This document is a Fire/Life Safety System Inspection and Testing Certificate for MP Building 350 at the Palo Alto VA Health Care System, performed on April 23, 2025. The comprehensive inspection covered 64 total devices across multiple fire safety system components, including tamper switches, waterflow switches, duct detectors, heat detectors, pull stations, smoke detectors, speakers, strobes, and voice evacuation systems. The inspection was conducted in strict accordance with multiple NFPA codes (101, 72, and 90A) and adhered to Joint Commission/VHA Standards.

The related federal contract opportunity (Solicitation Number 36C26126Q0026) is for Fire Alarm Maintenance at the VA Palo Alto Health Care System. The solicitation was amended to extend the submission date for quotes from November 13, 2025, to November 27, 2025, at 11:00am PST. The amendment also provides additional documentation such as inspection reports, drawings, and specifications to support potential bidders in preparing their quotes for the fire alarm maintenance service.

Text of this file

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate For

MP Bldg 350

795 Willow Rd

Menlo Park, CA 94025

This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR CONDITIONING/VENTILATING SYSTEMS.

This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Annual Inspection Inspection Completion Date Apr 23, 2025 Building: MP Bldg 350 Company: Facility - Palo Alto VA Contact: Anthony Losito Contact: Olaf Soto Title: Electronics Shop Supervisor Title: Inspector

Facility - Palo Alto VA

Download Date: 04/24/2025

Executive Summary Generated by: BuildingReports.com

Building Information Building: MP Bldg 350 Contact: Anthony Losito Address: 795 Willow Rd Phone: 650-852-3437 Address:

Fax:

City/State/ZIP Code: Menlo Park, CA 94025 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Facility - Palo Alto VA Inspector: Olaf Soto Address: 2700 Gregory St Ste 180 Phone: 650-362-4841 Address:

Fax:

City/State/ZIP Code: Savannah, GA 31404 Mobile:

Country: United States of America Email: olaf@redwoodcityalarms.com

System Control Unit Manufacturer: SimplexGrinnell Inspection Date: 04/23/2025 IDC Style:

Model Number: 8201 Install Date: 05/17/2017 SLC Style:

Software Version:

Version Date: 05/17/2017 NAC Style:

Location: 1st Hallway Near 134 Current Protection:

Inspection Completion Date: Apr 23, 2025 Building: MP Bldg 350

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Tamper Switch Waterflow Switch

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector Heat Detector Pull Station Smoke Detector

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Releasing Device Speaker Speaker/Strobe Strobe Voice Evacuation

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector

LS 02.01.34 EP 02

Protected master fire alarm control panel Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Control Panel

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Battery Total Device Count: 64

Certification Company: Facility - Palo Alto VA Building: MP Bldg 350 Inspector: Olaf Soto Contact: Anthony Losito file_0.jpg

Signed: Apr 23, 2025 Signed:

Inspection & Testing

Building: MP Bldg 350 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Tamper Switch

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Tamper Switch 1st Outside Left 45211157 0-5/17/2017 9:10 05/28-P

04/23-P Tamper Switch 1st Room 114 12622737 05/28-P

04/23-P Tamper Switch 1st Room 131 Lower 12603999 0-5/17/2017 9:10 05/28-P

04/23-P Tamper Switch 1st Room 131 12603998 0-5/17/2017 9:10 05/28-P

04/23-P Tamper Switch 1st Room 131 Lower 12603997 0-5/17/2017 9:10 05/28-P

04/23-P Tamper Switch 1st Outside 12604274 05/28-P

04/23-P Tamper Switch 2nd Inside 216 12603985 0-5/17/2017 9:49 05/28-P

04/23-P Device Total: 7

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Waterflow Switch

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Waterflow Switch 1st Room 131 Right 12603996 0-5/17/2017 9:16 05/28-P

04/23-P Waterflow Switch 2nd Inside 216 12603986 0-5/17/2017 9:47 05/28-P

04/23-P Device Total: 2

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Duct Detector Roof On unit outside 45205266 0-5/16/2018 7:49 05/17-P

04/23-P Device Total: 1

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Heat Detector

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Heat Detector 1st 131 RISER/MECH RM 45210367 0-5/17/2017 9:31 05/17-P

04/23-P Heat Detector 1st RESIDENT KITCHEN 106 KITCHEN 12622721 05/17-P

04/23-P Heat Detector 2nd SHAFT ELEVATOR SHAFT 45205273 0-5/17/2018 7:30 05/17-P

04/23-P Device Total: 3

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Pull Station

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Pull Station 1st Main Lobby 12604265 0-5/17/2017 8:52 05/20-P

04/23-P Pull Station 1st Exit To Outside From Day Area 12603994 0-5/17/2017 8:52 05/17-P

04/23-P Pull Station 1st Electrical 12603981 0-5/17/2017 9:05 05/17-P

04/23-P Pull Station 1st Corridor 125 12603979 0-5/17/2017 9:04 05/17-P

04/23-P Pull Station 1st Corridor 130 12603977 0-5/17/2017 9:04 05/17-P

04/23-P Pull Station 2nd Corridor 201 12604007 0-5/17/2017 9:04 05/17-P

04/23-P Pull Station 2nd Corridor 211 12603991 0-5/17/2017 9:04 05/17-P

04/23-P Pull Station 2nd Electrical Near 220 12603988 0-5/17/2017 9:05 05/17-P

04/23-P Device Total: 8

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Smoke Detector

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Smoke Detector 1st Main Lobby 45210363 0-5/17/2017 9:00 05/20-P

04/23-P Smoke Detector 1st Day Room 12622728 0-5/17/2017 9:00 05/20-P

04/23-P Smoke Detector 1st Main Lobby 12622727 0-5/17/2017 9:00 05/20-P

04/23-P Smoke Detector 1st Front Entry 113 12622723 0-5/17/2017 8:57 05/20-P

04/23-P Smoke Detector 1st Hallway Main Room 12604275 0-5/17/2017 8:54 05/20-P

04/23-P Smoke Detector 1st Hallway 12604003 0-5/17/2017 8:54 05/20-P

04/23-P Smoke Detector 2nd Corridor 213 12622752 0-5/17/2017 8:57 05/20-P

04/23-P Smoke Detector 2nd Front Desk Lobby 12622748 0-5/17/2017 8:57 05/20-P

04/23-P Smoke Detector 2nd Front Desk Lobby 12622747 0-5/17/2017 8:57 05/20-P

04/23-P Smoke Detector 2nd Front Desk Lobby Front of Elevator 12622745 0-5/17/2017 8:57 05/20-P

04/23-P Smoke Detector 2nd Corridor 211 12622739 0-5/17/2017 8:57 05/20-P

04/23-P Smoke Detector 2nd SHAFT ELEVATOR SHAFT 45205272 0-5/17/2018 7:28 05/20-P

04/23-P Device Total: 12

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Releasing Device

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Releasing Device 1st Entrance To Day Area 12622729 0-5/17/2017 9:04 05/20-P

04/23-P Releasing Device 1st Entrance To Day Area 12622726 0-5/17/2017 9:04 05/20-P

04/23-P Releasing Device 1st Hallway Main Room 12604264 0-5/17/2017 9:05 05/20-P

04/23-P Releasing Device 1st Hallway Main Room 12604263 0-5/17/2017 9:05 05/20-P

04/23-P Releasing Device 2nd Corridor 213 12604273 0-5/17/2017 9:56 05/20-P

04/23-P Releasing Device 2nd Hallway Near 213 12604268 0-5/17/2017 9:58 05/20-P

04/23-P Device Total: 6

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker 1st Main Lobby 12622734 0-5/17/2017 9:00 05/20-P

04/23-P Speaker 1st Main Lobby 12622724 0-5/17/2017 9:00 05/20-P

04/23-P Speaker 1st Day Room 12604276 0-5/17/2017 9:00 05/20-P

04/23-P Speaker 1st Corridor 132 12604266 0-5/17/2017 9:35 05/20-P

04/23-P Speaker 2nd Hallway Near 213 12622751 0-5/17/2017 9:51 05/20-P

04/23-P Speaker 2nd Hallway Near 214 12622750 0-5/17/2017 9:51 05/20-P

04/23-P Speaker 2nd Hallway Near 217 12622749 0-5/17/2017 9:51 05/20-P

04/23-P Speaker 2nd Front Desk Lobby 12622746 0-5/17/2017 9:35 05/20-P

04/23-P Speaker 2nd Corridor 208 12622744 0-5/17/2017 9:35 05/20-P

04/23-P Speaker 2nd Corridor 204 12622743 0-5/17/2017 9:35 05/20-P

04/23-P Device Total: 10

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker/Strobe

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker/Strobe 1st El Main Room 12603982 0-5/17/2017 9:09 05/20-P

04/23-P Device Total: 1

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Strobe

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Strobe 1st Hallway Main Room 45210364 0-5/17/2017 9:02 05/20-P

04/23-P Strobe 1st Corridor 134 12622722 0-5/17/2017 9:03 05/20-P

04/23-P Strobe 1st Corridor 125 12604006 0-5/17/2017 9:03 05/20-P

04/23-P Strobe 1st Day Room 12603995 0-5/17/2017 9:01 05/20-P

04/23-P Strobe 1st Main Lobby 12603976 0-5/17/2017 9:01 05/20-P

04/23-P Strobe 2nd Corridor 201 12603993 0-5/17/2017 9:03 05/20-P

04/23-P Strobe 2nd Corridor 206 12603992 0-5/17/2017 9:03 05/20-P

04/23-P Strobe 2nd Corridor 211 12603990 0-5/17/2017 9:03 05/20-P

04/23-P Strobe 2nd Hallway 12603989 0-5/17/2017 9:02 05/20-P

04/23-P Strobe 2nd Electrical Near 220 12603987 0-5/17/2017 9:45 05/20-P

04/23-P Device Total: 10

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Voice Evacuation

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Voice Evacuation 1st Hallway Near 134 12603975 0-5/17/2017 9:36 05/20-P

04/23-P Device Total: 1

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Duct Detector Roof On unit outside 45205266 0-5/16/2018 7:49 05/17-P

04/23-P Device Total: 1

LS 02.01.34 EP 02

Protected master fire alarm control panel Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Control Panel

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Control Panel 1st Hallway Near 134 12603955 0-5/17/2017 9:19 05/17-P

04/23-P Device Total: 1

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Battery

Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Battery 1st Control Room 45210366 0-1/4/2016 0:00

08/21-P 04/23-P Battery 1st Control Room 45210365 0-1/4/2016 0:00

08/21-P 04/23-P Device Total: 2

Service Summary

Building: MP Bldg 350 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity Passed Battery Tested Control Panel Tested Duct Detector Tested Heat Detector Tested Pull Station Tested Releasing Device Tested Smoke Detector Tested/Cleaned Speaker/Strobe Tested Speaker Tested Strobe Tested Tamper Switch Tested Voice Evacuation Tested Waterflow Switch Tested Total Grand Total

Auxiliary Functions Testing

Building: MP Bldg 350 Control Panel: 0 - SimplexGrinnell 8201 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated Passed Releasing Device

1st Entrance To Day Area Passed 12622726

1st Entrance To Day Area Passed 12622729

1st Hallway Main Room Passed 12604263

1st Hallway Main Room Passed 12604264

2nd Hallway Near 213 Passed 12604268

2nd Corridor 213 Passed 12604273

Battery & Power Supply Testing

Building: MP Bldg 350 Control Panel: 0 - SimplexGrinnell 8201 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Battery Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Tested Ah Passed Sealed Lead Acid 1st Control Room

35-NB

Sealed Lead Acid 1st Control Room

35-NB

Inventory & Warranty Report

Building: MP Bldg 350 Control Panel: 0 - SimplexGrinnell 8201 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Battery Control 3.13% Control Panel Control 1.56% Duct Detector Initiating 1.56% Heat Detector Initiating 4.69% Pull Station Initiating 12.50% Releasing Device Auxiliary 9.38% Smoke Detector Initiating 18.75% Speaker Indicating 15.63% Speaker/Strobe Indicating 1.56% Strobe Indicating 15.63% Tamper Switch Supervisory 10.94% Voice Evacuation Control 1.56% Waterflow Switch Initiating 3.13%

Type Qty Model # Description Install Date In Service - 5 Years to 10 Years Power-Sonic Battery

PS-12350-NB

Sealed Lead Acid 04/19/2019 Simplex Heat Detector

05/17/2018 Smoke Detector

05/17/2018

Releasing Device 298-9021

05/17/2017 Potter Tamper Switch

OSYSU-2

05/17/2017 Pyrotronics Heat Detector

DT-200F

05/17/2017

SIMPLEX

Duct Detector

SIMPLEX

05/17/2017 SimplexGrinnell Control Panel

05/17/2017 Pull Station 2098-9768

05/17/2017 Pull Station 2099-9768

05/17/2017

05/17/2017

2098-9201

05/17/2017 Smoke Detector 2098-9201

05/17/2017 Smoke Detector 298-9021

05/17/2017 Smoke Detector 298-9201

05/17/2017 Speaker

Speaker 4902-9707

05/17/2017 Speaker/Strobe

Strobe

Strobe 2098-9201

05/17/2017 Strobe 2099-9768

05/17/2017 Strobe

LSM-24-VFR

05/17/2017 Voice Evacuation

System Sensor Tamper Switch

OSY2

05/17/2017 Tamper Switch

PIBV2

05/17/2017 Waterflow Switch

WFD40

05/17/2017 Victaulic Tamper Switch 708W

Zone Address Report

Building: MP Bldg 350 Control Panel: 0 - SimplexGrinnell 8201 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID Zone/Circuit: 1/4/2016 0:00

Battery 1st Control Room Sealed Lead Acid 45210365

Battery 1st Control Room Sealed Lead Acid 45210366 Zone/Circuit: 5/16/2018 7:49

Duct Detector Roof On unit outside

45205266 Zone/Circuit: 5/17/2017 8:52

Pull Station 1st Exit To Outside From Day Area

12603994

Pull Station 1st Main Lobby

12604265 Zone/Circuit: 5/17/2017 8:54

Smoke Detector 1st Hallway

12604003

Smoke Detector 1st Hallway Main Room

12604275 Zone/Circuit: 5/17/2017 8:57

Smoke Detector 1st Front Entry 113

12622723

Smoke Detector 2nd Corridor 211

12622739

Smoke Detector 2nd Corridor 213

12622752

Smoke Detector 2nd Front Desk Lobby

12622747

Smoke Detector 2nd Front Desk Lobby

12622748

Smoke Detector 2nd Front Desk Lobby Front of Elevator

12622745 Zone/Circuit: 5/17/2017 9:00

Smoke Detector 1st Day Room

12622728

Speaker 1st Day Room

12604276

Smoke Detector 1st Main Lobby

12622727

Smoke Detector 1st Main Lobby

45210363

Speaker 1st Main Lobby

12622724

Speaker 1st Main Lobby

12622734 Zone/Circuit: 5/17/2017 9:01

Strobe 1st Day Room

12603995

Strobe 1st Main Lobby

12603976 Zone/Circuit: 5/17/2017 9:02

Strobe 1st Hallway Main Room

45210364

Strobe 2nd Hallway

12603989 Zone/Circuit: 5/17/2017 9:03

Strobe 1st Corridor 125

12604006

Strobe 1st Corridor 134

12622722

Strobe 2nd Corridor 201

12603993

Strobe 2nd Corridor 206

12603992

Strobe 2nd Corridor 211

12603990 Zone/Circuit: 5/17/2017 9:04

Pull Station 1st Corridor 125

12603979

Pull Station 1st Corridor 130

12603977

Releasing Device 1st Entrance To Day Area

12622726

Releasing Device 1st Entrance To Day Area

12622729

Pull Station 2nd Corridor 201

12604007

Pull Station 2nd Corridor 211

12603991 Zone/Circuit: 5/17/2017 9:05

Pull Station 1st Electrical

12603981

Releasing Device 1st Hallway Main Room

12604263

Releasing Device 1st Hallway Main Room

12604264

Pull Station 2nd Electrical Near 220

12603988 Zone/Circuit: 5/17/2017 9:09

Speaker/Strobe 1st El Main Room

12603982 Zone/Circuit: 5/17/2017 9:10

Tamper Switch 1st Outside Left

45211157

Tamper Switch 1st Room 131

12603998

Tamper Switch 1st Room 131 Lower

12603997

Tamper Switch 1st Room 131 Lower

12603999 Zone/Circuit: 5/17/2017 9:16

Waterflow Switch 1st Room 131 Right

12603996 Zone/Circuit: 5/17/2017 9:19

Control Panel 1st Hallway Near 134

12603955 Zone/Circuit: 5/17/2017 9:31

Heat Detector 1st 131 RISER/MECH RM

45210367 Zone/Circuit: 5/17/2017 9:35

Speaker 1st Corridor 132

12604266

Speaker 2nd Corridor 204

12622743

Speaker 2nd Corridor 208

12622744

Speaker 2nd Front Desk Lobby

12622746 Zone/Circuit: 5/17/2017 9:36

Voice Evacuation 1st Hallway Near 134

12603975 Zone/Circuit: 5/17/2017 9:45

Strobe 2nd Electrical Near 220

12603987 Zone/Circuit: 5/17/2017 9:47

Waterflow Switch 2nd Inside 216

12603986 Zone/Circuit: 5/17/2017 9:49

Tamper Switch 2nd Inside 216

12603985 Zone/Circuit: 5/17/2017 9:51

Speaker 2nd Hallway Near 213

12622751

Speaker 2nd Hallway Near 214

12622750

Speaker 2nd Hallway Near 217

12622749 Zone/Circuit: 5/17/2017 9:56

Releasing Device 2nd Corridor 213

12604273 Zone/Circuit: 5/17/2017 9:58

Releasing Device 2nd Hallway Near 213

12604268 Zone/Circuit: 5/17/2018 7:28

Smoke Detector 2nd SHAFT ELEVATOR SHAFT

45205272 Zone/Circuit: 5/17/2018 7:30

Heat Detector 2nd SHAFT ELEVATOR SHAFT

45205273

Other files

File Type Posted
FA Device Inventory.xlsx XLSX spreadsheet
36C26126Q0026 0002.docx DOCX document
Questions and Answers - Amendment 2.docx DOCX document
VAPA Test Schedule.pdf PDF
PAD Bldg 7 Annual Device Testing - February 2025.rtf RTF text file
MPD Bldg 351 Annual Device Testing - April 2025.rtf RTF text file
PAD Bldg 520 Annual Device Testing - May 2025.rtf RTF text file
MPD Bldg 329 Annual Device Testing - April 2025.rtf RTF text file
LVD Bldg 62C Annual Device Testing - April 2025.rtf RTF text file
PAD Bldg 500 Annual Device Testing - June 2025.rtf RTF text file
PAD Bldg 5 Annual Device Testing - February 2025.rtf RTF text file
MPD Bldg 352 Annual Device Testing - April 2025.rtf RTF text file
MPD Bldg 360 Annual Device Testing - April 2025.rtf RTF text file
LVD Bldg 62 Annual Device Testing - April 2025.rtf RTF text file
MPD Bldg 347 Annual Device Testing - April 2025.rtf RTF text file
MPD Bldg 365 Annual Device Testing - April 2025.rtf RTF text file
LVD Bldg 90 Annual Device Testing - April 2025.rtf RTF text file
MPD Bldg 331 Annual Device Testing - April 2025.rtf RTF text file
Questions and Answers .docx DOCX document
MPD Bldg 353 Annual Device Testing - April 2025.rtf RTF text file
36C26126Q0026 0001.docx DOCX document
36C26126Q0026.docx DOCX document
WD 2015-5641 Rev 28 dated 07-08-2025.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .