This document is a Fire/Life Safety System Inspection and Testing Certificate for MP Building 350 at the Palo Alto VA Health Care System, performed on April 23, 2025. The comprehensive inspection covered 64 total devices across multiple fire safety system components, including tamper switches, waterflow switches, duct detectors, heat detectors, pull stations, smoke detectors, speakers, strobes, and voice evacuation systems. The inspection was conducted in strict accordance with multiple NFPA codes (101, 72, and 90A) and adhered to Joint Commission/VHA Standards.
The related federal contract opportunity (Solicitation Number 36C26126Q0026) is for Fire Alarm Maintenance at the VA Palo Alto Health Care System. The solicitation was amended to extend the submission date for quotes from November 13, 2025, to November 27, 2025, at 11:00am PST. The amendment also provides additional documentation such as inspection reports, drawings, and specifications to support potential bidders in preparing their quotes for the fire alarm maintenance service.
Text of this file
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate For
MP Bldg 350
795 Willow Rd
Menlo Park, CA 94025
This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR CONDITIONING/VENTILATING SYSTEMS.
This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection Inspection Completion Date Apr 23, 2025 Building: MP Bldg 350 Company: Facility - Palo Alto VA Contact: Anthony Losito Contact: Olaf Soto Title: Electronics Shop Supervisor Title: Inspector
Facility - Palo Alto VA
Download Date: 04/24/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: MP Bldg 350 Contact: Anthony Losito Address: 795 Willow Rd Phone: 650-852-3437 Address:
Fax:
City/State/ZIP Code: Menlo Park, CA 94025 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Facility - Palo Alto VA Inspector: Olaf Soto Address: 2700 Gregory St Ste 180 Phone: 650-362-4841 Address:
Fax:
City/State/ZIP Code: Savannah, GA 31404 Mobile:
Country: United States of America Email: olaf@redwoodcityalarms.com
System Control Unit Manufacturer: SimplexGrinnell Inspection Date: 04/23/2025 IDC Style:
Model Number: 8201 Install Date: 05/17/2017 SLC Style:
Software Version:
Version Date: 05/17/2017 NAC Style:
Location: 1st Hallway Near 134 Current Protection:
Inspection Completion Date: Apr 23, 2025 Building: MP Bldg 350
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Tamper Switch Waterflow Switch
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector Heat Detector Pull Station Smoke Detector
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Releasing Device Speaker Speaker/Strobe Strobe Voice Evacuation
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector
LS 02.01.34 EP 02
Protected master fire alarm control panel Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Control Panel
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Battery Total Device Count: 64
Certification Company: Facility - Palo Alto VA Building: MP Bldg 350 Inspector: Olaf Soto Contact: Anthony Losito file_0.jpg
Signed: Apr 23, 2025 Signed:
Inspection & Testing
Building: MP Bldg 350 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Tamper Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Tamper Switch 1st Outside Left 45211157 0-5/17/2017 9:10 05/28-P
04/23-P Tamper Switch 1st Room 114 12622737 05/28-P
04/23-P Tamper Switch 1st Room 131 Lower 12603999 0-5/17/2017 9:10 05/28-P
04/23-P Tamper Switch 1st Room 131 12603998 0-5/17/2017 9:10 05/28-P
04/23-P Tamper Switch 1st Room 131 Lower 12603997 0-5/17/2017 9:10 05/28-P
04/23-P Tamper Switch 1st Outside 12604274 05/28-P
04/23-P Tamper Switch 2nd Inside 216 12603985 0-5/17/2017 9:49 05/28-P
04/23-P Device Total: 7
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Waterflow Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Waterflow Switch 1st Room 131 Right 12603996 0-5/17/2017 9:16 05/28-P
04/23-P Waterflow Switch 2nd Inside 216 12603986 0-5/17/2017 9:47 05/28-P
04/23-P Device Total: 2
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Duct Detector Roof On unit outside 45205266 0-5/16/2018 7:49 05/17-P
04/23-P Device Total: 1
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Heat Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Heat Detector 1st 131 RISER/MECH RM 45210367 0-5/17/2017 9:31 05/17-P
04/23-P Heat Detector 1st RESIDENT KITCHEN 106 KITCHEN 12622721 05/17-P
04/23-P Heat Detector 2nd SHAFT ELEVATOR SHAFT 45205273 0-5/17/2018 7:30 05/17-P
04/23-P Device Total: 3
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Pull Station
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Pull Station 1st Main Lobby 12604265 0-5/17/2017 8:52 05/20-P
04/23-P Pull Station 1st Exit To Outside From Day Area 12603994 0-5/17/2017 8:52 05/17-P
04/23-P Pull Station 1st Electrical 12603981 0-5/17/2017 9:05 05/17-P
04/23-P Pull Station 1st Corridor 125 12603979 0-5/17/2017 9:04 05/17-P
04/23-P Pull Station 1st Corridor 130 12603977 0-5/17/2017 9:04 05/17-P
04/23-P Pull Station 2nd Corridor 201 12604007 0-5/17/2017 9:04 05/17-P
04/23-P Pull Station 2nd Corridor 211 12603991 0-5/17/2017 9:04 05/17-P
04/23-P Pull Station 2nd Electrical Near 220 12603988 0-5/17/2017 9:05 05/17-P
04/23-P Device Total: 8
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Smoke Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Smoke Detector 1st Main Lobby 45210363 0-5/17/2017 9:00 05/20-P
04/23-P Smoke Detector 1st Day Room 12622728 0-5/17/2017 9:00 05/20-P
04/23-P Smoke Detector 1st Main Lobby 12622727 0-5/17/2017 9:00 05/20-P
04/23-P Smoke Detector 1st Front Entry 113 12622723 0-5/17/2017 8:57 05/20-P
04/23-P Smoke Detector 1st Hallway Main Room 12604275 0-5/17/2017 8:54 05/20-P
04/23-P Smoke Detector 1st Hallway 12604003 0-5/17/2017 8:54 05/20-P
04/23-P Smoke Detector 2nd Corridor 213 12622752 0-5/17/2017 8:57 05/20-P
04/23-P Smoke Detector 2nd Front Desk Lobby 12622748 0-5/17/2017 8:57 05/20-P
04/23-P Smoke Detector 2nd Front Desk Lobby 12622747 0-5/17/2017 8:57 05/20-P
04/23-P Smoke Detector 2nd Front Desk Lobby Front of Elevator 12622745 0-5/17/2017 8:57 05/20-P
04/23-P Smoke Detector 2nd Corridor 211 12622739 0-5/17/2017 8:57 05/20-P
04/23-P Smoke Detector 2nd SHAFT ELEVATOR SHAFT 45205272 0-5/17/2018 7:28 05/20-P
04/23-P Device Total: 12
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Releasing Device
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Releasing Device 1st Entrance To Day Area 12622729 0-5/17/2017 9:04 05/20-P
04/23-P Releasing Device 1st Entrance To Day Area 12622726 0-5/17/2017 9:04 05/20-P
04/23-P Releasing Device 1st Hallway Main Room 12604264 0-5/17/2017 9:05 05/20-P
04/23-P Releasing Device 1st Hallway Main Room 12604263 0-5/17/2017 9:05 05/20-P
04/23-P Releasing Device 2nd Corridor 213 12604273 0-5/17/2017 9:56 05/20-P
04/23-P Releasing Device 2nd Hallway Near 213 12604268 0-5/17/2017 9:58 05/20-P
04/23-P Device Total: 6
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker 1st Main Lobby 12622734 0-5/17/2017 9:00 05/20-P
04/23-P Speaker 1st Main Lobby 12622724 0-5/17/2017 9:00 05/20-P
04/23-P Speaker 1st Day Room 12604276 0-5/17/2017 9:00 05/20-P
04/23-P Speaker 1st Corridor 132 12604266 0-5/17/2017 9:35 05/20-P
04/23-P Speaker 2nd Hallway Near 213 12622751 0-5/17/2017 9:51 05/20-P
04/23-P Speaker 2nd Hallway Near 214 12622750 0-5/17/2017 9:51 05/20-P
04/23-P Speaker 2nd Hallway Near 217 12622749 0-5/17/2017 9:51 05/20-P
04/23-P Speaker 2nd Front Desk Lobby 12622746 0-5/17/2017 9:35 05/20-P
04/23-P Speaker 2nd Corridor 208 12622744 0-5/17/2017 9:35 05/20-P
04/23-P Speaker 2nd Corridor 204 12622743 0-5/17/2017 9:35 05/20-P
04/23-P Device Total: 10
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker/Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker/Strobe 1st El Main Room 12603982 0-5/17/2017 9:09 05/20-P
04/23-P Device Total: 1
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Strobe 1st Hallway Main Room 45210364 0-5/17/2017 9:02 05/20-P
04/23-P Strobe 1st Corridor 134 12622722 0-5/17/2017 9:03 05/20-P
04/23-P Strobe 1st Corridor 125 12604006 0-5/17/2017 9:03 05/20-P
04/23-P Strobe 1st Day Room 12603995 0-5/17/2017 9:01 05/20-P
04/23-P Strobe 1st Main Lobby 12603976 0-5/17/2017 9:01 05/20-P
04/23-P Strobe 2nd Corridor 201 12603993 0-5/17/2017 9:03 05/20-P
04/23-P Strobe 2nd Corridor 206 12603992 0-5/17/2017 9:03 05/20-P
04/23-P Strobe 2nd Corridor 211 12603990 0-5/17/2017 9:03 05/20-P
04/23-P Strobe 2nd Hallway 12603989 0-5/17/2017 9:02 05/20-P
04/23-P Strobe 2nd Electrical Near 220 12603987 0-5/17/2017 9:45 05/20-P
04/23-P Device Total: 10
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Voice Evacuation
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Voice Evacuation 1st Hallway Near 134 12603975 0-5/17/2017 9:36 05/20-P
04/23-P Device Total: 1
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Duct Detector Roof On unit outside 45205266 0-5/16/2018 7:49 05/17-P
04/23-P Device Total: 1
LS 02.01.34 EP 02
Protected master fire alarm control panel Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Control Panel
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Control Panel 1st Hallway Near 134 12603955 0-5/17/2017 9:19 05/17-P
04/23-P Device Total: 1
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Battery
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Battery 1st Control Room 45210366 0-1/4/2016 0:00
08/21-P 04/23-P Battery 1st Control Room 45210365 0-1/4/2016 0:00
08/21-P 04/23-P Device Total: 2
Service Summary
Building: MP Bldg 350 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity Passed Battery Tested Control Panel Tested Duct Detector Tested Heat Detector Tested Pull Station Tested Releasing Device Tested Smoke Detector Tested/Cleaned Speaker/Strobe Tested Speaker Tested Strobe Tested Tamper Switch Tested Voice Evacuation Tested Waterflow Switch Tested Total Grand Total
Auxiliary Functions Testing
Building: MP Bldg 350 Control Panel: 0 - SimplexGrinnell 8201 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated Passed Releasing Device
1st Entrance To Day Area Passed 12622726
1st Entrance To Day Area Passed 12622729
1st Hallway Main Room Passed 12604263
1st Hallway Main Room Passed 12604264
2nd Hallway Near 213 Passed 12604268
2nd Corridor 213 Passed 12604273
Battery & Power Supply Testing
Building: MP Bldg 350 Control Panel: 0 - SimplexGrinnell 8201 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Tested Ah Passed Sealed Lead Acid 1st Control Room
35-NB
Sealed Lead Acid 1st Control Room
35-NB
Inventory & Warranty Report
Building: MP Bldg 350 Control Panel: 0 - SimplexGrinnell 8201 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 3.13% Control Panel Control 1.56% Duct Detector Initiating 1.56% Heat Detector Initiating 4.69% Pull Station Initiating 12.50% Releasing Device Auxiliary 9.38% Smoke Detector Initiating 18.75% Speaker Indicating 15.63% Speaker/Strobe Indicating 1.56% Strobe Indicating 15.63% Tamper Switch Supervisory 10.94% Voice Evacuation Control 1.56% Waterflow Switch Initiating 3.13%
Type Qty Model # Description Install Date In Service - 5 Years to 10 Years Power-Sonic Battery
PS-12350-NB
Sealed Lead Acid 04/19/2019 Simplex Heat Detector
05/17/2018 Smoke Detector
05/17/2018
Releasing Device 298-9021
05/17/2017 Potter Tamper Switch
OSYSU-2
05/17/2017 Pyrotronics Heat Detector
DT-200F
05/17/2017
SIMPLEX
Duct Detector
SIMPLEX
05/17/2017 SimplexGrinnell Control Panel
05/17/2017 Pull Station 2098-9768
05/17/2017 Pull Station 2099-9768
05/17/2017
05/17/2017
2098-9201
05/17/2017 Smoke Detector 2098-9201
05/17/2017 Smoke Detector 298-9021
05/17/2017 Smoke Detector 298-9201
05/17/2017 Speaker
Speaker 4902-9707
05/17/2017 Speaker/Strobe
Strobe
Strobe 2098-9201
05/17/2017 Strobe 2099-9768
05/17/2017 Strobe
LSM-24-VFR
05/17/2017 Voice Evacuation
System Sensor Tamper Switch
OSY2
05/17/2017 Tamper Switch
PIBV2
05/17/2017 Waterflow Switch
WFD40
05/17/2017 Victaulic Tamper Switch 708W
Zone Address Report
Building: MP Bldg 350 Control Panel: 0 - SimplexGrinnell 8201 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID Zone/Circuit: 1/4/2016 0:00
Battery 1st Control Room Sealed Lead Acid 45210365
Battery 1st Control Room Sealed Lead Acid 45210366 Zone/Circuit: 5/16/2018 7:49
Duct Detector Roof On unit outside
45205266 Zone/Circuit: 5/17/2017 8:52
Pull Station 1st Exit To Outside From Day Area
12603994
Pull Station 1st Main Lobby
12604265 Zone/Circuit: 5/17/2017 8:54
Smoke Detector 1st Hallway
12604003
Smoke Detector 1st Hallway Main Room
12604275 Zone/Circuit: 5/17/2017 8:57
Smoke Detector 1st Front Entry 113
12622723
Smoke Detector 2nd Corridor 211
12622739
Smoke Detector 2nd Corridor 213
12622752
Smoke Detector 2nd Front Desk Lobby
12622747
Smoke Detector 2nd Front Desk Lobby
12622748
Smoke Detector 2nd Front Desk Lobby Front of Elevator
12622745 Zone/Circuit: 5/17/2017 9:00
Smoke Detector 1st Day Room
12622728
Speaker 1st Day Room
12604276
Smoke Detector 1st Main Lobby
12622727
Smoke Detector 1st Main Lobby
45210363
Speaker 1st Main Lobby
12622724
Speaker 1st Main Lobby
12622734 Zone/Circuit: 5/17/2017 9:01
Strobe 1st Day Room
12603995
Strobe 1st Main Lobby
12603976 Zone/Circuit: 5/17/2017 9:02
Strobe 1st Hallway Main Room
45210364
Strobe 2nd Hallway
12603989 Zone/Circuit: 5/17/2017 9:03
Strobe 1st Corridor 125
12604006
Strobe 1st Corridor 134
12622722
Strobe 2nd Corridor 201
12603993
Strobe 2nd Corridor 206
12603992
Strobe 2nd Corridor 211
12603990 Zone/Circuit: 5/17/2017 9:04
Pull Station 1st Corridor 125
12603979
Pull Station 1st Corridor 130
12603977
Releasing Device 1st Entrance To Day Area
12622726
Releasing Device 1st Entrance To Day Area
12622729
Pull Station 2nd Corridor 201
12604007
Pull Station 2nd Corridor 211
12603991 Zone/Circuit: 5/17/2017 9:05
Pull Station 1st Electrical
12603981
Releasing Device 1st Hallway Main Room
12604263
Releasing Device 1st Hallway Main Room
12604264
Pull Station 2nd Electrical Near 220
12603988 Zone/Circuit: 5/17/2017 9:09
Speaker/Strobe 1st El Main Room
12603982 Zone/Circuit: 5/17/2017 9:10
Tamper Switch 1st Outside Left
45211157
Tamper Switch 1st Room 131
12603998
Tamper Switch 1st Room 131 Lower
12603997
Tamper Switch 1st Room 131 Lower
12603999 Zone/Circuit: 5/17/2017 9:16
Waterflow Switch 1st Room 131 Right
12603996 Zone/Circuit: 5/17/2017 9:19
Control Panel 1st Hallway Near 134
12603955 Zone/Circuit: 5/17/2017 9:31
Heat Detector 1st 131 RISER/MECH RM
45210367 Zone/Circuit: 5/17/2017 9:35
Speaker 1st Corridor 132
12604266
Speaker 2nd Corridor 204
12622743
Speaker 2nd Corridor 208
12622744
Speaker 2nd Front Desk Lobby
12622746 Zone/Circuit: 5/17/2017 9:36
Voice Evacuation 1st Hallway Near 134
12603975 Zone/Circuit: 5/17/2017 9:45
Strobe 2nd Electrical Near 220
12603987 Zone/Circuit: 5/17/2017 9:47
Waterflow Switch 2nd Inside 216
12603986 Zone/Circuit: 5/17/2017 9:49
Tamper Switch 2nd Inside 216
12603985 Zone/Circuit: 5/17/2017 9:51
Speaker 2nd Hallway Near 213
12622751
Speaker 2nd Hallway Near 214
12622750
Speaker 2nd Hallway Near 217
12622749 Zone/Circuit: 5/17/2017 9:56
Releasing Device 2nd Corridor 213
12604273 Zone/Circuit: 5/17/2017 9:58
Releasing Device 2nd Hallway Near 213
12604268 Zone/Circuit: 5/17/2018 7:28
Smoke Detector 2nd SHAFT ELEVATOR SHAFT
45205272 Zone/Circuit: 5/17/2018 7:30
Heat Detector 2nd SHAFT ELEVATOR SHAFT
45205273