This document is a Fire/Life Safety System Inspection and Testing Certificate for Building 520 at the Palo Alto VA Medical Center, performed on May 30, 2025. The comprehensive inspection covered multiple fire safety systems across the facility, including 314 total devices tested across categories such as duct detectors, smoke detectors, pull stations, speaker/strobes, waterflow switches, and tamper switches. The inspection was conducted in accordance with NFPA 101 (2024 Edition), NFPA 72 (2022 Edition), and NFPA 90A (2022 Edition), utilizing a Notifier NFS2-3030D fire alarm control panel installed in 2015.
The inspection report details rigorous testing of fire safety equipment, with all 314 devices passing their respective tests, including annual tests of supervisory signal devices, water flow devices, duct detectors, heat detectors, manual fire alarm boxes, visual and audible fire alarms, and off-site fire responder notification systems. The document provides granular information on device locations, addresses, and testing results, with devices spread across multiple wings (A, B, C, D, F) of the facility. The inspection was performed by Facility - Palo Alto VA, with key contacts including Anthony Losito and inspector Olaf Soto, and was generated using BuildingReports.com software.
Text of this file
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate For
PA520
3801 Miranda Ave
Palo Alto, CA 94304
This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR CONDITIONING/VENTILATING SYSTEMS.
This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection Inspection Completion Date May 30, 2025 Building: PA520 Company: Facility - Palo Alto VA Contact: Anthony Losito Contact: Olaf Soto Title: Electronics Shop Supervisor Title: Inspector
Facility - Palo Alto VA
Download Date: 06/11/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: PA520 Contact: Anthony Losito Address: 3801 Miranda Ave Phone: 6508523437 Address:
Fax:
City/State/ZIP Code: Palo Alto, CA 94304 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Facility - Palo Alto VA Inspector: Olaf Soto Address: 2700 Gregory St Ste 180 Phone: 650-362-4841 Address:
Fax:
City/State/ZIP Code: Savannah, GA 31404 Mobile:
Country: United States of America Email: olaf@redwoodcityalarms.com
System Control Unit Manufacturer: Notifier Inspection Date: 05/30/2025 IDC Style:
Model Number: NFS2-3030D Install Date: 04/20/2015 SLC Style:
Software Version:
Version Date: 05/18/2017 NAC Style:
Location: 1st FACP E-EC1 Current Protection:
Inspection Completion Date: May 30, 2025 Building: PA520
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Tamper Switch
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Waterflow Switch
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector Heat Detector Pull Station Smoke Detector
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Bell Chime/Strobe Releasing Device Speaker Speaker/Strobe Strobe Voice Evacuation
EC 02.03.05 EP 05
Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Monitor Device
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector Fan Shutdown
LS 02.01.34 EP 02
Protected master fire alarm control panel Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Control Panel
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Annunciator Battery Power Supply Total Device Count: 314
Certification Company: Facility - Palo Alto VA Building: PA520 Inspector: Olaf Soto Contact: Anthony Losito file_0.jpg
Signed: May 30, 2025 Signed:
Inspection & Testing
Building: PA520 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g) Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Tamper Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Tamper Switch 1st In Room A-109 in ceiling hatch 45212935 1-L1 M32
08/21-P 05/30-P Tamper Switch 1st Outside By Room E-EC2 45212829 1-L1 M07
08/21-P 05/30-P Tamper Switch 1st Outside By Room E-EC2 45212828 1-L1 M07
08/21-P 05/30-P Tamper Switch 1st Inside In Room E-EC2 next to facp room 45212826 1-L1 M34
08/21-P 05/30-P Tamper Switch 1st restroom B-109 Pod B in ceiling hatch 45211852 1-L1 M30
08/21-P 05/30-P Tamper Switch 1st restroom B-109 Pod C in ceiling hatch 45211851 1-L1 M28
08/21-P 05/30-P Tamper Switch 1st In Room D-109 in ceiling hatch 45205335 1-L1 M11
08/21-P 05/19-P Device Total: 7
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Waterflow Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Waterflow Switch 1st In Room A-109 in ceiling hatch 45212934 1-L1 M33
08/21-P 05/30-P Waterflow Switch 1st Outside Room E-EC2 next to facp room 45212830 1-L1 M06
08/21-P 05/30-P Waterflow Switch 1st Inside Room E-EC2 next to facp room 45212827 1-L1 M35
08/21-P 05/30-P Waterflow Switch 1st restroom B-109 Pod B in ceiling hatch 45211853 1-L1 M31
08/21-P 05/30-P Waterflow Switch 1st restroom B-109 Pod C in ceiling hatch 45211850 1-L1 M29
08/21-P 05/30-P Waterflow Switch 1st In Room D-109 in ceiling hatch 45205336 1-L1 M12
08/21-P 05/19-P Device Total: 6
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Duct Detector 1st Room C-148 45211950 1-L1 D73 05/16-P
05/30-P Duct Detector 1st Room C-148 45211949 1-L1 D72 05/16-P
05/30-P Duct Detector 1st In Room A-109A 45212910 1-L1 D106 05/16-P
05/30-P Duct Detector 1st A-150 Medicine Room 45212884 1-L1 D109 05/16-F
05/30-P Duct Detector 1st A-150 Medicine Room 45212883 1-L1 D110 05/16-F
05/30-P Duct Detector 1st In Room B-160 45212874 1-L1 D90 05/16-P
05/30-P Duct Detector 1st In Room B-160 45212875 1-L1 D88 05/16-P
05/30-P Duct Detector 1st Entry To B-Wing 45212876 1-L1 D82 05/16-P
05/30-P Duct Detector 1st Entry To B-Wing 45212877 1-L1 D81 05/16-P
05/30-P Duct Detector 1st In Room C-160 45212878 1-L1 D60 05/16-P
05/30-P Duct Detector 1st In Room C-160 45212879 1-L1 D62 05/16-P
05/30-P Duct Detector 1st In Room C-160 45212880 1-L1 D61 05/16-P
05/30-P Duct Detector 1st In Room C-160 45212881 1-L1 D68 05/16-P
05/30-P Duct Detector 1st In Room B-160 45212873 1-L1 D89 05/16-P
05/30-P Duct Detector 1st In Room B-160 45212872 1-L1 D91 05/16-P
05/30-P Duct Detector 1st In Room B-160 45212871 1-L1 D92 05/16-P
05/30-P Duct Detector 1st By Room A-109 45212939 1-L1 D104 05/16-P
05/30-P Duct Detector 1st In Room C-154 45211952 1-L1 D71 05/16-P
05/30-P Duct Detector 1st Restroom D105 45212592 1-L1 D58 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212781 1-L1 D133 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212780 1-L1 D132 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212779 1-L1 D134 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212778 1-L1 D131 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212777 1-L1 D135 05/16-P
05/30-P Duct Detector 1st In Room F-108 45212776 1-L1 D139 05/16-P
05/30-P Duct Detector 1st In Room F-108 45212775 1-L1 D138 05/16-P
05/30-P Duct Detector 1st In Room F-108 45212774 1-L1 D137 05/16-P
05/30-P Duct Detector 1st In Room F-108 45212773 1-L1 D136 05/16-P
05/30-P Duct Detector 1st Room C-172 45212590 1-L1 D78 05/16-P
05/30-P Duct Detector 1st Room C-172 45212589 1-L1 D77 05/16-P
05/30-P Duct Detector 1st In Room C-154 45211953 1-L1 D69 05/16-P
05/30-P Duct Detector 1st Roof AC-D 45212587 1-L1 M119 05/16-F
05/30-P Duct Detector 1st Roof AC-C 45212586 1-L1 M118 05/16-P
05/30-P Duct Detector 1st In Room A-TC1 45211966 1-L1 D95 05/16-P
05/30-P Duct Detector 1st Roof AC -A 45211968 1-L1 M116 05/16-F
05/30-P Duct Detector 1st Roof AC-B 45211967 1-L1 M117 05/16-P
05/30-P Duct Detector 1st Corridor By F-130 45211964 1-L1 D126 05/16-P
05/30-P Duct Detector 1st Outside Entry 45211962 1-L1 D141 05/16-P
05/30-P Duct Detector 1st Outside Entry 45211961 1-L1 D140 05/16-P
05/30-P Duct Detector 1st Corridor Of C-174 45211960 1-L1 D74 05/16-P
05/30-P Duct Detector 1st Corridor Of C-174 45211959 1-L1 D76 05/16-P
05/30-P Duct Detector 1st In Room D-160 45211958 1-L1 D59 05/16-P
05/30-P Duct Detector 1st In Room C-146 45211955 1-L1 D66 05/16-P
05/30-P Duct Detector 1st In Room C-146 45211957 1-L1 D63 05/16-P
05/30-P Duct Detector 1st In Room C-146 45211956 1-L1 D65 05/16-P
05/30-P Duct Detector 1st In Room C-154 45211954 1-L1 D70 05/16-P
05/30-P Duct Detector 1st Room B-172 45211948 1-L1 D100 05/16-P
05/30-P Duct Detector 1st Entry Corridor C 45211947 1-L1 D80 05/16-P
05/30-P Duct Detector 1st Entry Corridor C 45211946 1-L1 D79 05/16-P
05/30-P Duct Detector 1st Room B-109 45211945 1-L1 D83 05/16-P
05/30-P Duct Detector 1st Room A-176 45211944 1-L1 D101 05/16-P
05/30-P Duct Detector 1st Room B-174 45211943 1-L1 D114 05/16-P
05/30-P Duct Detector 1st Room B-174 45211942 1-L1 D99 05/16-P
05/30-P Duct Detector 1st Corridor A-176 45211941 1-L1 D98 05/16-P
05/30-P Duct Detector 1st Corridor B-174 45211940 1-L1 D97 05/16-P
05/30-P Duct Detector 1st In Room A-148 45211939 1-L1 D107 05/16-P
05/30-P Duct Detector 1st In Room A-148 45211938 1-L1 D108 05/16-P
05/30-P Duct Detector 1st In Room A-160 45211937 1-L1 D111 05/16-P
05/30-P Duct Detector 1st In Room A-158 45211936 1-L1 D113 05/16-P
05/30-P Duct Detector 1st In Room B-160 45211935 1-L1 D112 05/16-P
05/30-P Duct Detector 1st In Room B-154 45211934 1-L1 D84 05/16-P
05/30-P Duct Detector 1st In Room B-154 45211933 1-L1 D85 05/16-P
05/30-P Duct Detector 1st In Room B-148 45211932 1-L1 D87 05/16-P
05/30-P Duct Detector 1st In Room B-147 45211931 1-L1 D96 05/16-P
05/30-P Duct Detector 1st In Room F-125 45211928 1-L1 D129 05/16-P
05/30-P Duct Detector 1st In Room F-125 45211927 1-L1 D127 05/16-P
05/30-P Duct Detector 1st In Room F-125 45211926 1-L1 D130 05/16-P
05/30-P Duct Detector 1st In Room F-127 45211925 1-L1 D128 05/16-P
05/30-P Duct Detector 1st Inside Room D-154 45208581 1-L1 D54 05/16-P
05/30-P Duct Detector 1st Inside Room D-154 45208580 1-L1 D53 05/16-P
05/30-P Duct Detector 1st Bldg F Roof 45206229 1-L1 M158 05/16-P
05/30-P Duct Detector 1st Restroom F-120 45206221 1-L1 D125 05/16-P
05/19-P Duct Detector 1st By Room A-109 45206206 1-L1 D103 05/16-P
05/19-P Duct Detector 1st In Room B-160 (B-146) 45205345 1-L1 D94 05/16-P
05/19-P Duct Detector 1st In Room B-160 (B-146) 45205344 1-L1 D93 05/16-P
05/19-P Duct Detector 1st By Room B-148 45205343 1-L1 D86 05/16-P
05/19-P Duct Detector 1st Corridor By C-160 45205341 1-L1 D67 05/16-P
05/19-P Duct Detector 1st In Room D-148 45205339 1-L1 D56 05/16-P
05/19-P Duct Detector 1st In Room D-148 45205338 1-L1 D55 05/16-P
05/19-P Duct Detector 1st Hallway by D-109 45205334 1-L1 D52 05/16-P
05/19-P Duct Detector 1st Hallway by D-109 45205333 1-L1 D51 05/16-P
05/19-P Duct Detector 1st In Room D-160 45205332 1-L1 D57 05/16-P
05/19-P Duct Detector 2nd In Men's Restroom F-222 45212810 1-L1 D142 05/16-P
05/30-P Duct Detector 2nd Corridor Of Room F-235 45212786 1-L1 D144 05/16-P
05/30-P Duct Detector 2nd In Room F-229 45212787 1-L1 D145 05/16-P
05/30-P Duct Detector 2nd In Room F-206 45212785 1-L1 D150 05/16-P
05/30-P Duct Detector 2nd In Room F-205 45212784 1-L1 D149 05/16-P
05/30-P Duct Detector 2nd Outside F-ME4 45212782 1-L1 D148 05/16-P
05/30-P Duct Detector 2nd In Room F-229 45211963 1-L1 D146 05/16-P
05/30-P Duct Detector 2nd In Room F-235 45211930 1-L1 D147 05/16-P
05/30-P Device Total: 90
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Heat Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Heat Detector 2nd In Room F-ME4 45212794 1-L1 D28 05/16-P
05/30-P Heat Detector 2nd In Room F-ME4 45212793 1-L1 D31 05/16-P
05/30-P Device Total: 2
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Pull Station
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Pull Station 1st D-Wing Entrance Lobby 45212972 1-L1 M14 05/16-P
05/30-P Pull Station 1st D-Wing Exit 45212968 1-L1 M15 05/16-P
05/30-P Pull Station 1st Main Lobby Entrance B and C 45212963 1-L1 M16 05/16-P
05/30-P Pull Station 1st C-Wing Reception 45212960 1-M24 05/16-P
05/30-P Pull Station 1st B-Wing Reception 45212957 1-M17 05/16-P
05/30-P Pull Station 1st Exit By A And B 45212950 1-L1 M18 05/16-P
05/30-P Pull Station 1st A-Wing Lobby 45212946 1-L1 M19 05/16-P
05/30-P Pull Station 1st By Room A-109 45212945 1-L1 M70 05/16-P
05/30-P Pull Station 1st By Room A-123 45212929 1-L1 M71 05/16-P
05/30-P Pull Station 1st By Room A-129 45212917 1-L1 M72 05/16-P
05/30-P Pull Station 1st Main Lobby 45212914 1-L1 M44 05/16-P
05/30-P Pull Station 1st Main Lobby 45212913 1-L1 M22 05/16-P
05/30-P Pull Station 1st By F-101 Lounge Area 45212912 1-L1 M21 05/16-P
05/30-P Pull Station 1st In Room A-170 45212907 1-L1 M74 05/16-P
05/30-P Pull Station 1st By Room A-123 45212901 1-L1 M75 05/16-P
05/30-P Pull Station 1st Exit By F-130 45212867 1-L1 M23 05/16-P
05/30-P Pull Station 1st Exit By Stair 2 45212866 1-L1 M45 05/16-P
05/30-P Pull Station 1st Exit By Restroom F-102 45212854 1-L1 M37 05/16-P
05/30-P Pull Station 1st FACP E-EC1 45212847 1-L1 M01 05/16-P
05/30-P Pull Station 1st D-Wing Reception Area 45212809 1-L1 M13 05/16-P
05/30-P Pull Station 1st Exit By A-134 45212588 1-L1 M73 05/16-P
05/30-P Pull Station 1st Bldg F Electrical Room F-EC1 45206215 1-L1 M156 05/16-P
05/19-P Pull Station 2nd By Stair 2 45212814 1-M144 05/16-P
05/30-P Pull Station 2nd Top Of Stairs 45212825 1-L1 M46 05/16-P
05/30-P Device Total: 24
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Smoke Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Smoke Detector 1st By Room B-145 45212956 1-D05 05/16-P
05/30-P Smoke Detector 1st By Room A-145 45212955 1-D04 05/16-P
05/30-P Smoke Detector 1st By Room A-109 45212943 1-L1 D32 05/16-P
05/30-P Smoke Detector 1st By Room A-117 45212942 1-L1 D33 05/16-P
05/30-P Smoke Detector 1st By Room A-121 45212931 1-L1 D35 05/16-P
05/30-P Smoke Detector 1st By Room A-125 45212930 1-L1 D36 05/16-P
05/30-P Smoke Detector 1st Above A-Wing Reception 45212921 1-L1 D45 05/16-P
05/30-P Smoke Detector 1st Above A-Wing Reception 45212920 1-L1 D34 05/16-P
05/30-P Smoke Detector 1st Corridor Of Reception Area 45212919 1-L1 D37 05/16-P
05/30-P Smoke Detector 1st By Room F-108 45212916 1-L1 D22 05/16-P
05/30-P Smoke Detector 1st By Room A-141 45212905 1-D040 05/16-P
05/30-P Smoke Detector 1st By Room A-132 45212899 1-L1 D38 05/16-P
05/30-P Smoke Detector 1st By Room A-132 45212898 1-L1 D39 05/16-P
05/30-P Smoke Detector 1st By Room A-152 45212886 1-L1 D42 05/16-P
05/30-P Smoke Detector 1st Elevator Lobby 45212851 1-L1 D17 05/16-P
05/30-P Smoke Detector 1st By Waiting Room F-108 45212850 1-L1 D21 05/16-P
05/30-P Smoke Detector 1st FACP Room E-EC1 45212831 1-L1 D01 05/16-P
05/30-P Smoke Detector 1st Corridor Of D-145 45211951 1-L1 D02 05/16-P
05/30-P Smoke Detector 1st Office In F-108 45212772 1-L1 D18 05/16-P
05/30-P Smoke Detector 1st Office In F-108 45212771 1-L1 D19 05/16-P
05/30-P Smoke Detector 1st In Room A-EC1 45211965 1-L1 D41 05/16-P
05/30-P Smoke Detector 1st Electrical Room F-EC1 45206216 1-L1 D20 05/16-P
05/19-P Smoke Detector 1st Corridor Of D-145 45205340 1-L1 D03 05/16-P
05/19-P Smoke Detector 2nd Corridor Near Elevator 45212823 1-L1 D23 05/16-P
05/30-P Smoke Detector 2nd Corridor Near Elevator 45212822 1-L1 D29 05/16-P
05/30-P Smoke Detector 2nd In Room F-206 45212801 1-L1 D26 05/16-P
05/30-P Smoke Detector 2nd In Room F-ME4 45212795 1-L1 D27 05/16-P
05/30-P Smoke Detector 2nd In Room F-ME4 45212792 1-L1 D30 05/16-P
05/30-P Smoke Detector 2nd Top Of Stairs 45212824 1-L1 D24 05/16-P
05/30-P Smoke Detector 2nd In Room F-206 45212802 1-L1 D25 05/16-P
05/19-P Device Total: 30
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Bell
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Bell 1st outside rm E-EC2 above door 45206149 05/16-P 08/21-P 05/19-P Device Total: 1
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Chime/Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Chime/Strobe 1st In room D-105 45206208 05/16-P
05/19-P Device Total: 1
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Releasing Device
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Releasing Device 1st Corridor Of F-101 45212857 05/16-P
05/30-P Releasing Device 1st Corridor Of F-101 45212856 05/16-P
05/30-P Device Total: 2
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker 1st C-Wing Reception 45212959 1-S2- 2 05/16-P
05/30-P Speaker 1st B-Wing Reception 45212958 1-S2- 2 05/16-P
05/30-P Speaker 1st In Room A-109 45212937 05/16-P
05/30-P Speaker 1st In Room A-115 45212933 05/16-P
05/30-P Speaker 1st In Room C-152 45212882
1-S2- 3 EOL
05/16-P
05/30-P Speaker 1st By Room F-134 45212869 1-S6- 10 05/16-P
05/30-P Speaker 1st By Room F-SC1 45212865 1-S6- 2 05/16-P
05/30-P Speaker 1st By Room F-112 45212861 1-S6- 4 05/16-P
05/30-P Speaker 1st D-Wing Reception Area 45212808 1-S1- 3 05/16-P
05/30-P Speaker 1st Conference Rm C-115 45205342 1-S2- 1 05/16-P
05/19-P Speaker 1st By Room D-115 45205337 1-S1- 2 05/16-P
05/19-P Speaker 2nd By Room F-238 45212816
1-S7- 14 EOL
05/16-P
05/30-P Speaker 2nd By Room F-223 45212813 1-S7- 2 05/16-P
05/30-P Speaker 2nd By Room F-211 45212804 1-S7- 4 05/16-P
05/30-P Speaker 2nd By Room F-245 45206218 1-S7- 9 05/16-P
05/30-P Device Total: 15
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker/Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker/Strobe 1st By Room D-184 45212974 1-N2-/S5- 6-Jul 05/16-P
05/30-P Speaker/Strobe 1st D-Wing Entrance Lobby 45212973 1-N2-/S5- 3-Apr 05/16-P
05/30-P Speaker/Strobe 1st In Room D-186 45212969 1-N2-/S5- 5-Jun 05/16-P
05/30-P Speaker/Strobe 1st By D-Wing Exit 45212967 1-N2-/S5- 7-Sep 05/16-P
05/30-P Speaker/Strobe 1st Corridor By C-186 45212965 1-N3-/S5- 9-Feb 05/16-P
05/30-P Speaker/Strobe 1st In Room C-186 45212964 1-N3-/S5- 10-Mar 05/16-P
05/30-P Speaker/Strobe 1st Lobby Of B And C Entrance 45212962 1-N3-/S5- 9-May 05/16-P
05/30-P Speaker/Strobe 1st In Room B-186 45212954 1-N3-/S5- 14-Jul 05/16-P
05/30-P Speaker/Strobe 1st Corridor By B-186 45212953 1-N3-/S5- 13-Jun 05/16-P
05/30-P Speaker/Strobe 1st Exit By A And B 45212951 05/16-P
05/30-P Speaker/Strobe 1st Corridor By A-186 45212949 1-N4-/S5- 17-May 05/16-P
05/30-P Speaker/Strobe 1st In Room A-186 45212948 1-N4-/S5- 18-Jun 05/16-P
05/30-P Speaker/Strobe 1st A-Wing Lobby 45212947 1-N4-/S5- 19-Jul 05/16-P
05/30-P Speaker/Strobe 1st By Room A-109 45212944
1-B4/S4 10 EOL
05/16-P
05/30-P Speaker/Strobe 1st By Room A-120 45212941 1-B4/S4 1 05/16-P
05/30-P Speaker/Strobe 1st In Room A-120 45212940 1-B4/S4 2 05/16-P
05/30-P Speaker/Strobe 1st In Room A-111 45212938 1-B4/S4 8 05/16-P
05/30-P Speaker/Strobe 1st By Room A-123 45212928
1-B3/S4 11 EOL
05/16-P
05/30-P Speaker/Strobe 1st In Room A-123 45212927 1-B4/S4 5 05/16-P
05/30-P Speaker/Strobe 1st In Room A-125 45212926 1-B3/S4 10 05/16-P
05/30-P Speaker/Strobe 1st In Room A-122 45212925 1-B4/S4 4 05/16-P
05/30-P Speaker/Strobe 1st In Room A-126 45212924 1-B3/S4 9 05/16-P
05/30-P Speaker/Strobe 1st In Room A-127 45212923 1-B3/S4 8 05/16-P
05/30-P Speaker/Strobe 1st In Room A-121 45212922 1-B4/S4 3 05/16-P
05/30-P Speaker/Strobe 1st In Room A-129 45212918 1-B3/S4 7 05/16-P
05/30-P Speaker/Strobe 1st By F-108 45212915
1-N9-/S6- 12/7 EOL
05/16-P
05/30-P Speaker/Strobe 1st F-101 Lobby 45212911 1-N10/S6 12-May 05/16-P
05/30-P Speaker/Strobe 1st In Room A-170 45212909 1-B1/S4 6 05/16-P
05/30-P Speaker/Strobe 1st Yard By Kitchen 45212908 05/16-P
05/30-P Speaker/Strobe 1st In Room A-143 45212904 1-B1/S4 2 05/16-P
05/30-P Speaker/Strobe 1st In Room A-145 45212903 1-B1/S4 1 05/16-P
05/30-P Speaker/Strobe 1st In Room A-150A 45212902 05/16-P
05/30-P Speaker/Strobe 1st Backyard By A-134 45212897 05/16-P
05/30-P Speaker/Strobe 1st By A-134 45212896 1-B3/S4 1 05/16-P
05/30-P Speaker/Strobe 1st In Room A-135 45212895 1-B2/S4 7 05/16-P
05/30-P Speaker/Strobe 1st In Room A-134 45212894 1-B3/S4 2 05/16-P
05/30-P Speaker/Strobe 1st In Room A-133 45212893 1-B3/S4 3 05/16-P
05/30-P Speaker/Strobe 1st In Room A-132 45212892 1-B3/S4 5 05/16-P
05/30-P Speaker/Strobe 1st In Room A-137 45212891 1-B2/S4 5 05/16-P
05/30-P Speaker/Strobe 1st In Room A-136 45212890 1-B2/S4 6 05/16-P
05/30-P Speaker/Strobe 1st In Room A-130 45212889 1-B3/S4 6 05/16-P
05/30-P Speaker/Strobe 1st In Room A-140 45212888 1-B2/S4 4 05/16-P
05/30-P Speaker/Strobe 1st In Room A-117 45212887 1-B4/S4 6 05/16-P
05/30-P Speaker/Strobe 1st In Room A-152 45212885 05/16-P
05/30-P Speaker/Strobe 1st By F-139 45212870 1-N10-/S6- 11-Feb 05/16-P
05/30-P Speaker/Strobe 1st By F-ME1 45212868 1-N9-/S6- 1-Jan 05/16-P
05/30-P Speaker/Strobe 1st By F-115 45212862 1-N9-/S6- 3-Jun 05/16-P
05/30-P Speaker/Strobe 1st By F-108 45212859 1-N9-/S6- 5-Sep 05/16-P
05/30-P Speaker/Strobe 1st In Conference Room F-107 45212858 1-N10-/S6- 8-Mar 05/16-P
05/30-P Speaker/Strobe 1st By F-103 Men's Restroom 45212855
1-N10-/S6- 7-14 EOL
05/16-P
05/30-P Speaker/Strobe 1st Elevator Lobby 45212849 1-N10-/S6- 13-Jun 05/16-P
05/30-P Speaker/Strobe 1st Elevator Lobby 45212848 1-N9-/S6- 6-Nov 05/16-P
05/30-P Speaker/Strobe 1st Backyard F-Wing 45206228 05/16-P
05/30-P Speaker/Strobe 1st Courtyard by Unit A entrance 45206227 1-N4-8/S5- 20 05/16-P
05/30-P Speaker/Strobe 1st Courtyard by between F & D 45206226 05/16-F
05/30-P Speaker/Strobe 1st Courtyard by Unit D entrance 45206225 05/16-P
05/30-P Speaker/Strobe 1st Courtyard entrance between Unit C & D 45206224 05/16-P
05/30-P Speaker/Strobe 1st Courtyard by entrance B & C 45206223 05/16-P
05/30-P Speaker/Strobe 1st Courtyard entrance between Unit A & B 45206222 05/16-P
05/30-P Speaker/Strobe 1st Corridor by Room A-180 5680684 1-B1-5/S 6 05/16-P
05/19-P Speaker/Strobe 2nd By Room F-201 45212821 1-N12/S7 10-Apr 05/16-P
05/30-P Speaker/Strobe 2nd In Room F-201 45212820 1-N12/S7 13-Jan 05/16-P
05/30-P Speaker/Strobe 2nd In Room F-243 45212819 1-N12/S7 12-Feb 05/16-P
05/30-P Speaker/Strobe 2nd By Room F-242 45212817 1-N12/S7 11-Mar 05/16-P
05/30-P Speaker/Strobe 2nd By F-EC1 45212815 1-N11-/S7 1-Jan 05/16-P
05/30-P Speaker/Strobe 2nd By Room F-217 45212807 1-N11-/S7- 3-Apr 05/16-P
05/30-P Speaker/Strobe 2nd By Room F-207 45212803 1-N11-/S7- 5-Jul 05/16-P
05/30-P Speaker/Strobe 2nd In Room F-206 45212800 1-N12/S7 7-Aug 05/16-P
05/30-P Speaker/Strobe 2nd By Room F-206 45212799 1-N11/S7 6-Sep 05/16-P
05/30-P Speaker/Strobe 2nd Corridor By F-247 45212796
1-N12/S7 9/8 EOL
05/16-P
05/30-P Device Total: 70
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Strobe 1st D-178 Restroom 45212971 05/16-P
05/30-P Strobe 1st C-178 Restroom 45212966 05/16-P
05/30-P Strobe 1st B-188 Restroom 45212961
1-N3- 8 EOL
05/16-P
05/30-P Strobe 1st B-178 Restroom 45212952 1-N4- 3 05/16-P
05/30-P Strobe 1st In Room A-109 45212936 05/16-P
05/30-P Strobe 1st In Room A-115 45212932 05/16-P
05/30-P Strobe 1st By A-140 45212900 1-B4- 3 05/16-P
05/30-P Strobe 1st F-122 Women's Restroom 45212864 1-N9- 3 05/16-P
05/30-P Strobe 1st F-120 Men's Restroom 45212863 1-N9- 4 05/16-P
05/30-P Strobe 1st In Women's Restroom F-102 45212853 1-N10- 8 05/16-P
05/30-P Strobe 1st In Men's Restroom F-103 45212852
1-N10- 9 EOL
05/16-P
05/30-P Strobe 1st In Office F-110 45212769 1-N9- 8 05/16-P
05/30-P Strobe 1st In Office inside F-108 45212770 1-N9- 10 05/16-P
05/30-P Strobe 1st Restroom D105 45212591 1-N10- 8 05/16-P
05/30-P Strobe 1st Room F-118 45212585 1-N9- 5 05/16-P
05/30-P Strobe 1st A-178 Restroom 45206205 1-N4- 4 05/16-P
05/19-P Strobe 1st in Room F-123 45205348 1-N9- 2 05/16-P
05/19-P Strobe 1st In Room F-116 45205347 1-N9- 7 05/16-P
05/19-P Strobe 1st In Room B-109 10008490 1-S3- 1 05/16-P
05/19-P Strobe 2nd Corridor Of F-243 45212818 1-N12- 5 05/16-P
05/30-P Strobe 2nd Women's Restroom F-224 45212812 1-N11- 2 05/16-P
05/30-P Strobe 2nd Mens Restroom F-222 45212811 1-N11- 3 05/16-P
05/30-P Strobe 2nd In Room F-218 45212806 1-N11- 5 05/16-P
05/30-P Strobe 2nd In Kitchen 45212805 1-N11- 6 05/16-P
05/30-P Strobe 2nd Men's Restroom F-246 45212798 1-N12- 7 05/16-P
05/30-P Strobe 2nd Women's Restroom F-247 45212797 1-N12- 6 05/16-P
05/30-P Device Total: 26
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Voice Evacuation
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Voice Evacuation 1st FACP E-EC1 45212837 2-A 05/16-P
05/30-P Voice Evacuation 1st FACP E-EC1 45212836 2-B 05/16-P
05/30-P Voice Evacuation 1st FACP E-EC1 45212835 2-C 05/16-P
05/30-P Device Total: 3
EC 02.03.05 EP 05
Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4) Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-22 Table 14.4.3.2 (4)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Monitor Device
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Monitor Device 1st In Room F-108 office 45206220 1-L1 M39 05/16-P
05/19-P Monitor Device 1st In Room F-108 45206219 1-L1 M43 05/16-P
05/19-P Monitor Device 1st Electrical Rm F-EC1 45206213 05/16-P
05/19-P Monitor Device 1st In Room F-EC1 45206212 1-L1 M40 05/16-P
05/19-P Monitor Device 1st FACP E-EC1 45206209 05/16-P
05/19-P Monitor Device 1st In Room A-EC1 45206200 1-L1 M48 05/16-P
05/19-P Monitor Device 2nd In Room F-ME4 45212791 1-L1 M53 05/16-P
05/30-P Monitor Device 2nd In Room F-ME4 45212790 1-L1 M52 05/16-P
05/30-P Monitor Device 2nd In Room F-ME4 45212789 1-L1 M55 05/16-P
05/30-P Monitor Device 2nd In Room F-ME4 45212788 1-L1 M54 05/16-P
05/30-P Monitor Device 2nd In Room F-205 45212783 1-L1 M49 05/16-P
05/30-P Monitor Device 2nd In Room F-206 In Hatch 45211929 1-L1 M48 05/16-P
05/30-P Monitor Device 2nd In Room F-EC1 45205349 1-L1 M59 05/16-P
05/30-P Device Total: 13
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Duct Detector 1st Room C-148 45211950 1-L1 D73 05/16-P
05/30-P Duct Detector 1st Room C-148 45211949 1-L1 D72 05/16-P
05/30-P Duct Detector 1st In Room A-109A 45212910 1-L1 D106 05/16-P
05/30-P Duct Detector 1st A-150 Medicine Room 45212884 1-L1 D109 05/16-F
05/30-P Duct Detector 1st A-150 Medicine Room 45212883 1-L1 D110 05/16-F
05/30-P Duct Detector 1st In Room B-160 45212874 1-L1 D90 05/16-P
05/30-P Duct Detector 1st In Room B-160 45212875 1-L1 D88 05/16-P
05/30-P Duct Detector 1st Entry To B-Wing 45212876 1-L1 D82 05/16-P
05/30-P Duct Detector 1st Entry To B-Wing 45212877 1-L1 D81 05/16-P
05/30-P Duct Detector 1st In Room C-160 45212878 1-L1 D60 05/16-P
05/30-P Duct Detector 1st In Room C-160 45212879 1-L1 D62 05/16-P
05/30-P Duct Detector 1st In Room C-160 45212880 1-L1 D61 05/16-P
05/30-P Duct Detector 1st In Room C-160 45212881 1-L1 D68 05/16-P
05/30-P Duct Detector 1st In Room B-160 45212873 1-L1 D89 05/16-P
05/30-P Duct Detector 1st In Room B-160 45212872 1-L1 D91 05/16-P
05/30-P Duct Detector 1st In Room B-160 45212871 1-L1 D92 05/16-P
05/30-P Duct Detector 1st By Room A-109 45212939 1-L1 D104 05/16-P
05/30-P Duct Detector 1st In Room C-154 45211952 1-L1 D71 05/16-P
05/30-P Duct Detector 1st Restroom D105 45212592 1-L1 D58 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212781 1-L1 D133 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212780 1-L1 D132 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212779 1-L1 D134 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212778 1-L1 D131 05/16-P
05/30-P Duct Detector 1st Hard Cap Ceiling By Glass Door 45212777 1-L1 D135 05/16-P
05/30-P Duct Detector 1st In Room F-108 45212776 1-L1 D139 05/16-P
05/30-P Duct Detector 1st In Room F-108 45212775 1-L1 D138 05/16-P
05/30-P Duct Detector 1st In Room F-108 45212774 1-L1 D137 05/16-P
05/30-P Duct Detector 1st In Room F-108 45212773 1-L1 D136 05/16-P
05/30-P Duct Detector 1st Room C-172 45212590 1-L1 D78 05/16-P
05/30-P Duct Detector 1st Room C-172 45212589 1-L1 D77 05/16-P
05/30-P Duct Detector 1st In Room C-154 45211953 1-L1 D69 05/16-P
05/30-P Duct Detector 1st Roof AC-D 45212587 1-L1 M119 05/16-F
05/30-P Duct Detector 1st Roof AC-C 45212586 1-L1 M118 05/16-P
05/30-P Duct Detector 1st In Room A-TC1 45211966 1-L1 D95 05/16-P
05/30-P Duct Detector 1st Roof AC -A 45211968 1-L1 M116 05/16-F
05/30-P Duct Detector 1st Roof AC-B 45211967 1-L1 M117 05/16-P
05/30-P Duct Detector 1st Corridor By F-130 45211964 1-L1 D126 05/16-P
05/30-P Duct Detector 1st Outside Entry 45211962 1-L1 D141 05/16-P
05/30-P Duct Detector 1st Outside Entry 45211961 1-L1 D140 05/16-P
05/30-P Duct Detector 1st Corridor Of C-174 45211960 1-L1 D74 05/16-P
05/30-P Duct Detector 1st Corridor Of C-174 45211959 1-L1 D76 05/16-P
05/30-P Duct Detector 1st In Room D-160 45211958 1-L1 D59 05/16-P
05/30-P Duct Detector 1st In Room C-146 45211955 1-L1 D66 05/16-P
05/30-P Duct Detector 1st In Room C-146 45211957 1-L1 D63 05/16-P
05/30-P Duct Detector 1st In Room C-146 45211956 1-L1 D65 05/16-P
05/30-P Duct Detector 1st In Room C-154 45211954 1-L1 D70 05/16-P
05/30-P Duct Detector 1st Room B-172 45211948 1-L1 D100 05/16-P
05/30-P Duct Detector 1st Entry Corridor C 45211947 1-L1 D80 05/16-P
05/30-P Duct Detector 1st Entry Corridor C 45211946 1-L1 D79 05/16-P
05/30-P Duct Detector 1st Room B-109 45211945 1-L1 D83 05/16-P
05/30-P Duct Detector 1st Room A-176 45211944 1-L1 D101 05/16-P
05/30-P Duct Detector 1st Room B-174 45211943 1-L1 D114 05/16-P
05/30-P Duct Detector 1st Room B-174 45211942 1-L1 D99 05/16-P
05/30-P Duct Detector 1st Corridor A-176 45211941 1-L1 D98 05/16-P
05/30-P Duct Detector 1st Corridor B-174 45211940 1-L1 D97 05/16-P
05/30-P Duct Detector 1st In Room A-148 45211939 1-L1 D107 05/16-P
05/30-P Duct Detector 1st In Room A-148 45211938 1-L1 D108 05/16-P
05/30-P Duct Detector 1st In Room A-160 45211937 1-L1 D111 05/16-P
05/30-P Duct Detector 1st In Room A-158 45211936 1-L1 D113 05/16-P
05/30-P Duct Detector 1st In Room B-160 45211935 1-L1 D112 05/16-P
05/30-P Duct Detector 1st In Room B-154 45211934 1-L1 D84 05/16-P
05/30-P Duct Detector 1st In Room B-154 45211933 1-L1 D85 05/16-P
05/30-P Duct Detector 1st In Room B-148 45211932 1-L1 D87 05/16-P
05/30-P Duct Detector 1st In Room B-147 45211931 1-L1 D96 05/16-P
05/30-P Duct Detector 1st In Room F-125 45211928 1-L1 D129 05/16-P
05/30-P Duct Detector 1st In Room F-125 45211927 1-L1 D127 05/16-P
05/30-P Duct Detector 1st In Room F-125 45211926 1-L1 D130 05/16-P
05/30-P Duct Detector 1st In Room F-127 45211925 1-L1 D128 05/16-P
05/30-P Duct Detector 1st Inside Room D-154 45208581 1-L1 D54 05/16-P
05/30-P Duct Detector 1st Inside Room D-154 45208580 1-L1 D53 05/16-P
05/30-P Duct Detector 1st Bldg F Roof 45206229 1-L1 M158 05/16-P
05/30-P Duct Detector 1st Restroom F-120 45206221 1-L1 D125 05/16-P
05/19-P Duct Detector 1st By Room A-109 45206206 1-L1 D103 05/16-P
05/19-P Duct Detector 1st In Room B-160 (B-146) 45205345 1-L1 D94 05/16-P
05/19-P Duct Detector 1st In Room B-160 (B-146) 45205344 1-L1 D93 05/16-P
05/19-P Duct Detector 1st By Room B-148 45205343 1-L1 D86 05/16-P
05/19-P Duct Detector 1st Corridor By C-160 45205341 1-L1 D67 05/16-P
05/19-P Duct Detector 1st In Room D-148 45205339 1-L1 D56 05/16-P
05/19-P Duct Detector 1st In Room D-148 45205338 1-L1 D55 05/16-P
05/19-P Duct Detector 1st Hallway by D-109 45205334 1-L1 D52 05/16-P
05/19-P Duct Detector 1st Hallway by D-109 45205333 1-L1 D51 05/16-P
05/19-P Duct Detector 1st In Room D-160 45205332 1-L1 D57 05/16-P
05/19-P Duct Detector 2nd In Men's Restroom F-222 45212810 1-L1 D142 05/16-P
05/30-P Duct Detector 2nd Corridor Of Room F-235 45212786 1-L1 D144 05/16-P
05/30-P Duct Detector 2nd In Room F-229 45212787 1-L1 D145 05/16-P
05/30-P Duct Detector 2nd In Room F-206 45212785 1-L1 D150 05/16-P
05/30-P Duct Detector 2nd In Room F-205 45212784 1-L1 D149 05/16-P
05/30-P Duct Detector 2nd Outside F-ME4 45212782 1-L1 D148 05/16-P
05/30-P Duct Detector 2nd In Room F-229 45211963 1-L1 D146 05/16-P
05/30-P Duct Detector 2nd In Room F-235 45211930 1-L1 D147 05/16-P
05/30-P Device Total: 90
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Fan Shutdown
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Fan Shutdown 1st Bldg F Roof 45206231 1-L1 M157 05/16-P
05/30-P Fan Shutdown 1st Bldg A, B, C, D Roof (AC-D) 45205354 1-L1 M120 05/16-P
05/19-P Fan Shutdown 1st Bldg A, B, C, D Roof (AC-C) 45205353 1-L1 M121 05/16-P
05/19-P Fan Shutdown 1st Bldg A, B, C, D Roof 45205352 1-L1 M122 05/16-P
05/19-P Fan Shutdown 1st Bldg A, B, C, D Roof (AC-A) 45205351 1-L1 M123 05/16-P
05/19-P Device Total: 5
LS 02.01.34 EP 02
Protected master fire alarm control panel Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Control Panel
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Control Panel 1st FACP E-EC1 45212838
08/21-P 05/30-P Device Total: 1
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Annunciator
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Annunciator 1st By Room D-105 45206207 05/16-P 08/21-P 05/19-P Annunciator 1st By Bldg F Front entrance 45205350 05/16-P 08/21-P 05/19-P Device Total: 2
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Battery
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Battery 1st FACP E-EC1 45212846
08/21-F 05/30-P Battery 1st FACP E-EC1 45212845
08/21-F 05/30-P Battery 1st FACP E-EC1 45212844 05/16-F 08/21-F 05/30-P Battery 1st FACP E-EC1 45212843 05/16-F 08/21-F 05/30-P Battery 1st FACP E-EC1 45212842 05/16-F 08/21-F 05/30-P Battery 1st FACP E-EC1 45212841 05/16-F 08/21-F 05/30-P Battery 1st FACP E-EC1 45212840 05/16-F 08/21-F 05/30-P Battery 1st FACP E-EC1 45212839 05/16-F 08/21-P 05/30-P Battery 1st FACP E-EC1 45212834 05/16-F 08/21-F 05/30-P Battery 1st FACP E-EC1 45212833 05/16-F 08/21-F 05/30-P Battery 1st Bldg F Elec Rm F-EC1 45206211
08/21-P 05/19-P Battery 1st Bldg F Elec Rm F-EC1 45206210
08/21-P 05/19-P Battery 1st In room A-EC1 45206203
08/21-P 05/19-P Battery 1st In room A-EC1 45206202
08/21-P 05/19-P Device Total: 14
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Power Supply
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Power Supply 1st FACP E-EC1 45212832
08/21-P 05/30-P Power Supply 1st Room F-EC1 45206214
08/21-P 05/19-P Device Total: 2
Service Summary
Building: PA520 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity Passed Annunciator Tested Battery Tested Bell Tested Chime/Strobe Tested Control Panel Tested Duct Detector Tested Fan Shutdown Tested Heat Detector Tested Monitor Device Tested Power Supply Tested Pull Station Tested Releasing Device Tested Smoke Detector Tested/Cleaned Speaker/Strobe Tested Speaker Tested Strobe Tested Tamper Switch Tested Voice Evacuation Tested Waterflow Switch Tested Total Grand Total
Auxiliary Functions Testing
Building: PA520 Control Panel: 1 - Notifier NFS2-3030D The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated Passed Fan Shutdown
1st Bldg A, B, C, D Roof Passed 45205352
1st Bldg A, B, C, D Roof (AC-A) Passed 45205351
1st Bldg A, B, C, D Roof (AC-C) Passed 45205353
1st Bldg A, B, C, D Roof (AC-D) Passed 45205354
1st Bldg F Roof Passed 45206231 Releasing Device
1st Corridor Of F-101 Passed 45212856
1st Corridor Of F-101 Passed 45212857
Battery & Power Supply Testing
Building: PA520 Control Panel: 1 - Notifier NFS2-3030D The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Tested Ah Passed Sealed Lead Acid 1st Bldg F Elec Rm F-EC1
Sealed Lead Acid 1st Bldg F Elec Rm F-EC1
1st FACP E-EC1
75-NB
75-NB
1st In room A-EC1
1st In room A-EC1
Inventory & Warranty Report
Building: PA520 Control Panel: 1 - Notifier NFS2-3030D The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Annunciator Control 0.64% Battery Control 4.46% Bell Indicating 0.32% Chime/Strobe Indicating 0.32% Control Panel Control 0.32% Duct Detector Initiating 28.66% Fan Shutdown Auxiliary 1.59% Heat Detector Initiating 0.64% Monitor Device Monitor 4.14% Power Supply Control 0.64% Pull Station Initiating 7.64% Releasing Device Auxiliary 0.64% Smoke Detector Initiating 9.55% Speaker Indicating 4.78% Speaker/Strobe Indicating 22.29% Strobe Indicating 8.28% Tamper Switch Supervisory 2.23% Voice Evacuation Control 0.96% Waterflow Switch Initiating 1.91%
Type Qty Model # Description Install Date In Service - 1 Year to 2 Years Power-Sonic Battery
Sealed Lead Acid 08/10/2023 In Service - 3 Years to 5 Years Power-Sonic Battery
Sealed Lead Acid 05/13/2021 Notifier Monitor Device
FCM-1
09/16/2020 Power-Sonic Battery
Sealed Lead Acid 09/16/2020 In Service - 5 Years to 10 Years Power-Sonic Battery
Sealed Lead Acid 05/01/2018 Notifier Annunciator
FDU-80
05/17/2017 Duct Detector D4S
05/17/2017 Duct Detector
DNR FSP-851
05/17/2017 Fan Shutdown
FRM-1
05/17/2017 Heat Detector
FSP-851
05/17/2017 Monitor Device
FCM-1
05/17/2017 Monitor Device
FRM-1
05/17/2017 Power Supply
FCPS-24S6
05/17/2017 Pull Station 45211946
05/17/2017 Pull Station
NBG-12LX
05/17/2017 Releasing Device
05/17/2017 Smoke Detector
FSP-851
05/17/2017 Tamper Switch
Tamper Switch
OSY2
05/17/2017 Waterflow Switch
Siemens Speaker/Strobe
CH-MC-W
05/17/2017 Speaker/Strobe
CN121080
05/17/2017 Speaker/Strobe
SET-MC-R
05/17/2017 System Sensor Duct Detector D4P120
05/17/2017 Waterflow Switch
WFD30-2V
05/17/2017 Victaulic Tamper Switch
05/17/2017 Wheelock Speaker E70-R
05/17/2017 Speaker E90-W
05/17/2017 Speaker/Strobe E50-241575W
05/17/2017 Speaker/Strobe E90-24100C
05/17/2017 Speaker/Strobe
E90-24100C-FW
05/17/2017 Speaker/Strobe
ET70WP-24185WFR
05/17/2017 Speaker/Strobe
ET70WP-2475W
05/17/2017 Strobe
RSS-24MCW
05/17/2017 Strobe STW-White
05/17/2017 Strobe
WH-STWC
05/17/2017 wheelock Chime/Strobe
E70-24MCW-FR
05/17/2017 In Service - 10 Years to 15 Years Notifier Control Panel
NFS2-3030D
04/20/2015 Building: PA520 Control Panel: 2 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date In Service - 5 Years to 10 Years Edwards Bell
03/14/2018 Notifier Voice Evacuation
DAA2-5070
Zone Address Report
Building: PA520 Control Panel: 1 - Notifier NFS2-3030D The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Zone/Circuit: B1-5/S Speaker/Strobe 1st Corridor by Room A-180
5680684 Zone/Circuit: B1/S4 Speaker/Strobe 1st In Room A-145
45212903 Speaker/Strobe 1st In Room A-143
45212904 Speaker/Strobe 1st In Room A-170
45212909 Zone/Circuit: B2/S4 Speaker/Strobe 1st In Room A-140
45212888 Speaker/Strobe 1st In Room A-137
45212891 Speaker/Strobe 1st In Room A-136
45212890 Speaker/Strobe 1st In Room A-135
45212895 Zone/Circuit: B3/S4 Speaker/Strobe 1st By A-134
45212896 Speaker/Strobe 1st In Room A-134
45212894 Speaker/Strobe 1st In Room A-133
45212893 Speaker/Strobe 1st In Room A-132
45212892 Speaker/Strobe 1st In Room A-130
45212889 Speaker/Strobe 1st In Room A-129
45212918 Speaker/Strobe 1st In Room A-127
45212923 Speaker/Strobe 1st In Room A-126
45212924 Speaker/Strobe 1st In Room A-125
45212926
11 EOL
Speaker/Strobe 1st By Room A-123
45212928 Zone/Circuit: B4- Strobe 1st By A-140
45212900 Zone/Circuit: B4/S4 Speaker/Strobe 1st By Room A-120
45212941 Speaker/Strobe 1st In Room A-120
45212940 Speaker/Strobe 1st In Room A-121
45212922 Speaker/Strobe 1st In Room A-122
45212925 Speaker/Strobe 1st In Room A-123
45212927 Speaker/Strobe 1st In Room A-117
45212887 Speaker/Strobe 1st In Room A-111
45212938
10 EOL
Speaker/Strobe 1st By Room A-109
45212944 Zone/Circuit: L1 D01 Smoke Detector 1st FACP Room E-EC1
45212831 D02 Smoke Detector 1st Corridor Of D-145
45211951 D03 Smoke Detector 1st Corridor Of D-145
45205340 D17 Smoke Detector 1st Elevator Lobby
45212851 D18 Smoke Detector 1st Office In F-108
45212772 D19 Smoke Detector 1st Office In F-108
45212771 D20 Smoke Detector 1st Electrical Room F-EC1
45206216 D21 Smoke Detector 1st By Waiting Room F-108
45212850 D22 Smoke Detector 1st By Room F-108
45212916 D23 Smoke Detector 2nd Corridor Near Elevator
45212823 D24 Smoke Detector 2nd Top Of Stairs
45212824 D25 Smoke Detector 2nd In Room F-206
45212802 D26 Smoke Detector 2nd In Room F-206
45212801 D27 Smoke Detector 2nd In Room F-ME4
45212795 D28 Heat Detector 2nd In Room F-ME4
45212794 D29 Smoke Detector 2nd Corridor Near Elevator
45212822 D30 Smoke Detector 2nd In Room F-ME4
45212792 D31 Heat Detector 2nd In Room F-ME4
45212793 D32 Smoke Detector 1st By Room A-109
45212943 D33 Smoke Detector 1st By Room A-117
45212942 D34 Smoke Detector 1st Above A-Wing Reception
45212920 D35 Smoke Detector 1st By Room A-121
45212931 D36 Smoke Detector 1st By Room A-125
45212930 D37 Smoke Detector 1st Corridor Of Reception Area
45212919 D38 Smoke Detector 1st By Room A-132
45212899 D39 Smoke Detector 1st By Room A-132
45212898 D41 Smoke Detector 1st In Room A-EC1
45211965 D42 Smoke Detector 1st By Room A-152
45212886 D45 Smoke Detector 1st Above A-Wing Reception
45212921 D51 Duct Detector 1st Hallway by D-109
45205333 D52 Duct Detector 1st Hallway by D-109
45205334 D53 Duct Detector 1st Inside Room D-154
45208580 D54 Duct Detector 1st Inside Room D-154
45208581 D55 Duct Detector 1st In Room D-148
45205338 D56 Duct…