This document is a Fire/Life Safety System Inspection report for Building 500 at the Palo Alto VA Medical Center, conducted on June 4, 2025. The comprehensive inspection covered multiple fire protection and life safety systems across ground, first, second, and third floors, including 574 total devices tested. Key systems evaluated included smoke detectors, fire alarms, damper controls, speakers/strobes, pull stations, waterflow switches, and elevator safety interfaces, with testing performed in accordance with NFPA 101 (2024), NFPA 72 (2022), and NFPA 90A (2024) standards.
The inspection revealed mostly successful results, with 573 devices passing tests and only one damper control device failing (located in the 1st East Hallway). Notable findings include a motor malfunction in a 3rd Floor Corridor duct detector and a door release seal issue preventing full closure in the 3rd Right Wing Corridor. The fire alarm control panel is a Notifier NFS2-3030 model, installed in May 2017, with testing conducted by Facility - Palo Alto VA personnel. This report directly relates to a concurrent federal contract opportunity (Solicitation 36C26126Q0026) for Fire Alarm Maintenance at the VA Palo Alto Health Care System, with quote submissions extended to November 27, 2025.
Text of this file
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate For
PA500
3801 Miranda Ave
Palo Alto, CA 94304
This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR CONDITIONING/VENTILATING SYSTEMS.
This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection Inspection Completion Date Jun 4, 2025 Building: PA500 Company: Facility - Palo Alto VA Contact: Anthony Losito Contact: Olaf Soto Title: Electronics Shop Supervisor Title: Inspector
Facility - Palo Alto VA
Download Date: 06/11/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: PA500 Contact: Anthony Losito Address: 3801 Miranda Ave Phone: 6508523437 Address:
Fax:
City/State/ZIP Code: Palo Alto, CA 94304 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Facility - Palo Alto VA Inspector: Olaf Soto Address: 2700 Gregory St Ste 180 Phone: 650-362-4841 Address:
Fax:
City/State/ZIP Code: Savannah, GA 31404 Mobile:
Country: United States of America Email: olaf@redwoodcityalarms.com
System Control Unit Manufacturer: Notifier Inspection Date: 06/04/2025 IDC Style: B Model Number: NFS2-3030 Install Date: 05/16/2017 SLC Style:
Software Version:
Version Date: 12/31/1969 NAC Style: Y Location: Ground Lobby Current Protection: Breaker
Central Station Signal Verification Type:
Mfg: Notifier Model #: HS-NCM-MF Test Time/Date: 6/4/25 8:44:05 PM Restore Time:
Note:
Type of Signal Signal Confirmation Notes
Confirmed Time:
Inspection Completion Date: Jun 4, 2025 Building: PA500
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Power Loss Supervisory Device Tamper Switch
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Waterflow Switch
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector Heat Detector Pull Station Smoke Detector
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Releasing Device Speaker Speaker/Strobe Strobe Voice Evacuation
EC 02.03.05 EP 05
Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Communicator Monitoring
EC 02.03.05 EP 18
Operation of fire and smoke dampers to verify full closure. NFPA 90A-2024: 5.4.8; NFPA 80-2022: 19.5; NFPA 105-2022: 7.6.2 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Damper Control
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector
LS 02.01.34 EP 02
Protected master fire alarm control panel Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Control Panel
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Annunciator Battery Expander Panel Power Supply Special Control
LS 02.01.50 EP 07
Annual - Elevators are fully equipped and protected Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Elevator Total Device Count: 574
Certification Company: Facility - Palo Alto VA Building: PA500 Inspector: Olaf Soto Contact: Anthony Losito file_0.jpg
Signed: Jun 4, 2025 Signed:
Discrepancy Report
Building: PA500 Control Panel: 1 - Notifier NFS2-3030 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade No items found during this inspection.
& ScanID ` Location L Problem Address & Reference EC 02.03.05 EP 18 Operation of fire and smoke dampers to verify full closure. NFPA 90A-2024: 5.4.8; NFPA 80-2022: 19.5; NFPA 105-2022: 7.6.2 Damper Control 45207967 1st East Hallway
1-1 D11
Proposed Solutions Report
Building: PA500 Control Panel: 1 - Notifier NFS2-3030 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 18
Operation of fire and smoke dampers to verify full closure. NFPA 90A-2024: 5.4.8; NFPA 80-2022: 19.5; NFPA 105-2022: 7.6.2 Damper Control 45207967 1st East Hallway
RST451
T/M
Internal WO/PO #: (none) T/M
Notes & Recommendations
Building: PA500 Control Panel: 1 - Notifier NFS2-3030 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) 45211150 Duct Detector 3rd Floor Corridor A3-136 Passed Motor not working (stuck on closed) EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) 45211016 Releasing Device 3rd Right Wing Corridor Outside A3-405 Passed Door Release functions but seal wont let door close EC 02.03.05 EP 18 Operation of fire and smoke dampers to verify full closure. NFPA 90A-2024: 5.4.8; NFPA 80-2022: 19.5; NFPA 105-2022: 7.6.2 45207967 Damper Control 1st East Hallway
Stuck on closed
Inspection & Testing
Building: PA500 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g) Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Power Loss
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Power Loss 1st A1-EL1 Back 45207957 1-1 M08 05/14-P
06/04-P Device Total: 1
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g) Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Supervisory Device
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Supervisory Device Ground Elevator Control Room 45210345 1-1 M102 05/14-P
06/04-P Supervisory Device Ground Electrical Room NAC Expander Panel 45210335 1-1 M28 05/14-P
06/04-P Supervisory Device Ground Lobby 45210320 1-1 M099 05/14-P
06/04-P Device Total: 3
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g) Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Tamper Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Tamper Switch 1st Southwest Stairwell 45208025 1-4 M025
08/14-P 06/04-P Tamper Switch 1st Southwest Stairwell 45208017 1-1 M76
08/14-P 06/04-P Tamper Switch 1st Southwest Stairwell 45208016 1-1 M74
08/14-P 06/04-P Tamper Switch 1st street side os&y x2 45206148 1-4 M063
08/14-P 06/04-P Tamper Switch 1st outside front of bldg street PIV 45206147 1-4 M062
08/14-P 06/04-P Tamper Switch 1st outside at riser in room b1me2 45206146 1-2 M52
08/14-P 06/04-P Tamper Switch 1st outside at riser in room b1me2 45206145 1-2 M46
08/14-P 06/04-P Tamper Switch 1st outside at riser in room b1me2 45206144 1-2 M44
08/14-P 06/04-P Tamper Switch 2nd Right Wing Rear Stairwell 45207834 1-3 M45
08/14-P 06/04-P Tamper Switch 2nd Right Wing Rear Stairwell 45207833 1-3 M47
08/14-P 06/04-P Tamper Switch 3rd Right Wing Rear Stairwell 45207828 1-5 M59
08/14-P 06/04-P Tamper Switch 3rd Right Wing Rear Stairwell 45207827 1-5 M51
08/14-P 06/04-P Device Total: 12
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Waterflow Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Waterflow Switch 1st East Stairwell across from EMS Supply rm B1-539 45208026 1-4 M026
08/14-P 06/04-P Waterflow Switch 1st Southwest Stairwell 45208019 1-1 M75
08/14-P 06/04-P Waterflow Switch 1st Southwest Stairwell 45208018 1-1 M77
08/14-P 06/04-P Waterflow Switch 1st outside room b1-me2 45206143 1-2 M47
08/14-P 06/04-P Waterflow Switch 1st outside in room b1me2 45206142 1-2 M45
08/14-P 06/04-P Waterflow Switch 1st outside in room b1me2 45206141 1-2 M43
08/14-P 06/04-P Waterflow Switch 2nd Right Wing Rear Stairwell 45207832 1-3 M046
08/14-P 06/04-P Waterflow Switch 2nd Right Wing Rear Stairwell 45207831 1-3 M048
08/14-P 06/04-P Waterflow Switch 3rd Right Wing Rear Stairwell 45207830 1-5 M60
08/14-P 06/04-P Waterflow Switch 3rd Right Wing Rear Stairwell 45207829 1-5 M52
08/14-P 06/04-P Device Total: 10
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Duct Detector 1st Ned Storage B1-542 45211674 1-2 D13 05/14-P
06/04-P Duct Detector 1st B1-539 EMS Supply 45211670 1-2 D11 05/14-P
06/04-P Duct Detector 1st B Wing Inside Room B1-507 Therapy Suite 45211110 1-2 D14 05/14-P
06/04-P Duct Detector 1st Right Wing Inside Room B1-507 Therapy Suite 45211036 1-2 D14 05/14-P
06/04-P Duct Detector 1st A1-504 45208579 1-L1 D15 05/14-P
06/04-P Duct Detector 1st A1-605 45208578 1-L1 D22 05/14-P
06/04-P Duct Detector 1st Corridor Near A1-216 01 Level 45208577 1-L1 D17 05/14-P
06/04-P Duct Detector 1st East Hallway 45207997 1-1 D11 05/14-P
06/04-P Duct Detector 1st East Hallway 45207987 1-1 M59 05/14-P
06/04-P Duct Detector 1st East Hallway 45207986 1-1 M60 05/14-P
06/04-P Duct Detector 1st Behind FACP 45205329 1-1 S07 05/14-P
06/04-P Duct Detector 1st Behind FACP 45205328 1-1 S08 05/14-P
06/04-P Duct Detector 1st A1-306 Clean Utility Room 45205327 1-1 D50 05/14-P
06/04-P Duct Detector 1st Inside Room A1-603 45205326 1-1 D16 05/14-P
06/04-P Duct Detector 1st By Room A1-224 Corridor 45205325 1-1 D30 05/14-P
06/04-P Duct Detector 1st By Room A1-224 Corridor 45205324 1-1 D31 05/14-P
06/04-P Duct Detector 2nd A2-306 Clean Utility 45211682 1-3 D24 05/14-P
06/04-P Duct Detector 2nd A2-506 Laundry 45211680 1-3 D12 05/14-P
06/04-P Duct Detector 2nd A2-504 Storage 45211679 1-3 D14 05/14-P
06/04-P Duct Detector 2nd A2-131A Dressing Room 45211678 1-3 D20 05/14-P
06/04-P Duct Detector 2nd A2-131A Dressing Room 45211677 1-3 D21 05/14-P
06/04-P Duct Detector 2nd A2-126 Office 45211676 1-3 D22 05/14-P
06/04-P Duct Detector 2nd B2-306 Storage 45211675 1-4 D03 05/14-P
06/04-P Duct Detector 2nd By Room B2-214 45211597 1-4 7 05/14-P
06/04-P Duct Detector 2nd By Room B2-214 45211596 1-4 6 05/14-P
06/04-P Duct Detector 2nd By Room B2-508 45211582 1-4 10 05/14-P
06/04-P Duct Detector 2nd By Room 600-G 45211569 1-4 13 05/14-P
06/04-P Duct Detector 2nd Right Wing Corridor Outside A2-115 45210982 1-3 D06 05/14-P
06/04-P Duct Detector 2nd Right Wing Corridor Outside A2-126 45210964 1-3 D23 05/14-P
06/04-P Duct Detector 2nd Right Wing Corridor Outside A2-230 45210952 1-3 D17 05/14-P
06/04-P Duct Detector 2nd Right Wing Corridor Outside A2-230 45210951 1-3 D18 05/14-P
06/04-P Duct Detector 2nd Right Wing Corridor Outside A2-220 45210944 1-3 D07 05/14-P
06/04-P Duct Detector 2nd Right Wing Corridor Outside A2-204 45210937 1-3 D02 05/14-P
06/04-P Duct Detector 2nd Elevator Lobby Left of Elevator Entrance 45210926 1-3 D04 05/14-P
06/04-P Duct Detector 2nd A2-101 45208576 1-L2 D05 05/14-P
06/04-P Duct Detector 2nd A2-607 Room 45208575 1-L2 D11 05/14-P
06/04-P Duct Detector 2nd B2-502 45208574 1-L2 D09 05/14-P
06/04-P Duct Detector 2nd By Room B2-114 45205323 1-4 D05 05/14-P
06/04-P Duct Detector 2nd Break Room A2-605 45205322 1-3 D13 05/14-P
06/04-P Duct Detector 3rd Break Room A3-318 45211686 1-5 D02 05/14-P
06/04-P Duct Detector 3rd Right Wing Corridor Outside A3-238 45211031 1-5 D18 05/14-P
06/04-P Duct Detector 3rd Right Wing Elevator Lobby Left of Elevator Entrance 45210993 1-5 D04 05/14-P
06/04-P Duct Detector 3rd Right Wing Elevator Lobby Left of Elevator Entrance 45210986 1-5 D37 05/14-P
06/04-P Duct Detector 3rd Room Inside Room A3-404 Supply Room 45208640 1-2 D14 05/14-P
06/04-P Duct Detector 3rd Right Wing Bathroom A3-101 45207841 1-5 D05 05/14-P
06/04-P Duct Detector Roof AHU-6 45211908 1-L04 D28 05/14-P
06/04-P Duct Detector Roof AHU-6 45211907 1-L04 D27 05/14-P
06/04-P Duct Detector Roof AHU-5 45211906 1-L04 D25 05/14-P
06/04-P Duct Detector Roof AHU-5 45211905 1-L04 D26 05/14-P
06/04-P Duct Detector Roof AHU-4 45211904 1-L5 D31 05/14-P
06/04-P Duct Detector Roof AHU-4 45211903 1-L5 D30 05/14-P
06/04-P Duct Detector Roof AHU-3 45211902 1-L5 D34 05/14-P
06/04-P Duct Detector Roof AHU-3 45211901 1-L5 D35 05/14-P
06/04-P Duct Detector Roof AHU-1 45211900 1-L5 D32 05/14-P
06/04-P Duct Detector Roof AHU-1 45211899 1-L5 D33 05/14-P
06/04-P Duct Detector Roof AHU-2 45211898 1-L5 D29 05/14-P
06/04-P Duct Detector Roof AHU-2 45211897 1-L05 D28 05/14-P
06/04-P Duct Detector 3rd Floor Corridor A3-136 45211150 1-5 D20 05/14-P
05/19-P Device Total: 58
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Heat Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Heat Detector 2nd Inside Room B2-600D Finish 45208633 1-4 14 05/14-P
06/04-P Device Total: 1
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Pull Station
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Pull Station 1st Corridor by Stair 4 Entrance 45211135 1-1 M80 05/14-P
06/04-P Pull Station 1st Rear Exit by sliding doors 45211134 1-1 M73 05/14-P
06/04-P Pull Station 1st Southeast Stairwell 4 45208020 1-1 M78 05/14-P
06/04-P Pull Station 1st East Hallway 45207991 1-1 M79 05/14-P
06/04-P Pull Station 1st East RM A1-504 45207978 1-1 M41 05/14-P
06/04-P Pull Station 1st East RM A1-503 45207975 1-1 M43 05/14-P
06/04-P Pull Station 1st East Hallway 45207966 1-1 M45 05/14-P
06/04-P Pull Station 1st East Hallway 45207964 1-1 M47 05/14-P
06/04-P Pull Station 1st East Stair 45207947 1-1 M16 05/14-P
06/04-P Pull Station 1st East Wing Stair 45207945 1-1 M17 05/14-P
06/04-P Pull Station 1st East WS 45207939 1-1 M14 05/14-P
06/04-P Pull Station 1st Front Lobby 45207936 1-1 M01 05/14-P
06/04-P Pull Station 2nd Corridor Lobby 45211609 1-4 M40 05/14-P
06/04-P Pull Station 2nd By CB2-150 45211605 1-4 M01 05/14-P
06/04-P Pull Station 2nd Corridor By Room B2-221 45211595 1-4 M18 05/14-P
06/04-P Pull Station 2nd Exit 45211587 1-4 M24 05/14-P
06/04-P Pull Station 2nd Hallway With Rail 45211564 1-4 M06 05/14-P
06/04-P Pull Station 2nd Corridor Lobby 45211557 1-4 M36 05/14-P
06/04-P Pull Station 2nd Breezeway Leaving Left Wing Into Right Wing 45210992 1-4 M34 05/14-P
06/04-P Pull Station 2nd Breezeway Elevator Lobby Between Left and Right Wing by St 45210988 1-3 M49 05/14-P
06/04-P Pull Station 2nd Right Wing Corridor Outside A2-119 45210971 1-3 M21 05/14-P
06/04-P Pull Station 2nd Right Wing Corridor Outside A2-120 45210970 1-3 M22 05/14-P
06/04-P Pull Station 2nd Right Wing Corridor Outside A2-802 45210961 1-3 M44 05/14-P
06/04-P Pull Station 2nd Right Wing Corridor Outside A2-830 45210956 1-3 M43 05/14-P
06/04-P Pull Station 2nd Right Wing Corridor Outside A2-228 45210947 1-3 M37 05/14-P
06/04-P Pull Station 2nd Right Wing Corridor Outside A2-226 45210946 1-3 M36 05/14-P
06/04-P Pull Station 2nd Right Wing Corridor Outside A2-224 45210945 1-3 M20 05/14-P
06/04-P Pull Station 2nd Right Wing Corridor Outside A2-202 Exit to Stairwell 45210938 1-3 M06 05/14-P
06/04-P Pull Station 2nd Right Wing Reception Outside A2-300A 45210932 1-3 M09 05/14-P
06/04-P Pull Station 2nd Right Wing Corridor Outside A2-300B 45210930 1-3 M10 05/14-P
06/04-P Pull Station 3rd Right Wing Corridor Outside A3-119 45211042 1-5 M21 05/14-P
06/04-P Pull Station 3rd Right Wing Corridor Outside A3-117 45211038 1-5 M19 05/14-P
06/04-P Pull Station 3rd Right Wing Corridor Outside A3-236 45211029 1-5 M36 05/14-P
06/04-P Pull Station 3rd Right Wing Corridor Outside A3-232 45211023 1-5 M35 05/14-P
06/04-P Pull Station 3rd Right Wing Corridor Outside A3-401 45211021 1-5 M62 05/14-P
06/04-P Pull Station 3rd Right Wing Corridor Outside A3-405 45211015 1-5 M61 05/14-P
06/04-P Pull Station 3rd Right Wing Corridor Outside A3-226 45211012 1-5 M40 05/14-P
06/04-P Pull Station 3rd Right Wing Corridor Outside A3-200 by Stairwell 45211003 1-5 M09 05/14-P
06/04-P Pull Station 3rd Right Wing Corridor Outside A3-301 45210997 1-5 M11 05/14-P
06/04-P Pull Station Roof Right Wing Elevator Lobby 45207836 1-5 M53 05/14-P
06/04-P Pull Station 1st Floor Corridor B1-140 45211125 1-2 M26 05/14-P
06/04-P Pull Station 1st Floor Corridor B1- 539 45211113 1-2 M42 05/14-P
06/04-P Pull Station 1st Floor Stairwell B1-543 45211107 1-2 M41 05/14-P
06/04-P Pull Station 1st Floor Corridor B1-503 45211103 1-2 M27 05/14-P
06/04-P Pull Station 1st Floor Corridor B1- Near Front Entry 45211097 1-2 M01 05/14-P
06/04-P Pull Station 1st Floor Corridor B1- Near Front Entry 45211095 1-2 M25 05/14-P
06/04-P Pull Station 1st Floor Corridor B1-401 45211087 1-2 M24 05/14-P
06/04-P Pull Station 1st Floor Corridor B1-209 45211083 1-2 M16 05/14-P
06/04-P Pull Station 1st Floor Corridor B1-207 45211082 1-2 M14 05/14-P
06/04-P Pull Station 1st Floor Corridor B1301 45211078
1-2 MO2
05/14-P
06/04-P Pull Station 3rd Floor Corridor A3-145 45211141 1-5 M50 05/14-P
06/04-P Pull Station Ground Hallway Near A1-220 45210331 1-1 M50 05/14-P
06/04-P Pull Station Ground Hallway Near A1-220 45210326 1-1 M26 05/14-P
06/04-P Device Total: 53
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Smoke Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Smoke Detector 1st Electrical Room A1-EC1 45211881 1-1 D09 05/14-P
06/04-P Smoke Detector 1st Electrical Room 45211642 1-2 D03 05/14-P
06/04-P Smoke Detector 1st East A1-EL2 45208024 1-1 D26 05/14-P
06/04-P Smoke Detector 1st East A1-EL2 45208023 1-1 D25 05/14-P
06/04-P Smoke Detector 1st Rear Elev Lobby 45208004 1-1 D29 05/14-P
06/04-P Smoke Detector 1st East Hallway 45207977 1-1 D13 05/14-P
06/04-P Smoke Detector 1st East Hallway 45207976 1-1 D14 05/14-P
06/04-P Smoke Detector 1st East Hallway 45207969 1-1 D12 05/14-P
06/04-P Smoke Detector 1st East Hallway 45207968 1-1 D10 05/14-P
06/04-P Smoke Detector 1st A1-EL1 Back 45207956 1-1 D05 05/14-P
06/04-P Smoke Detector 1st Front Lobby 45207938 1-1 D03 05/14-P
06/04-P Smoke Detector 1st RM A1-EL1 1-1 D04 05/14-P
06/04-P Smoke Detector 2nd Electrical Room A2-EC1 45211703 1-3 D10 05/14-P
06/04-P Smoke Detector 2nd Electrical Room A2-EC2 45211681 1-3 D01 05/14-P
06/04-P Smoke Detector 2nd Electrical Room B2-EC2 45211655 1-4 D08 05/14-P
06/04-P Smoke Detector 2nd Electrical Room B2-EC1 45211647 1-4 D04 05/14-P
06/04-P Smoke Detector 2nd Corridor Lobby By Double Doors 45211607 1-4 12 05/14-P
06/04-P Smoke Detector 2nd Corridor Lobby By Double Doors 45211606 1-4 11 05/14-P
06/04-P Smoke Detector 2nd Corridor By Double Doors 45211580 1-4 15 05/14-P
06/04-P Smoke Detector 2nd Corridor By Double Doors 45211579 1-4 14 05/14-P
06/04-P Smoke Detector 2nd Corridor Elevator Lobby 45211568 1-4 16 05/14-P
06/04-P Smoke Detector 2nd Corridor Elevator Lobby 45211567 1-4 17 05/14-P
06/04-P Smoke Detector 2nd Corridor Elevator Lobby 45211566 1-3 19 05/14-P
06/04-P Smoke Detector 2nd Corridor Lobby 45211565 1-4 D02 05/14-P
06/04-P Smoke Detector 2nd By Double Doors 45211561 1-4 D01 05/14-P
06/04-P Smoke Detector 2nd Right Wing Corridor Outside A2-226 Smoke Door 45210980 1-3 D08 05/14-P
06/04-P Smoke Detector 2nd Right Wing Corridor Outside A2-608 Smoke Door 45210979 1-3 D09 05/14-P
06/04-P Smoke Detector 2nd Right Wing Corridor Outside A2-119 Smoke Door 45210976 1-3 D15 05/14-P
06/04-P Smoke Detector 2nd Right Wing Corridor Outside A2-120 Smoke Door 45210973 1-3 D16 05/14-P
06/04-P Smoke Detector 2nd Elevator Lobby Between Elevator Entrances 45210928 1-3 D03 05/14-P
06/04-P Smoke Detector 3rd Electrical Room A3-EC1 45211689 1-5 D01 05/14-P
06/04-P Smoke Detector 3rd Electrical Room A3-EC2 45211685 1-5 D13 05/14-P
06/04-P Smoke Detector 3rd Right Wing Corridor Outside A3-119 45211040 1-5 D08 05/14-P
06/04-P Smoke Detector 3rd Right Wing Corridor Outside A3-117 45211039 1-5 D07 05/14-P
06/04-P Smoke Detector 3rd Right Wing Corridor Outside A3-236 45211027 1-5 D15 05/14-P
06/04-P Smoke Detector 3rd Right Wing Corridor Outside A3-232 45211024 1-5 D14 05/14-P
06/04-P Smoke Detector 3rd Right Wing Corridor Outside A3-401 45211019 1-5 D09 05/14-P
06/04-P Smoke Detector 3rd Right Wing Corridor Outside A3-402 45211018 1-5 D11 05/14-P
06/04-P Smoke Detector 3rd Right Wing Elevator Lobby Between Elevator Entrances 45210995 1-5 D03 05/14-P
06/04-P Smoke Detector Roof Right Wing Elevator Lobby 45207837 1-5 D26 05/14-P
06/04-P Smoke Detector 1st Floor Emergency Elec B1-EC2 45211663 1-2 D08 05/14-P
06/04-P Smoke Detector 1st Floor Corridor B1114 45211114 1-2 D16 05/14-P
06/04-P Smoke Detector 1st Floor Corridor B1 Near Front Entry 45211100 1-2 D02 05/14-P
06/04-P Smoke Detector 1st Floor Corridor B1 Near Front Entry 45211099 1-2 D01 05/14-P
06/04-P Smoke Detector 1st Floor Corridor B1207 45211091 1-2 D04 05/14-P
06/04-P Smoke Detector 1st Floor Corridor B1-209 45211090 1-2 D05 05/14-P
06/04-P Smoke Detector 1st Floor Corridor B1219 45211085 1-2 D07 05/14-P
06/04-P Smoke Detector 1st Floor Corridor B1219 45211084 1-2 D06 05/14-P
06/04-P Smoke Detector 1st Floor Corridor B1307 45211080 1-2 D15 05/14-P
06/04-P Smoke Detector 3rd Floor Soiled Linen Room A3-501 45211684 1-5 D16 05/14-P
06/04-P Smoke Detector 3rd Floor Corridor A3-145 45211146 1-5 D24 05/14-P
06/04-P Smoke Detector 3rd Floor Storage A3-140A 45211690 1-5 D23 05/14-P
06/04-P Smoke Detector 3rd Floor Storage A3-140A 45211857 1-5 D21 05/14-P
06/04-P Smoke Detector 3rd Floor Storage A3-140A 45211858 1-5 D22 05/14-P
06/04-P Smoke Detector Ground Electrical Room NAC Expander Panel 45210336 1-1 D20 05/14-P
06/04-P Smoke Detector Ground Hallway Near A1-222 45210330 1-1 D019 05/14-P
06/04-P Smoke Detector Ground Hallway Near A1-222 45210329 1-1 D018 05/14-P
06/04-P Smoke Detector Ground Lobby 45210322 1-1 D02 05/14-P
06/04-P Smoke Detector Ground Lobby 45210321 1-1 D01 05/14-P
06/04-P Device Total: 59
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Releasing Device
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Releasing Device 1st Corridor by Room B1-209 45211672 05/14-P
06/04-P Releasing Device 1st Corridor by Room B1-207 45211671 05/14-P
06/04-P Releasing Device 1st East Hallway 45208003 05/14-P
06/04-P Releasing Device 1st East Hallway 45208002 05/14-P
06/04-P Releasing Device 1st East Hallway 45208001 05/14-P
06/04-P Releasing Device 1st East Hallway 45208000 05/14-P
06/04-P Releasing Device 2nd By CB2-150 45211603 05/14-P
06/04-P Releasing Device 2nd By CB2-150 45211602 05/14-P
06/04-P Releasing Device 2nd By B2-501 45211578 05/14-P
06/04-P Releasing Device 2nd By B2-501 45211577 05/14-P
06/04-P Releasing Device 2nd Corridor Lobby 45211560 05/14-P
06/04-P Releasing Device 2nd Corridor Lobby 45211559 05/14-P
06/04-P Releasing Device 2nd Right Wing Corridor Outside A2-608 45210978 05/14-P
06/04-P Releasing Device 2nd Right Wing Corridor Outside A2-226 45210977 05/14-P
06/04-P Releasing Device 2nd Right Wing Corridor Outside A2-119 45210975 05/14-P
06/04-P Releasing Device 2nd Right Wing Corridor Outside A2-120 45210974 05/14-P
06/04-P Releasing Device 3rd Right Wing Corridor Outside A3-119 45211044 05/14-P
06/04-P Releasing Device 3rd Right Wing Corridor Outside A3-117 45211043 05/14-P
06/04-P Releasing Device 3rd Right Wing Corridor Outside A3-236 45211026 05/14-P
06/04-P Releasing Device 3rd Right Wing Corridor Outside A3-232 45211025 05/14-P
06/04-P Releasing Device 3rd Right Wing Corridor Outside A3-402 45211017 05/14-P
06/04-P Releasing Device 3rd Right Wing Corridor Outside A3-405 45211016 05/14-P
05/19-P Releasing Device 1st Floor Corridor Near Entry Right 45211156 05/14-P
06/04-P Releasing Device 1st Floor Corridor Near Entry Left 45211153 05/14-P
06/04-P Releasing Device Ground Hallway Near A1-220 45210328 05/14-P
06/04-P Releasing Device Ground Hallway Near A1-220 45210327 05/14-P
06/04-P Device Total: 26
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker 1st Southeast Stairwell 45208021 1-V4 19 05/14-P
06/04-P Speaker 1st East Stair 45207948 1-V3 3 05/14-P
06/04-P Speaker 2nd Right Wing Inside Stairwell by A2-202 45210940 1-V5 2 05/14-P
06/04-P Speaker 2nd Southwest Stairwell 45210347 1-V 8.28 05/14-P
06/04-P Speaker 2nd Southeast Stairwell 45210346 1-V 6.6 05/14-P
06/04-P Speaker 3rd Right Wing Inside Stairwell by A3-200 45211004 1-V9 6 05/14-P
06/04-P Speaker 3rd Right Wing Exit to Roof on Left Wing 45207838 05/14-P
06/04-P Speaker 1st Floor Stairwell B1-543 45211108 1-V2 27 05/14-P
06/04-P Speaker 3rd Floor Stairwell Rear 45211154 1-V10 13 05/14-P
06/04-P Device Total: 9
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker/Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker/Strobe 1st RM A1-120B 45211884
1-V3.7 B1.7EOL
05/14-P
06/04-P Speaker/Strobe 1st Staff Lounge A1-119 45211883 1-V3.17 B2.5 05/14-P
06/04-P Speaker/Strobe 1st Room A1-117 45211882 1-V3.15 B2.2 05/14-P
06/04-P Speaker/Strobe 1st East Hallway Conference Telehealth A1-115 45211880 1-V3.14 B2.1 05/14-P
06/04-P Speaker/Strobe 1st Elevator Lobby 45211136 1-V4.20 A2.10 05/14-P
06/04-P Speaker/Strobe 1st Interior Central Courtyard 45208022
1-NO ADDRESS ON DEVICE
05/14-P
06/04-P Speaker/Strobe 1st Elevator Lobby 45208015 1-V4 / A2 21 / 11 05/14-P
06/04-P Speaker/Strobe 1st East Hall BY A1 45208014 1-V4 / A1 4-Feb 05/14-P
06/04-P Speaker/Strobe 1st Out RM A1-232 45208012 1-V4 / A1 7-Mar 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45208008 1-V4 / A1 6-Apr 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45208007 1-V4 / A2 17 / 7 05/14-P
06/04-P Speaker/Strobe 1st RM A1-800B 45208005 1-V4 / A2 15 / 4 05/14-P
06/04-P Speaker/Strobe 1st RM A1-700GA 45207995 1-V4 / A2 16 / 5 05/14-P
06/04-P Speaker/Strobe 1st East RM A1-700 45207993 1-V4 / A2 18 / 8 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45207992 1-V4 / A2 14 / 3 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45207990 1-V4 / A2 13 / 2 05/14-P
06/04-P Speaker/Strobe 1st Laundry A1-127 45207983 1-V4 / A3 7-Oct 05/14-P
06/04-P Speaker/Strobe 1st 2nd Workstation 45207981 1-V4 / A3 4-Jun 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45207979
1-V3 / B2 20 EOL / 8 EOL
05/14-P
06/04-P Speaker/Strobe 1st 2nd Workst 45207972 1-V4 / B3 5-May 05/14-P
06/04-P Speaker/Strobe 1st East RM A1-120B 45207971 1-V4 / B3 6-Sep 05/14-P
06/04-P Speaker/Strobe 1st East RM A1-120 45207970 1-V4 / B3 2-Aug 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45207965 1-V4 / B3 3-Jul 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45207963 1-V3 / B2 18 / 4 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45207962 1-V3 / B2 16 / 3 05/14-P
06/04-P Speaker/Strobe 1st East RM A1-EL1 45207954 1-V3 / B3 4-Sep 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45207951 1-V3 / B3 1-Aug 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45207950 1-V3 / B1 4-Apr 05/14-P
06/04-P Speaker/Strobe 1st East Stair 45207946 1-V3 / B1 2-Feb 05/14-P
06/04-P Speaker/Strobe 1st East Hallway 45207944 1-V3 / B1 1-Jan 05/14-P
06/04-P Speaker/Strobe 1st East WS 45207940 1-V3 / B3 6-Nov 05/14-P
06/04-P Speaker/Strobe 1st Front Lobby 45207937 1-V3 / B3 10-Dec 05/14-P
06/04-P Speaker/Strobe 1st Front Lobby 45207935
1-V3 / B3 13 / 11 EOL
05/14-P
06/04-P Speaker/Strobe 1st Right Wing Courtyard Between Wings 45207843 05/14-P
06/04-P Speaker/Strobe 1st Outside B1-Me2 45205330 1-V8./H1. 8.1 05/14-P
06/04-P Speaker/Strobe 2nd B2-101 Conference Room 45211700
1-V8.1 H2.9EOL
05/14-P
06/04-P Speaker/Strobe 2nd In Room B2-401 45211699 1-V8.11 H1.4 05/14-P
06/04-P Speaker/Strobe 2nd Staff Lounge A2-131 Corridor Outside Balcony/Adjacent to Elevator Lo 45211694 1-V6.4 E3.7 05/14-P
06/04-P Speaker/Strobe 2nd By B2-402 45211654 1-V8./H1. 5-Dec 05/14-P
06/04-P Speaker/Strobe 2nd In Room B2-402 45211653 1-V8./H1. 5-Dec 05/14-P
06/04-P Speaker/Strobe 2nd Hallway Rail 45211652 1-V2./C2. 24/6 05/14-P
06/04-P Speaker/Strobe 2nd Hallway Rail 45211651 1-V8./G3. 19/3 05/14-P
06/04-P Speaker/Strobe 2nd Room Next To B2-402 45211640 1-V8./H1. 14/7 05/14-P
06/04-P Speaker/Strobe 2nd By Restrooms 45211627 1-V8./H1. 2-Sep 05/14-P
06/04-P Speaker/Strobe 2nd Corridor Lobby 45211610 1-V7./H3. 2-Feb 05/14-P
06/04-P Speaker/Strobe 2nd Corridor Lobby 45211608 1-V7./H3. 1-Jan 05/14-P
06/04-P Speaker/Strobe 2nd By CB2-150 45211604 1-V8./H2. 8-Feb 05/14-P
06/04-P Speaker/Strobe 2nd By B2-305 45211601 1-V8./H2. 7-Mar 05/14-P
06/04-P Speaker/Strobe 2nd By B2-315 45211600 1-V8./H2. 4-Apr 05/14-P
06/04-P Speaker/Strobe 2nd By Room B2-208 45211598 1-V7./H3. 3-May 05/14-P
06/04-P Speaker/Strobe 2nd By Room B2-221 45211594
1-V8./H1. 18/12 EOL
05/14-P
06/04-P Speaker/Strobe 2nd By Room B2-406 45211593 1-V8./H2 17/11 05/14-P
06/04-P Speaker/Strobe 2nd By Room B2-230 45211592 1-V8./H1. 16/10 05/14-P
06/04-P Speaker/Strobe 2nd By Room B2-243 45211591 1-V8./G1. 26/2 05/14-P
06/04-P Speaker/Strobe 2nd Kitchen B2-252 45211590 1-G1./V8. 25-Jan 05/14-P
06/04-P Speaker/Strobe 2nd By B2-254 45211589 1-V8./G1. 27/4 05/14-P
06/04-P Speaker/Strobe 2nd Exit 45211588 1-V8./G1. 29/5 05/14-P
06/04-P Speaker/Strobe 2nd Kitchen B2-508 45211586 1-V8./G1 30/6 05/14-P
06/04-P Speaker/Strobe 2nd Kitchen B2-506 45211585 1-V8./G2. 34/1 05/14-P
06/04-P Speaker/Strobe 2nd By Room B2-501 45211583 1-V8./G3. 20/6 05/14-P
06/04-P Speaker/Strobe 2nd By Double Doors 45211581 1-V8./G2. 35/3 05/14-P
06/04-P Speaker/Strobe 2nd In Room 600-B 45211576 1-V8./G3. 24/10 05/14-P
06/04-P Speaker/Strobe 2nd By Room 600-B 45211574
1-V8./G2. 37/5 EOL
05/14-P
06/04-P Speaker/Strobe 2nd By Room 600-B 45211573 1-V8./G1. 32/9 05/14-P
06/04-P Speaker/Strobe 2nd By Room 600-B 45211572 1-V8./G1. 33/10 05/14-P
06/04-P Speaker/Strobe 2nd By Room 600-G 45211571 1-V8./G1. 31/7 05/14-P
06/04-P Speaker/Strobe 2nd Hallway Rail 45211563 1-V8./H2. 1-Jul 05/14-P
06/04-P Speaker/Strobe 2nd Conference Room 45211562 1-V8./H2. 2-Jun 05/14-P
06/04-P Speaker/Strobe 2nd Corridor Lobby 45211558 1-V7./H3. 3-Mar 05/14-P
06/04-P Speaker/Strobe 2nd Breezeway Leaving Left Wing Into Right Wing- Above 4M34 45210991 05/14-P
06/04-P Speaker/Strobe 2nd Breezeway Elevator Lobby Between Right and Left Wing 45210987 1-V6/E3 8-May 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing A2-211 45210985 1-V5/F3 16/7 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-101 45210981 1-V5/F3 15/5 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-119 45210972
1-V5/F3 17/9 EOL(2)
05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-120 45210969 1-V6/E3 1-Jan 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-605 45210967 1-V6/E2 2-Jul 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing A2-120 45210966 1-V6/E3 2-Feb 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-600 45210965 1-V6/E2 3-Aug 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside Balcony/Adjacent to Elevator Lo 45210963 1-V6/E3 6-Mar 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-706 45210962
1-V6/E1 17/9 EOL
05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-802 45210960 1-V6/E2 4-Sep 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Conference Room outside A2-808 45210959
1-V6/E2 11/8 EOL
05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-808 45210958 1-V6/E2 7-Oct 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-818 45210957 1-V6/E1 16/6 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-830 45210955 1-V6/E1 15/5 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-236 45210954 1-V6/E1 14/3 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-232 45210953 1-V6/E1 13/2 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-224 45210950 1-V5/F2 4-May 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-226 45210949 1-V5/F2 5-Jun 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-228 45210948 1-V6/E1 1-Dec 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-218 45210943 1-V5/F2 3-Apr 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-212 45210942 1-V5/F2 2-Mar 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-408 45210941 1-V5/F3 14/2 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-202 Exit to Stairwell 45210939 1-V5/F2 1-Jan 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-309 45210936 1-V5/F1 1-Aug 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-304 45210935 1-V5/F1 2-Sep 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing A2-301 45210934 1-V5/F1 5-Nov 05/14-P
06/04-P Speaker/Strobe 2nd Right Wing Corridor Outside A2-301 45210931 1-V5/F1 4-Oct 05/14-P
06/04-P Speaker/Strobe 2nd Elevator Lobby Across from elevator entrance 45210929 1-V5/F1 6-Dec 05/14-P
06/04-P Speaker/Strobe 2nd Elevator Lobby Left of Elevator 45210927 1-V5/F1 13/7 05/14-P
06/04-P Speaker/Strobe 2nd Women's Restroom B2-112 45205861 1-V8./H1. 10.3 05/14-P
06/04-P Speaker/Strobe 2nd Mens Restroom B2-112 45205860 1-V8./H1. 8.1 05/14-P
06/04-P Speaker/Strobe 2nd Room B2-600A 45205858 1-V8./G2. 36/4 05/14-P
06/04-P Speaker/Strobe 2nd Mens Restroom B2-112 45205331 1-V8./H1. 8.1 05/14-P
06/04-P Speaker/Strobe 3rd Room A3-119 45211861 1-V10.3 13.4 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing A3-130 45211048 1-V10/I3 7-Jun 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-130 45211047 1-V10/I3 8-Jul 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Kitchen Across from Reception 45211046 1-V10/I3 6-May 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing A3-120 45211045 1-V10/I3 3-Feb 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-119 45211041 1-V10/I3 5-Apr 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-117 45211037 1-V9/J3 17/6 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-107 45211035 1-V9/J3 16/5 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-508 45211032 1-V10/I1 1-Aug 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-238 45211030
1-V10/I1 9/3 EOL
05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-232 45211022 1-V9/J2 5-Nov 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-401 45211020 1-V10/I3 1-Jan 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-405 45211014
1-V9/J2 12/7 EOL
05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-EC2 45211013 1-V9/J2 6-Oct 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-224 45211009 1-V9/J2 2-Sep 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-214 45211007 1-V9/J1 6-Aug 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-202 45211005 1-V9/J1 4-Jul 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-200 by Stairwell 45211002 1-V9/J1 3-May 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-319 45211001 1-V9/J1 2-Jan 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing A3-305 45211000 1-V9/J1 8-Mar 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-305 45210999 1-V9/J1 7-Feb 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Corridor Outside A3-301 45210996 1-V9/J1 9-Apr 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Elevator Lobby Left of Elevator 45210994 1-V9/J3 13/1 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Bathroom A3-103 45207842 1-V9/J3 15/4 05/14-P
06/04-P Speaker/Strobe 3rd Right Wing Bathroom A3-101 45207840 1-V9/J3 14/3 05/14-P
06/04-P Speaker/Strobe Roof Right Wing Elevator Lobby 45207835 1-V10/I2 17/10 05/14-P
06/04-P Speaker/Strobe 1st Floor Therapy Staff B1-120G 45211666 1-V3.20 C1.5 05/14-P
06/04-P Speaker/Strobe 1st Floor Emergency Elec B1-EC2 45211662 1-V2.10 C3.1 05/14-P
06/04-P Speaker/Strobe 1st Floor Electrical B1-EC2A 45211661 1-V2.11 C3.2 05/14-P
06/04-P Speaker/Strobe 1st Floor Student Workroom B1-511 45211660 1-V2.25 C2.7 05/14-P
06/04-P Speaker/Strobe 1st Floor Lobby 45211139 1-V1.7 D1.10 05/14-P
06/04-P Speaker/Strobe 1st Floor Confrence Room B1-110 45211138 1-V1.1 D1.1 05/14-P
06/04-P Speaker/Strobe 1st Floor Confrence Room B1-110 45211137 1-V1.4 D1.7 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B527 45211132 1-V2.30 C4.8 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B-520 45211131 1-V2.26 C2.8 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-507 45211130 1-V2.24 C2.7 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-539 45211128 1-V2.28 C4.1 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-140 45211127 1-V2.22 C2.4 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-140 45211126 1-V2.17 C1.1 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-135 45211124 1-V2.18 C1.2 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-308 45211123 1-V2.19 C1.4 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-117 45211122 1-V2.21 C1.6 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-120 45211120 1-V2.15 C3.8 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-120 45211118 1-V1.16 C3.9 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-114 45211117 1-V2.2 D3.2 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1408 45211116 1-V2.1 D3.3 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-117 45211115 1-V2.9 D3.8 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-536 45211109 1-V2.29 C4.2 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-501 45211104 1-V2.23 C2.5 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor Near Front Entry 45211098 1-V1.8 D1.11 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1 Near Front Entry 45211096 1-V2.3 D3.1 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1230 45211094 1-V2.7 D2.9 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-207 45211093 1-V1.2 D.2 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-209 45211092 1-V2.4 D2.1 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1401 45211089 1-V2.8 D3.4 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1408 45211088 1-V2.5 D2.6 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1221 45211086 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1-317 45211081 1-V1.3 D1.3 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1301 45211079 1-V1.5 D1.5 05/14-P
06/04-P Speaker/Strobe 1st Floor Corridor B1301 45211077 05/14-P
06/04-P Speaker/Strobe 3rd Floor Corridor A3-140 45211151 1-V.10.10 12.4 05/14-P
06/04-P Speaker/Strobe 3rd Floor Corridor A3-145 45211149 1-V.10.16 12.9 05/14-P
06/04-P Speaker/Strobe 3rd Floor Corridor A3-145 45211144 1-V.10.12 12.5 05/14-P
06/04-P Speaker/Strobe 3rd Floor Corridor A3-145 45211142 1-V.10.14 12.6 05/14-P
06/04-P Speaker/Strobe 3rd Floor Corridor A3-145 45211148 1-V.10.15 12.7 05/14-P
06/04-P Speaker/Strobe Ground Hallway Near A1-222 45210338 1-V/B 4.1/1.2 05/14-P
06/04-P Speaker/Strobe Ground Hallway Near A1-220 45210325 1-V/B 3.6/1.6 05/14-P
06/04-P Speaker/Strobe Ground Hallway Near A1-120 45210324 1-V/B 3.5/1.5 05/14-P
06/04-P Device Total: 172
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Strobe 1st Room A1-228 45211886 1-A1 0.3 05/14-P
06/04-P Strobe 1st Quiet Therapy A1-800E 45211885 1-A1 9 05/14-P
06/04-P Strobe 1st Break Room B1-214 45211878 1-D2 0.3 05/14-P
06/04-P Strobe 1st Mens Restroom B1-218 45211877 05/14-P
06/04-P Strobe 1st Womens Restroom B1-216 45211876 1-D2 0.4 05/14-P
06/04-P Strobe 1st Quiet Therapy B1-120B 45211667 1-V3 0.7 05/14-P
06/04-P Strobe 1st RM A1-230 45208013 1-A1 5 05/14-P
06/04-P Strobe 1st East RM A1-800C 45208011
1-A1 11 EOL
05/14-P
06/04-P Strobe 1st East RM A1-800D 45208010 1-A1 10 05/14-P
06/04-P Strobe 1st East RM A1-800F 45208009 1-A1 9 05/14-P
06/04-P Strobe 1st East RM A1-800B 45208006 1-A2 6 05/14-P
06/04-P Strobe 1st RM A1-700 N 45207994 1-A2 9 05/14-P
06/04-P Strobe 1st East RM A1-131 45207989 1-A3 9 05/14-P
06/04-P Strobe 1st East RM A1-129 45207988 1-A3 8 05/14-P
06/04-P Strobe 1st East RM A1-607 45207982
1-NO ADDRESS ON DEVICE
05/14-P
06/04-P Strobe 1st East RM A1-503 45207974 1-B2 7 05/14-P
06/04-P Strobe 1st East RM A1-402 45207953 1-B3 2 05/14-P
06/04-P Strobe 1st East RM A1-407 45207949 1-B1 3 05/14-P
06/04-P Strobe 1st East RM A1-301A 45207943 1-B3 9 05/14-P
06/04-P Strobe 1st East RM A1-301 45207942 1-B3 8 05/14-P
06/04-P Strobe 1st East RM A1-303 45207941 1-B3 7 05/14-P
06/04-P Strobe 2nd Restroom A2-609 45211704 05/14-P
06/04-P Strobe 2nd Mens Restroom A2-102 45211702 05/14-P
06/04-P Strobe 2nd Right Wing A2-120 45211701 1-F1 0.3 05/14-P
06/04-P Strobe 2nd Keyboard Lab B2-251 45211698 1-G1 0.3 05/14-P
06/04-P Strobe 2nd Women's Restroom A2-407 45211697 1-F3 0.1 05/14-P
06/04-P Strobe 2nd Gaming Room A2-120D 45211696 1-E3 0.4 05/14-P
06/04-P Strobe 2nd Copy Room A2-129 45211695 1-E3 0.5 05/14-P
06/04-P Strobe 2nd Room A2-817 45211693 1-E1 0.7 05/14-P
06/04-P Strobe 2nd Keyboard Lab A2-815 45211692 1-E1 0.8 05/14-P
06/04-P Strobe 2nd Womens Restroom A2-804 45211691 1-E2 0.6 05/14-P
06/04-P Strobe 2nd Mens Restroom A2-802 45211687 1-E2 0.5 05/14-P
06/04-P Strobe 2nd Room With Key Pad Entrance 45211599 1-H2. 5 05/14-P
06/04-P Strobe 2nd Men's Restroom B2-503 45211584 1-G3. 4 05/14-P
06/04-P Strobe 2nd In Room 600-B 45211575
1-G3. 11 EOL
05/14-P
06/04-P Strobe 2nd In Room 600-G 45211570
1-G1. 11 EOL
05/14-P
06/04-P Strobe 2nd Breezeway Between Left and Right Wing 45210990 1-G3 9 05/14-P
06/04-P Strobe 2nd Breezeway Between Left and Right Wing 45210989 1-G3 8 05/14-P
06/04-P Strobe 2nd Right Wing A2-103 45210984 1-F3 6 05/14-P
06/04-P Strobe 2nd Right Wing A2-211 45210983 1-F3 8 05/14-P
06/04-P Strobe 2nd Right Wing A2-120 45210968 1-E3 3 05/14-P
06/04-P Strobe 2nd Room B2-406 45205863 1-H1 0.9 05/14-P
06/04-P Strobe 2nd Room B2-600A1 45205862 1-G1 0.8 05/14-P
06/04-P Strobe 2nd Women's Restroom B2-501 45205859 1-G3. 5 05/14-P
06/04-P Strobe 3rd Copy Room A3-401 45211860 1-I3. 2 05/14-P
06/04-P Strobe 3rd Conference Room A3-135 45211856 1-I2 0.3 05/14-P
06/04-P Strobe 3rd Right Wing Break Room A3-318 45211688 1-J1 0.1 05/14-P
06/04-P Strobe 3rd Right Wing Corridor Outside A3-502 45211033
1-I3 9 EOL
05/14-P
06/04-P Strobe 3rd Right Wing Corridor Outside A3-507 45211028 1-I1 2 05/14-P
06/04-P Strobe 3rd Right Wing Corridor Outside A3-227 45211011 1-J2 4 05/14-P
06/04-P Strobe 3rd Right Wing Corridor Outside A3-226 45211010 1-J2 3 05/14-P
06/04-P Strobe 3rd Right Wing A3-221 45211008 1-J2 1 05/14-P
06/04-P Strobe 3rd Right Wing A3-205 45211006 1-J1 5 05/14-P
06/04-P Strobe 3rd Right Wing A3-301 45210998
1-J1 10 EOL
05/14-P
06/04-P Strobe 3rd Right Wing Corridor Outside A3-101 45207839 1-J3 2 05/14-P
06/04-P Strobe 3rd Right Wing Corridor Outside A3-136 45207826 1-I2 2 05/14-P
06/04-P Strobe 1st Floor Pantry Room B1-110A 45211879 1-D1 0.4 05/14-P
06/04-P Strobe 1st Floor Quiet Therapy B1-130B 45211673 1-C3 0.6 05/14-P
06/04-P Strobe 1st Floor Group Room B1-117 45211668 1-D3 0.5 05/14-P
06/04-P Strobe 1st Floor Quiet Therapy A B1-120A 45211665 1-V3 0.6 05/14-P
06/04-P Strobe 1st Floor Break Room B1-525 45211658 1-C4 0.7 05/14-P
06/04-P Strobe 1st Floor Copy Room B1-527 45211657 1-C4 0.6 05/14-P
06/04-P Strobe 1st Floor EMS Lounge B1-537 45211656 1-C4 0.3 05/14-P
06/04-P Strobe 1st Floor Lobby 45211140 1-D1 9 05/14-P
06/04-P Strobe 1st Floor Corridor B1-533 45211133 1-C4 0.9 05/14-P
06/04-P Strobe 1st Floor Corridor B1-533 45211129 1-C4 5 05/14-P
06/04-P Strobe 1st Floor Corridor…
This is the start of the file's text. The full file is on GovTribe.