This document provides details for a federal contract solicitation to upgrade electrical systems at the Loma Linda VA Healthcare System. The requirement is for the removal and replacement of approximately 150 120/208 volt electrical panels. The project will be set aside for Service-Disabled Veteran-Owned Small Businesses and firms must be listed as verified in the SBA VetCert database. The NAICS code is 236220 for commercial and institutional building construction with a $45 million size standard. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 is the contracting agency. Responses are due based on the standard solicitation timeline.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Loma Linda - Jerry L. Pettis VAHCS - Loma Linda, California

Electrical Condition Assessment - Arc Flash Hazard Evaluation

Prepared for: Dept. of Veterans Affairs Section 6 Page 6 Prepared by: Wiley|Wilson

BUS: 1_SW US-1A West R: 1_FDR A-3 12.000 5.860 5.860 5.740 0.017 0.083 Yes Yes SWG 152 20.871 36.000 0.703 (*N22a) (*S0)

BUS: 1_SW US-1B West R: 1_FDR B-3 12.000 5.840 5.840 5.720 0.017 0.083 Yes Yes SWG 152 20.813 36.000 0.701 (*N22a) (*S0)

BUS: 1_SW US-2A East R: 1_FDR B-2 12.000 6.010 6.010 5.890 0.017 0.083 Yes Yes SWG 152 21.476 36.000 0.723 (*N22a) (*S0)

BUS: 1_SW US-2B East R: 1_FDR A-2 12.000 6.010 6.010 5.890 0.017 0.083 Yes Yes SWG 152 21.483 36.000 0.723 (*N22a) (*S0)

BUS: 1_SW US-3A West R: 1_FDR A-3 12.000 5.800 5.800 5.680 0.017 0.083 Yes Yes SWG 152 20.649 36.000 0.696 (*N22a) (*S0)

BUS: 1_SW US-3B West R: 1_FDR A-3 12.000 5.790 5.790 5.680 0.017 0.083 Yes Yes SWG 152 20.625 36.000 0.695 (*N22a) (*S0)

BUS: 1_SW US-4A East R: 1_FDR B-2 12.000 6.060 6.060 5.930 0.017 0.083 Yes Yes SWG 152 21.676 36.000 0.729 (*N22a) (*S0)

BUS: 1_SW US-4B East R: 1_FDR A-2 12.000 6.060 6.060 5.940 0.017 0.083 Yes Yes SWG 152 21.683 36.000 0.730 (*N22a) (*S0)

BUS: 1_SW US-5A East R: 1_FDR A-1 12.000 6.060 6.060 5.930 0.017 0.083 Yes Yes SWG 152 21.667 36.000 0.729 (*N22a) (*S0)

BUS: 1_SW US-5B East R: 1_FDR B-1 12.000 6.040 6.040 5.920 0.017 0.083 Yes Yes SWG 152 21.605 36.000 0.727 (*N22a) (*S0)

BUS: 1_SW US-6 East R: 1_FDR A-1 12.000 6.050 6.050 5.920 0.017 0.083 Yes Yes SWG 152 21.633 36.000 0.728 (*N22a) (*S0)

BUS: 1_US-7-1 R: 1_FDR A-3 12.000 5.740 5.740 5.620 0.017 0.083 Yes Yes SWG 152 20.402 36.000 0.688 (*N22a) (*S0)

DISC: CGFC_FC1 FU: CGFC_FC1 0.480 2.250 1.120 0.910 2.000 0.000 Yes Yes PNL 25 84.186 18.000 15.024 (*N9) (*S3)

DISC: CGFC_FC2 FU: CGFC_FC2 0.480 2.250 1.120 0.910 2.000 0.000 Yes Yes PNL 25 84.186 18.000 15.024 (*N9) (*S3)

PNL: CGFC_FCL CB: CGFC_T-FCL 0.208 1.540 1.540 1.170 1.981 0.000 Yes Yes PNL 25 50.383 18.000 6.470 (*N5) (*S0)

DISC: 1_AH-23 Suply Fan CB: 1_AH-23 0.480 14.180 14.180 8.840 0.010 0.000 Yes Yes PNL 25 7.601 18.000 0.290 (*S3)

DISC: 1_AHU-31 MCP: 1_AH-31 0.480 12.440 12.440 7.900 0.015 0.000 Yes Yes PNL 25 9.039 18.000 0.386 (*S3)

TABLE 6.1 - ARC FLASH EVALUATION REPORT

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Medium Voltage System

Service Bays 1-3

Notes

Prepared for: Dept. of Veterans Affairs Section 6 Page 7 Prepared by: Wiley|Wilson

TABLE 6.1 - ARC FLASH EVALUATION REPORT

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

DISC: 1_AJAY Elev CB: 1_MCC-M1A 0.208 1.970 1.930 1.360 2.000 0.000 Yes Yes PNL 25 56.217 18.000 7.745 (*N9) (*N22a) (*S3)

DISC: 1_AutoRad 1 FU: 1_Auto Rad 1 0.480 12.500 12.500 7.930 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

DISC: 1_CB 1 Room 6 FU: 1_CB 1 Room 6 0.480 11.030 11.030 7.130 0.010 0.000 Yes Yes PNL 25 6.601 18.000 0.230 (*S3)

DISC: 1_CB2 FU: 1_CB 2 Room 7 0.480 9.190 9.190 6.100 0.008 0.000 Yes Yes PNL 25 5.330 18.000 0.162 (*N4b) (*S3)

DISC: 1_CU-1(FC-1) FU: 1_FC-1 0.480 8.090 8.090 5.470 0.004 0.000 Yes Yes PNL 25 3.251 18.000 0.072 (*N4b) (*S3)

DISC: 1_E-1 MCP: 1_E1

CageWasher Ex Fan 0.480 2.070 2.070 1.710 0.015 0.000 Yes Yes PNL 25 3.296 18.000 0.074 (*S3)

DISC: 1_E-10 MCP: 1_E10 Fl 1 Radio Iso 0.480 3.780 3.770 2.850 0.015 0.000 Yes Yes PNL 25 4.624 18.000 0.128 (*S3)

DISC: 1_E-3 MCP: 1_E3 Ex Fan Canopy Fl 1 0.480 2.220 2.220 1.810 0.015 0.000 Yes Yes PNL 25 3.432 18.000 0.079 (*S3)

DISC: 1_E-4 MCP: 1_E-4 0.480 4.440 4.350 3.210 0.015 0.000 Yes Yes PNL 25 5.064 18.000 0.149 (*S3)

DISC: 1_E-8 MCP: 1_E8 Gen Ex Fl 1 Ex Fan 0.480 3.290 3.260 2.520 0.015 0.000 Yes Yes PNL 25 4.279 18.000 0.113 (*S3)

DISC: 1_E-9 MCP: 1_E9 Fl 1 Fume Hood 0.480 3.780 3.770 2.850 0.015 0.000 Yes Yes PNL 25 4.624 18.000 0.128 (*S3)

DISC: 1_EF-68 MCP: 1_EF-68 0.480 2.240 2.220 1.810 0.015 0.000 Yes Yes PNL 25 3.448 18.000 0.079 (*S3)

DISC: 1_EF-7B MCP: 1_Unk 0.480 1.470 1.460 1.270 0.015 0.000 Yes Yes PNL 25 2.713 18.000 0.054 (*N21a) (*S2)

DISC: 1_P-1 CB: 1_P-1 0.480 10.230 9.760 5.420 0.039 0.000 Yes Yes PNL 25 13.057 18.000 0.706 (*N3) (*S4)

DISC: 1_P-2 CB: 1_P-2 0.480 12.940 12.490 7.890 0.014 0.000 Yes Yes PNL 25 8.874 18.000 0.374 (*S3)

DISC: 1_PHP 2.1 FU: 1_2IHA 0.480 1.350 1.340 1.000 0.000 0.000 Yes Yes PNL 25 74.056 18.000 12.174 (*N3) (*N4a) (*N5) (*S4)

DISC: 1_PHP 2.2 FU: 1_2IHA 0.480 1.350 1.340 1.000 0.000 0.000 Yes Yes PNL 25 74.056 18.000 12.174 (*N3) (*N4a) (*N5) (*S4)

DISC: 1_PHP 2.3 FU: 1_2IHA 0.480 1.240 1.230 0.930 0.000 0.000 Yes Yes PNL 25 81.275 18.000 14.181 (*N3) (*N4a) (*N5) (*S4)

DISC: 1_Pnl B CB: 1_MCC-M1A 0.208 3.790 3.790 2.200 2.000 0.000 Yes Yes PNL 25 76.129 18.000 12.738 (*N9) (*N22a) (*S3)

Prepared for: Dept. of Veterans Affairs Section 6 Page 8 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

DISC: 1_PUMP 4-3-1 FU: 1_Pnl 4IHA 0.480 3.550 3.520 2.680 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N5) (*S0)

DISC: 1_Pump 4-3-2 FU: 1_Pnl 4IHA 0.480 3.020 2.970 2.320 0.000 0.000 Yes Yes PNL 25 18.290 18.000 1.227 (*N4a) (*N5) (*S4)

DISC: 1_Pump 4-3-3 FU: 1_Pnl 4IHA 0.480 2.840 2.800 2.210 0.000 0.000 Yes Yes PNL 25 24.271 18.000 1.952 (*N4a) (*N5) (*S4)

DISC: 1_RM 3 FU: 1_Rad #3 0.480 2.320 2.320 1.880 0.000 0.000 Yes Yes PNL 25 36.577 18.000 3.826 (*N4a) (*S4)

DISC: 1_RM 4 FU: 1_Room 4 0.480 2.270 2.270 1.850 0.000 0.000 Yes Yes PNL 25 37.733 18.000 4.026 (*N4a) (*S4)

DISC: 1_SW-4CA CB: 1_MDBA Main 0.480 14.890 12.940 6.810 2.000 0.000 Yes Yes PNL 25 163.863 18.000 44.816 (*N3) (*N9) (*S4)

DISC: 1_SW-4CI CB: 1_US-1A Main 0.480 16.110 13.700 8.380 2.000 0.000 Yes Yes PNL 25 189.827 18.000 57.051 (*N9) (*S5)

DISC: 1_SW-4EA CB: 1_MDBA Main 0.480 14.780 12.880 6.780 2.000 0.000 Yes Yes PNL 25 162.265 18.000 44.102 (*N3) (*N9) (*S6)

DISC: 1_SW-4EI CB: 1_US-1A Main 0.480 15.610 13.270 8.160 2.000 0.000 Yes Yes PNL 25 187.063 18.000 55.694 (*N9) (*S5)

EP: 1_Grinder CB: 1_Grinder 0.480 5.850 5.800 4.110 0.016 0.000 Yes Yes PNL 25 6.156 18.000 0.205 (*S3)

EP: 1_Irrigation CB: 1_Irrigation Booster Pump 0.480 11.230 11.020 7.100 0.015 0.000 Yes Yes PNL 25 8.400 18.000 0.342 (*S3)

EP: 1_Smart Flow CB: 1_Smart Flow 0.480 8.680 8.630 5.780 0.014 0.000 Yes Yes PNL 25 7.215 18.000 0.267 (*S3)

MCC: 1_MCC-M1A CB: 1_MCC-M1A 0.480 24.770 24.740 14.210 0.070 0.000 Yes Yes MCC 25 34.053 18.000 3.402 (*N22a) (*S3)

MCC: 1_MCC-MAA CB: 1_MCC-MAA 0.480 23.080 22.880 13.280 0.070 0.000 Yes Yes MCC 25 32.730 18.000 3.188 (*S3)

MCC: 1_MCC-MAB CB: 1_MCC-MAB 0.480 11.420 10.880 7.000 0.070 0.000 Yes Yes MCC 25 22.029 18.000 1.665 (*N21a) (*S2)

PNL: 1_1AHA FU: 1_Pnl 1AHA 0.480 16.880 16.880 10.250 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1ALA FU: 1_Pnl 1ALA 0.208 6.590 6.590 3.240 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1ALB FU: 1_Pnl 1ALB 0.208 6.400 6.400 3.180 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1ALC FU: 1_Pnl 1ALC 0.208 6.400 6.400 3.180 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

Prepared for: Dept. of Veterans Affairs Section 6 Page 9 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_1ALD FU: 1_Pnl 1ALD 0.208 5.880 5.880 2.550 0.017 0.000 Yes Yes PNL 25 4.573 18.000 0.126 (*N3) (*S4)

PNL: 1_1ALE CB: 1_1ALE Main 0.208 6.520 6.520 2.740 0.010 0.000 Yes Yes PNL 25 3.512 18.000 0.082 (*N3) (*S3)

PNL: 1_1ALF CB: 1_1ALF Main 0.208 1.210 1.210 0.990 0.010 0.000 Yes Yes PNL 25 1.793 18.000 0.027 (*S3)

PNL: 1_1IHA FU: 1_1IHA 0.480 18.600 18.600 11.140 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1ILA FU: 1_Pnl 1ILA 0.208 10.210 10.210 4.410 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*S0)

PNL: 1_1ILB FU: 1_Pnl 1ILB 0.208 10.020 10.020 4.350 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*S0)

PNL: 1_1ILC FU: 1_Pnl 1ILC 0.208 10.020 10.020 4.350 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*S0)

PNL: 1_1ILD FU: 1_Pnl 1ILD 0.208 9.250 9.250 3.500 0.021 0.000 Yes Yes PNL 25 6.484 18.000 0.224 (*N3) (*N21b) (*N22a) (*S4)

PNL: 1_1ILE FU: 1_Pnl 1ILE 0.208 9.660 9.660 4.250 0.008 0.000 Yes Yes PNL 25 4.197 18.000 0.110 (*N4b) (*S3)

PNL: 1_1ILF FU: 1_Pnl 1ILF 0.208 10.960 10.960 4.640 0.008 0.000 Yes Yes PNL 25 4.448 18.000 0.121 (*N4b) (*S3)

PNL: 1_1ILG CB: 1_1ILG Main 0.208 1.220 1.220 0.990 0.010 0.000 Yes Yes PNL 25 1.803 18.000 0.027 (*S3)

PNL: 1_1ILG (T-13) FU: 1_T-13 0.208 5.050 5.050 2.290 2.000 0.000 Yes Yes PNL 25 78.600 18.000 13.424 (*N3) (*N5) (*N9) (*S3)

PNL: 1_2AHA FU: 1_Pnl 2AHA 0.480 14.320 14.320 8.910 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2CA CB: 1_2CA Main 0.208 5.340 5.340 2.380 2.000 0.000 Yes Yes PNL 25 80.539 18.000 13.971 (*N3) (*N9) (*N22a) (*S3)

PNL: 1_2CA1 CB: 1_2CA1 Main 0.208 4.800 4.800 2.600 0.017 0.000 Yes Yes PNL 25 4.637 18.000 0.129 (*S3)

PNL: 1_2CA1B CB: 1_2CA1B Main 0.208 4.710 4.710 2.560 0.010 0.000 Yes Yes PNL 25 3.363 18.000 0.076 (*S3)

PNL: 1_2CA3 CB: 1_2CA3 Main 0.208 3.200 3.200 1.950 0.017 0.000 Yes Yes PNL 25 3.846 18.000 0.095 (*S3)

PNL: 1_2CA4A CB: 1_2CA Main 0.208 4.300 4.300 2.400 2.000 0.000 Yes Yes PNL 25 81.150 18.000 14.145 (*N5) (*N9) (*S3)

PNL: 1_2CA4B CB: 1_Pnl 2CA4B 0.208 3.460 3.460 2.060 0.017 0.000 Yes Yes PNL 25 3.985 18.000 0.101 (*S3)

Prepared for: Dept. of Veterans Affairs Section 6 Page 10 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_2CA4C CB: 1_Pnl 2CA4C 0.208 3.460 3.460 2.060 0.017 0.000 Yes Yes PNL 25 3.985 18.000 0.101 (*S3)

PNL: 1_2CA4D CB: 1_2CA4D Main 0.208 4.610 4.610 2.530 0.019 0.000 Yes Yes PNL 25 4.931 18.000 0.143 (*N22a) (*S3)

PNL: 1_2CA4D1 CB: 1_Pnl 2CA4D1 0.208 4.440 4.440 2.460 0.010 0.000 Yes Yes PNL 25 3.272 18.000 0.073 (*N22a) (*S3)

PNL: 1_2CA4D2 CB: 1_Pnl 2CA4D2 0.208 4.440 4.440 2.460 0.010 0.000 Yes Yes PNL 25 3.272 18.000 0.073 (*N22a) (*S3)

PNL: 1_2CI CB: 1_2CI Main 0.208 5.210 5.210 2.750 2.000 0.000 Yes Yes PNL 25 88.698 18.000 16.368 (*N9) (*N22a) (*S3)

PNL: 1_2CI1 CB: 1_2CI1 Main 0.208 4.300 4.300 2.410 0.017 0.000 Yes Yes PNL 25 4.410 18.000 0.119 (*N22a) (*S3)

PNL: 1_2CI2 CB: 1_2CI2 Main 0.208 3.650 3.650 2.140 0.017 0.000 Yes Yes PNL 25 4.086 18.000 0.105 (*N22a) (*S3)

PNL: 1_2CI3 CB: 1_2CI3 Main 0.208 3.250 3.250 1.980 0.017 0.000 Yes Yes PNL 25 3.874 18.000 0.096 (*N22a) (*S3)

PNL: 1_2CI4 CB: 1_2CI4 Main 0.208 3.150 3.150 1.930 0.017 0.000 Yes Yes PNL 25 3.817 18.000 0.094 (*N22a) (*S3)

PNL: 1_2EA CB: 1_2EA Main 0.208 2.840 2.840 1.800 0.020 0.000 Yes Yes PNL 25 4.061 18.000 0.104 (*S3)

PNL: 1_2EA1 CB: 1_2EA1 Main 0.208 2.660 2.660 1.720 0.017 0.000 Yes Yes PNL 25 3.531 18.000 0.083 (*S3)

PNL: 1_2EA2 CB: 1_2EA2 Main 0.208 2.380 2.380 1.590 0.017 0.000 Yes Yes PNL 25 3.351 18.000 0.076 (*S3)

PNL: 1_2EA3 CB: 1_2EA3 Main 0.208 2.220 2.220 1.510 0.017 0.000 Yes Yes PNL 25 3.247 18.000 0.072 (*S3)

PNL: 1_2EA4 CB: 1_2EA4 Main 0.208 2.170 2.170 1.490 0.017 0.000 Yes Yes PNL 25 3.213 18.000 0.071 (*S3)

PNL: 1_2EI CB: 1_2EI Main 0.208 2.750 2.750 1.760 0.020 0.000 Yes Yes PNL 25 4.003 18.000 0.101 (*S3)

PNL: 1_2EI1 CB: 1_2EI1 Main 0.208 2.350 2.350 1.570 0.017 0.000 Yes Yes PNL 25 3.334 18.000 0.075 (*S3)

PNL: 1_2EI2 CB: 1_2EI2 Main 0.208 2.250 2.250 1.520 0.017 0.000 Yes Yes PNL 25 3.265 18.000 0.073 (*S3)

PNL: 1_2EI3 CB: 1_2EI3 Main 0.208 2.100 2.100 1.450 0.017 0.000 Yes Yes PNL 25 3.164 18.000 0.069 (*S3)

PNL: 1_2EI4 CB: 1_2EI4 Main 0.208 1.800 1.800 1.310 0.017 0.000 Yes Yes PNL 25 2.950 18.000 0.061 (*S3)

Prepared for: Dept. of Veterans Affairs Section 6 Page 11 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_2IHA FU: 1_2IHA 0.480 16.520 16.400 9.990 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N22a) (*S0)

PNL: 1_2ILA FU: 1_2ILA 0.208 6.420 6.420 3.190 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2ILB FU: 1_2ILB 0.208 6.420 6.420 3.190 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2ILC FU: 1_2ILC 0.208 6.850 6.850 3.340 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2ILC 2 CB: 1_2ILC 2 Main 0.208 1.160 1.160 0.960 0.010 0.000 Yes Yes PNL 25 1.759 18.000 0.026 (*N22a) (*S3)

PNL: 1_3AHA FU: 1_3AHA 0.480 12.720 12.720 8.050 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3ALA FU: 1_Pnl 3ALA 0.208 6.770 6.770 3.310 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3ALB FU: 1_Pnl 3ALB 0.208 7.550 7.550 3.570 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3ALC FU: 1_Pnl 3ALC 0.208 7.300 7.300 3.490 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3ALD FU: 1_Pnl 3ALD 0.208 7.300 7.300 3.490 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3ALE CB: 1_3ALE Main 0.208 1.210 1.210 0.990 0.010 0.000 Yes Yes PNL 25 1.792 18.000 0.027 (*S3)

PNL: 1_3IHA FU: 1_3IHA 0.480 14.740 14.740 9.140 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3ILA FU: 1_3ILA 0.208 8.010 8.010 3.720 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3ILB FU: 1_3ILB 0.208 7.470 7.470 3.540 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3ILC FU: 1_3ILC 0.208 5.700 5.700 2.930 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3ILD CB: 1_3ILD Main 0.208 1.210 1.210 0.990 0.010 0.000 Yes Yes PNL 25 1.792 18.000 0.027 (*S3)

PNL: 1_3ILS FU: 1_3ILS 0.208 2.190 2.190 1.500 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4AHA FU: 1_4AHA 0.480 11.690 11.690 7.490 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4ALA FU: 1_Pnl 4ALA 0.208 6.020 6.020 3.050 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

Prepared for: Dept. of Veterans Affairs Section 6 Page 12 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_4ALB FU: 1_Pnl 4ALB 0.208 6.020 6.020 3.050 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4ALC FU: 1_Pnl 4ALC 0.208 6.020 6.020 3.050 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4ALD FU: 1_Pnl 4ALD 0.208 6.020 6.020 3.050 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4ALE FU: 1_Pnl 4ALE 0.208 6.170 6.170 2.630 0.025 0.000 Yes Yes PNL 25 5.997 18.000 0.197 (*N3) (*S8)

PNL: 1_4ALF CB: 1_4ALF Main 0.208 1.210 1.210 0.990 0.015 0.000 Yes Yes PNL 25 2.300 18.000 0.041 (*S3)

PNL: 1_4CA CB: 1_ATS-CA 0.480 20.440 20.440 12.080 0.014 0.000 Yes Yes PNL 25 11.388 18.000 0.564 (*N5) (*N22a) (*S3)

PNL: 1_4CA1 CB: 1_ATS-CA 0.480 15.710 15.710 9.640 0.017 0.000 Yes Yes PNL 25 11.097 18.000 0.540 (*N5) (*N22a) (*S3)

PNL: 1_4CA2 CB: 1_4CA2 Main 0.480 11.400 11.400 7.330 0.017 0.000 Yes Yes PNL 25 9.288 18.000 0.403 (*N22a) (*S3)

PNL: 1_4CA3 CB: 1_4CA3 Main 0.480 9.660 9.660 6.370 0.017 0.000 Yes Yes PNL 25 8.462 18.000 0.346 (*N22a) (*S3)

PNL: 1_4CA4 CB: 1_4CA4 Main 0.480 9.180 9.180 6.090 0.017 0.000 Yes Yes PNL 25 8.223 18.000 0.330 (*N22a) (*S3)

PNL: 1_4CI CB: 1_4CI Main 0.480 22.620 22.620 13.170 0.020 0.000 Yes Yes PNL 25 15.083 18.000 0.894 (*N22a) (*S3)

PNL: 1_4CI1 CB: 1_4CI1 Main 0.480 12.860 12.860 8.130 0.017 0.000 Yes Yes PNL 25 9.942 18.000 0.451 (*N22a) (*S3)

PNL: 1_4CI2 CB: 1_4CI2 Main 0.480 10.120 10.120 6.630 0.017 0.000 Yes Yes PNL 25 8.688 18.000 0.362 (*N22a) (*S3)

PNL: 1_4CI3 CB: 1_4CI3 Main 0.480 8.680 8.680 5.810 0.017 0.000 Yes Yes PNL 25 7.967 18.000 0.314 (*N22a) (*S3)

PNL: 1_4CI4 CB: 1_4CI4 Main 0.480 8.280 8.280 5.580 0.017 0.000 Yes Yes PNL 25 7.758 18.000 0.300 (*N22a) (*S3)

PNL: 1_4EA CB: 1_4EA Main 0.480 15.820 15.820 9.700 0.020 0.000 Yes Yes PNL 25 12.332 18.000 0.642 (*S3)

PNL: 1_4EA1 CB: 1_4EA1 Main 0.480 13.050 13.050 8.230 0.017 0.000 Yes Yes PNL 25 10.022 18.000 0.457 (*S3)

PNL: 1_4EA2 CB: 1_4EA2 Main 0.480 9.810 9.810 6.450 0.017 0.000 Yes Yes PNL 25 8.535 18.000 0.351 (*S3)

PNL: 1_4EA3 CB: 1_4EA3 Main 0.480 8.470 8.470 5.690 0.017 0.000 Yes Yes PNL 25 7.858 18.000 0.307 (*S3)

Prepared for: Dept. of Veterans Affairs Section 6 Page 13 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_4EA4 CB: 1_4EA4 Main 0.480 8.090 8.090 5.470 0.017 0.000 Yes Yes PNL 25 7.660 18.000 0.294 (*N21b) (*S3)

PNL: 1_4EI CB: 1_4EI Main 0.480 14.930 14.930 9.230 0.020 0.000 Yes Yes PNL 25 11.936 18.000 0.609 (*S3)

PNL: 1_4EI1 CB: 1_4EI1 Main 0.480 8.890 8.890 5.930 0.017 0.000 Yes Yes PNL 25 8.075 18.000 0.321 (*S3)

PNL: 1_4EI2 CB: 1_4EI2 Main 0.480 7.430 7.430 5.090 0.017 0.000 Yes Yes PNL 25 7.302 18.000 0.272 (*S3)

PNL: 1_4EI3 CB: 1_4EI3 Main 0.480 6.610 6.610 4.600 0.017 0.000 Yes Yes PNL 25 6.833 18.000 0.244 (*S3)

PNL: 1_4EI4 CB: 1_4EI4 Main 0.480 6.370 6.370 4.460 0.017 0.000 Yes Yes PNL 25 6.694 18.000 0.236 (*S3)

PNL: 1_4IHA FU: 1_Pnl 4IHA 0.480 14.210 13.990 8.720 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4ILA FU: 1_Pnl 4ILA 0.208 5.860 5.860 2.990 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4ILB FU: 1_Pnl 4ILB 0.208 5.990 5.990 3.040 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4ILD CB: 1_4ILD Main 0.208 1.220 1.220 0.990 0.010 0.000 Yes Yes PNL 25 1.797 18.000 0.027 (*S3)

PNL: 1_4LIC FU: 1_Pnl 4ILC 0.208 4.860 4.860 2.620 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_B CB: 1_Pnl B 0.208 2.820 2.820 1.790 2.000 0.000 Yes Yes PNL 25 66.533 18.000 10.211 (*N9) (*N22a) (*S3)

PNL: 1_DPHH CB: 1_DPHH 0.480 13.750 12.460 7.800 0.070 0.000 Yes Yes PNL 25 24.459 18.000 1.977 (*N21b) (*S3)

PNL: 1_MP CB: 1_M1S 0.480 11.560 11.560 7.420 0.021 0.000 Yes Yes PNL 25 10.648 18.000 0.505 (*N5) (*S3)

PNL: 1_MP Cath Lab FU: 1_Main Disc Cath Lab 0.480 8.210 8.210 5.540 0.010 0.000 Yes Yes PNL 25 5.590 18.000 0.175 (*S3)

PNL: 1_MP2 CB: 1_Cath Lab UPS 0.480 4.380 4.380 3.240 0.009 0.000 Yes Yes PNL 25 3.695 18.000 0.089 (*S3)

PNL: 1_PHL CB: 1_PHL Main 0.208 0.800 0.800 0.630 2.000 0.000 Yes Yes PNL 25 33.589 18.000 3.326 (*N3) (*N9) (*S3)

PNL: 1_Pnl 2ALA FU: 1_Pnl 2ALA 0.208 6.350 6.350 3.160 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_Pnl 2ALB FU: 1_Pnl 2ALB 0.208 6.180 6.180 3.100 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

Prepared for: Dept. of Veterans Affairs Section 6 Page 14 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_Pnl 2ALC FU: 1_Pnl 2ALC 0.208 6.180 6.180 3.100 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_Pnl 2ALD FU: 1_Pnl 2ALD 0.208 6.020 6.020 3.050 0.008 0.000 Yes Yes PNL 25 3.372 18.000 0.077 (*N4b) (*S3)

PNL: 1_Pnl 2CA2 CB: 1_2CA2 Main 0.208 3.590 3.590 2.120 0.017 0.000 Yes Yes PNL 25 4.055 18.000 0.104 (*S3)

PNL: 1_Pnl BAH FU: 1_Pnl BAH 0.480 13.080 13.080 8.250 0.004 0.000 Yes Yes PNL 25 4.261 18.000 0.112 (*N4b) (*S3)

PNL: 1_RLA CB: 1_XF T-A5 Pnl RLA 0.208 1.370 1.370 0.910 1.233 0.000 Yes Yes PNL 25 31.923 18.000 3.060 (*N3) (*S4)

PNL: 1_UPS Rm 329 Bypass CB: 1_UPS Room 329 0.480 23.530 23.530 13.620 0.070 0.000 Yes Yes PNL 25 33.087 18.000 3.245 (*S3)

PNL: 1_UPS Rm 329 Bypass 2 CB: 1_M1S 0.480 21.470 21.470 12.590 0.019 0.000 Yes Yes PNL 25 14.058 18.000 0.797 (*S3)

PNL: SB04-3 UPS FU: 1_Pnl 4IHA 0.208 11.090 11.090 4.680 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N5) (*N22a) (*S0)

PNL: Starbucks_ILD FU: 1_Pnl ILD (Starbucks) 0.208 3.380 3.380 2.030 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: Unlabeled Phone Room Pnl FU: 1_Pnl 1ILD 0.208 2.810 2.810 1.520 0.936 0.000 Yes Yes PNL 25 37.783 18.000 4.035 (*N3) (*N22a) (*S4)

SWBD: 1_D1AH CB: 1_D1AH 0.480 23.560 23.560 13.640 0.070 0.000 Yes Yes PNL 25 33.111 18.000 3.249 (*N21b) (*S3)

SWBD: 1_D1AL CB: 1_D1AH 0.208 7.620 7.620 3.060 0.150 0.000 Yes Yes PNL 25 19.614 18.000 1.376 (*N3) (*N5) (*S3)

SWBD: 1_D1IH CB: 1_Pnl D1IH 0.480 26.710 26.710 15.180 0.070 0.000 Yes Yes PNL 25 35.533 18.000 3.648 (*S3)

SWBD: 1_D1IL FU: 1_T-11 0.208 10.580 10.580 3.850 0.511 0.000 Yes Yes PNL 25 47.922 18.000 5.960 (*N3) (*S4)

SWBD: 1_D2AH CB: 1_D2AH 0.480 22.080 22.080 12.900 0.070 0.000 Yes Yes PNL 25 31.926 18.000 3.060 (*S3)

SWBD: 1_D2AL FU: 1_XF T-A2 0.208 6.560 6.560 3.240 0.000 0.000 Yes Yes PNL 25 21.470 18.000 1.596 (*N4a) (*S4)

SWBD: 1_D2IH CB: 1_Pnl D2IH 0.480 23.610 23.480 13.580 0.070 0.000 Yes Yes PNL 25 33.148 18.000 3.255 (*S3)

SWBD: 1_D2IL CB: 1_Pnl D2IH 0.208 7.460 7.460 3.540 0.070 0.000 Yes Yes PNL 25 13.619 18.000 0.756 (*N5) (*S3)

SWBD: 1_D3AL CB: 1_D3AH 0.208 8.190 8.190 3.210 0.150 0.000 Yes Yes PNL 25 20.168 18.000 1.440 (*N3) (*N5) (*S5)

Prepared for: Dept. of Veterans Affairs Section 6 Page 15 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

SWBD: 1_D3HA CB: 1_D3AH 0.480 20.770 20.770 12.250 0.070 0.000 Yes Yes PNL 25 30.846 18.000 2.892 (*S3)

SWBD: 1_D3IH CB: 1_Pnl D3IH 0.480 21.970 21.960 12.840 0.070 0.000 Yes Yes PNL 25 31.829 18.000 3.045 (*S3)

SWBD: 1_D3IL FU: 1_XF T-13 0.208 8.240 8.240 3.230 0.147 0.000 Yes Yes PNL 25 20.069 18.000 1.429 (*N3) (*S4)

SWBD: 1_D4AH CB: 1_D4AH 0.480 19.610 19.610 11.650 0.070 0.000 Yes Yes PNL 25 29.857 18.000 2.742 (*S3)

SWBD: 1_D4AL CB: 1_D4AH 0.208 8.090 8.090 3.180 0.150 0.000 Yes Yes PNL 25 20.053 18.000 1.427 (*N3) (*N5) (*S6)

SWBD: 1_D4IH CB: 1_Pnl D4IH 0.480 20.660 20.430 12.050 0.070 0.000 Yes Yes PNL 25 30.754 18.000 2.878 (*S3)

SWBD: 1_D4IL FU: 1_XF T-14 0.208 6.530 6.530 3.220 0.000 0.000 Yes Yes PNL 25 22.041 18.000 1.666 (*N4a) (*S4)

SWBD: 1_HXRP CB: 1_Pnl HXRP 0.480 11.990 11.990 6.510 0.150 0.000 Yes Yes PNL 25 31.482 18.000 2.991 (*N3) (*S6)

SWBD: 1_MDBA CB: 1_MDBA Main 0.480 25.240 23.250 13.320 0.320 0.000 Yes Yes PNL 25 83.555 18.000 14.840 (*S3)

SWBD: 1_US-1A CB: 1_US-1A Main 0.480 16.280 13.850 8.460 2.000 0.000 Yes Yes PNL 25 190.818 18.000 57.540 (*N9) (*S5)

SWBD: 1_US-1B CB: 1_US-1B Main 0.480 16.310 13.880 8.470 2.000 0.000 Yes Yes PNL 25 191.046 18.000 57.653 (*N9) (*S6)

DISC: 1_AH-2 CB: 1_AH-2 SF SB2

Tunnel 0.480 8.690 8.690 5.820 0.015 0.000 Yes Yes PNL 25 7.414 18.000 0.279 (*S11)

Disc: 1_AH-24 RF CB: 1_R-21 RF 0.480 3.140 3.140 2.440 0.018 0.000 Yes Yes PNL 25 4.626 18.000 0.129 (*S11)

DISC: 1_CB-TX1T CB: 1_DP-TX1T 0.480 13.070 13.070 8.240 0.020 0.000 Yes Yes PNL 25 11.079 18.000 0.539 (*N5) (*N22a) (*S2)

DISC: 1_Comp 4 Rm. 1B-32 FU: 1_Comp 4 Rm 1B- 32 0.208 2.630 2.630 1.450 0.008 0.000 Yes Yes PNL 25 2.067 18.000 0.034 (*N3) (*N4b) (*S11)

DISC: 1_Comp2 CB: 1_Comp2 Rm 1B- 17 0.208 1.200 1.200 0.840 0.311 0.000 Yes Yes PNL 25 13.054 18.000 0.705 (*N3) (*S12)

DISC: 1_Comp3 CB: 1_Comp3 1B-08 0.208 1.200 1.200 0.840 0.311 0.000 Yes Yes PNL 25 13.054 18.000 0.705 (*N3) (*S12)

DISC: 1_CTR-A 11-13-15 CB: 1_Comp1 Rm 1B- 09 0.208 1.200 1.200 0.840 0.311 0.000 Yes Yes PNL 25 13.054 18.000 0.705 (*N3) (*S12)

Service Bays 2-4

Prepared for: Dept. of Veterans Affairs Section 6 Page 16 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

DISC: 1_Elev #1 FU: Elev #1 0.480 26.540 26.150 14.870 0.004 0.000 Yes Yes PNL 25 6.345 18.000 0.216 (*N4b) (*N22a) (*S10)

DISC: 1_Fan Coil #1 FU: 1_Fan Coil 1 0.480 9.500 9.500 6.280 0.004 0.000 Yes Yes PNL 25 3.559 18.000 0.084 (*N4b) (*S0)

DISC: 1_Fuel Tanks CB: 1_Fuel Tanks 0.480 3.630 3.630 2.760 0.150 0.000 Yes Yes PNL 25 18.356 18.000 1.234 (*S11)

DISC: 1_NE Patio Offices FU: 1_2NE Patio- Offices 0.480 4.270 4.270 3.170 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

DISC: 1_P1A MCP: 1_Chiller Pump 1A 0.480 3.150 3.140 2.440 0.015 0.000 Yes Yes PNL 25 4.170 18.000 0.108 (*S0)

DISC: 1_P1B MCP: 1_Chiller Pump 1B 0.480 3.150 3.140 2.440 0.015 0.000 Yes Yes PNL 25 4.170 18.000 0.108 (*S0)

DISC: 1_Roof Chiller FU: 1_Dist ILHpl Roof Chiller 0.480 12.210 11.870 6.430 0.008 0.000 Yes Yes PNL 25 5.618 18.000 0.177 (*N3) (*N4b) (*S10)

DISC: 1_SW-CD CB: 1_MDBD Main 0.480 15.340 15.070 9.280 2.000 0.000 Yes Yes PNL 25 186.574 18.000 55.455 (*N9) (*S14)

DISC: 1_SW-CL FU: 1_US-2A East 0.480 27.290 24.310 13.770 2.000 0.000 Yes Yes PNL 25 265.619 18.000 99.012 (*N5) (*N9) (*S10)

DISC: 1_SW-ED CB: 1_MDBD Main 0.480 22.540 22.280 11.030 2.000 0.000 Yes Yes PNL 25 216.042 18.000 70.543 (*N3) (*N9) (*S11)

DISC: 1_SW-EL CB: 1_US 2A Main 0.480 24.430 21.760 12.530 2.000 0.000 Yes Yes PNL 25 250.922 18.000 90.182 (*N9) (*S10)

DISC: 1_Unk secondary of T- QL CB: 1_TQL 2QL1 0.208 1.710 1.710 1.260 1.992 0.000 Yes Yes PNL 25 53.084 18.000 7.049 (*S16)

DISC: CRAC UNIT #1 CB: 1_CRAC UNIT #1 0.480 9.360 9.360 6.200 0.015 0.000 Yes Yes PNL 25 7.679 18.000 0.295 (*S15)

DISC: CRAC UNIT #2 CB: 1_CRAC UNIT #2 0.480 9.360 9.360 6.200 0.015 0.000 Yes Yes PNL 25 7.679 18.000 0.295 (*S15)

DISC: MRI Trailer Power FU: 1_MRI Outside Disc SW 0.480 10.860 10.860 7.040 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

MCC: 1_MCC-MDA CB: 1_MCC-MDA 0.480 12.850 12.850 8.120 0.240 0.000 Yes Yes MCC 25 49.877 18.000 6.364 (*S12)

MCC: 1_MCC-MLA CB: 1_MCC-MLA 0.480 23.760 23.720 13.710 0.070 0.000 Yes Yes MCC 25 33.268 18.000 3.274 (*S10)

PNL: 1_1DHA FU: 1_1DHA 0.480 15.680 15.680 9.630 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1DLA FU: 1_1DLA 0.208 10.160 10.160 4.400 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*S0)

Prepared for: Dept. of Veterans Affairs Section 6 Page 17 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_1DLB FU: 1_1DLB 0.208 9.950 9.950 4.340 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*N22a) (*S0)

PNL: 1_1DLC FU: 1_1DLC 0.208 9.300 9.300 4.130 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1DLD FU: 1_1DLD 0.208 6.610 6.610 3.250 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1DLE FU: 1_1DLE 0.208 8.800 8.800 3.380 0.025 0.000 Yes Yes PNL 25 6.980 18.000 0.252 (*N3) (*S12)

PNL: 1_1DLF FU: 1_XFMR T-D1 0.208 9.210 9.210 3.490 0.805 0.000 Yes Yes PNL 25 59.748 18.000 8.559 (*N3) (*S12)

PNL: 1_1LHA FU: 1_1LHA 0.480 17.680 17.680 10.670 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1LLA FU: 1_1LLA 0.208 9.450 9.450 4.180 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1LLB FU: 1_1LLB 0.208 9.810 9.810 4.290 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1LLC FU: 1_1LLC 0.208 8.980 8.980 4.030 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1LLD FU: 1_1LLD 0.208 8.540 8.540 3.890 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_1LLE FU: 1_1LLE 0.208 10.470 10.470 4.490 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*N22a) (*S0)

PNL: 1_1LLF FU: 1_1LLF 0.208 6.330 6.330 3.150 0.008 0.000 Yes Yes PNL 25 3.450 18.000 0.079 (*N4b) (*S10)

PNL: 1_1LLG CB: 1_1LLG Main 0.208 1.200 1.200 0.980 0.010 0.000 Yes Yes PNL 25 1.785 18.000 0.027 (*S10)

PNL: 1_2CD CB: 1_XFMR T-CD 0.208 5.340 5.340 2.800 0.001 0.000 Yes Yes PNL 25 0.876 18.000 0.008 (*N5) (*S11)

PNL: 1_2CD1 CB: 1_XFMR T-CD 0.208 4.580 4.580 2.510 0.001 0.000 Yes Yes PNL 25 0.816 18.000 0.007 (*N5) (*S11)

PNL: 1_2CD2 CB: 1_XFMR T-CD 0.208 4.050 4.050 2.310 0.001 0.000 Yes Yes PNL 25 0.771 18.000 0.007 (*N5) (*S11)

PNL: 1_2CD3 CB: 1_XFMR T-CD 0.208 3.590 3.590 2.120 0.001 0.000 Yes Yes PNL 25 0.729 18.000 0.006 (*N5) (*S11)

PNL: 1_2CD4A CB: 1_XFMR T-CD 0.208 3.620 3.620 2.130 0.001 0.000 Yes Yes PNL 25 0.732 18.000 0.006 (*N5) (*S11)

PNL: 1_2CD4B CB: 1_2CD4B 0.208 3.500 3.500 2.080 0.017 0.000 Yes Yes PNL 25 4.005 18.000 0.101 (*S11)

Prepared for: Dept. of Veterans Affairs Section 6 Page 18 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_2CD4C CB: 1_2CD4C 0.208 3.500 3.500 2.080 0.017 0.000 Yes Yes PNL 25 4.005 18.000 0.101 (*S11)

PNL: 1_2CL CB: 1_2CL Main 0.208 5.350 5.350 2.380 2.000 0.000 Yes Yes PNL 25 80.691 18.000 14.014 (*N3) (*N9) (*N22a) (*S10)

PNL: 1_2CL1 CB: 1_2CL1 Main 0.208 3.750 3.750 2.180 0.017 0.000 Yes Yes PNL 25 4.136 18.000 0.107 (*N22a) (*S10)

PNL: 1_2CL2 CB: 1_2CL2 Main 0.208 3.590 3.590 2.120 0.017 0.000 Yes Yes PNL 25 4.055 18.000 0.104 (*N22a) (*S10)

PNL: 1_2CL3 CB: 1_2CL3 Main 0.208 3.200 3.200 1.950 0.017 0.000 Yes Yes PNL 25 3.846 18.000 0.095 (*N22a) (*S10)

PNL: 1_2CL4A CB: 1_2CL Main 0.208 4.010 4.010 2.290 2.000 0.000 Yes Yes PNL 25 78.621 18.000 13.429 (*N5) (*N9) (*N22a) (*S10)

PNL: 1_2CL4B CB: 1_2CL4B 0.208 3.870 3.870 2.230 0.017 0.000 Yes Yes PNL 25 4.197 18.000 0.110 (*S10)

PNL: 1_2CL4C CB: 1_2CL4C 0.208 3.870 3.870 2.230 0.017 0.000 Yes Yes PNL 25 4.197 18.000 0.110 (*S10)

PNL: 1_2DHA FU: 1_2DHA 0.480 20.410 20.410 12.060 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N22a) (*S0)

PNL: 1_2DLA FU: 1_2DLA 0.208 7.300 7.300 3.490 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2DLB FU: 1_2DLB 0.208 7.510 7.510 3.560 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2DLC FU: 1_2DLC 0.208 7.260 7.260 3.480 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2DLD FU: 1_2DLD 0.208 6.440 6.440 3.190 0.008 0.000 Yes Yes PNL 25 3.478 18.000 0.081 (*N4b) (*S11)

PNL: 1_2DLE CB: 1_2DLE Main 0.208 1.160 1.160 0.960 0.010 0.000 Yes Yes PNL 25 1.759 18.000 0.026 (*N22a) (*S11)

PNL: 1_2ED CB: 1_2ED Main 0.208 2.820 2.820 1.790 0.020 0.000 Yes Yes PNL 25 4.049 18.000 0.103 (*S11)

PNL: 1_2ED1 CB: 1_2ED1 Main 0.208 2.650 2.650 1.710 0.017 0.000 Yes Yes PNL 25 3.521 18.000 0.082 (*S11)

PNL: 1_2ED2 CB: 1_2ED2 Main 0.208 2.470 2.470 1.630 0.017 0.000 Yes Yes PNL 25 3.413 18.000 0.078 (*S11)

PNL: 1_2ED3 CB: 1_2ED3 Main 0.208 2.310 2.310 1.550 0.017 0.000 Yes Yes PNL 25 3.306 18.000 0.074 (*S11)

PNL: 1_2ED4 CB: 1_2ED4 Main 0.208 1.850 1.850 1.330 0.017 0.000 Yes Yes PNL 25 2.985 18.000 0.063 (*S11)

Prepared for: Dept. of Veterans Affairs Section 6 Page 19 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_2EL CB: 1_2EL Main 0.208 2.640 2.640 1.710 0.020 0.000 Yes Yes PNL 25 3.928 18.000 0.098 (*S10)

PNL: 1_2EL1 CB: 1_2EL1 Main 0.208 2.070 2.070 1.440 0.017 0.000 Yes Yes PNL 25 3.141 18.000 0.068 (*S10)

PNL: 1_2EL2 CB: 1_2EL2 Main 0.208 2.260 2.260 1.530 0.017 0.000 Yes Yes PNL 25 3.273 18.000 0.073 (*S10)

PNL: 1_2EL3 CB: 1_2EL3 Main 0.208 2.110 2.110 1.460 0.017 0.000 Yes Yes PNL 25 3.173 18.000 0.069 (*S10)

PNL: 1_2EL4 CB: 1_2EL4 Main 0.208 1.980 1.980 1.390 0.017 0.000 Yes Yes PNL 25 3.078 18.000 0.066 (*S10)

PNL: 1_2LHA FU: 1_2LHA 0.480 17.290 17.290 10.470 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2LLA FU: 1_2LLA 0.208 9.730 9.730 4.270 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*S0)

PNL: 1_2LLB FU: 1_2LLB 0.208 9.730 9.730 4.270 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*S0)

PNL: 1_2LLC FU: 1_2LLC 0.208 9.090 9.090 4.070 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2LLD FU: 1_2LLD 0.208 8.720 8.720 3.950 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_2LLE CB: 1_2LLE Main 0.208 1.180 1.180 0.970 0.010 0.000 Yes Yes PNL 25 1.770 18.000 0.027 (*S10)

PNL: 1_2LLE Ne Patio Offices FU: 1_Disc 2NE Patio- Offices 0.208 2.000 2.000 1.410 0.000 0.000 Yes Yes PNL 25 36.828 18.000 3.869 (*N4a) (*N5) (*S12)

PNL: 1_2QL1 CB: 1_2QL1 Main 0.208 1.580 1.580 1.010 2.000 0.000 Yes Yes PNL 25 46.076 18.000 5.588 (*N3) (*N9) (*S12)

PNL: 1_3DHA FU: 1_3DHA 0.480 12.330 12.330 7.840 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3DLA FU: 1_3DLA 0.208 8.700 8.700 3.350 0.090 0.000 Yes Yes PNL 25 15.350 18.000 0.920 (*N3) (*S12)

PNL: 1_3DLB FU: 1_3DLB 0.208 8.700 8.700 3.350 0.090 0.000 Yes Yes PNL 25 15.350 18.000 0.920 (*N3) (*S12)

PNL: 1_3DLC FU: 1_3DLC 0.208 9.030 9.030 4.050 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3DLD FU: 1_3DLD 0.208 8.660 8.660 3.930 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3DLE FU: 1_3DLE 0.208 11.660 11.660 4.840 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*S0)

Prepared for: Dept. of Veterans Affairs Section 6 Page 20 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_3DLF CB: 1_3DLF Main 0.208 1.200 1.200 0.980 0.010 0.000 Yes Yes PNL 25 1.784 18.000 0.027 (*S11)

PNL: 1_3LHA FU: 1_3LHA 0.480 16.450 16.450 10.030 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3LLA FU: 1_3LLA 0.208 9.400 9.400 4.170 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3LLB FU: 1_3LLB 0.208 9.250 9.250 3.500 0.074 0.000 Yes Yes PNL 25 14.001 18.000 0.791 (*N3) (*N21b) (*S12)

PNL: 1_3LLC FU: 1_3LLC 0.208 8.940 8.940 4.020 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_3LLD CB: 1_3LLD Main 0.208 1.200 1.200 0.980 0.010 0.000 Yes Yes PNL 25 1.784 18.000 0.027 (*S10)

PNL: 1_3LLE CB: 1_3LLE Main 0.208 8.490 8.490 3.300 0.030 0.000 Yes Yes PNL 25 7.681 18.000 0.295 (*N3) (*S12)

PNL: 1_4CD CB: 1_4CD Main 0.480 20.460 20.460 12.090 0.020 0.000 Yes Yes PNL 25 14.253 18.000 0.815 (*S11)

PNL: 1_4CD1 CB: 1_4CD1 Main 0.480 15.690 15.690 9.640 0.017 0.000 Yes Yes PNL 25 11.120 18.000 0.542 (*S11)

PNL: 1_4CD2 CB: 1_4CD2 Main 0.480 12.860 12.860 8.130 0.017 0.000 Yes Yes PNL 25 9.942 18.000 0.451 (*S11)

PNL: 1_4CD3 CB: 1_4CD3 Main 0.480 10.750 10.750 6.970 0.017 0.000 Yes Yes PNL 25 8.986 18.000 0.382 (*S11)

PNL: 1_4CD4 CB: 1_4CD4 Main 0.480 7.030 7.030 4.850 0.017 0.000 Yes Yes PNL 25 7.075 18.000 0.258 (*S11)

PNL: 1_4CL CB: 1_4CL Main 0.480 22.040 22.040 12.880 0.020 0.000 Yes Yes PNL 25 14.865 18.000 0.873 (*N22a) (*S10)

PNL: 1_4CL1 CB: 1_4CL1 Main 0.480 9.960 9.960 6.540 0.017 0.000 Yes Yes PNL 25 8.611 18.000 0.356 (*N22a) (*S10)

PNL: 1_4CL2 CB: 1_4CL2 Main 0.480 12.610 12.610 7.990 0.017 0.000 Yes Yes PNL 25 9.832 18.000 0.443 (*N22a) (*S10)

PNL: 1_4CL3 CB: 1_4CL3 Main 0.480 10.530 10.530 6.850 0.017 0.000 Yes Yes PNL 25 8.882 18.000 0.375 (*N22a) (*S10)

PNL: 1_4CL4 CB: 1_4CL4 Main 0.480 8.980 8.980 5.980 0.017 0.000 Yes Yes PNL 25 8.125 18.000 0.324 (*N22a) (*S10)

PNL: 1_4DHA FU: 1_ATS ABT 0.480 14.090 14.090 8.790 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4DLA FU: 1_4DLA 0.208 9.470 9.470 4.190 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

Prepared for: Dept. of Veterans Affairs Section 6 Page 21 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_4DLB FU: 1_4DLB 0.208 9.470 9.470 4.190 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4DLC FU: 1_4DLC 0.208 9.070 9.070 4.060 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4DLD FU: 1_4DLD 0.208 8.700 8.700 3.950 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4DLE FU: 1_4DLE 0.208 8.610 8.610 3.330 0.038 0.000 Yes Yes PNL 25 9.002 18.000 0.383 (*N3) (*S12)

PNL: 1_4DLF FU: 1_4DLF 0.208 9.110 9.110 3.460 0.078 0.000 Yes Yes PNL 25 14.283 18.000 0.818 (*N3) (*S12)

PNL: 1_4DLG FU: 1_XFMR T-D4A 0.208 3.370 3.370 2.030 2.000 0.000 Yes Yes PNL 25 72.605 18.000 11.785 (*N5) (*N9) (*S11)

PNL: 1_4DLH CB: 1_4DLH Main 0.208 1.190 1.190 0.970 0.010 0.000 Yes Yes PNL 25 1.777 18.000 0.027 (*S11)

PNL: 1_4ED CB: 1_4ED Main 0.480 14.360 14.360 8.930 0.020 0.000 Yes Yes PNL 25 11.679 18.000 0.588 (*S11)

PNL: 1_4ED1 CB: 1_4ED1 Main 0.480 12.030 12.030 7.680 0.017 0.000 Yes Yes PNL 25 9.573 18.000 0.424 (*S11)

PNL: 1_4ED2 CB: 1_4ED2 Main 0.480 10.210 10.210 6.670 0.017 0.000 Yes Yes PNL 25 8.730 18.000 0.364 (*S11)

PNL: 1_4ED3 CB: 1_4ED3 Main 0.480 8.800 8.800 5.880 0.017 0.000 Yes Yes PNL 25 8.033 18.000 0.318 (*S11)

PNL: 1_4ED4 CB: 1_4ED4 Main 0.480 6.140 6.140 4.320 0.017 0.000 Yes Yes PNL 25 6.558 18.000 0.228 (*S11)

PNL: 1_4EL CB: 1_4EL Main 0.480 14.160 14.160 8.830 0.020 0.000 Yes Yes PNL 25 11.588 18.000 0.580 (*S10)

PNL: 1_4EL1 CB: 1_4EL1 Main 0.480 7.780 7.780 5.290 0.017 0.000 Yes Yes PNL 25 7.491 18.000 0.284 (*S10)

PNL: 1_4EL2 CB: 1_4EL2 Main 0.480 9.380 9.380 6.210 0.017 0.000 Yes Yes PNL 25 8.325 18.000 0.337 (*S10)

PNL: 1_4EL3 CB: 1_4EL3 Main 0.480 8.130 8.130 5.490 0.017 0.000 Yes Yes PNL 25 7.680 18.000 0.295 (*S10)

PNL: 1_4EL4 CB: 1_4EL4 Main 0.480 7.150 7.150 4.930 0.017 0.000 Yes Yes PNL 25 7.147 18.000 0.262 (*S10)

PNL: 1_4LHA FU: 1_4LHA 0.480 15.340 15.340 9.450 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N22a) (*S0)

PNL: 1_4LLA FU: 1_4LLA 0.208 9.680 9.680 4.250 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

Prepared for: Dept. of Veterans Affairs Section 6 Page 22 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: 1_4LLB FU: 1_4LLB 0.208 8.860 8.860 3.990 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4LLC FU: 1_4LLC 0.208 9.560 9.560 4.210 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4LLD FU: 1_4LLD 0.208 9.500 9.500 4.190 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4LLE FU: 1_4LLE 0.208 10.580 10.580 4.530 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N21b) (*S0)

PNL: 1_4LLF FU: 1_4LLF 0.208 9.820 9.820 4.290 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_4LLG FU: 1_4LLG 0.208 9.590 9.590 3.590 0.055 0.000 Yes Yes PNL 25 11.899 18.000 0.606 (*N3) (*S12)

PNL: 1_4LLG MINI XFMR CB: 1_4LLG MINI

XFMR Main 0.208 1.190 1.190 0.980 0.010 0.000 Yes Yes PNL 25 1.781 18.000 0.027 (*N22a) (*S10)

PNL: 1_BDH FU: 1_BDH 0.480 12.370 12.370 7.860 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*S0)

PNL: 1_CTR-A FU: 1_1DLC 0.208 1.280 1.280 1.030 0.000 0.000 Yes Yes PNL 25 76.350 18.000 12.799 (*N4a) (*N5) (*S12)

PNL: 1_CTR-B FU: 1_1DLB 0.208 0.880 0.880 0.790 2.000 0.000 Yes Yes PNL 25 39.040 18.000 4.257 (*N9) (*N22a) (*S0)

PNL: 1_CTR-C FU: 1_1LLE 0.208 2.230 2.230 1.520 0.000 0.000 Yes Yes PNL 25 38.782 18.000 4.211 (*N4a) (*N22a) (*S14)

PNL: 1_CTR-E FU: 1_4LLC 0.208 1.590 1.590 1.020 0.000 0.000 Yes Yes PNL 25 53.074 18.000 7.047 (*N3) (*N4a) (*N5) (*S14)

PNL: 1_DP UPS-IT CB: 1_IT UPS 0.208 6.060 6.060 3.060 2.000 0.000 Yes Yes PNL 25 95.079 18.000 18.345 (*N5) (*N9) (*S11)

PNL: 1_DP UPS-UPS CB: 1_IT UPS 0.208 6.080 6.080 3.070 2.000 0.000 Yes Yes PNL 25 95.251 18.000 18.399 (*N9) (*S11)

PNL: 1_DP1T CB: 1_DP1T Main 0.208 8.160 8.160 3.770 2.000 0.000 Yes Yes PNL 25 109.490 18.000 23.125 (*N9) (*S15)

PNL: 1_DP-4QL CB: 1_DP-4QL Main 0.480 8.840 8.840 5.020 0.050 0.000 Yes Yes PNL 25 13.956 18.000 0.787 (*N3) (*S12)

PNL: 1_IT CB: 1_PNL 1T 0.208 6.380 6.380 3.170 2.000 0.000 Yes Yes PNL 25 97.695 18.000 19.180 (*N9) (*S15)

PNL: 1_IT UPS CB: 1_UPS Main Input 0.208 6.250 6.250 3.130 2.000 0.000 Yes Yes PNL 25 96.440 18.000 18.778 (*N9) (*S11)

PNL: 1_LP CB: 1_Fuel Tanks 0.208 2.150 2.150 1.480 2.000 0.000 Yes Yes PNL 25 58.998 18.000 8.383 (*N5) (*N9) (*S11)

Prepared for: Dept. of Veterans Affairs Section 6 Page 23 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

PNL: MSA_H1 CB: MSA_MSA Main 0.480 15.880 15.880 9.730 0.014 0.000 Yes Yes PNL 25 10.088 18.000 0.462 (*N5) (*S11)

PNL: MSA_L1A CB: MSA_L1A 0.208 7.500 7.500 3.550 0.018 0.000 Yes Yes PNL 25 5.872 18.000 0.190 (*S11)

PNL: MSA_L1B CB: MSA_L1B 0.208 6.650 6.650 2.780 2.000 0.000 Yes Yes PNL 25 89.508 18.000 16.614 (*N3) (*N9) (*S12)

PNL: MSA_L1C CB: MSA_L1C 0.208 6.870 6.870 3.340 0.010 0.000 Yes Yes PNL 25 4.006 18.000 0.102 (*S11)

PNL: MSA_MSB CB: MSA_T1 0.208 7.620 7.620 3.590 2.000 0.000 Yes Yes PNL 25 106.102 18.000 21.963 (*N5) (*N9) (*S0)

SWBD: 1_D1DH CB: 1_D1DH 0.480 13.010 13.010 8.210 0.150 0.000 Yes Yes PNL 25 37.706 18.000 4.021 (*S12)

SWBD: 1_D1DL FU: 1_XFMR T-D1 0.208 10.370 10.370 3.790 0.546 0.000 Yes Yes PNL 25 49.833 18.000 6.355 (*N3) (*S12)

SWBD: 1_D1LH CB: 1_D1LH 0.480 25.740 25.320 14.470 0.070 0.000 Yes Yes PNL 25 34.800 18.000 3.525 (*S10)

SWBD: 1_D1LL FU: 1_XFMR T-L1 0.208 10.870 10.870 3.920 0.467 0.000 Yes Yes PNL 25 45.515 18.000 5.477 (*N3) (*S12)

SWBD: 1_D2DH CB: 1_D2DH 0.480 22.110 22.110 12.910 0.070 0.000 Yes Yes PNL 25 31.945 18.000 3.063 (*S11)

SWBD: 1_D2DL CB: 1_D2DH 0.208 8.260 8.260 3.800 0.070 0.000 Yes Yes PNL 25 14.277 18.000 0.817 (*N5) (*S14)

SWBD: 1_D2LH CB: 1_D2LH 0.480 24.580 24.580 14.140 0.070 0.000 Yes Yes PNL 25 33.912 18.000 3.379 (*S10)

SWBD: 1_D2LL FU: 1_XFMR T-L2 0.208 10.490 10.490 3.820 0.526 0.000 Yes Yes PNL 25 48.144 18.000 6.005 (*N3) (*S12)

SWBD: 1_D3DH CB: 1_D3DH 0.480 11.940 11.940 6.480 0.150 0.000 Yes Yes PNL 25 32.281 18.000 3.116 (*N3) (*S12)

SWBD: 1_D3DL FU: 1_XFMR T-D3 0.208 10.050 10.050 3.710 0.605 0.000 Yes Yes PNL 25 52.287 18.000 6.876 (*N3) (*S12)

SWBD: 1_D3LH CB: 1_D3LH 0.480 15.370 15.040 7.870 0.150 0.000 Yes Yes PNL 25 35.990 18.000 3.725 (*N3) (*S13)

SWBD: 1_D3LL FU: 1_XFMR T-L3 0.208 10.790 10.790 3.900 0.893 0.000 Yes Yes PNL 25 67.221 18.000 10.385 (*N3) (*S12)

SWBD: 1_D4DH CB: 1_D4DH 0.480 21.580 21.580 12.650 0.070 0.000 Yes Yes PNL 25 31.511 18.000 2.995 (*S11)

SWBD: 1_D4DL FU: 1_XFMRT-D4 0.208 10.130 10.130 3.730 0.589 0.000 Yes Yes PNL 25 51.642 18.000 6.738 (*N3) (*S12)

Prepared for: Dept. of Veterans Affairs Section 6 Page 24 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

SWBD: 1_D4LH CB: 1_D4LH 0.480 22.660 22.660 13.190 0.070 0.000 Yes Yes PNL 25 32.390 18.000 3.134 (*S10)

SWBD: 1_D4LL FU: 1_XFMR T-L4 0.208 10.730 10.730 3.890 0.488 0.000 Yes Yes PNL 25 46.469 18.000 5.666 (*N3) (*S12)

SWBD: 1_DP-ATSQL CB: 1_MDBL 0.480 19.730 19.730 11.720 0.070 0.000 Yes Yes PNL 25 29.915 18.000 2.750 (*S2)

SWBD: 1_DP-ATSQL-b CB: 1_DP-ATSQL MDBD 0.480 22.640 22.640 11.200 0.070 0.000 Yes Yes PNL 25 29.087 18.000 2.627 (*N3) (*S11)

SWBD: 1_DPLH CB: 1_DPLH 0.480 28.720 27.160 15.270 0.070 0.000 Yes Yes PNL 25 37.015 18.000 3.901 (*S10)

SWBD: 1_DP-TX1T CB: 1_DP-TX1T 0.480 16.700 16.700 10.160 0.020 0.000 Yes Yes PNL 25 12.717 18.000 0.676 (*N22a) (*S2)

SWBD: 1_DP-TX1T-b CB: 1_4CD 0.480 20.070 20.070 11.890 0.012 0.000 Yes Yes PNL 25 10.354 18.000 0.482 (*S11)

SWBD: 1_MDBD CB: 1_MDBD Main 0.480 15.700 15.420 9.470 2.000 0.000 Yes Yes PNL 25 188.717 18.000 56.504 (*N9) (*S14)

SWBD: 1_US 2A FU: 1_US-2A East 0.480 28.860 25.710 14.440 2.000 0.000 Yes Yes PNL 25 273.434 18.000 103.837 (*N5) (*N9) (*S10)

SWBD: 1_US 2B CB: 1_US 2B Main 0.480 16.950 13.830 8.400 2.000 0.000 Yes Yes PNL 25 195.845 18.000 60.049 (*N9) (*S14)

SWBD: MSA_MSA CB: MSA_MSA Main 0.480 10.850 10.850 7.030 0.100 0.000 Yes Yes PNL 25 26.598 18.000 2.268 (*S12)

DISC: 1_AH-1 FU: 1_3MHB 0.480 4.900 4.900 3.030 0.013 0.000 Yes Yes PNL 25 4.427 18.000 0.120 (*N3) (*N5) (*S4)

DISC: 1_AH-20 CB: 1_AH-20 SF 0.480 11.340 11.330 7.300 0.014 0.000 Yes Yes PNL 25 8.289 18.000 0.335 (*S3)

DISC: 1_AHU-1 UNK FU: 1_1MHA 0.480 2.210 2.210 1.800 0.000 0.000 Yes Yes PNL 25 39.337 18.000 4.311 (*N4a) (*N5) (*S4)

DISC: 1_Backup Chiller FU: 1_3MHB 0.480 9.620 9.520 6.280 0.008 0.000 Yes Yes PNL 25 5.468 18.000 0.169 (*N4b) (*N5) (*S3)

DISC: 1_CH-1 FU: 1_CH-1 0.480 19.010 18.740 11.190 0.004 0.000 Yes Yes PNL 25 5.258 18.000 0.159 (*N4b) (*S3)

DISC: 1_CH-2 FU: 1_CH-2 0.480 17.120 16.850 10.220 0.004 0.000 Yes Yes PNL 25 4.957 18.000 0.144 (*N4b) (*S3)

DISC: 1_Chiller DPMHB-4 CB: 1_Chiller 3rd Flr Comp 0.480 3.990 3.880 2.910 0.015 0.000 Yes Yes PNL 25 4.741 18.000 0.134 (*S2)

Service Bays 5-7

Prepared for: Dept. of Veterans Affairs Section 6 Page 25 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

DISC: 1_Chiller Roof CB: 1_CHILLER 0.480 15.680 13.880 8.520 0.025 0.000 Yes Yes PNL 25 14.060 18.000 0.797 (*S3)

DISC: 1_EF-13 FU: 1_MCC-MMB 0.480 2.890 2.890 2.270 0.000 0.000 Yes Yes PNL 25 19.749 18.000 1.391 (*N4a) (*N5) (*S4)

DISC: 1_EF-36 MCP: 1_EF E-36 0.480 2.080 2.080 1.720 0.015 0.000 Yes Yes PNL 25 3.308 18.000 0.074 (*S3)

DISC: 1_EF60 FU: 1_MCC-MMB 0.480 4.190 4.190 3.120 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N5) (*S0)

DISC: 1_EF-66 FU: 1_MCC-MMB 0.480 5.570 5.570 3.980 0.000 0.000 Yes Yes PNL 25 6.938 18.000 0.250 (*N4a) (*N5) (*S0)

DISC: 1_EF-70 MCP: 1_EF-70 0.480 2.090 2.080 1.720 0.015 0.000 Yes Yes PNL 25 3.313 18.000 0.074 (*S3)

DISC: 1_HU-1 CB: 1_MRI HU-1 0.208 1.860 1.860 1.330 0.019 0.000 Yes Yes PNL 25 3.232 18.000 0.071 (*S3)

DISC: 1_MRI-2 FU: 1_MRI Rm 3A-9E 0.480 22.960 22.960 13.340 0.004 0.000 Yes Yes PNL 25 5.848 18.000 0.189 (*N4b) (*S3)

DISC: 1_PDB1 FU: 1_Switch 1 Pnl A 3E26 0.480 11.860 11.860 7.590 0.008 0.000 Yes Yes PNL 25 6.153 18.000 0.205 (*N4b) (*S3)

DISC: 1_Pump Rm 2SB5 FU: 1_2MLC 0.208 0.780 0.780 0.730 0.000 0.000 Yes Yes PNL 25 42.234 18.000 4.844 (*N4a) (*N5) (*S4)

DISC: 1_Small Hood MCP: 1_Hood Pharma 0.208 0.570 0.570 0.570 0.015 0.000 Yes Yes PNL 25 1.085 18.000 0.004 (*N11) (*S3) DISC: 1_Solar PV Disc SW-2 (FU: Solar PV Disc SW-2 LineSide)

CB: 1_DPMHA

Penthouse 4 0.480 13.150 10.860 6.850 2.000 0.000 Yes Yes PNL 25 161.390 18.000 43.712 (*N9) (*S6)

DISC: 1_SW-4CU CB: 1_US 3B Main 0.480 16.800 13.150 6.800 2.000 0.000 Yes Yes PNL 25 169.636 18.000 47.437 (*N3) (*N5) (*N9) (*S6)

DISC: 1_SW-4EU CB: 1_US 3B Main 0.480 16.560 12.960 7.890 2.000 0.000 Yes Yes PNL 25 187.578 18.000 55.946 (*N5) (*N9) (*S6)

DISC: 1_SW-CM CB: 1_US 3A Main 0.480 28.620 24.850 13.980 2.000 0.000 Yes Yes PNL 25 266.412 18.000 99.497 (*N9) (*S2)

DISC: 1_SW-EM CB: 1_US 3A Main 0.480 29.460 25.570 14.320 2.000 0.000 Yes Yes PNL 25 270.245 18.000 101.857 (*N9) (*S2)

DISC: 1_UNK CB: 1_2CU3A Main 0.208 3.670 3.670 1.830 0.955 0.000 Yes Yes PNL 25 43.346 18.000 5.055 (*N3) (*S8)

DISC: CLC2_CB-C MaxTripTime @2.0s 0.480 35.470 35.470 19.340 2.000 0.000 Yes Yes PNL 25 321.465 18.000 135.420 (*N2) (*N9) (*S0)

DISC: CLC2_CB-EM-CLC1 MaxTripTime @2.0s 0.480 34.080 34.080 18.690 2.000 0.000 Yes Yes PNL 25 314.357 18.000 130.541 (*N2) (*N9) (*S0)

Prepared for: Dept. of Veterans Affairs Section 6 Page 26 Prepared by: Wiley|Wilson

Bus Name Bus (kV)Protective Device

Name

Bus Bolted Fault (kA)

Incident Energy

(cal/cm2)

Arc Flash Boundary

(in.)

Working Distance

(in.)

Ground

Prot Dev Bolted Fault (kA)

Prot Dev Arcing Fault (kA)

Trip/ Delay Time (sec.)

Breaker Opening

Time (sec.)

Equip Type

Gap (mm)

Bus Arcing Fault (kA)

Notes

DISC: CLC2_CB-L MaxTripTime @2.0s 0.480 35.330 35.330 19.270 2.000 0.000 Yes Yes PNL 25 320.780 18.000 134.947 (*N2) (*N9) (*S0)

DISC: CLC2_CH-1 CB: CLC2_CHILLER 0.480 9.320 8.920 5.910 0.050 0.000 Yes Yes…