This document is a comprehensive Fire/Life Safety System Inspection Certificate for the MPD Building 365 located at 795 Willow Rd in Menlo Park, CA, performed by the Facility - Palo Alto VA on June 11, 2025. The inspection was conducted in accordance with multiple NFPA standards (101, 72, and 90A) and covered extensive testing of fire safety systems, including 262 total devices across multiple categories such as smoke detectors, heat detectors, pull stations, speaker/strobes, releasing devices, and control panels.

The inspection meticulously documented the testing of various fire safety components, with all 262 devices passing their respective tests. The fire alarm control system is a Notifier NFS2-3030 model installed on May 17, 2017, with devices ranging from 3-5 years to over 5 years old. This detailed report correlates directly with a related federal contract opportunity (Solicitation Number: 36C26126Q0026) for Fire Alarm Maintenance at the VA Palo Alto Health Care System, with quote submissions extended to November 27, 2025, suggesting this inspection report may be supporting documentation for the upcoming maintenance contract.

Text of this file

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate For

MP365

795 Willow Rd

Menlo Park, CA 94025

This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR CONDITIONING/VENTILATING SYSTEMS.

This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Annual Inspection Inspection Completion Date Jun 11, 2025 Building: MP365 Company: Facility - Palo Alto VA Contact: Anthony Losito Contact: Olaf Soto Title: Electronics Shop Supervisor Title: Inspector

Facility - Palo Alto VA

Download Date: 06/24/2025

Executive Summary Generated by: BuildingReports.com

Building Information Building: MP365 Contact: Anthony Losito Address: 795 Willow Rd Phone: 650-852-3437 Address:

Fax:

City/State/ZIP Code: Menlo Park, CA 94025 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Facility - Palo Alto VA Inspector: Olaf Soto Address: 2700 Gregory St Ste 180 Phone: 650-362-4841 Address:

Fax:

City/State/ZIP Code: Savannah, GA 31404 Mobile:

Country: United States of America Email: olaf@redwoodcityalarms.com

System Control Unit Manufacturer: Notifier Inspection Date: 06/11/2025 IDC Style:

Model Number: NFS2-3030 Install Date: 05/17/2017 SLC Style:

Software Version:

Version Date: 05/17/2017 NAC Style:

Location: 1st Inside CC1-06 Current Protection:

Inspection Completion Date: Jun 11, 2025 Building: MP365

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Tamper Switch

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Waterflow Switch

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector Heat Detector Pull Station Smoke Detector

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Bell Horn Releasing Device Speaker/Strobe Strobe Voice Evacuation

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector

LS 02.01.34 EP 02

Protected master fire alarm control panel Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Control Panel

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Annunciator Battery Expander Panel Power Supply Total Device Count: 262

Certification Company: Facility - Palo Alto VA Building: MP365 Inspector: Olaf Soto Contact: Anthony Losito file_0.jpg

Signed: Jun 11, 2025 Signed:

Notes & Recommendations

Building: MP365 Control Panel: 0 - Notifier NFS2-3030 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.

ScanID Note Device Type Location Comment EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) 44231068 Horn 1st Outside Loading Dock Near Sliding Doors Next To Risers Passed Low sound but works

Inspection & Testing

Building: MP365 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g) Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Tamper Switch

Device Type Location ScanID Address Q2/25 Tamper Switch 1st Outside To the left of risers 45211855 06/11-P Tamper Switch 1st Outside To the left of risers 45211854 06/11-P Tamper Switch 1st Outside Of Building Front of risers 45211835 06/11-P Tamper Switch 1st Outside Back Entrance 45205934 06/11-P Tamper Switch 1st Outside Back Entrance 45205933 06/11-P Device Total: 5

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Waterflow Switch

Device Type Location ScanID Address Q2/25 Waterflow Switch 1st Outside Back Entrance 45205936 06/11-P Waterflow Switch 1st Outside Back Entrance 45205935 06/11-P Device Total: 2

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector

Device Type Location ScanID Address Q2/25 Duct Detector 1st Corridor A-110 45210461 06/11-P Duct Detector 1st Corridor A-110 45210460 06/11-P Duct Detector 1st Corridor A-115 45205920 06/11-P Duct Detector 1st Corridor A-115 45205919 06/11-P Duct Detector 1st Corridor A-127 45205916 06/11-P Duct Detector 1st Corridor A-127 45205915 06/11-P Duct Detector 1st Corridor A-135 45205911 06/11-P Duct Detector 1st Corridor A-135 45205910 06/11-P Duct Detector 1st Hallway Near D-112B 45205404 06/11-P Duct Detector 1st Hallway Near D-112B 45205403 06/11-P Duct Detector 1st Inside Dining Room A-200 45205071 06/11-P Duct Detector 1st Inside Dining Room A-200 45205070 06/11-P Device Total: 12

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Heat Detector

Device Type Location ScanID Address Q2/25 Heat Detector 1st Room A-200B 45205927 06/11-P Heat Detector 1st Room A-234 45205926 06/11-P Heat Detector 1st Bathroom Men's 45205431 06/11-P Heat Detector 1st Inside Room A-154B 45205178 06/11-P Heat Detector 1st Inside Room A-160B 45205176 06/11-P Heat Detector 1st Inside Room A-160C 45205173 06/11-P Heat Detector 1st Inside RM A-160 45205170 06/11-P Heat Detector 1st Inside RM A-160 45205169 06/11-P Heat Detector 1st D-Wing Inside Training Kitchen 2 44231056 06/11-P Heat Detector 1st D-Wing Inside Training Kitchen 1 44231054 06/11-P Heat Detector 1st Bathroom Womens 44231053 06/11-P Device Total: 11

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Pull Station

Device Type Location ScanID Address Q2/25 Pull Station 1st In A-200 Dining room 45211194 06/11-P Pull Station 1st Corridor A-210A 45211185 06/11-P Pull Station 1st Corridor A-227 45211173 06/11-P Pull Station 1st Entrance To Southwest Wing B 45210408 06/11-P Pull Station 1st Side Door 45210403 06/11-P Pull Station 1st Exit Door 45210391 06/11-P Pull Station 1st Room A-230 45205939 06/11-P Pull Station 1st Corridor A-177 45205907 06/11-P Pull Station 1st Near A-154C 45205428 06/11-P Pull Station 1st At Side Entrance 45205410 06/11-P Pull Station 1st At Main Entrance 45205384 06/11-P Pull Station 1st Exit Door 45205381 06/11-P Pull Station 1st Inside Room A-160 Emergency Exit 45205171 06/11-P Pull Station 1st Wing B South Emergency Exit 45205155 06/11-P Device Total: 14

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Smoke Detector

Device Type Location ScanID Address Q2/25 Smoke Detector 1st Corridor A-200 45211192 06/11-P Smoke Detector 1st Corridor A-211 Left 45211190 06/11-P Smoke Detector 1st Corridor A-211 45211189 06/11-P Smoke Detector 1st Corridor A-210 45211188 06/11-P Smoke Detector 1st Corridor A-210 45211187 06/11-P Smoke Detector 1st Corridor A-210 45211184 06/11-P Smoke Detector 1st Corridor A-210 45211183 06/11-P Smoke Detector 1st Corridor A-210 45211182 06/11-P Smoke Detector 1st Corridor A-222 45211178 06/11-P Smoke Detector 1st Corridor A-232 45211177 06/11-P Smoke Detector 1st Corridor A-227 45211176 06/11-P Smoke Detector 1st Room A-220 45210463 06/11-P Smoke Detector 1st Near A-120 45210405 06/11-P Smoke Detector 1st Near A-120 45210402 06/11-P Smoke Detector 1st Near C-100 45210399 06/11-P Smoke Detector 1st Inside C-106 45210395 06/11-P Smoke Detector 1st Hallway Near CC1-06 45210394 06/11-P Smoke Detector 1st Room A-230 45205937 06/11-P Smoke Detector 1st Room A-210A 45205929 06/11-P Smoke Detector 1st Corridor A-201 45205923 06/11-P Smoke Detector 1st Corridor A-200A 45205922 06/11-P Smoke Detector 1st Corridor A-129 45205914 06/11-P Smoke Detector 1st Corridor A-177A 45205908 06/11-P Smoke Detector 1st Corridor A-140 45205905 06/11-P Smoke Detector 1st Corridor A-210 45205902 06/11-P Smoke Detector 1st Corridor A-146 45205899 06/11-P Smoke Detector 1st Room A-EC1 45205898 06/11-P Smoke Detector 1st Conference Room 45205427 06/11-P Smoke Detector 1st Conference Room 45205426 06/11-P Smoke Detector 1st Conference Room 45205425 06/11-P Smoke Detector 1st Room A-SC1 45205424 06/11-P Smoke Detector 1st Hallway Near E-104 45205420 06/11-P Smoke Detector 1st Hallway Near E-108 45205419 06/11-P Smoke Detector 1st Hallway Near E-117 45205413 06/11-P Smoke Detector 1st Hallway Near D-120 45205409 06/11-P Smoke Detector 1st Hallway Near D-120 45205408 06/11-P Smoke Detector 1st Hallway Near D-119 45205407 06/11-P Smoke Detector 1st Hallway Near D-112B 45205402 06/11-P Smoke Detector 1st Hallway Near D-100 45205397 06/11-P Smoke Detector 1st Hallway Near D-100 45205396 06/11-P Smoke Detector 1st Hallway A-117 45205393 06/11-P Smoke Detector 1st Near A-125 45205392 06/11-P Smoke Detector 1st Near Main Entrance 45205386 06/11-P Smoke Detector 1st Conference Room 45205379 06/11-P Smoke Detector 1st Conference Room 45205378 06/11-P Smoke Detector 1st Near C-100 45205377 06/11-P Smoke Detector 1st Wing A Inside RM A-155 45205183 06/11-P Smoke Detector 1st Wing A Inside RM A-155 45205181 06/11-P Smoke Detector 1st Insides Room A-154A 45205180 06/11-P Smoke Detector 1st Wing A Hallway Outside RM A-160 45205168 06/11-P Smoke Detector 1st Wing A Hallway Outside RM A-155 45205165 06/11-P Smoke Detector 1st Wing A Hallway Outside RM A-153 45205161 06/11-P Smoke Detector 1st B Wing Inside Room B-127 45205160 06/11-P Smoke Detector 1st B Wing Inside Room B-126 45205157 06/11-P Smoke Detector 1st Wing B Inside Room B-125 45205151 06/11-P Smoke Detector 1st Wing B Inside Room B-124 45205148 06/11-P Smoke Detector 1st Wing B Inside Room B-123 45205147 06/11-P Smoke Detector 1st B Wing Inside Room B-122 45205144 06/11-P Smoke Detector 1st Wing B Hallway Outside RM B-125 45205143 06/11-P Smoke Detector 1st Wing B Inside Room B-121 45205139 06/11-P Smoke Detector 1st Wing B Inside Room B-120 45205138 06/11-P Smoke Detector 1st Wing B Inside Room B-119 45205135 06/11-P Smoke Detector 1st Wing B Inside Room B-118 45205134 06/11-P Smoke Detector 1st Wing B Hallway Outside RM B-119 45205132 06/11-P Smoke Detector 1st Wing B Inside Room B-117 45205126 06/11-P Smoke Detector 1st Wing B Inside Room B-116 45205125 06/11-P Smoke Detector 1st Wing B Inside Room B-115 45205122 06/11-P Smoke Detector 1st Wing B Inside Room B-114 45205121 06/11-P Smoke Detector 1st B Wing Inside Room B-112 45205117 06/11-P Smoke Detector 1st Wing B Inside Room B-110 45205114 06/11-P Smoke Detector 1st Wing B Inside Room B-111 45205113 06/11-P Smoke Detector 1st B Wing Inside Room B-113 45205109 06/11-P Smoke Detector 1st B Wing Hallway Outside Room B-113 45205107 06/11-P Smoke Detector 1st B Wing Inside Room B-109 45205103 06/11-P Smoke Detector 1st Wing B Inside Room B-108 45205100 06/11-P Smoke Detector 1st B Wing Hallway Outside RM B-125 45205097 06/11-P Smoke Detector 1st Wing B Inside Room B-106 45205094 06/11-P Smoke Detector 1st B Wing Hallway Outside RM B-107 45205090 06/11-P Smoke Detector 1st B Wing Inside Room B-103 45205084 06/11-P Smoke Detector 1st Southeast Wing B Outside RM B-102 45205081 06/11-P Smoke Detector 1st Entrance To Southeast Wing Hallway B 45205080 06/11-P Smoke Detector 1st Inside Dining Room A-200 45205069 06/11-P Smoke Detector 1st Inside Dining Room A-200 45205068 06/11-P Smoke Detector 1st Inside Dining Room A-200 45205067 06/11-P Smoke Detector 1st Inside Dining Room A-200 45205066 06/11-P Smoke Detector 1st Inside Room C-105 45205061 06/11-P Smoke Detector 1st Inside Room C-104 45205057 06/11-P Smoke Detector 1st Inside Room C-107 45205056 06/11-P Smoke Detector 1st Inside CC1-06 45205054 06/11-P Smoke Detector 1st Golf Area Patio Rm E-C2 Elec.

44231066 06/11-P Smoke Detector 1st Golf Area Patio Rm A-TC2 Teldata 2 44231065 06/11-P Smoke Detector 1st Inside Office A-145A 44231064 06/11-P Smoke Detector 1st Wing A Inside RM A-155 44231060 06/11-P Smoke Detector 1st D-Wing Training Kitchen 2 D-104 44231057 06/11-P Smoke Detector 1st Outside Riser Rm A-240 EMS Receiving 44231050 06/11-P Device Total: 95

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Bell

Device Type Location ScanID Address Q2/25 Bell 1st Outside Loading Dock Near Sliding Doors Above Risers 44231069 06/11-P Device Total: 1

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Horn

Device Type Location ScanID Address Q2/25 Horn 1st Outside Loading Dock Near Sliding Doors Next To Risers 44231068 06/11-P Horn 1st Outside Back Of Bldg A ove Wood Shop Exit door 44231067 06/11-P Device Total: 2

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Releasing Device

Device Type Location ScanID Address Q2/25 Releasing Device 1st Corridor B A-120 45210407 06/11-P Releasing Device 1st Corridor B A-120 45210406 06/11-P Releasing Device 1st Wing A Double Doors Outside RM A-153 45205164 06/11-P Releasing Device 1st Wing A Double Doors Outside RM A-153 45205163 06/11-P Device Total: 4

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker/Strobe

Device Type Location ScanID Address Q2/25 Speaker/Strobe 1st Corridor A-110 45211200 06/11-P Speaker/Strobe 1st Corridor A-100A 45211199 06/11-P Speaker/Strobe 1st Corridor A-201 45211198 06/11-P Speaker/Strobe 1st Corridor A-200E 45211196 06/11-P Speaker/Strobe 1st Corridor A-200E Corner 45211195 06/11-P Speaker/Strobe 1st Corridor A-210B 45211186 06/11-P Speaker/Strobe 1st Corridor A-211 45211181 06/11-P Speaker/Strobe 1st Corridor A-227 45211174 06/11-P Speaker/Strobe 1st Restroom A-200C 45210472 06/11-P Speaker/Strobe 1st Rest Room B-120 45210464 06/11-P Speaker/Strobe 1st Near Side Door 45210404 06/11-P Speaker/Strobe 1st Inside C-106 45210397 06/11-P Speaker/Strobe 1st Outside C-106 C-106 45210392 06/11-P Speaker/Strobe 1st Hallway Near C-104 45210390 06/11-P Speaker/Strobe 1st Room A-230 45205938 06/11-P Speaker/Strobe 1st Corridor A-222 45205930 06/11-P Speaker/Strobe 1st Room A-200B 45205925 06/11-P Speaker/Strobe 1st Corridor A-203 45205924 06/11-P Speaker/Strobe 1st Corridor A-129 45205913 06/11-P Speaker/Strobe 1st Corridor A-177 45205906 06/11-P Speaker/Strobe 1st Room A-140 45205904 06/11-P Speaker/Strobe 1st Corridor CA1-03 45205903 06/11-P Speaker/Strobe 1st Corridor A-146 45205901 06/11-P Speaker/Strobe 1st Bathroom Men's 45205432 06/11-P Speaker/Strobe 1st Inside A-154 45205430 06/11-P Speaker/Strobe 1st Inside A-154 By Door 45205429 06/11-P Speaker/Strobe 1st Hallway Wing E Near E-119 45205412 06/11-P Speaker/Strobe 1st At Side Entrance 45205401 06/11-P Speaker/Strobe 1st Hallway Wing D Near D-100 45205394 06/11-P Speaker/Strobe 1st By A-117 At Main Entrance 45205388 06/11-P Speaker/Strobe 1st At Main Entrance 45205385 06/11-P Speaker/Strobe 1st Conference Room 45205382 06/11-P Speaker/Strobe 1st Inside Room A-155 45205182 06/11-P Speaker/Strobe 1st Inside Room A-154B 45205179 06/11-P Speaker/Strobe 1st Inside Room A-160 45205175 06/11-P Speaker/Strobe 1st Inside Room A-160C 45205174 06/11-P Speaker/Strobe 1st Inside Room A-160 Emergency Exit 45205172 06/11-P Speaker/Strobe 1st Wing A Hallway Outside RM A-154 45205166 06/11-P Speaker/Strobe 1st Wing A Outside RM A-151 45205162 06/11-P Speaker/Strobe 1st B Wing Inside RM B-127 45205159 06/11-P Speaker/Strobe 1st B Wing Inside RM B-126 45205158 06/11-P Speaker/Strobe 1st Wing B South Emergency Exit 45205156 06/11-P Speaker/Strobe 1st B Wing Inside RM B-125 45205152 06/11-P Speaker/Strobe 1st B Wing Inside RM B-124 45205149 06/11-P Speaker/Strobe 1st B Wing Inside RM B-123 45205146 06/11-P Speaker/Strobe 1st B Wing Inside RM B-122 45205145 06/11-P Speaker/Strobe 1st B Wing Inside RM B-121 45205140 06/11-P Speaker/Strobe 1st B Wing Inside RM B-120 45205137 06/11-P Speaker/Strobe 1st B Wing Inside RM B-119 45205136 06/11-P Speaker/Strobe 1st B Wing Inside RM B-118 45205133 06/11-P Speaker/Strobe 1st B Wing Hallway Outside RM B-117 45205130 06/11-P Speaker/Strobe 1st B Wing Inside RM B-117 45205127 06/11-P Speaker/Strobe 1st B Wing Inside RM B-116 45205124 06/11-P Speaker/Strobe 1st B Wing Inside RM B-115 45205123 06/11-P Speaker/Strobe 1st B Wing Inside RM B-114 45205120 06/11-P Speaker/Strobe 1st B Wing Inside RM B-112 45205116 06/11-P Speaker/Strobe 1st B Wing Inside RM B-110 45205115 06/11-P Speaker/Strobe 1st B Wing Inside RM B-111 45205112 06/11-P Speaker/Strobe 1st B Wing Inside RM B-113 45205110 06/11-P Speaker/Strobe 1st B Wing Hallway Outside B-111 45205106 06/11-P Speaker/Strobe 1st B Wing Inside RM B-109 45205104 06/11-P Speaker/Strobe 1st B Wing Inside RM B-108 45205101 06/11-P Speaker/Strobe 1st B Wing Inside RM B-106A 45205096 06/11-P Speaker/Strobe 1st B Wing Inside RM B-107 45205092 06/11-P Speaker/Strobe 1st B Wing Inside RM B-107 45205091 06/11-P Speaker/Strobe 1st B Wing Inside RM B-103 45205083 06/11-P Speaker/Strobe 1st Inside Dining Room Outside RM A-200C 45205065 06/11-P Speaker/Strobe 1st Hallway Outside Room C-101 45205064 06/11-P Speaker/Strobe 1st Inside Room C-105 45205062 06/11-P Speaker/Strobe 1st Inside Room C-104 45205058 06/11-P Speaker/Strobe 1st Inside Room C-107 45205055 06/11-P Speaker/Strobe 1st Inside Room A-145B 44231063 06/11-P Speaker/Strobe 1st MAIN HALL Inside Room A-150 Restroom 44231062 06/11-P Speaker/Strobe 1st Inside Room A-160B 44231061 06/11-P Speaker/Strobe 1st E-WING HALL Outside Office E-107 44231059 06/11-P Speaker/Strobe 1st D-WING HALL Outside Office D-106 44231058 06/11-P Speaker/Strobe 1st D-WING HALL Inside Kitchen 1 44231055 06/11-P Speaker/Strobe 1st Bathroom Womens 44231052 06/11-P Speaker/Strobe 1st Outside Riser Inside Room A-240 EMS Receiving 44231051 06/11-P Device Total: 79

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Strobe

Device Type Location ScanID Address Q2/25 Strobe 1st Inside Bathroom C-106 45210396 06/11-P Strobe 1st Room A-210A 45205928 06/11-P Strobe 1st B Wing Inside RM B-125A Bathroom 45205153 06/11-P Strobe 1st B Wing Inside RM B-124A Bathroom 45205150 06/11-P Strobe 1st B Wing Inside RM B-121A 45205141 06/11-P Strobe 1st B Wing Inside RM B-116A 45205129 06/11-P Strobe 1st B Wing Inside RM B-117A 45205128 06/11-P Strobe 1st B Wing Inside RM B-112A Bathroom 45205118 06/11-P Strobe 1st B Wing Inside RM B-113A Bathroom 45205111 06/11-P Strobe 1st B Wing Inside RM B-109A 45205105 06/11-P Strobe 1st B Wing Inside RM B-108A Bathroom 45205102 06/11-P Strobe 1st B Wing Inside RM B-106A1 Bathroom 45205098 06/11-P Strobe 1st B Wing Inside RM B-106 45205095 06/11-P Strobe 1st B Wing Inside RM B-107A Bathroom 45205093 06/11-P Strobe 1st B Wing Inside RM B-103A Bathroom 45205085 06/11-P Strobe 1st Inside Room C-105A 45205063 06/11-P Strobe 1st Inside Room C-104A 45205059 06/11-P Device Total: 17

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Voice Evacuation

Device Type Location ScanID Address Q2/25 Voice Evacuation 1st Inside CC1-06 44230119 06/11-P Voice Evacuation 1st Inside CC1-06 44230118 06/11-P Device Total: 2

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector

Device Type Location ScanID Address Q2/25 Duct Detector 1st Corridor A-110 45210461 06/11-P Duct Detector 1st Corridor A-110 45210460 06/11-P Duct Detector 1st Corridor A-115 45205920 06/11-P Duct Detector 1st Corridor A-115 45205919 06/11-P Duct Detector 1st Corridor A-127 45205916 06/11-P Duct Detector 1st Corridor A-127 45205915 06/11-P Duct Detector 1st Corridor A-135 45205911 06/11-P Duct Detector 1st Corridor A-135 45205910 06/11-P Duct Detector 1st Hallway Near D-112B 45205404 06/11-P Duct Detector 1st Hallway Near D-112B 45205403 06/11-P Duct Detector 1st Inside Dining Room A-200 45205071 06/11-P Duct Detector 1st Inside Dining Room A-200 45205070 06/11-P Device Total: 12

LS 02.01.34 EP 02

Protected master fire alarm control panel Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Control Panel

Device Type Location ScanID Address Q2/25 Control Panel 1st Inside CC1-06 45205049 06/11-P Device Total: 1

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Annunciator

Device Type Location ScanID Address Q2/25 Annunciator 1st Corridor A-100 45205921 06/11-P Annunciator 1st Main Entrance 45205383 06/11-P Device Total: 2

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Battery

Device Type Location ScanID Address Q2/25 Battery 1st Room A-SC1 45210466 06/11-P Battery 1st Room A-SC1 45210465 06/11-P Battery 1st Inside CC1-06 45205053 06/11-P Battery 1st Inside CC1-06 45205052 06/11-P Battery 1st Inside CC1-06 45205048 06/11-P Battery 1st Inside CC1-06 45205047 06/11-P Battery 1st Inside CC1-06 45205045 06/11-P Battery 1st Inside CC1-06 45205044 06/11-P Battery 1st Inside CC1-06 45205043 06/11-P Battery 1st Inside CC1-06 44230117 06/11-P Battery 1st Inside CC1-06 44230114 06/11-P Battery 1st Inside CC1-06 44230113 06/11-P Device Total: 12

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 At a minimum, control equipment shall be tested to verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Expander Panel

Device Type Location ScanID Address Q2/25 Expander Panel 1st Room A-SC1 45205421 06/11-P Device Total: 1

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Power Supply

Device Type Location ScanID Address Q2/25 Power Supply 1st Inside CC1-06 44230116 06/11-P Power Supply 1st Inside CC1-06 44230115 06/11-P Device Total: 2

Service Summary

Building: MP365 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity Passed Annunciator Tested Battery Tested Bell Tested Control Panel Tested Duct Detector Tested Expander Panel Tested Heat Detector Tested Horn Tested Power Supply Tested Pull Station Tested Releasing Device Tested Smoke Detector Tested/Cleaned Speaker/Strobe Tested Strobe Tested Tamper Switch Tested Voice Evacuation Tested Waterflow Switch Tested Total Grand Total

Auxiliary Functions Testing

Building: MP365 Control Panel: 0 - Notifier NFS2-3030 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated Passed Releasing Device

1st Corridor B A-120 Passed 45210406

1st Corridor B A-120 Passed 45210407

1st Wing A Double Doors Outside RM A-153 Passed 45205163

1st Wing A Double Doors Outside RM A-153 Passed 45205164

Inventory & Warranty Report

Building: MP365 Control Panel: 0 - Notifier NFS2-3030 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Annunciator Control 0.76% Battery Control 4.58% Bell Indicating 0.38% Control Panel Control 0.38% Duct Detector Initiating 4.58% Expander Panel Control 0.38% Heat Detector Initiating 4.20% Horn Indicating 0.76% Power Supply Control 0.76% Pull Station Initiating 5.34% Releasing Device Auxiliary 1.53% Smoke Detector Initiating 36.26% Speaker/Strobe Indicating 30.15% Strobe Indicating 6.49% Tamper Switch Supervisory 1.91% Voice Evacuation Control 0.76% Waterflow Switch Initiating 0.76%

Type Qty Model # Description Install Date In Service - 3 Years to 5 Years PowerSonic Battery

PS-12120

05/11/2022 Power sonic Battery ps-1270

12/05/2021 PowerSonic Battery

PS-12180

12/05/2021 Edwards Bell 438D-10N5

12/16/2020 System Sensor Horn

HRK

12/16/2020 power sonic Battery ps-1270

12/05/2020 In Service - 5 Years to 10 Years

GENESIS

Battery

NP7-12

01/16/2018

WHEELOCK/SAFEPATH4

Voice Evacuation

SP40S

01/16/2018 PowerSonic Battery

PS-1270

10/10/2017 Battery

PS-1270 F1

10/10/2017 Notifier Annunciator

LCD-80

05/17/2017 Control Panel

NFS2-3030

05/17/2017 Duct Detector

DNR

05/17/2017 Duct Detector

FRM-1

05/17/2017 Duct Detector

FSP-851

05/17/2017 Expander Panel

FCPS-24S6

05/17/2017 Heat Detector

FST-851

05/17/2017 Heat Detector

FST-851R

05/17/2017 Pull Station

NBG-12LX

05/17/2017 Pull Station

NGB-12LX

05/17/2017 Releasing Device

05/17/2017 Smoke Detector

DNR

05/17/2017 Smoke Detector

FSP-851

05/17/2017 Smoke Detector

NSP-851

05/17/2017 Speaker/Strobe

05/17/2017 Speaker/Strobe

SPS

05/17/2017 Speaker/Strobe

SPS(R)(A)P

05/17/2017 Strobe

SR

05/17/2017 Potter Tamper Switch

OSYSU-2

05/17/2017 Tamper Switch

PCVS-2

05/17/2017 System Sensor Speaker/Strobe

SPSR

05/17/2017 Strobe

SR

05/17/2017 Waterflow Switch

WFD30-2

05/17/2017 Victaulic Tamper Switch

WP-8

05/17/2017

WHEELOCK/SAFEPATH4

Voice Evacuation

SP40S

05/17/2017 Notifier Power Supply fcpd-24s6

01/01/2016

Other files

File Type Posted
FA Device Inventory.xlsx XLSX spreadsheet
36C26126Q0026 0002.docx DOCX document
Questions and Answers - Amendment 2.docx DOCX document
VAPA Test Schedule.pdf PDF
PAD Bldg 7 Annual Device Testing - February 2025.rtf RTF text file
MPD Bldg 350 Annual Device Testing - April 2025.rtf RTF text file
MPD Bldg 351 Annual Device Testing - April 2025.rtf RTF text file
PAD Bldg 520 Annual Device Testing - May 2025.rtf RTF text file
MPD Bldg 329 Annual Device Testing - April 2025.rtf RTF text file
LVD Bldg 62C Annual Device Testing - April 2025.rtf RTF text file
PAD Bldg 500 Annual Device Testing - June 2025.rtf RTF text file
PAD Bldg 5 Annual Device Testing - February 2025.rtf RTF text file
MPD Bldg 352 Annual Device Testing - April 2025.rtf RTF text file
MPD Bldg 360 Annual Device Testing - April 2025.rtf RTF text file
LVD Bldg 62 Annual Device Testing - April 2025.rtf RTF text file
MPD Bldg 347 Annual Device Testing - April 2025.rtf RTF text file
LVD Bldg 90 Annual Device Testing - April 2025.rtf RTF text file
MPD Bldg 331 Annual Device Testing - April 2025.rtf RTF text file
Questions and Answers .docx DOCX document
MPD Bldg 353 Annual Device Testing - April 2025.rtf RTF text file
36C26126Q0026 0001.docx DOCX document
36C26126Q0026.docx DOCX document
WD 2015-5641 Rev 28 dated 07-08-2025.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .