This document is a Fire/Life Safety System Inspection and Testing Certificate for Building 331 at the Menlo Park VA facility, dated April 2025. The comprehensive inspection was performed by Facility - Palo Alto VA, with inspector Olaf Soto, and covered multiple fire safety system components including duct detectors, heat detectors, smoke detectors, pull stations, speakers, strobes, and communication equipment. The inspection was conducted in compliance with NFPA 101 (2024 Edition), NFPA 72 (2022 Edition), and NFPA 90A (2022 Edition), with a total of 237 devices tested across various building zones.
The inspection utilized a SimplexGrinnell 4100 control panel installed in 2017 and systematically tested multiple device categories, with most devices passing inspection. Key testing areas included semi-annual water flow device checks, annual testing of detectors and alarms, and verification of auxiliary functions. The report includes detailed sections on device testing, battery and power supply status, inventory and warranty information, and zone address mapping. Of note, one annunciator in the C-Wing Reception Desk (Location C-104) was flagged with an issue, specifically that its buttons do not work, which may require maintenance or replacement.
Text of this file
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate For
MP331
795 Willow Rd
Menlo Park, CA 94025
This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR CONDITIONING/VENTILATING SYSTEMS.
This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection Inspection Completion Date Apr 10, 2025 Building: MP331 Company: Facility - Palo Alto VA Contact: Doug Gambrell Contact: Olaf Soto Title: Manager Title: Inspector
Facility - Palo Alto VA
Download Date: 04/21/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: MP331 Contact: Doug Gambrell Address: 795 Willow Rd Phone: 4403192479 Address:
Fax:
City/State/ZIP Code: Menlo Park, CA 94025 Mobile:
Country: United States of America Email: d.gambrell@scdatacom.net
Inspection Performed By Company: Facility - Palo Alto VA Inspector: Olaf Soto Address: 2700 Gregory St Ste 180 Phone: 650-362-4841 Address:
Fax:
City/State/ZIP Code: Savannah, GA 31404 Mobile:
Country: United States of America Email: olaf@redwoodcityalarms.com
System Control Unit Manufacturer: SimplexGrinnell Inspection Date: 03/27/2025 IDC Style:
Model Number: 4100 Install Date: 05/19/2017 SLC Style:
Software Version:
Version Date: 05/19/2017 NAC Style:
Location: 1st Mechanical Room Current Protection:
Central Station Signal Verification Type:
Mfg: SimplexGrinnell Model #:
Test Time/Date: 3/27/25 1:23:16 PM Restore Time:
Note:
Inspection Completion Date: Apr 10, 2025 Building: MP331
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Tamper Switch Waterflow Switch
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector Heat Detector Pull Station Smoke Detector
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Releasing Device Speaker Speaker/Strobe Strobe Voice Evacuation
EC 02.03.05 EP 05
Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Communicator
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector
LS 02.01.34 EP 02
Protected master fire alarm control panel Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Control Panel
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Annunciator Battery Expander Panel Power Supply Special Control Total Device Count: 237
Certification Company: Facility - Palo Alto VA Building: MP331 Inspector: Olaf Soto Contact: Doug Gambrell
Discrepancy Report
Building: MP331 Control Panel: 1 - SimplexGrinnell 4100 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade No items found during this inspection.
& ScanID ` Location L Problem Address & Reference LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Annunciator 12603185 Ground C-Wing Reception Desk C-104
Proposed Solutions Report
Building: MP331 Control Panel: 1 - SimplexGrinnell 4100 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Annunciator 12603185 Ground C-Wing Reception Desk C-104
4603-9101 T/M
Internal WO/PO #: (none) T/M
Notes & Recommendations
Building: MP331 Control Panel: 1 - SimplexGrinnell 4100 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 12603185 Annunciator Ground C-Wing Reception Desk C-104
Buttons dont work
Inspection & Testing
Building: MP331 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Tamper Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Tamper Switch Ground floor B Corr C1-4 Valve 45211321 1-M2 15 05/23-P 08/20-P 03/27-P
Tamper Switch Ground floor Electrical room A106 12603061 1-M1 30 05/23-P 08/20-P 03/27-P
Tamper Switch Ground floor Near D Wing Courtyard Exit Ceiling 12602973 1-M4 30 05/23-P 08/20-P 03/27-P
Tamper Switch Ground floor Near C Wing Courtyard Exit Ceiling 12602768 1-M3 6 05/23-P 08/20-P 03/27-P
Tamper Switch Ground floor Electrical room A106 12535808 1-M1 31 05/23-P 08/20-P 03/27-P
Tamper Switch Garden Outdoor Inside A Oxygen Storage Room 12602986 1-M1 39 05/23-P 08/20-P 03/27-P
Device Total: 6
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Waterflow Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Waterflow Switch Ground floor Electrical room A106 45211323 1-M1 4 05/23-P 08/20-P 03/25-P
Waterflow Switch Ground floor Electrical room A106 Wing A Mech room 45211322 1-M1 3 05/23-P 08/20-P 03/25-P
Waterflow Switch Ground floor Behind B Wing 45211320 1-M2 16 05/23-P 08/20-P 03/25-P
Waterflow Switch Ground floor Behind D Wing 45211319 1-M4 5 05/23-P 08/20-P 03/25-P
Waterflow Switch Ground floor Behind D Wing 45211318 1-M3 5 05/23-P 08/20-P 03/25-P
Waterflow Switch Garden Outdoor Inside A Oxygen Storage Room 45211317 1-M1 38 05/23-P 08/20-P 03/25-P
Device Total: 6
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Duct Detector 1st Room B-136 Shower 45210863 1-2 34
04/10-P Duct Detector 1st Mechanical Room 45208528 1-57
1st C WING C136 EMS RM 44230121 3-M 21
1st Mechanical Room 45213140 1-56
03/27-P
1st Corridor B-116 12602978 1-Feb-36
Roof Return BLDG D AHU 4 RETURN 12602991 4-37
03/25-P
Roof BLDG B AHU 2 ROOF 45208529 2-38
Ground D WING SHOWER D 136 44230275 1-M4 34
Ground B-Wing Corridor Outside B160 12602977 1-M4 35
Ground D-Wing Corridor Outside D-160 12602972
Ground D-Wing Corridor Outside D-114 12602970 1-M4 33
Ground C-Wing Corridor Outside C-160 12602964 1-M4 37
Ground C-Wing Room C-160 12602963 1-3 13
Ground C-Wing Corridor Outside C-136 12602770 1-M3 40
Ground C-Wing Corridor Outside C-116 12602769 1-M3 -36
Device Total: 15
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Heat Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Heat Detector 1st Mechanical A-106 45205866
Device Total: 1
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Pull Station
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Pull Station 1st Inside Room A-134 45205880 1-M1 49
Pull Station 1st Inside Room A-139 45205852 1-M1 48
1st Main Entrance Outside RM A-101 45211484 1-M1 47
1st Hallway Outside Room A-122 45211488 1-M1 45
1st Mechanical Room Near Exit 45212985
1st Corridor B-156 12603178
1st Corridor B-166 12603173
1st Corridor A-129 12603083
1st Room A-142 12603078
1st Outside Compressor Room 12602989 1-M1
1st Corridor B-132 12535809
1st FACP Closet RM 111 12603089 1-M1 35
1st Corridor B-118 12603106
1st Corridor B-106 12603098
Ground C-Wing Corridor Outside C-105/Exit to Courtyard 12603188 1-M3 -24
Ground D-Wing Reception Exit to Courtyard (Left) 12603164 1-M4 -3
Ground D-Wing Exit to Courtyard/ Right of Reception/ Before En 12603158 1-M4 -31
Ground D-Wing Corridor Outside D-156 12603127 1-M4 -13
Ground D-Wing Corridor Outside D-118 12603149 1-M4 -24
Ground C-Wing Corridor Outside C-156 12603179 1-M3 -12
Ground C-Wing Left of Reception/By Exit to Courtyard 12603137 1-M3 -2
Ground C-Wing Corridor Outside C-118 12603196 1-M3 -34
Device Total: 22
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Smoke Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Smoke Detector 1st Outside Compressor Room 45210892 1-M1
Smoke Detector 1st Corridor D-166 45205850
03/28-P
1st Corridor B-105 45205872 1-M1 52
03/28-P
1st Corridor B-101 12603171
1st Corridor B-100 12603120
1st Corridor B-126 12603109
1st Room B-169 12602981
1st Room B-139 12602975
1st Corridor B-100 12535456 1-1
1st Corridor B-105 45205888 1-M1 53
1st Mechanical Room 45212979
1st Corridor B-156 12603176
1st Corridor B-139 12603117
1st Corridor B-140 12603118
1st Corridor B-148 12603119
1st Corridor B-162 12603175
1st Corridor B-166 12603174
1st Corridor B-138 12603172
1st Corridor B-106 12603101
1st Corridor B-112 12603105
1st Corridor B-122 12603108
1st Corridor B-132 12603111
1st Corridor B-134 12603112
1st Corridor B-136 12603115
Ground D-Wing Partition Doors to A-Wing (D-Wing Side) 45212988 1-M1 -51
Ground Mechanical Room A-105 45210855 1-1 5
Ground D-Wing Corridor Outside D-134 14603145
Ground C-Wing Corridor Outside C-116 12603194 1-M3 -33
Ground C-Wing Corridor Outside C-139 12603184 1-M3 -15
Ground D-Wing Corridor Outside Reception (Left) 12603162 1-M4 -2
Ground D-Wing D-100 Linen 12603161
Ground D-Wing Corridor Outside D-105 12603160 1-M4 -25
Ground D-Wing Partition Door to C-Wing (D-Wing Side) 12603159 1-M4 -29
Ground D-Wing Corridor Outside D-106 12603154 1-M4 -18
Ground C-Wing Corridor by Partition Doors to D-Wing 12603139
Ground C-Wing Corridor Outside C-166 12603133 1-M3 -7
Ground D-Wing Corridor Outside D-166 12603130 1-M4 -6
Ground D-Wing Corridor Outside D-162 12603128 1-M4 -9
Ground D-Wing Corridor Outside D-158 12603126 1-M1 -51
Ground D-Wing Corridor Outside D-148 12603125 1-M4 -11
Ground D-Wing Corridor Outside D-142 12603123 1-M4 -14
Ground D-Wing D-110 Supply 12602969
Ground D-Wing Corridor Outside Nurse Station (Right of Recepti 12603142 1-M4 -26
Ground D-Wing Room D-169 12602968
Ground C-Wing Room C-101 12602774
Ground C-Wing Room C-139 Supply 12602772
Ground D-Wing Corridor 134 12603145 1-M4
Ground D-Wing Corridor Outside D-132 12603147 1-M4 -15
Ground D-Wing Corridor Outside D-126 12603148 1-M4 -20
Ground D-Wing Corridor Outside D-116 12603151 1-M4 -23
Ground D-Wing Corridor Outside D-112 12603152 1-M4 -22
Ground C-Wing Corridor Outside C-136 12603203 1-M3 -35
Ground C-Wing Corridor Outside C-134 12603200 1-M3 28
Ground C-Wing Corridor Outside C-132 12603198 1-M3 29
Ground C-Wing Corridor Outside C-126 12603197 1-M3 -30
Ground C-Wing Corridor Outside C-112 12603193
Ground C-Wing Corridor Outside C-106 12603191 1-M3 -25
Ground C-Wing Corridor Outside C-105 12603186 1-M3 -23
Ground C-Wing Corridor Outside C-142 12603183
Ground C-Wing Corridor Outside C-148 12603182
Ground C-Wing Corridor Outside C-158 12603181
Ground C-Wing Corridor Outside C-161 12603134 1-M3 -8
Ground C-Wing Room C-169 12602766
Ground C-Wing Corridor Outside C-103 12603135 1-M3 -22
Ground C-Wing Corridor by Partition Doors to D-Wing/Left of Ex 12603138
Device Total: 65
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Releasing Device
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Releasing Device Ground D-Wing Partition Doors to A-Wing (A-Wing Side on Floor) 45212987
Releasing Device Ground D-Wing Partition Doors to A-Wing (D-Wing Side) 45212986
Ground B-Wing Entry 44230274
Ground B-Wing Entry 44230273
Ground C-Wing Corridor Outside C-134 12603202
Ground C-Wing DBL DOOR IN FRONT OF RM C136 12603201
Ground C-Wing DBL DOOR IN FRONT OF RM C106 12603190
Ground C-Wing DBL DOOR IN FRONT OF RM C106 12603189
Ground D-Wing By Room D-106 12603156
Ground D-Wing By Room D-106 12603155
Ground DBL DOOR ACROSS FROM RM D-134 D WING 12603144
Ground DBL DOOR ACROSS FROM RM D-134 D WING 12603143
Ground C-Wing Entry 12603141
Ground C-Wing Entry 12603140
Ground B-Wing B136 12603114
Ground B-Wing B136 12603113
Ground B-Wing Entry 12603103
Ground B-Wing Entry 12603102
Device Total: 18
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Speaker 1st Corridor B-138 12604719
Speaker 1st Corridor B-156 12604718
1st Corridor B-142 12604717
1st Corridor B-130 12604716
1st Corridor B-116 12604715
1st Corridor B-106 12604714
1st Corridor D-106 12604695
1st Corridor D-166 12604471
Ground C-Wing Corridor Outside C-142 12604706
Ground C-Wing Corridor Outside C-158 12604705
Ground C-Wing Corridor Outside C-103/Left of Reception 12604704
Ground D-Wing Corridor Outside D-158 12604699
Ground D-Wing Corridor Outside D-140 12604698
Ground D-Wing Corridor Outside D-132 12604697
Ground D-Wing Corridor Outside D-116 12604696
Ground C-Wing Corridor Outside C-130 12604694
Ground C-Wing Corridor Outside C-116 12604693
Ground C-Wing Corridor Outside C-106 12604692
Device Total: 18
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker/Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Speaker/Strobe 1st Corridor B-105 45205887
Speaker/Strobe 1st Inside Room A-139 45205883
1st Inside Room A-134 45205879
1st Corridor A-126 45205875
1st Corridor A-131 45205874
1st Corridor A-132 45205873
1st Kitchen A-141 45205832
1st Corridor D-166 45205831
1st Main Entrance Outside RM A-101 45211485
1st Hallway Outside RM A-108 45211486
1st Hallway Outside RM A-122 45211489
1st Outside Compressor Room 12602988
1st Mechanical Room 12535807
Device Total: 13
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Strobe 1st Corridor B-128 45205886
Strobe 1st Corridor A-132 45205885
1st Corridor A-129 45205884
1st Inside Room A-137 45205882
1st Restroom Near A-137 45205881
1st Women's Bathroom Across From A-134 45205878
1st Men's Bathroom Across From A-134 45205877
1st Hallway Across From A-134 45205876
1st Inside Bathroom In Room A-139 45205851
1st Inside Room A-133 45210864
1st A-Wing Room A-124 45210893
1st Inside Room A-109 45211487
1st Men's Bathroom Across From A-111 45211490
1st Men's Bathroom Across From A-111 45211491
1st Women's Bathroom Across From A-113 45211492
1st Women's Bathroom Across From A-113 45211493
1st Inside Room A-101 45211494
1st Corridor B-166 12604474
1st Corridor B-142 12604473
1st Corridor B-156 12603177
1st D WING D164 CORRIDOR 12603129
1st Corridor B-132 12603110
1st Corridor B-118 12603107
1st Corridor B-108 12603104
1st Corridor B-105 12603097
Ground C-Wing Corridor Outside C-142 12604470
Ground C-Wing Corridor by Partition Doors to D-Wing 12604469
Ground C-Wing Corridor Outside C-132 12603199
Ground C-Wing Corridor Outside C-118 12603195
Ground C-Wing Corridor Outside C-106 12603192
Ground C-Wing Corridor Outside C-105 by Exit 12603187
Ground C-Wing Corridor Outside C-156 12603180
Ground D-Wing Reception Exit to Courtyard (Left) 12603165
Ground D-Wing Exit to Courtyard/Right of Reception/Before Entr 12603157
Ground D-Wing Corridor Outside D-108 12603153
Ground D-Wing Corridor Outside D-118 12603150
Ground D-Wing Corridor Outside D-132 12603146
Ground C-Wing Left of Reception/ By Exit to Courtyard 12603132
Ground D-Wing Corridor Outside D-142 12603124
Ground D-Wing Corridor Outside D-156 12602974
Ground C-Wing Corridor Outside C-165 12602967
Device Total: 41
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Voice Evacuation
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Voice Evacuation 1st Mechanical Room 12535814
EC 02.03.05 EP 05
Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4) Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-22 Table 14.4.3.2 (4)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Communicator
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Communicator 1st Mechanical Room 45212984
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Duct Detector 1st Room B-136 Shower 45210863 1-2 34
1st Mechanical Room
1-57
1st C WING C136 EMS RM
3-M 21
1st Mechanical Room 45213140 1-56
1st Corridor B-116 12602978 1-Feb-36
Roof Return BLDG D AHU 4 RETURN
4-37
Roof BLDG B AHU 2 ROOF
2-38
Ground D WING SHOWER D 136 44230275 1-M4 34
Ground B-Wing Corridor Outside B160 12602977
Ground D-Wing Corridor Outside D-160 12602972
Ground D-Wing Corridor Outside D-114 12602970 1-M4 33
Ground C-Wing Corridor Outside C-160 12602964 1-M4 37
Ground C-Wing Room C-160 12602963 1-3 13
Ground C-Wing Corridor Outside C-136 12602770 1-M3 40
Ground C-Wing Corridor Outside C-116 12602769 1-M3 -36
Device Total: 15
LS 02.01.34 EP 02
Protected master fire alarm control panel Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Control Panel
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Control Panel 1st Mechanical Room 12535815
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Annunciator
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Annunciator Ground D-Wing Reception Desk D-104 12603136
Annunciator Ground B-Wing Reception Desk B-3316 12603116
Annunciator Ground C-Wing Reception Desk C-104 12603185
03/27-F
Device Total: 3
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Battery
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Battery 1st C Wing 45210416
08/20-P
04/10-P Battery 1st C Wing 45210415
08/20-P
04/10-P Battery 1st D Wing 45210414
08/20-P
04/10-P Battery 1st D Wing 45210413
08/20-P
04/10-P Battery 1st LEFT RECEPTIONIST Area B Wing 45206288
08/20-P
04/10-P Battery 1st RIGHT RECEPTIONIST Area B Wing 45206286
08/20-P
04/10-P Battery 1st Mechanical Room Expander Panel 45205868
08/20-P 03/27-P
Battery 1st Mechanical Room Expander Panel 45205867
08/20-P 03/27-P
Battery 1st FACP Mechanical Room 44230683
08/20-P 03/27-P
Battery 1st FACP Mechanical Room 44230684
08/20-P 03/27-P
Device Total: 10
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 At a minimum, control equipment shall be tested to verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Expander Panel
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Expander Panel 1st C Wing 45210419
Expander Panel 1st C Wing 45210418
1st C Wing 45210417
1st D Wing 45210412
1st D Wing 45210411
1st D Wing 45210410
1st D Wing 45210409
1st Mechanical Room 45212980
1st Mechanical Room 45212981
1st Mechanical Room 45212982
1st Mechanical Room 45212983
1st D Wing
Device Total: 12
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Power Supply
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Power Supply 1st C Wing 45210420
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Special Control
Device Type Location ScanID Address Q2/24 Q3/24 Q1/25 Q2/25 Special Control 1st Mechanical Room 45205869 1-18
Special Control 1st Mechanical Room 45205870 1-19
Special Control 1st Mechanical Room 45205871 1-16
Device Total: 3
Service Summary
Building: MP331 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity Failed/Other Annunciator Tested Total Passed Annunciator Tested Battery Tested Communicator Tested Control Panel Tested Duct Detector Tested Expander Panel Tested Heat Detector Tested Power Supply Tested Pull Station Tested Releasing Device Tested Smoke Detector Tested/Cleaned Speaker/Strobe Tested Speaker Tested Special Control Tested/Cleaned Strobe Tested Tamper Switch Tested Voice Evacuation Tested Waterflow Switch Tested Total Untested Duct Detector
Total Grand Total
Auxiliary Functions Testing
Building: MP331 Control Panel: 1 - SimplexGrinnell 4100 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated Passed Releasing Device
Ground B-Wing Entry Passed 12603102
Ground B-Wing Entry Passed 12603103
Ground B-Wing Entry Passed 44230273
Ground B-Wing Entry Passed 44230274
Ground B-Wing B136 Passed 12603113
Ground B-Wing B136 Passed 12603114
Ground C-Wing Corridor Outside C-134 Passed 12603202
Ground C-Wing DBL DOOR IN FRONT OF RM C106 Passed 12603189
Ground C-Wing DBL DOOR IN FRONT OF RM C106 Passed 12603190
Ground C-Wing DBL DOOR IN FRONT OF RM C136 Passed 12603201
Ground C-Wing Entry Passed 12603140
Ground C-Wing Entry Passed 12603141
Ground D-Wing By Room D-106 Passed 12603155
Ground D-Wing By Room D-106 Passed 12603156
Ground D-Wing Partition Doors to A-Wing (A-Wing Side on Floor) Passed 45212987
Ground D-Wing Partition Doors to A-Wing (D-Wing Side) Passed 45212986
Ground DBL DOOR ACROSS FROM RM D-134 D WING Passed 12603143
Ground DBL DOOR ACROSS FROM RM D-134 D WING Passed 12603144
Battery & Power Supply Testing
Building: MP331 Control Panel: 1 - SimplexGrinnell 4100 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Tested Ah Passed Sealed Lead Acid 1st Mechanical Room Expander Panel
35-NB
Sealed Lead Acid 1st Mechanical Room Expander Panel
1st C Wing
1st C Wing
1st D Wing
1st D Wing
1st FACP Mechanical Room
1st FACP Mechanical Room
1st LEFT RECEPTIONIST Area B Wing
1st RIGHT RECEPTIONIST Area B Wing
Inventory & Warranty Report
Building: MP331 Control Panel: 1 - SimplexGrinnell 4100 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Annunciator Control 1.27% Battery Control 4.22% Communicator Control 0.42% Control Panel Control 0.42% Duct Detector Initiating 6.33% Expander Panel Control 5.06% Heat Detector Initiating 0.42% Power Supply Control 0.42% Pull Station Initiating 9.28% Releasing Device Auxiliary 7.59% Smoke Detector Initiating 27.43% Speaker Indicating 7.59% Speaker/Strobe Indicating 5.49% Special Control Control 1.27% Strobe Indicating 17.30% Tamper Switch Supervisory 2.53% Voice Evacuation Control 0.42% Waterflow Switch Initiating 2.53%
Type Qty Model # Description Install Date In Service - 3 Years to 5 Years Power-Sonic Battery
PS-12350 NB
Sealed Lead Acid 08/19/2020 In Service - 5 Years to 10 Years Power-Sonic Battery
PS-12350 NB
Sealed Lead Acid 10/25/2019 Battery
PS-12350 NB
Sealed Lead Acid 02/13/2019 Battery
PS-12350 NB
Sealed Lead Acid 01/21/2019 Battery
PS-12350 NB
Sealed Lead Acid 01/16/2018 Simplex Annunciator 4603-9101
05/19/2017 Duct Detector 4098-9701
05/19/2017 Duct Detector 4098-9784
05/19/2017 Pull Station 2099-9138
05/19/2017 Pull Station
RMS-1T
05/19/2017
05/19/2017
4098-9784
05/19/2017 Smoke Detector 4098-9792, 4098-98
05/19/2017 Speaker 4902-9721
05/19/2017 Strobe
MS-24-VFR
05/19/2017 SimplexGrinnell Communicator
Control Panel
05/19/2017 Duct Detector 4096-9756
05/19/2017 Duct Detector 4098-9701
05/19/2017 Expander Panel 740-666
05/19/2017 Expander Panel 740-681
05/19/2017 Expander Panel 740-683
05/19/2017 Expander Panel 741-052
05/19/2017 Heat Detector
200DTF
05/19/2017 Power Supply 740-801
05/19/2017 Pull Station
NBG-12LX
05/19/2017 Pull Station
RMS-1T
05/19/2017 Smoke Detector 4098-9784
05/19/2017 Speaker/Strobe 4903-9357
05/19/2017 Speaker/Strobe 4903-9426
05/19/2017 Special Control 4905-9938
05/19/2017 Strobe
49VO-WRF
05/19/2017 Strobe
LSM-24-VFR
05/19/2017 Voice Evacuation
Central Tamper Switch 6R84
05/18/2017 Potter Electric Tamper Switch
05/18/2017 Waterflow Switch
05/18/2017 Waterflow Switch
VSR-F
05/18/2017 Waterflow Switch
WFD-25
05/18/2017 SimplexGrinnell Duct Detector 4098-9701
05/18/2017 Pull Station 2099-9768
05/18/2017 Smoke Detector 297-9021
05/18/2017 Smoke Detector 4097-9714
05/18/2017 Speaker 4902-9707
05/18/2017 Speaker/Strobe 4903-9357
05/18/2017 Strobe
LSM-24-VFR
05/18/2017 Building: MP331 Control Panel: 2 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date In Service - 5 Years to 10 Years SimplexGrinnell Duct Detector 4096-9756
05/19/2017 Building: MP331 Control Panel: 3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date In Service - 5 Years to 10 Years SimplexGrinnell Duct Detector 4096-9756
05/19/2017 Building: MP331 Control Panel: 4 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date In Service - 5 Years to 10 Years SimplexGrinnell Duct Detector 4096-9756
Zone Address Report
Building: MP331 Control Panel: 1 - SimplexGrinnell 4100 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Zone/Circuit: 1 Smoke Detector Ground Mechanical Room A-105
45210855
Releasing Device Ground B-Wing Entry
12603102
Releasing Device Ground B-Wing Entry
12603103
Releasing Device Ground B-Wing Entry
44230273
Releasing Device Ground B-Wing Entry
44230274
Releasing Device Ground B-Wing B136
12603113
Releasing Device Ground B-Wing B136
12603114
Releasing Device Ground C-Wing DBL DOOR IN FRONT OF RM C106
12603189
Releasing Device Ground C-Wing DBL DOOR IN FRONT OF RM C106
12603190
Releasing Device Ground C-Wing DBL DOOR IN FRONT OF RM C136
12603201
Releasing Device Ground C-Wing Entry
12603140
Releasing Device Ground C-Wing Entry
12603141
Smoke Detector Ground C-Wing Room C-169
12602766
Releasing Device Ground D-Wing By Room D-106
12603155
Smoke Detector Ground D-Wing Room D-169
12602968
Releasing Device Ground DBL DOOR ACROSS FROM RM D-134 D WING
12603143
Releasing Device Ground DBL DOOR ACROSS FROM RM D-134 D WING
12603144
Smoke Detector 1st Corridor B-100
12535456 Zone/Circuit: 2 Duct Detector 1st Room B-136 Shower
45210863 Zone/Circuit: 3 Duct Detector Ground C-Wing Room C-160
12602963 Zone/Circuit: Feb-36
Duct Detector 1st Corridor B-116
12602978 Zone/Circuit: M1 Waterflow Switch Ground floor Electrical room A106 Wing A Mech room
45211322 Waterflow Switch Ground floor Electrical room A106
45211323 Tamper Switch Ground floor Electrical room A106
12603061 Tamper Switch Ground floor Electrical room A106
12535808 Pull Station 1st FACP Closet RM 111
12603089 Waterflow Switch Garden Outdoor Inside A Oxygen Storage Room
45211317 Tamper Switch Garden Outdoor Inside A Oxygen Storage Room
12602986 Pull Station 1st Hallway Outside Room A-122
45211488 Pull Station 1st Main Entrance Outside RM A-101
45211484 Pull Station 1st Inside Room A-139
45205852 Pull Station 1st Inside Room A-134
45205880 Smoke Detector 1st Corridor B-105
45205872 Smoke Detector 1st Corridor B-105
45205888 -51 Smoke Detector Ground D-Wing Corridor Outside D-158
12603126 -51 Smoke Detector Ground D-Wing Partition Doors to A-Wing (D-Wing Side)
45212988
Pull Station 1st Outside Compressor Room
12602989
Smoke Detector 1st Outside Compressor Room
45210892 Zone/Circuit: M2 Tamper Switch Ground floor B Corr C1-4 Valve
45211321 Waterflow Switch Ground floor Behind B Wing
45211320 Zone/Circuit: M3 Waterflow Switch Ground floor Behind D Wing
45211318 Tamper Switch Ground floor Near C Wing Courtyard Exit Ceiling
12602768 Smoke Detector Ground C-Wing Corridor Outside C-134
12603200 Smoke Detector Ground C-Wing Corridor Outside C-132
12603198 Duct Detector Ground C-Wing Corridor Outside C-136
12602770 -2 Pull Station Ground C-Wing Left of Reception/By Exit to Courtyard
12603137 -7 Smoke Detector Ground C-Wing Corridor Outside C-166
12603133 -8 Smoke Detector Ground C-Wing Corridor Outside C-161
12603134 -12 Pull Station Ground C-Wing Corridor Outside C-156
12603179 -15 Smoke Detector Ground C-Wing Corridor Outside C-139
12603184 -22 Smoke Detector Ground C-Wing Corridor Outside C-103
12603135 -23 Smoke Detector Ground C-Wing Corridor Outside C-105
12603186 -24 Pull Station Ground C-Wing Corridor Outside C-105/Exit to Courtyard
12603188 -25 Smoke Detector Ground C-Wing Corridor Outside C-106
12603191 -30 Smoke Detector Ground C-Wing Corridor Outside C-126
12603197 -33 Smoke Detector Ground C-Wing Corridor Outside C-116
12603194 -34 Pull Station Ground C-Wing Corridor Outside C-118
12603196 -35 Smoke Detector Ground C-Wing Corridor Outside C-136
12603203 -36 Duct Detector Ground C-Wing Corridor Outside C-116
12602769 Zone/Circuit: M4 Waterflow Switch Ground floor Behind D Wing
45211319 Tamper Switch Ground floor Near D Wing Courtyard Exit Ceiling
12602973 Duct Detector Ground D-Wing Corridor Outside D-114
12602970 Duct Detector Ground D WING SHOWER D 136
44230275 Duct Detector Ground B-Wing Corridor Outside B160
12602977 Duct Detector Ground D-Wing Corridor Outside D-160
12602972 Duct Detector Ground C-Wing Corridor Outside C-160
12602964 -2 Smoke Detector Ground D-Wing Corridor Outside Reception (Left)
12603162 -3 Pull Station Ground D-Wing Reception Exit to Courtyard (Left)
12603164 -6 Smoke Detector Ground D-Wing Corridor Outside D-166
12603130 -9 Smoke Detector Ground D-Wing Corridor Outside D-162
12603128 -11 Smoke Detector Ground D-Wing Corridor Outside D-148
12603125 -13 Pull Station Ground D-Wing Corridor Outside D-156
12603127 -14 Smoke Detector Ground D-Wing Corridor Outside D-142
12603123 -15 Smoke Detector Ground D-Wing Corridor Outside D-132
12603147 -18 Smoke Detector Ground D-Wing Corridor Outside D-106
12603154 -20 Smoke Detector Ground D-Wing Corridor Outside D-126
12603148 -22 Smoke Detector Ground D-Wing Corridor Outside D-112
12603152 -23 Smoke Detector Ground D-Wing Corridor Outside D-116
12603151 -24 Pull Station Ground D-Wing Corridor Outside D-118
12603149 -25 Smoke Detector Ground D-Wing Corridor Outside D-105
12603160 -26 Smoke Detector Ground D-Wing Corridor Outside Nurse Station (Right of Recepti
12603142 -29 Smoke Detector Ground D-Wing Partition Door to C-Wing (D-Wing Side)
12603159 -31 Pull Station Ground D-Wing Exit to Courtyard/ Right of Reception/ Before En
12603158
Smoke Detector Ground D-Wing Corridor 134
12603145 Special Control 1st Mechanical Room
45205871 Special Control 1st Mechanical Room
45205869 Special Control 1st Mechanical Room
45205870 Duct Detector 1st Mechanical Room
45213140 Duct Detector 1st Mechanical Room
Control Panel: 2 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Duct Detector Roof BLDG B AHU 2 ROOF
Control Panel: 3 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Zone/Circuit: M Duct Detector 1st C WING C136 EMS RM
Control Panel: 4 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Duct Detector Roof Return BLDG D AHU 4 RETURN