTC RATING 217.3 W
MODULES PER SOURCE CIRCUIT 11 & 12
SITE LATITUDE N 32.5 °
AMBIENT TEMP: ASHRAE 2% HIGH 30 °C
AMBIENT TEMP: ASHRAE MEAN OF EXTREME
ANNUAL DB MIN
2 °C
NO. OF SOURCE CIRCUITS PER INVERTER 4
TOTAL MODULE COUNT 876
TOTAL STC-DC SYSTEM SIZE 210.2kW
MOUNTING SYSTEM SUNLINK
INVERTER MODEL POWER-ONE PVI-10.0-I-OUTD-S-US-480
INVERTER CEC EFFICIENCY 97%
INTERCONNECTION VOLTAGE 480V
INTERCONNECTION TYPE LOAD SIDE BREAKER
ARRAY AZIMUTH 180°
MODULE TILT 20°
3 TYP
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
3' OBJECT OFFSET
(RECOMMENDED)
(N)WIND DEFLECTORS(TYP)
18' OFFSET FROM EDGE
OF BUILDING
MODULE RACKING LATERAL LINKS
MODULE RACKING LONGITUDINAL LINKS
MODULE RACKING TILT
BRACKETS
H
A P
P R
O X
A P
P R
O X
APPROX. 61' APPROX. 55'-6"
A P
P R
O X
A P
P R
O X
APPROX. 61'
APPROX. 55'-6"
21'-10"
21'-11"
21'-11" 21'-10"
APPROX. 6'-10"
APPROX.
GEOGRAPHIC
NORTH
SCALE:
ARRAY PLAN - NORTH
1" = 8' - 0"
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-112
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
16'
GRAPHICAL SCALE
0 8'4'
KEY PLAN
APPROX.
GEOGRAPHIC
NORTH
L E G E N D
PHOTOVOLTAIC MODULE
OMITTED MODULE
SHADE
AREA
ENLARGED
ROOF EDGE OFFSET
OBSTRUCTION OFFSET
NOTES:
1. NOT USED.
KEYED NOTES:
1. SHADING ON DECEMBER 21ST FROM 10AM
TO 2PM SHOWN FOR REFERENCE. SHADE IS
PROJECTED ONTO ROOF SURFACE. SHADE
IMPACT ON ELEVATED ARRAY WILL BE
REDUCED. SHADING FROM NEARBY TREES
WAS NOT CONSIDERED IN THIS LAYOUT.
2. DIMENSION IS TO THE CENTERLINE OF TILT
BRACKET.
3. EXISTING ROOF DRAIN. ARRAY SHALL BE
PLACED OVER DRAIN AND SHALL NOT BLOCK
OR OBSTRUCT DRAIN.
4. EXISTING VENT. PLACE ARRAYS TO CLEAR
EXISTING OBSTRUCTIONS.
4 (TYP.)
3(TYP.)
4 (TYP.)
N
0°
90°270°
180°
ARRAY
AZIMUTH
SYSTEM SUMMARY
LOCATION SAN DIEGO
SYSTEM MAIN ROOF
MODULE MODEL KYOCERA KD240GX-LPB
MODULE STC DC RATING 240 W
MODULE PTC RATING 217.3 W
MODULES PER SOURCE CIRCUIT 11 & 12
SITE LATITUDE N 32.5 °
AMBIENT TEMP: ASHRAE 2% HIGH 30 °C
AMBIENT TEMP: ASHRAE MEAN OF EXTREME
ANNUAL DB MIN
2 °C
NO. OF SOURCE CIRCUITS PER INVERTER 4
TOTAL MODULE COUNT 876
TOTAL STC-DC SYSTEM SIZE 210.2kW
MOUNTING SYSTEM SUNLINK
INVERTER MODEL POWER-ONE PVI-10.0-I-OUTD-S-US-480
INVERTER CEC EFFICIENCY 97%
INTERCONNECTION VOLTAGE 480V
INTERCONNECTION TYPE LOAD SIDE BREAKER
ARRAY AZIMUTH 180°
MODULE TILT 20°
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
APPROX. 44'-4"
APPROX. 44'-4"
A P
P R
O X
APPROX. 38'-10" APPROX. 66'-7"
A P
P R
O X
A P
P R
O X
APPROX. 55'-6"
21'-10"
22'-6"
12'-5"9'-10"
10'-10"
35'-6"
A P
P R
O X
18' OFFSET FROM EDGE
OF BUILDING
MODULE RACKING LATERAL LINKS
MODULE RACKING LONGITUDINAL LINKS
MODULE RACKING TILT
BRACKETS
3' OBJECT OFFSET
(RECOMMENDED)
H
(E) CONDUIT FOR
SIGN LIGHTING
A P
P R
O X
9'-11"
SCALE:
ARRAY PLAN - EAST
1" = 8' - 0"
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-113
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
GRAPHICAL SCALE
APPROX.
GEOGRAPHIC
NORTH
16'0 8'4'
KEY PLAN
APPROX.
GEOGRAPHIC
NORTH
L E G E N D
PHOTOVOLTAIC MODULE
OMITTED MODULE
SHADE
AREA
ENLARGED
ROOF EDGE OFFSET
OBSTRUCTION OFFSET
NOTES:
1. NOT USED.
KEYED NOTES:
1. SHADING ON DECEMBER 21ST FROM 10AM
TO 2PM SHOWN FOR REFERENCE. SHADE IS
PROJECTED ONTO ROOF SURFACE. SHADE
IMPACT ON ELEVATED ARRAY WILL BE
REDUCED. SHADING FROM NEARBY TREES
WAS NOT CONSIDERED IN THIS LAYOUT.
2. DIMENSION IS TO THE CENTERLINE OF TILT
BRACKET.
3. EXISTING ROOF DRAIN. ARRAY SHALL BE
PLACED OVER DRAIN AND SHALL NOT BLOCK
OR OBSTRUCT DRAIN.
N
0°
90°270°
180°
ARRAY
AZIMUTH
SYSTEM SUMMARY
LOCATION SAN DIEGO
SYSTEM MAIN ROOF
MODULE MODEL KYOCERA KD240GX-LPB
MODULE STC DC RATING 240 W
MODULE PTC RATING 217.3 W
MODULES PER SOURCE CIRCUIT 11 & 12
SITE LATITUDE N 32.5 °
AMBIENT TEMP: ASHRAE 2% HIGH 30 °C
AMBIENT TEMP: ASHRAE MEAN OF EXTREME
ANNUAL DB MIN
2 °C
NO. OF SOURCE CIRCUITS PER INVERTER 4
TOTAL MODULE COUNT 876
TOTAL STC-DC SYSTEM SIZE 210.2kW
MOUNTING SYSTEM SUNLINK
INVERTER MODEL POWER-ONE PVI-10.0-I-OUTD-S-US-480
INVERTER CEC EFFICIENCY 97%
INTERCONNECTION VOLTAGE 480V
INTERCONNECTION TYPE LOAD SIDE BREAKER
ARRAY AZIMUTH 180°
MODULE TILT 20°
TYP
A P
P R
O X
A P
P R
O X
APPROX. 16'-7"
APPROX. 22'-2"
APPROX. 49'-11"
72'-11"
APPROX. 33'-3"
21'-11"
A P
P R
O X
A P
P R
O X
41'-8"
38'-7"
(N)WIND DEFLECTORS (TYP)
3' OBJECT OFFSET
(RECOMMENDED)
18' OFFSET FROM EDGE
OF BUILDING
MODULE RACKING LATERAL LINKS, TYP
MODULE RACKING LONGITUDINAL LINKS, TYP
MODULE RACKING TILT
BRACKETS
H
(E) CONDUIT FOR
SIGN LIGHTING
SCALE:
ARRAY PLAN - SOUTH
1" = 8' - 0"
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-114
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
GRAPHICAL SCALE
APPROX.
GEOGRAPHIC
NORTH
16'0 8'4'
KEY PLAN
APPROX.
GEOGRAPHIC
NORTH
L E G E N D
AREA
ENLARGED
PHOTOVOLTAIC MODULE
OMITTED MODULE
SHADE
ROOF EDGE OFFSET
OBSTRUCTION OFFSET
NOTES:
1. NOT USED.
KEYED NOTES:
1. SHADING ON DECEMBER 21ST FROM 10AM
TO 2PM SHOWN FOR REFERENCE. SHADE IS
PROJECTED ONTO ROOF SURFACE. SHADE
IMPACT ON ELEVATED ARRAY WILL BE
REDUCED. SHADING FROM NEARBY TREES
WAS NOT CONSIDERED IN THIS LAYOUT.
2. DIMENSION IS TO THE CENTERLINE OF TILT
BRACKET.
3. EXISTING ROOF DRAIN. ARRAY SHALL BE
PLACED OVER DRAIN AND SHALL NOT BLOCK
OR OBSTRUCT DRAIN.
4. EXISTING VENT. PLACE ARRAYS TO CLEAR
EXISTING OBSTRUCTIONS.
5. TRIM WIND DEFLECTOR TO ALLOW DRAIN
ACCESS.
N
0°
90°270°
180°
ARRAY
AZIMUTH
SYSTEM SUMMARY
LOCATION SAN DIEGO
SYSTEM MAIN ROOF
MODULE MODEL KYOCERA KD240GX-LPB
MODULE STC DC RATING 240 W
MODULE PTC RATING 217.3 W
MODULES PER SOURCE CIRCUIT 11 & 12
SITE LATITUDE N 32.5 °
AMBIENT TEMP: ASHRAE 2% HIGH 30 °C
AMBIENT TEMP: ASHRAE MEAN OF EXTREME
ANNUAL DB MIN
2 °C
NO. OF SOURCE CIRCUITS PER INVERTER 4
TOTAL MODULE COUNT 876
TOTAL STC-DC SYSTEM SIZE 210.2kW
MOUNTING SYSTEM SUNLINK
INVERTER MODEL POWER-ONE PVI-10.0-I-OUTD-S-US-480
INVERTER CEC EFFICIENCY 97%
INTERCONNECTION VOLTAGE 480V
INTERCONNECTION TYPE LOAD SIDE BREAKER
ARRAY AZIMUTH 180°
MODULE TILT 20°
TYP
TYP
D-2
D-3
D-4
T-3
T-4
U-1
U-2
U-3
U-4
T-1
T-2
QB-4
QB-3
R-3
R-4
S-2
S-3
S-4
R-1
R-2
QA-2
S-1
S-2
1.
(N) STRING INVERTERS (TYP.)
(N) PV AC SUB-PANEL
(N) WALKWAYS
A
E-401
2.
(TYP.)
K&L
F
(TYP.)
(E) CONDUIT FOR
SIGN LIGHTING
A
(TYP.)
E
2 STRINGS TO
INVERTER Q ON SOUTH
ROOF
APPROX.
GEOGRAPHIC
NORTH
NOTES:
1. SOME RACKING COMPONENTS NOT SHOWN
FOR CLARITY.
2. EQUIPMENT LOCATIONS AND CONDUIT
ROUTES ARE SHOWN DIAGRAMMATICALLY.
FIELD COORDINATE MOST FEASIBLE
EQUIPMENT LOCATIONS AND CONDUIT
ROUTING.
3. SEE E-601 FOR INVERTER/STRING
SCHEDULES.
KEYED NOTES:
SCALE:
EQUIPMENT LOCATION &
DC WIRING PLAN - WEST
1" = 8' - 0"
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-121
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
1. OMITTED MODULE(S). RACKING IS INSTALLED
BUT NO MODULE(S) ARE INSTALLED.
2. SEE E-125 FOR AC CONDUIT.
L E G E N D
16'
GRAPHICAL SCALE
0 8'4'
KEY PLAN
APPROX.
GEOGRAPHIC
NORTH
AREA
ENLARGED
PHOTOVOLTAIC MODULE
OMITTED MODULE
STRINGING
(N) WALK PATH
DC CONDUIT
N
A-1
A-2
A-3
A-4
B-1
B-3
B-4
C-2
C-4
D-2
D-3
D-4
F-3
F-4
G-1
G-2
G-4
G-3
E-1
E-3
E-2
E-4
F-1
F-2
C-1
B-2
C-3
D-1
A
E-401
1.
E
(TYP.)
F
(TYP.)
1.
1.
1.
(N) STRING INVERTERS (TYP.)
(N) PV AC SUB-PANEL
1.
APPROX.
GEOGRAPHIC
NORTH
NOTES:
1. SOME RACKING COMPONENTS NOT SHOWN
FOR CLARITY.
2. EQUIPMENT LOCATIONS AND CONDUIT
ROUTES ARE SHOWN DIAGRAMMATICALLY.
FIELD COORDINATE MOST FEASIBLE
EQUIPMENT LOCATIONS AND CONDUIT
ROUTING.
3. SEE E-601 FOR INVERTER/STRING
SCHEDULES.
KEYED NOTES:
SCALE:
EQUIPMENT LOCATION &
DC WIRING PLAN - NORTH
1" = 8' - 0"
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-122
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
L E G E N D
16'
GRAPHICAL SCALE
0 8'4'
KEY PLAN
APPROX.
GEOGRAPHIC
NORTH
AREA
ENLARGED
PHOTOVOLTAIC MODULE
OMITTED MODULE
STRINGING
DC CONDUIT
1. CONTRACTOR TO FIELD LOCATE CONDUIT
ROUTE. VERIFY ROUTE DOES NOT EXCEED
CONDUCTOR LENGTH SHOWN IN TABLES ON
SHEETS E-601 & E-602. IF ROUTE EXCEEDS,
VERIFY NEW LENGTH WITH ENGINEER OF
RECORD. CONDUITS SHALL BE SUPPORTED
PER DETAILS K, L & M ON SHEET E-501.
(N) WALK PATH
H-1
H-2
H-3
H-4
L-1
L-2
L-3
L-4
M-1
M-2
M-3
J-4
K-4
K-3
K-1
K-2
J-3
J-2
J-1
M-4
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
KYOCERA KD235 KYOCERA KD235 KYOCERA KD235
(N) STRING INVERTERS (TYP.)
(N) PV AC SUB-PANEL
A
E-401
1.
E
(TYP.)
F
(TYP.)
(E) CONDUIT FOR
SIN LIGHTING
1.
1.
1.
1.
(N) DAS
4" CONDUIT TO (E)
SERVICE DISCONNECT
1" CONDUIT TO DAS
APPROX.
GEOGRAPHIC
NORTH
NOTES:
1. SOME RACKING COMPONENTS NOT SHOWN
FOR CLARITY.
2. EQUIPMENT LOCATIONS AND CONDUIT
ROUTES ARE SHOWN DIAGRAMMATICALLY.
FIELD COORDINATE MOST FEASIBLE
EQUIPMENT LOCATIONS AND CONDUIT
ROUTING.
3. SEE E-601 FOR INVERTER/STRING
SCHEDULES.
KEYED NOTES:
SCALE:
EQUIPMENT LOCATION &
DC WIRING PLAN - EAST
1" = 8' - 0"
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-123
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
1. CONTRACTOR TO FIELD LOCATE CONDUIT
ROUTE. VERIFY ROUTE DOES NOT EXCEED
CONDUCTOR LENGTH SHOWN IN TABLES ON
SHEETS E-601 & E-602. IF ROUTE EXCEEDS,
VERIFY NEW LENGTH WITH ENGINEER OF
RECORD. CONDUITS SHALL BE SUPPORTED
PER DETAILS K, L & M ON SHEET E-501.
L E G E N D
16'
GRAPHICAL SCALE
0 8'4'
KEY PLAN
APPROX.
GEOGRAPHIC
NORTH
AREA
ENLARGED
PHOTOVOLTAIC MODULE
OMITTED MODULE
STRINGING
DC CONDUIT
QA-1
P-1
QA-2
P-2
P-3
P-4
N-2N-1
N-4
N-3
(N) STRING INVERTERS (TYP.)
(N) PV AC SUB-PANEL
A
E-401
E
(TYP.)
F
(TYP.)
(E) CONDUIT FOR
SIGN LIGHTING
1.
1.
1.
2 STRINGS FROM WEST
ROOF TO INVERTER Q
APPROX.
GEOGRAPHIC
NORTH
NOTES:
1. SOME RACKING COMPONENTS NOT
SHOWN FOR CLARITY.
2. EQUIPMENT LOCATIONS AND CONDUIT
ROUTES ARE SHOWN
DIAGRAMMATICALLY. FIELD COORDINATE
MOST FEASIBLE EQUIPMENT LOCATIONS
AND CONDUIT ROUTING.
3. SEE E-601 FOR INVERTER/STRING
SCHEDULES.
KEYED NOTES:
SCALE:
EQUIPMENT LOCATION &
DC WIRING PLAN - SOUTH
1" = 8' - 0"
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-124
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
L E G E N D
16'
GRAPHICAL SCALE
0 8'4'
KEY PLAN
APPROX.
GEOGRAPHIC
NORTH
AREA
ENLARGED
PHOTOVOLTAIC MODULE
OMITTED MODULE
STRINGING
DC CONDUIT
1. CONTRACTOR TO FIELD LOCATE CONDUIT
ROUTE. VERIFY ROUTE DOES NOT EXCEED
CONDUCTOR LENGTH SHOWN IN TABLES ON
SHEETS E-601 & E-602. IF ROUTE EXCEEDS,
VERIFY NEW LENGTH WITH ENGINEER OF
RECORD. CONDUITS SHALL BE SUPPORTED
PER DETAILS K, L & M ON SHEET E-501.
(E) STAIR WELL 7
(E) FIRST FLOOR
BALCONY FACADE
(E) BASEMENT
LEVEL NORTH
EXTERIOR WALL
(N) AC DISCONNECTS
(N) METER
(N) AC
DISCONNECT
(N) AC CONDUIT
FROM INVERTERS
(N) AC CONDUIT
TO POCC
BASEMENT LEVEL
DETAIL NOT
SHOWN
B
(N) PULL BOX
36x36x12
(N) 12x12x36 GUTTER
(N) AC CONDUIT
FROM INVERTERS
(N) AC CONDUIT
TO POCC
ELECTRICAL
ROOM B231
(E) SUBSTATION C
(E) SWBD C2
POCC
(E) SUBSTATION D
TELEPHONE
ROOM B167
(N) AC CONDUIT FROM ROOF
PENETRATION THROUGH
STACKED ELECTRICAL ROOMS
(FROM INVERTERS)
(N) PULL BOX
36x36x12
(N) AC CONDUIT TO BASEMENT
(N) AC CONDUIT FROM PV PANEL IN
PENTHOUSE ROOM 7006
(FROM INVERTERS)
(N) NORTH ARRAY STRING
INVERTERS AND PV AC
PANELBOARD
(N) EAST ARRAY STRING
INVERTERS AND PV AC
PANELBOARD (TYP.)
(N) SOUTH ARRAY STRING
INVERTERS AND PV AC
PANELBOARD
(N) WEST ARRAY
STRING INVERTERS,
PV AC PANELBOARD
(N) SWITCHBOARD IN
PENTHOUSE
ELECTRICAL ROOM
(N)REVENUE METER
AND DAS ENCLOSURE
FUTURE BACK OF MODULE
TEMPERATURE SENSOR
FUTURE WEATHER
STATION
FUTURE PLANE OF ARRAY
IRRADIANCE SENSOR
FUTURE DATA CONDUIT
FUTURE WEATHER STATION
POWER CONDUIT
E-501
C
E-501
B
E-501
A
APPROX.
GEOGRAPHIC
NORTH
NOTES:
1. EQUIPMENT LOCATIONS AND CONDUIT
ROUTES ARE SHOWN DIAGRAMMATICALLY.
FIELD COORDINATE MOST FEASIBLE
EQUIPMENT LOCATIONS AND CONDUIT
ROUTING.
KEYED NOTES:
SCALE:
A
EQUIPMENT LOCATION PLAN - OVERVIEW
1" = 20' - 0"
1. SOME EQUIPMENT NOT SHOW FOR CLARITY.
2. CONTRACTOR TO FIELD LOCATE CONDUIT
ROUTE. VERIFY ROUTE DOES NOT EXCEED
CONDUCTOR LENGTH SHOWN IN TABLES ON
SHEETS E-601 & E-602. IF ROUTE EXCEEDS,
VERIFY NEW LENGTH WITH ENGINEER OF
RECORD. CONDUITS SHALL BE SUPPORTED
ON ROOF TOP AND ATTACHED TO WALLS
PER DETAILS J, K, L & M ON SHEET E-501.
L E G E N D
40'
GRAPHICAL SCALE
0 20'10'
AC CONDUIT PATH
PV EQUIPMENT
SCALE:
C
EQUIPMENT LOCATION PLAN
BASEMENT LEVEL AC ROUTE
1/8" = 1' - 0"
SCALE:
B
EQUIPMENT LOCATION PLAN
6TH FLOOR INTERSTITIAL
1 : 100
GRAPHICAL SCALE
0 4' 16'8'
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-125
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
APPROVED RECORD DOCUMENT
This record document is approved for the design shown in these drawings. The engineer has not reviewed the construction project for compliance with the record documents.
Blue Oak Energy, Inc.
Davis, CA
By: ZACK ZOLLER Date: 05.23.2012
2 (TYP.)
(N) AC DISCONNECT
(N)CT CABINET FOR
SDG&E METER
(N) AC
DISCONNECT
(E)STAIR WELL #7
(E) NORTH EXTERIOR
BASEMENT WALL
(N) PULL BOX 36X36X12
6" MIN.
6"
6' MAX.
HEIGHT
6' MAX
HEIGHT
APPROX. 12'-6" (4 INVERTERS)
APPROX. 17'-8" (5 INVERTERS)
APPROX. 20'-2" (7 INVERTERS)
6'
S-502
A U
R O
R A
A U
R O
R A
A U
R O
R A
A U
R O
R A
A U
R O
R A
A U
R O
R A
A U
R O
R A
APPROX. 12"
APPROX. 7'-1"
APPROX. 10'-4" (3 INVERTERS)2'-1" (REF)
NOTES:
1. ALL WALL PENETRATIONS SHALL BE
SEALED WITH FIRE RATED CAULKING TO
MAINTAIN THE PROPER FIRE RATING OF
THE WALL.
KEYED NOTES:
1560 Drew Avenue, Davis, CA 95618 - www.blueoakenergy.com - Phone: 530.747.2026
PRELIMINARY 50% DESIGN 08-19-11
E-401
PRELIMINARY 60% ARRAY RE-DESIGN 09-19-11
PRELIMINARY 90% DESIGN 10-12-11
THIS DRAWING IS THE PROPERTY
OF BLUE OAK ENERGY, INC.
UNTIL RELEASED TO THE VA AS
RECORD DOCUMENTS. THIS
INFORMATION IS CONFIDENTIAL
AND IS TO BE USED ONLY IN
CONNECTION WITH WORK
DESCRIBED BY BLUE OAK
ENERGY, INC. NO PART IS TO BE
DISCLOSED TO OTHERS
WITHOUT WRITTEN PERMISSION
FROM BLUE OAK ENERGY, INC.
CONFIDENTIALITY
STATEMENT:
100% PERMIT SET 10-17-11
REV 1 - VA COMMENTS ADDRESSED 12-06-11
REV 2 - 3RD PARTY COMMENTS ADDRESSED 01-30-12
REV 3 - S & W WING REDESIGN FOR FUTURE HVAC 09-07-12
REV 4 - REDESIGN FOR INSTALLED HVAC/VENTS 03-14-13
REV 5 - RECORD DRAWINGS 05-23-13
1. SEE DETAILS A & B ON SHEET S-502 FOR
INVERTER RACK SUPPORT.
2. FOR 3 INVERTERS, ONLY 2 X 5'-2" RACK
SECTIONS NEEDED FOR THE 3 INVERTERS
AND AC PANELBOARD.
SCALE:
B
EQUIPMENT ELEVATION
3/8" = 1' -0"
SCALE:
A
INVERTER ELEVATIONS
3/4" = 1' -0"
1.
4'
GRAPHICAL SCALE
0 2'1'
2'
GRAPHICAL SCALE
0 1'6''
2.
SERVICE LOOP
SERVICE LOOP
ZIP-TIE JUMPER TO
LONG. LINK (TYP)
LONG. LINK (TYP)
TILT BRACKET (TYP)
MODULE
JUNCTION BOX
(TYP)
JUMPER
MODULE
LEADS (TYP)
MODULE (TYP)
1-5/8" UNISTRUT
CHANNEL 12 GA
GALVANIZED
2-HOLE 12 GA STEEL
GALVANIZED STRIP
UNIS…