MPD Bldg 351 Annual Device Testing - April 2025.rtf
RTF text file 194 KB Posted
- Attached to
- H342--Fire Alarm Maintenance
- Solicitation number
- 36C26126Q0026
About this file
This document is a Fire/Life Safety System Inspection and Testing Certificate for Building 351 at the VA Palo Alto Health Care System, conducted on April 23, 2025. The comprehensive inspection covered multiple fire safety systems and devices, including smoke detectors, heat detectors, pull stations, tamper switches, waterflow switches, speakers, strobes, and releasing devices. Of the 71 total devices tested, 7 smoke detectors failed, specifically located in various hallways and lobby areas of the first floor, with noted "Open CKT" (open circuit) issues.
The inspection was performed in accordance with multiple NFPA (National Fire Protection Association) standards, including NFPA 101 (2024 Edition), NFPA 72 (2022 Edition), and NFPA 90A (2022 Edition). The inspection is directly related to a corresponding federal contract opportunity (Solicitation Number 36C26126Q0026) for Fire Alarm Maintenance at the VA Palo Alto Health Care System, with quote submissions extended to November 27, 2025. The inspection was conducted by Facility - Palo Alto VA, with the primary contact being Anthony Losito and the inspector being Olaf Soto.
Text of this file
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate For
MP Bldg 351
795 Willow Rd
Menlo Park, CA 94025
This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR CONDITIONING/VENTILATING SYSTEMS.
This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection Inspection Completion Date Apr 23, 2025 Building: MP Bldg 351 Company: Facility - Palo Alto VA Contact: Anthony Losito Contact: Olaf Soto Title: Electronics Shop Supervisor Title: Inspector
Facility - Palo Alto VA
Download Date: 04/24/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: MP Bldg 351 Contact: Anthony Losito Address: 795 Willow Rd Phone: 650-852-3437 Address:
Fax:
City/State/ZIP Code: Menlo Park, CA 94025 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Facility - Palo Alto VA Inspector: Olaf Soto Address: 2700 Gregory St Ste 180 Phone: 650-362-4841 Address:
Fax:
City/State/ZIP Code: Savannah, GA 31404 Mobile:
Country: United States of America Email: olaf@redwoodcityalarms.com
System Control Unit Manufacturer: SimplexGrinnell Inspection Date: 04/23/2025 IDC Style:
Model Number: 8201 Install Date: 05/17/2017 SLC Style:
Software Version:
Version Date: 05/17/2017 NAC Style:
Location: 1st Hallway Near 134 Current Protection:
Inspection Completion Date: Apr 23, 2025 Building: MP Bldg 351
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Tamper Switch Waterflow Switch
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector Heat Detector Pull Station Smoke Detector
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Releasing Device Speaker Speaker/Strobe Strobe Voice Evacuation
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Duct Detector
LS 02.01.34 EP 02
Protected master fire alarm control panel Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Control Panel
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Devices Tested This Quarter Pass Fail Tested YTD (2025) Untested YTD (2025) Total Quantity Battery Total Device Count: 71
Certification Company: Facility - Palo Alto VA Building: MP Bldg 351 Inspector: Olaf Soto Contact: Anthony Losito file_0.jpg
Signed: Apr 23, 2025 Signed:
Discrepancy Report
Building: MP Bldg 351 Control Panel: 0 - SimplexGrinnell 8201 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade No items found during this inspection.
& ScanID ` Location L Problem Address & Reference EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Smoke Detector 12603927 1st East Wing Hallway Outside RM 111
12603928 1st Entrance To East Wing Hallway
12603946 1st Entrance To South Wing
12603935 1st Main Lobby Above Entrance To Stairwell
12603943 1st Main Lobby Above Main Elevator
12603945 1st Main Lobby Above Main Entrance
12603948 1st South Wing Hallway Outside RM 117
Proposed Solutions Report
Building: MP Bldg 351 Control Panel: 0 - SimplexGrinnell 8201 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Smoke Detector 12603927 1st East Wing Hallway Outside RM 111
298-9201 T/M 12603928 1st Entrance To East Wing Hallway
298-9201 T/M 12603946 1st Entrance To South Wing
298-9201 T/M 12603935 1st Main Lobby Above Entrance To Stairwell
298-9201 T/M 12603943 1st Main Lobby Above Main Elevator
298-9201 T/M 12603945 1st Main Lobby Above Main Entrance
298-9201 T/M 12603948 1st South Wing Hallway Outside RM 117
298-9201 T/M
Internal WO/PO #: (none) T/M
Notes & Recommendations
Building: MP Bldg 351 Control Panel: 0 - SimplexGrinnell 8201 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.
ScanID Note Device Type Location Comment EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) 12603927 Smoke Detector 1st East Wing Hallway Outside RM 111
Open CKT 12603928 Smoke Detector 1st Entrance To East Wing Hallway
Open CKT 12603946 Smoke Detector 1st Entrance To South Wing
Open CKT 12603935 Smoke Detector 1st Main Lobby Above Entrance To Stairwell
Open CKT 12603943 Smoke Detector 1st Main Lobby Above Main Elevator
Open CKt Zn3 12603945 Smoke Detector 1st Main Lobby Above Main Entrance
Open CKT 12603948 Smoke Detector 1st South Wing Hallway Outside RM 117
Open CKT
Inspection & Testing
Building: MP Bldg 351 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Tamper Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Tamper Switch 1st Outside 45210453 05/28-P
04/23-P Tamper Switch 1st PIV 12604261 05/28-P
04/23-P Tamper Switch 1st Inside Elevator Mechanical Room 12603936 05/28-P
04/23-P Tamper Switch 1st Hallway Control Room 12603904 05/28-P
04/23-P Tamper Switch 1st Hallway Control Room 12603903 05/28-P
04/23-P Tamper Switch 1st Hallway Control Room 12603902 05/28-P
04/23-P Tamper Switch 2nd Closet Room 216 12603910 05/28-P
04/23-P Device Total: 7
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11) Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Waterflow Switch
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Waterflow Switch 1st Hallway Control Room 12603905 05/28-P
04/23-P Waterflow Switch 2nd Closet Room 216 12603911 05/28-P
04/23-P Device Total: 2
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Duct Detector Roof ON AHU1-SF B351 MOUNTED OUTSIDE 12603931 05/20-P
04/23-P Device Total: 1
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Heat Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Heat Detector 1st East Wing Inside RM 106 12603908 05/20-P
04/23-P Heat Detector 2nd SHAFT ELAVATOR SHAFT 45205275 05/20-P
04/23-P Device Total: 2
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Pull Station
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Pull Station 1st Hallway Near 134 45210377 05/20-P
04/23-P Pull Station 1st Main Entrance Main Lobby 12604248 05/20-P
04/23-P Pull Station 1st Electrical Room Emergency Exit 12603940 05/20-P
04/23-P Pull Station 1st East Emergency Exit 12603922 05/20-P
04/23-P Pull Station 2nd Corridor 211 12604250 05/20-P
04/23-P Pull Station 2nd Corridor 201 12603915 05/20-P
04/23-P Pull Station 2nd Corridor 221 12603909 05/20-P
04/23-P Device Total: 7
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Smoke Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Smoke Detector 1st Day Room Ceiling 45205003 05/20-P
04/23-P Smoke Detector 1st Day Room Ceiling 45205004 05/20-P
04/23-P Smoke Detector 1st Main Lobby Above Main Elevator 12603943 05/20-P
04/23-F Smoke Detector 1st South Wing Hallway Outside RM 117 12603948 05/20-P
04/23-F Smoke Detector 1st East Wing Hallway Outside RM 111 12603927 05/20-P
04/23-F Smoke Detector 1st Entrance To South Wing 12603946 05/20-P
04/23-F Smoke Detector 1st Entrance To East Wing Hallway 12603928 05/20-P
04/23-F Smoke Detector 1st Main Lobby Above Entrance To Stairwell 12603935 05/20-P
04/23-F Smoke Detector 1st Main Lobby Above Main Entrance 12603945 05/20-P
04/23-F Smoke Detector 2nd SHAFT ELEVATOR SHAFT 45205274 05/20-P
04/23-P Smoke Detector 2nd Corridor 211 12603973 05/20-P
04/23-P Smoke Detector 2nd Lobby 12603966 05/20-P
04/23-P Smoke Detector 2nd Lobby 208 12603964 05/20-P
04/23-P Smoke Detector 2nd Elevator 12603962 05/20-P
04/23-P Smoke Detector 2nd Corridor 213 12603953 05/20-P
04/23-P Device Total: 15
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Releasing Device
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Releasing Device 1st Double Door Entrance To South Wing 12603949 05/20-P
04/23-P Releasing Device 1st Double Door Entrance To South Wing 12603947 05/20-P
04/23-P Releasing Device 1st Entrance To Stairwell 12603937 05/20-P
04/23-P Releasing Device 1st Double Doors To East Wing 12603926 05/20-P
04/23-P Releasing Device 1st Double Doors To East Wing 12603925 05/20-P
04/23-P Releasing Device 2nd Corridor 213 Right 12604253 05/20-P
04/23-P Releasing Device 2nd Corridor 213 Left 12603965 05/20-P
04/23-P Releasing Device 2nd Entrance To Stairwell 12603963 05/20-P
04/23-P Device Total: 8
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker 1st Day Room Ceiling 12604256 05/20-P
04/23-P Speaker 1st Hallway Near 130 12603952 05/20-P
04/23-P Speaker 1st Hallway Near 126 12603951 05/20-P
04/23-P Speaker 1st South Hallway Outside RM 118 12603950 05/20-P
04/23-P Speaker 1st Main Entrance Above Elevator 12603944 05/20-P
04/23-P Speaker 1st East Wing Hallway Outside RM 109 12603924 05/20-P
04/23-P Speaker 1st East Wing Outside RM 106 12603923 05/20-P
04/23-P Speaker 2nd Corridor 206 12603972 05/20-P
04/23-P Speaker 2nd Corridor 219 12603969 05/20-P
04/23-P Speaker 2nd Corridor 214 12603968 05/20-P
04/23-P Speaker 2nd Corridor 213 12603967 05/20-P
04/23-P Speaker 2nd Lobby 12603961 05/20-P
04/23-P Speaker 2nd Corridor 204 12603960 05/20-P
04/23-P Device Total: 13
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Speaker/Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Speaker/Strobe 1st Electrical Closet Emergency Exit 12603941 05/20-P
04/23-P Device Total: 1
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Strobe
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Strobe 1st Day Room Pillar 45205005 05/20-P
04/23-P Strobe 1st East Wing Hallway Outside RM 109 12604249 05/20-P
04/23-P Strobe 1st Main Entrance Main Lobby 12604243 05/20-P
04/23-P Strobe 1st Hallway Near Rear Exit 12603929 05/20-P
04/23-P Strobe 1st East Emergency Exit 12603907 05/20-P
04/23-P Strobe 1st Hallway Near Room 125 12603906 05/20-P
04/23-P Strobe 2nd Corridor 211 12604254 05/20-P
04/23-P Strobe 2nd Corridor 214 12603921 05/20-P
04/23-P Strobe 2nd Corridor 201 12603914 05/20-P
04/23-P Strobe 2nd Corridor 206 12603913 05/20-P
04/23-P Strobe 2nd Corridor 221 12603912 05/20-P
04/23-P Device Total: 11
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Voice Evacuation
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Voice Evacuation 1st Hallway Near 134 45210376 05/20-P
04/23-P Device Total: 1
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1 Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Duct Detector
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Duct Detector Roof ON AHU1-SF B351 MOUNTED OUTSIDE 12603931 05/20-P
04/23-P Device Total: 1
LS 02.01.34 EP 02
Protected master fire alarm control panel Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Control Panel
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Control Panel 1st Hallway Near 134 45210375 05/20-P
04/23-P Device Total: 1
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q2/25 Pass Q2/25 Fail Q2/25 Tested YTD (2025) Total Quantity Battery
Device Type Location ScanID Address Q2/24 Q3/24 Q2/25 Battery 1st Hallway Near 134 12603874
08/20-P 04/23-P Battery 1st Hallway Near 134 12603873
08/20-P 04/23-P Device Total: 2
Service Summary
Building: MP Bldg 351 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity Failed/Other Smoke Detector Tested/Cleaned Total Passed Battery Tested Control Panel Tested Duct Detector Tested Heat Detector Tested Pull Station Tested Releasing Device Tested Smoke Detector Tested/Cleaned Speaker/Strobe Tested Speaker Tested Strobe Tested Tamper Switch Tested Voice Evacuation Tested Waterflow Switch Tested Total Grand Total
Auxiliary Functions Testing
Building: MP Bldg 351 Control Panel: 0 - SimplexGrinnell 8201 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated Passed Releasing Device
1st Double Door Entrance To South Wing Passed 12603947
1st Double Door Entrance To South Wing Passed 12603949
1st Double Doors To East Wing Passed 12603925
1st Double Doors To East Wing Passed 12603926
1st Entrance To Stairwell Passed 12603937
2nd Corridor 213 Left Passed 12603965
2nd Corridor 213 Right Passed 12604253
2nd Entrance To Stairwell Passed 12603963
Battery & Power Supply Testing
Building: MP Bldg 351 Control Panel: 0 - SimplexGrinnell 8201 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Tested Ah Passed Sealed Lead Acid 1st Hallway Near 134
35-NB
Sealed Lead Acid 1st Hallway Near 134
35-NB
Inventory & Warranty Report
Building: MP Bldg 351 Control Panel: 0 - SimplexGrinnell 8201 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 2.82% Control Panel Control 1.41% Duct Detector Initiating 1.41% Heat Detector Initiating 2.82% Pull Station Initiating 9.86% Releasing Device Auxiliary 11.27% Smoke Detector Initiating 21.13% Speaker Indicating 18.31% Speaker/Strobe Indicating 1.41% Strobe Indicating 15.49% Tamper Switch Supervisory 9.86% Voice Evacuation Control 1.41% Waterflow Switch Initiating 2.82%
Type Qty Model # Description Install Date In Service - 5 Years to 10 Years Power-Sonic Battery
PS-12350 NB
Sealed Lead Acid 01/30/2020
SIMPLEX
Smoke Detector
05/17/2018 Aleum Company Tamper Switch
BFG
10/16/2017 System Sensor Waterflow Switch
WFD40
10/16/2017
Releasing Device
05/17/2017 Aleum Company Tamper Switch
BFG
05/17/2017 Potter Electric Speaker
Tamper Switch
OSYSU-2
05/17/2017 Waterflow Switch
VSR-F
05/17/2017 SimplexGrinnell Control Panel
05/17/2017 Duct Detector 298-9021
05/17/2017 Heat Detector
EZDT
05/17/2017 Pull Station 2099-9668
05/17/2017 Pull Station 2099-9768
05/17/2017 Releasing Device
Smoke Detector 298-9021
05/17/2017 Smoke Detector 298-9201
05/17/2017
4902-9707
05/17/2017 Speaker/Strobe
Strobe
Strobe
LSM-24-VFR
05/17/2017 Voice Evacuation
System Sensor Tamper Switch
OSY2
05/17/2017 Tamper Switch
PIBV2