S05 - Vendor Questions and RFI with Answers - 36C26123R0099 - E Wing AHU Upgrade.pdf
PDF 5 MB Posted
- Attached to
- VISN 21 MACC Group 2 - E Wing AHU Upgrade
- Solicitation number
- 36C26123R0099
About this file
This document summarizes responses to vendor questions regarding solicitation number 36C26123R0099 for the E Wing AHU Upgrade at the Veterans Health Administration VISN 21 MACC Group 2 contract. The responses provide clarification on project requirements such as allowing an extended project duration of 60 weeks for new air handler equipment with long lead times. Temporary cooling requirements and locations are also specified. Additional details are given on fire alarm and sprinkler work scopes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S05 - Request for Information (RFI) - E Wing HVAC Upgrade.docx | DOCX document | |
| P12 - ICRA - E Wing HVAC Upgrades.pdf | ||
| 36C26123R0099 - E Wing HVAC Upgrade.docx | DOCX document | |
| P01 - Bid Documents Full Size - E Wing HVAC Upgrade.pdf | ||
| P01 - Bid Document Specifications - E Wing HVAC Upgrade.pdf | ||
| P07 - WD - HI20230001 - E Wing HVAC Upgrade.txt | TXT text file | |
| S02 - Division Construction Costs - E Wing HVAC Upgrade.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
36C26123R0099 - E Wing AHU Upgrade RFI’s
RFI #1 – RFP calls for the project to be completed in 270 calendar days. The lead time for AHU Equipment is approximately 60 weeks out, can the project duration be extended?
RCC: Equipment lead times are still trending around this long, sometimes shorter. Recommend for the VA to extend as needed for the approved air handlers per contractor feedback.
RFI #2 – In reference to GI100, Phasing Notes under Rooms that need temporary cooling, please provide required capacity or tonnage of temp AC needed to provide per room per Level. Please confirm if outside air duct of the temp AC can be release above ceiling.
RCC: The preferred method of temporary cooling is by portable AC units per room, with heat rejection to route above ceiling into plenum space.
RFI #3 – Please provide construction drawings and details for the fire alarm system including location of the new duct smoke detectors, new smoke or fire dampers and other fire alarm devices such as addressable relays, etc..that need to be replaced or install per floor at Mechanical Room.
RCC: Fire Alarm devices are called out on the electrical drawings. Exact location and installation method is on the contractor to coordinate in the field. See response to RFI#5.
RFI# 4 – Please provide as-built of the Fire Alarm system at each Mechanical Rooms with schematic or riser diagram. Please provide the manufacturer and brand of the fire alarm panel to connect the fire alarm devices.
VA Response: A fire panel alarm and sensor upgrade is anticipated to complete prior to construction of the E- Wing AHU Upgrades. See Attachment 1 for the 100% Construction Design Drawings. Construction to complete in June 2024. The manufacturer of the new fire alarm panel is Notifier.
RFI#5 – The fire alarm system for E-Wing will be upgraded soon in a different VA project that was recently awarded which includes the Mechanical Rooms fire alarm devices. Please advise if this scope of work will be descope from this solicitation since it is covered by a different contract already.
VA Response: New fire alarm devices shall be descoped from this solicitation. However, the Contractor is responsible for removal and re-installation of fire alarm devices as required during construction.
RFI#6 – In reference to EP101, enlarge plans for electrical room 1B-106, C1-1 and 2C-110D RCC: Enlarged Plans are shown for those rooms, with relevant information included. RFI is not understandable.
RFI#7 - Fan schedule Note 1 on sheet T1-M-002 states 1-VFD serving the duplex fans but also calls for a dedicated fully redundant VFD. Electrical drawings do not show the redundant VFD. Is intent to have 1-VFD per motor or is intent to have 2 separate electrical feeders with 1-VFD on each feed?
RCC: There is a single point for an electrical connection that will serve both the primary and the redundant VFD.
So there is one feeder to the equipment which will have 2 VFDs.
RFI#8 - Can temp cooling be staged outside building near parking lot?
RCC: No. The preferred method of temporary cooling is by portable AC units per room, with heat rejection to route above ceiling into plenum space.
RFI#9 – Please provide anticipated location of the new riser or floor to floor/ wall to wall penetration as the existing condition where the existing disconnect safety switch and VFD is tight and looks like no space to penetrate.
RCC: The conduit riser was anticipated to be located in the northwest corner of the mechanical room (see drawing below). Coordinate exact route in the field.
RFI#10 – In reference to Drawings T1-AS101 to AS103. Please confirm that the mechanical rooms walls/ partition are non-rated walls as no rating drawn in the plans.
RCC: Room walls are not rated per existing fire protection plans.
RFI#11 – In reference to firestop scope of work, please advise what brand or manufacturer is the VA currently using in E-Wing? Also please provide typical firestop detail required for this project on both floor to floor penetration and wall to wall penetration.
RCC: Details provided below.
RFI#12 – Please advise thickness of the existing concrete floor slab to be cored for new conduit riser. Please confirm RCC: Slab thicknesses vary. Field verify location of holes to avoid drilling through joists and other large supporting members.
RFI#13 – Please confirm no hazardous abatement scope of work anticipated in this solicitation such as lead or asbestos abatement. Is there a current hazardous survey report available? If so please provide.
RCC: Hazardous materials was not expected and is not in scope of work. No hazardous materials were identified during site survey.
RFI#14 – Please confirm no repair of exiting flooring coating is anticipated in this scope of work as no spec has been provided.
RCC: Per VA. Not anticipated to be included.
RFI#15 – Drawing T1-GI100 Phasing notes Phase 1B states to core slabs and provide new electrical risers in mechanical spaces to prepare for new equipment connections. While drawing T1-E-501 detail 1 – Existing partial one line diagram – demo shows only demolition of circuit breaker, conduit and wire up to BMECH Panel and BMECH Panel. No demolition of electrical riser from BMECH Panel up to the AHUs per floor. Please clarify scope of work regarding the existing electrical riser from BMECH Panel up to AHUs per floor.
RCC: The conduits and cables to existing AHUs will be removed back to BMECH Panel after removed from demo’ed AHUs.
RFI#16 - During the site visit, the Mechanical Rooms become storage area for tools/ carts/ spares/ etc..please confirm if these will be removed by the VA prior starting of construction work at no cost to the General Contractor.
RCC: VA to clear out rooms as needed. Contractor to provide a month notice to provide ample time to empty out mechanical rooms as needed prior to transitioning from mechanical room to the next.
RFI#17 – Please confirm VA Facility Maintenance to support the General Contractor during outages for Electrical, Fire Sprinkler and Mechanical Systems including turning on/ off electrical panels for lock out tag out, on/ off existing valves, draining to existing floor drain/ filling up water for flushing, hydrotesting, etc on fire sprinkler/ mechanical system per floor, during work hours, off hours and weekends as needed at no cost to the General Contractor.
VA response: VA can support.
RFI#18 - Please advise location and sq footage of lay down area and staging area for this solicitation.
VA Response: Staging location is approximately 40 sq ft X 40 sq ft. See photo below.
RFI#19 – Please confirm Contractor can use and have access to existing elevators for personnel and material handling use for this project.
VA Response: Elevator can be used by the contractor before and after business hours. The contractor will be responsible in protecting the interior of the elevator. Contractor shall be aware and shall not exceed the weight limit that is posted within the elevator.
RFI#20 - Specs 230923 states to use Pitot type airflow station. Confirm that contractor can use Accutrol type airflow station.
RCC: Per VA. Contractor to provide submittal for preapproval.
RFI#21 - Specs 230923 state airflow stations to be rated for 250 degF. This is an expensive add, standard ones are rated at 120 degF.
RCC: Per VA. This should be acceptable since the air handlers do not have heating capability.
RFI#22 - Per phasing plan, occupants on each floor can chose to stay or vacate during construction. Please provide hours of operation for each floor and confirm no temporary cooling required for rooms not specified.
VA Response: Occupants may choose to work in their office. It will be up to their leadership if they will be allowed to work from home. However, cooling may not be required for areas that are not identified.
“***PHASE 2,3,4,5 - VACATING THE FLOOR DURING CONSTRUCTION WILL NEED TO BE
COORDINATED WITH OCCUPANTS OF EACH FLOOR. IT WILL BE UP TO EACH FLOOR IF THEY
WANT TO VACATE. IF CONTRACTOR IS REQUESTING FOR OCCUPANTS TO VACATE, VA
REQUIRES A MINIMUM OF 14 DAYS ADVANCE NOTICE FOR EACH FLOOR.
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
FIRE PANELS ALARM AND
ASSOCIATED SENSORS
UPGRADE
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
FULLY SPRINKLERED
WVS RR
G-001
COVER SHEET
FIRE PANELS ALARM AND ASSOCIATED SENSORS
UPGRADE
459 PATTERSON ROAD
HONOLULU, HI 96819
APOGEE PROJECT #: 19-148VA PROJECT #: 459-16-106
PROJECT SITE MAP
HONOLULU VAMC
N
SCALE: NTS
PROJECT LOCATION MAP
HONOLULU VAMC
N
SCALE: NTS
DRAWING LIST
1 2
DocuSign Envelope ID: 7A00D387-BA17-4E36-BAED-87F57688728F
5/18/2022
JSherwood Stamp
VHAHONTangR Highlight
VHAHONTangR Highlight
VHAHONTangR Highlight
VHAHONTangR Highlight
VHAHONTangR Highlight
VHAHONTangR Highlight
VHAHONTangR Highlight
VHAHONTangR Highlight
VHAHONTangR Highlight
VHAHONTangR Highlight
VHAHONTangR Highlight
GENERAL NOTES
ABBREVIATIONS
INFECTION CONTROL RISK ASSESSMENT NOTES:
FIBER OPTIC
SINGLE MODE
MULTIMODE
DRIVE
STREET
CONCRETE MASONRY UNIT
EQUAL
STAINLESS
NOT RATED
ABOVE FINISHED FLOOR
EXPANSION JOINT
CONTROL JOINT
QUICK RELEASE SPRINKLER
FAHRENHEIT
LIMIT OF DEMOLITION
EXISTING
NEW
NOT IN CONTRACT
EXPOSED TO STRUCTURE
NOT TO SCALE
SIMILAR
BUILDING
PHONE
INCORPORATED
SOUTH
DEAD LEG
GALLONS PER MINUTE
ON CENTER
CONTRACTING OFFICER REPRESENTATIVE
PUBLIC ADDRESS MASS NOTIFICATION SYSTEM
INFORMATION TECHNOLOGY
FO
SM
MM
DR.
ST.
CMU
EQ.
STL.
NR.
A.F.F.
EJ
CJ
Q.R.S.
°F
(E)
(N)
N.I.C.
E.T.S.
N.T.S.
SIM.
BLDG.A.
PH.
INC.
S.
DL
GPM
O.C.
COR
PAMNS
IT
1. CONTRACTOR SHALL VISIT ALL AREAS OF WORK, INCLUDING WALKING THE SITE, MEASURING EXISTING DIMENSIONS AND OBSERVING
EXISTING CONDITIONS BEFORE BEGINNING WORK, ORDERING MATERIALS, OR STARTING ANY CONSTRUCTION. CONTRACTOR TO FIELD
VERIFY ALL DIMENSIONS OF EXISTING SITE CONDITION PRIOR TO START OF WORK AND ORDERING OF MATERIALS.
2. CONTRACTOR IS RESPONSIBLE FOR DETERMINING INFECTION CONTROL PRECAUTION MEASURES BASED ON THE TYPE AND LOCATION OF
WORK BEING PERFORMED. CONFIRM PRECAUTION MEASURES WITH COR PRIOR TO BEGININING WORK IN SAID AREA.
3. PENTRATIONS THRU RATED CONSTRUCTION (FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS, SMOKE PARTITIONS, HORIZONTAL ASSEMBLIES, AND VERTICAL OPENINGS) SHALL MAINTAIN CONTINUITY OF RATED CONSTRUCTION. CONTRACTOR
RESPONSIBLE FOR IDENTIFYING RATED AREAS AND FIRESTOPPING ALL PENETRATIONS. CONTACT COR AND A/E FOR CLARIFICATION AS
NEEDED. VA GUIDELINES STATE ALL RATED CONSTRUCTION TO BE CLEARLY LABELED.
4. CONTRACTOR SHALL RECYCLE REMOVED MATERIALS WHENEVER POSSIBLE. SEE DIVISION 1 SPECIFICATIONS
5. CONTRACTOR TO PROTECT AREA ADJACENT TO THE DEMOLITION AND NEW CONSTRUCTION WORK TO PREVENT DAMAGES. (IF DAMAGED, REPAIR, PATCH, REPLACE, OR SAND SMOOTH AND TO MATCH EXISTING ADJACENT MATERIALS.)
6. CONTRACTOR SHALL REPORT TO COR IMMEDIATELY WHEN DISCREPANCIES TO THE DRAWINGS ARE FOUND IN THE FIELD.
7. CONTRACTOR TO INSTALL TEMPORARY BALL-IN-TUBE SYSTEM TO MONITOR AND ENSURE PRESSURE LEVEL TO MEET VA GUIDELINE
WITHIN CONSTRUCTION AREA. (CONTRACTOR TO VERIFY LOCATIONS) WITH VA COR PRIOR TO INSTALLATION.
ICRA CLASSIFICATIONS
BUILDING RISK
GROUP
CONSTRUCTION PROJECT
ACTIVITY
CLASSIFICATION
BUILDING T1 (E-WING)
BUILDING 30 (ACC)
BUILDING 32
(PARKING GARAGE)
BUILDING 110 (CFA)
LOW RISK
HIGH RISK
LOW RISK
HIGHEST RISK
TYPE B
TYPE B
TYPE B
TYPE B
CLASS II
CLASS II
CLASS II
CLASS III
NOTE: REFERENCE VA PACIFIC ISLANDS HEALTHCARE SYSTEM INFECTION CONTROL ASSESSMENT MATRIX OF PRECAUTIONS
FOR CONSTRUCTION AND RENOVATION IN CONSTRUCTION DOCUMENTS FOR FURTHER INFORMATION.
CLASS III ICRA REQUIREMENTS ONLY APPLY TO BUILDING 110 FCP WORK.
DEMO KEY NOTES
KEY NOTES
1. PLASTIC BARRIER WITH ZIPPER ACCESS. SEE DETAIL THIS SHEET.
2. ZIPPER ACCESS POINT.
3. REMOVE EXISTING BASE.
4. RELOCATE ALL DEVICES LOCATED IN EXISTING WALL TO FACE OF NEW 6" STUD WALL.
1. ADD 6" 20 GA. METAL STUD WALL TIGHT TO EXISTING WITH 5/8" TYPE X GYPSUM BOARD TO 8" ABOVE EXISTING CEILING. TAPE AND FINISH, LEVEL 4, AND PREP WALL FOR PAINT. PAINT WALL, COLOR TO BE SELECTED BY VA, 1 COAT PRIMER, 2 COATS LATEX, EGGSHELL.
2. INSTALL NEW BASE TO MATCH EXISTING.
3. EXISTING ACT CEILING TO REMAIN. TRIM GRID AND TILES TO FIT TO NEW STUD WALL.
X
X
* OBTAIN INFECTION CONTROL PERMIT BEFORE CONSTRUCTION BEGINS.
COMPLETE ALL CRITICAL BARRIERS OR IMPLEMENT CONTROL CUBE METHOD BEFORE CONSTRUCTION BEGINS.
SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE COR.
COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
VACUUM WORK AREA WITH HEPA FILTERED VACUUMS. WET MOP AREA WITH DISINFECTANT. REMOVE ISOLATION OF HVAC SYSTEM
IN AREAS WHERE WORK IS BEING PERFORMED.
COVER ALL RETURNS AND SUPPLY DUCTS AT THE GRATE/DIFFUSES WITH FILTER MEDIA OR BLANKED OFF ENTIRELY PER ICRA
REQUIREMENTS.
KEEP CONSTRUCTION SITE CLEAN AND NEAT AT ALL TIMES.
CONTRACTOR TO CLEAN THE CONSTRUCTION AREA, AND PREPARE FOR COR TO INSPECT.
VA ECM STAFF WILL PERFORM FINAL VERIFICATION OF CLEANING AND SANITATION. COR TO PERFORM FINAL INSPECTION.
SWIVEL CASTERS
WITH TWO
LOCKING BRAKES
MOBILE CART
A D
J U
S T
A B
L E
H
E I G
H T
HEPA NEGATIVE
AIR UNIT
EXISTING WALL
EXISTING CEILING
F.F.
PLASTIC SHEET BARRIER NON RATED
6 MIL PLASTIC SHEET
BARRIER
EXISTING WALL
ASSEMBLY
EXISTING CEILING
BOTTOM SEALING
RUNNER
TOP SEALING
RUNNER
SUPPORT POLES,
QUANTITY PER
MANUF.
RECOMMENDATIONS
AS
REQU.
1A106
TOILET
1A104
TOILET
1A103B
VET SVC
1A103C1A103D
OFFICE1A103E
DIRECTOR
1A-103A
OFFICE
1A-103
ELEVATORELEVATOR
SNACK
SHOPRECEPTION
WAITING AREA
SECURITY/
1A-101
INFO
SLOPE
OFFICE OF VET SVC
STAIR
FAMILY
(STATE OF HAWAII)
WOMENS
TOILET
MENS
OFFICE
NO-1
A102
A102
WAITING AREA
WAITING AREA
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
FIRE PANELS ALARM AND
ASSOCIATED SENSORS
UPGRADE
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
FULLY SPRINKLERED
WVS RR
E-WING - FLOOR PLANS AND ICRA
INFORMATION
A-102
HEPA CART DETAIL
ICRA BARRIER WALL TYPE
SCALE 1/ 2 " = 1' - 0"
SCALE 3/4 " = 1' - 0"
1 E-WING BUILDING PARTIAL PLAN
SCALE: 1/8" = 1' 0"
NORTH
PLAN
0 4 8 16
2 ENLARGED PLAN - DEMOLITION
SCALE: 1/4" = 1' 0"
0 2 4 8
NORTH
PLAN
3 ENLARGED PLAN - NEW WORK
SCALE: 1/4" = 1' 0"
0 2 4 8
NORTH
PLAN
E-WING
DocuSign Envelope ID: 7A00D387-BA17-4E36-BAED-87F57688728F
5/18/2022
PHARMACY
B-A101
ELEVATOR ELEVATOR
B-A100
B-A104
B-A105
ELECTRICAL
B-A101B
TO
C
RA
WL S
PA
CE
B A106
MEN
IRM
B-A107
MECHANICAL
ROOM
TO
C
RA
WL S
PA
CE
TO CRAWL SPACE
B-A103
WOMEN
IRM
STORAGE
STAIR
CORRIDOR
F
F
S
SD
F
F
F
F
F
S
F
SD
F
S
F
S
F
S
F
S
F
S
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
NORTH
PLAN
0 4 8 161 E-WING BASEMENT FIRE ALALRM PLAN
SCALE: 1/8" = 1' 0"
E-WING BASEMENT FIRE ALARM
PLAN
JWBRSB
1. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
2. ELEVATOR RECALL SMOKE DETECTOR. SEE
FIRE ALARM INTERFACE WITH ELEVATORS
DETAIL 2/FA501 FOR MORE INFO.
3. EXISTING SPRINKLER TAMPER AND FLOW
SWITCH FIRE PROTECTION DEVICES
(SPRINKLER DEVICES) TO REMAIN, PROVIDE
NEW MONITORING MODULARS AND CONNECT
TO NEW FIRE ALARM SYSTEM.
EWFA101
T1-EW
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
32 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED BASEMENT FLOOR.
DocuSign Envelope ID: 26F43C1C-3576-4228-B012-7D5AB3485581
5/18/20225/18/2022
TOILET
1A104
1A103B
VET SVC
1A103C1A103D
OFFICE1A103E
DIRECTOR
1A-103A
OFFICE
1A-103
ELEVATORELEVATOR
SNACK
SHOPRECEPTION
WAITING AREA
SECURITY/
1A-101
INFO
COPY AREA
OFFICE
1-B100B
ELECTRICAL
1-B103
STORAGE
1-B102
1-B104
RM
1-B105
OFFICE
1-B106
1-B108
OFFICE
1-B113A
1-B111
1-B112
OFFICE
OFFICE
1-B114
1-B113B
OFFICE1-B117
1-B116
1-B115A
OFFICE
1-B115B
OFFICE
SLOPE
OFFICE OF VET SVC
OFFICE
CONFERENCE
OFFICE
1-B110
OFFICE
OFFICE OFFICE
OFFICE
TELE
STAIR
FAMILY
(STATE OF HAWAII)
WOMENS
TOILET
STAIR
1-B107
OFFICE
NO-1
CORRIDOR
F
S
F
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
F
F S
F
F
S
F S
F
F
S
F A
C P
SD
F
UP
UP
FS
SD
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
NORTH
PLAN
0 4 8 161 E-WING FIRST FLOOR FIRE ALALRM PLAN
SCALE: 1/8" = 1' 0"
E-WING FIRST FLOOR FIRE
ALARM PLAN
JWBRSB
MATCH LINE, SEE EWFA103
EWFA102
T1-EW
1. EXISTING MAIN FIRE ALARM CONTROL PANEL
SHALL BE REPLACED WITH NEW FIRE ALARM
CONTROL PANEL AND TO BE RECESS IN NEW
STUD WALL. SEE ARCHITECTURAL SHEET A-102
FOR PATCHING AND PAINTING.
2. ELEVATOR RECALL SMOKE DETECTOR. SEE
FIRE ALARM INTERFACE WITH ELEVATORS
DETAIL 2/FA501 FOR MORE INFO.
3. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
4. EXISTING FIRE ALARM PULL BOX WITH CONDUIT
TO BE REUSED FOR NEW FIRE ALARM CABLING.
SPLICING AND WIRE NUT SHALL NOT BE USED.
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
33 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED FIRST FLOOR.
1-C119
1-C118
1-C116
1-C115
ROLLING SHUTTER
OFFICE
OFFICE
OFFICE
1-C113
OFFICE
1-C114
FILE RM
1-C112
ASST
1-C111
CONFERENCE RM
1-C108
ELECTRICAL
1-C109
STORAGE
OFFICE
CHEIF ENGINEER
1-C110
1-C106
1-C101B
1-C105
1-C100
1-C101
STORAGE
HOMELESS SECTION
AMERICAN LOGIAN
OFFICE
1-C107A
1-C107
1-C104A
1-C104
1-C104B
OFFICE
1-C103
1-C102
RECEPTION
1-C102A
DISABLED AMERICAN
DIRECTOR
1A105
1-C103B
MECH RM
1A106
TOILET
1A104
TOILET
1A103B
VET SVC
1A-103A
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE1-C101A
1-C120
1-C120A
WOOD EQUIP.
COPY/SUPPLY
1-C103A
1-C120B
LOCKSMITH
VTF
COPY
CARPENTRY
STAIR
FAMILY
OFFICE
VFW
CHILLER PLANT
EMERGENCY GENERATOR
TELE
TOILET
OPEN
OFFICE
ADMIN
MENS TOILET
STAIR
NO-1
OFFICE
1-C114A
OFFICE
1-C114B
OFFICE
CORRIDOR
CORRIDOR
CORRIDOR
F
F
F
S
DD
DD
F
S
F
F
S
F
S
F
F
S
F
F
F
S
F
S
F
F
S
F
S
F S
F
S
F
UP
UP
DD
+6'
F
+6'
+6'
SD
EXISTING
PANEL
'1EL1'
PIV
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
NORTH
PLAN
0 4 8 161 E-WING FIRST FLOOR FIRE ALALRM PLAN
SCALE: 1/8" = 1' 0"
E-WING FIRST FLOOR FIRE
ALARM PLAN
JWBRSB
MATCH LINE, SEE EWFA102
EWFA103
T1-EW
1. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
2. EXISTING FIRE ALARM PULL BOX WITH CONDUIT
TO BE REUSED.
3. REPLACE EXISTING INTELLIGENT NETWORK
FIRE ALARM PANEL WITH NEW AND CONNECT
TO PARKING GARAGE, E-WING, CENTER OF
AGING, AND AMBULATORY CARE CLINIC.
4. EXISTING SPRINKLER TAMPER AND FLOW
SWITCH FIRE PROTECTION DEVICES
(SPRINKLER DEVICES) TO REMAIN, PROVIDE
NEW MONITORING MODULARS AND CONNECT
TO NEW FIRE ALARM SYSTEM.
5. LOCATION OF EXISTING PIV, CONTRACTOR
SHALL EXCAVATE, GRADE AND PREP LOCATION
FOR NEW CONDUIT, WIRE, TAMPER SWITCH,
AND MONITOR MODULE, VERIFY EXACT
LOCATION.
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
34 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED FIRST FLOOR.
TOILET
2A-107
WOMENS
TOILET
2A-105STAIR
NO-1
CORRIDOR
COPY RM
2A-104
PGM ANALYST
VBA REGIONAL
OFFICE
2A-104A
SECY
2A-100CDIRECTOR VA
REGIONAL
OFFICE
2A-100B
CONFERENCE RM
2-A100
WOMENS
TOILET
2-A103
ELEVATORELEVATOR
OFFICE
2-A101
OPEN OFFICE
2-B100
OFFICE
2-B101A
OFFICE
2-B101B
ELECTRICAL
2-B103
STORAGE
2-B102
OPEN OFFICE
2-B101
TEL
2-B104
CORRIDOR
OPEN OFFICE
2-B105
CORRIDOR
STAIR
HAC
2-B107
STORAGE
FILE RM
2-B106
F
S
F
F
F
F
S
F
F
S
F
S
F
S
F
S
F
S
F
S
F S
SD
F
F
F
S
F S
UP
UP
DN
DN
+6'
F
S
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
E-WING SECOND FLOOR FIRE
ALARM PLAN
NORTH
PLAN
0 4 8 161 E-WING SECOND FLOOR FIRE ALALRM PLAN
SCALE: 1/8" = 1' 0"
JWBRSB
MATCH LINE, SEE EWFA105
EWFA104
T1-EW
1. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
2. EXISTING FIRE ALARM PULL BOX WITH CONDUIT
TO BE REUSED.
3. ELEVATOR RECALL SMOKE DETECTOR. SEE
FIRE ALARM INTERFACE WITH ELEVATORS
DETAIL 2/FA501 FOR MORE INFO.
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
35 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED SECOND FLOOR.
HOUSEKEEPING
2-C100B
COPY
AREA
2-C101E
CORRIDOR
OFFICE
2-C104
CHIEF
MANAGEMENT SVC
OFFICE
2-C103
OFFICE
2-C102
STAIR
CHIEF
OFFICE
(QM)
2-C101D1
OPEN OFFICES
2-C101D
CORRIDOR
OFFICE
2-C101G
OFFICE
2-C101F
OFFICE
2-C101C
OFFICE
2-C101B
OFFICE
2-C101A
OFFICE
2-C100F
OFFICE
2-C100G
2-C100E
ELECTRICAL
2-C100D
TELE
2-C100C
COPY RM
2-C100A
OPEN OFFICES
2-C100
MENS
TOILET
2A-108
MECHANICAL
2A-106
MENS
TOILET
2A-107
WOMENS
TOILET
2A-105
COPY RM
2A-104
PGM ANALYST
VBA REGIONAL
OFFICE
2A-104A
F
F
F
DD
F
S
F
S
F
S
F
S
F
F
S
F S
F
S
F
S
UP
DN
DN
UP
F
S
+6'
F
S
DD
EXISTING
PANEL
'2EL1'
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
E-WING SECOND FLOOR FIRE
ALARM PLAN
NORTH
PLAN
0 4 8 161 E-WING SECOND FLOOR FIRE ALALRM PLAN
SCALE: 1/8" = 1' 0"
JWBRSB
MATCH LINE, SEE EWFA104
EWFA105
T1-EW
1. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
2. EXISTING FIRE ALARM PULL BOX WITH CONDUIT
TO BE REUSED.
3. EXISTING SPRINKLER TAMPER AND FLOW
SWITCH FIRE PROTECTION DEVICES
(SPRINKLER DEVICES) TO REMAIN, PROVIDE
NEW MONITORING MODULARS AND CONNECT
TO NEW FIRE ALARM SYSTEM.
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
36 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED SECOND FLOOR.
H.R.PH4 PRIVACY
OFFICER
OFFICE
3-A103
STORAGE
3B105A
3B106H
3B106F
CORRIDOR
STOR
3-A103A
HSK
3A104
WOMENS
TOILET
3-A105
STAIR
NO 1
WOMENS
TOILET
3-A102
ELEVATORELEVATOR
3-A101A
OFFICE
3-A101B
HRM
3-A101
OFFICE
3-A101C
HRIS OFFICE
3-A101E
HUMAN RESOURCE
MANAGEMENT
3-B100
PROCESSING AND
RECORD ROOM
3B100C
ASSISTANT CHIEF
OFFICE
3B100E
HRM
3-A100
CREDIT
UNION
3-B101
HRM NURSE
RECRUITER
OFFICE
3B102A
HRM
3-B102
FILE RM
3B100D
PAYROLL
OFFICE
3B104
FINANCIAL
RESOURCE
MANAGEMENT
3-B103
ELECTRICAL
3B105B
TELE
3B105C
3-B105
CORRIDOR
3-B106
OFFICE
3B106G
CORRIDOR
OFFICE
3B106A
3B106B
CHIEF OF
DEPARTMENT
3B106C
WORK AREA
3B108
CORRIDOR
ACCOUNTING
CHIEF
3B106E
OFFICE
3B106D
HSK
3B107
STAIR
F
S
F
F
S
F
S
F
S
F
S
F
F
F
F
S
F
S
F
SD
F
F
S
F S
F
S
F
S
F
S
UP
UP
DN
DN
EXISTING
PANEL
'3EL2'
F
S
F
S
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
E-WING THIRD FLOOR FIRE
ALARM PLAN
NORTH
PLAN
0 4 8 161 E-WING THIRD FLOOR FIRE ALALRM PLAN
SCALE: 1/8" = 1' 0"
JWBRSB
MATCH LINE, SEE EWFA107
EWFA106
T1-EW
1. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
2. EXISTING FIRE ALARM PULL BOX WITH CONDUIT
TO BE REUSED.
3. ELEVATOR RECALL SMOKE DETECTOR. SEE
FIRE ALARM INTERFACE WITH ELEVATORS
DETAIL 2/FA501 FOR MORE INFO.
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
37 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED THIRD FLOOR.
UP
RAMP
DN
STORAGE
3-C107
IRM
OFFICE
3-C109
IRM
3-C108
OFFICE
3-C108C
CORRIDOR
STAIR
ELEC RM
3-C108F
IRM
OFFICE
3-C108E
SERVER RM
3-C108D
OFFICE
3-C108G
OFFICE
3-C108B
OFFICE
3-C108A
CORRIDOR
IRM
OFFICE
3-C104
OFFICE
3-C101A
ACQUISITION AND MATERIAL
MANAGEMENT SERVICE
3-C101
MECHANICAL ROOM
3A106
STOR
3-A103A
HSK
3A104
ELECTRICAL
3-C106
IRM
3-C105
SYSTEMS
REDESIGN
OFFICE
3-C103
CHIEF
3-C102
CONFERENCE ROOM
3-C100
MENS
TOILET
3-A108
MENS
TOILET
3A107
WOMENS
TOILET
3-A105
STAIR
NO 1
F
F
F
DD
F
S
F
S
F
F
S
F
S
F
F
S
F
S
DD
DD
DD
F
F
S
F
S
F
S
UP
DN
DN
UP
F
+6'
+6'
+6'
F
S
DD
DD
F
S
EXISTING
PANEL
+6'
+6'
+6'
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
E-WING THIRD FLOOR FIRE
ALARM PLAN
NORTH
PLAN
0 4 8 161 E-WING THIRD FLOOR FIRE ALALRM PLAN
SCALE: 1/8" = 1' 0"
JWBRSB
MATCH LINE, SEE EWFA106
EWFA107
T1-EW
1. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
2. EXISTING FIRE ALARM PULL BOX WITH CONDUIT
TO BE REUSED.
3. EXISTING SPRINKLER TAMPER AND FLOW
SWITCH FIRE PROTECTION DEVICES
(SPRINKLER DEVICES) TO REMAIN, PROVIDE
NEW MONITORING MODULARS AND CONNECT
TO NEW FIRE ALARM SYSTEM.
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
38 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED THIRD FLOOR.
STORAGE
4-B110
RESEARCH
DEPARTMENT
OFFICE
4-A101
OFFICE OF ACOS
EDUCATION
4A-103A
CORRIDOR
WOMENS
TOILET
4A-106
STAIR
NO 1
ELEVATOR
#4
ELEVATOR
#4
WOMENS
TOILET
OFFICE
4-A100
DIRECTOR'S
CONFERENCE
RM
4-A105OFFICE
4-A104A
OFFICE
4-A104
OFFICE
4-B100E
CONFERENCE RM
4-B100D
OFFICE
4-B101
OFFICE
4-A101A
OFFICE
4-A101B
OFFICE
4-A101C
OFFICE OF DEPUTY
DIRECTOR OF
UNIVERSITY OF HAWAI
4-B100A
OFFICE
4-B100C
DIRECTOR
4-B100B
OFFICE
4-B102B
OFFICE
4-B102A
OFFICE
4-B102
COPY AREA
CORRIDOR
CORRIDOR
OFFICE
4-B102C
OFFICE
4-B102D
INSTITUTE FOR
THE DIRECTOR
4-B105A
OFFICE
4-B103
OFFICE
4-B104
STORAGE
4-B106
ELEC
4-B107
TEL
4-B108
STORAGE
4-B109
OFFICE
4-B111
IMAGING UNIT OFFICE
4-B112
OFFICE
4-B112A
OFFICE
4-B114
OFFICE
4-B113
CONFERENCE RM
4-B117
OFFICE
4-B116
OFFICE
4-B115
STAIR
F
F
S
F
F
F
S
F
S
F
S
F
S
SD
SD
SD
F
F
S
F
HD
FS
F
S
F
S
F
S
F
UP
UP
DN
DN
F
S
EXISTING
PANEL
'4EL2'
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
E-WING FOURTH FLOOR FIRE
ALARM PLAN
NORTH
PLAN
0 4 8 161 E-WING FOURTH FLOOR FIRE ALARM PLAN
SCALE: 1/8" = 1' 0"
JWBRSB
MATCH LINE, SEE EWFA109
EWFA108
T1-EW
1. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
2. EXISTING FIRE ALARM PULL BOX WITH CONDUIT
TO BE REUSED.
3. ELEVATOR RECALL SMOKE DETECTOR. SEE
FIRE ALARM INTERFACE WITH ELEVATORS
DETAIL 2/FA501 FOR MORE INFO.
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
39 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED FOURTH FLOOR.
FILE STORAGE RM
4C-117
HEALTH SYSTEM
SPECIALIST
4C-119
OFFICE
CREDENTIALING
4C-103
OFFICE
4C-100B
OPEN OFFICE
4C-116
4C-111
CONFERENCE RM
4-C122
STAIR
CHIEF OF STAFF
4C-118
STAFF
LOUNGE
4C-120
CORRIDOR
TOILET
4C-118A
DIRECTOR
4C-115
COMPLAINT AND
FACILITY PLANING
4C-113
FILE/FAX/COPY
PRINT RM
4C-114
OFFICE
4C-112
OFFICE
4C-110
ASST COUNSEL
OFFICER
4C-107
ASSOCIATE
DIRECTOR
4C-109
OFFICE
4C-108
STORAGE
4C-106
ELEC
4C-105
TEL
4C-104
CORRIDOR
4C-103B
OFFICE PUBLIC
AFFAIRS
4C-102
HAC
4C-101
OFFICE OF THE
REGIONAL COUNCIL
4C-103A
OFFICE OF THE
REGIONAL COUNSEL
4C-100
MENS
TOILET
4A-109
WOMENS
TOILET
4A-106
MENS
TOILET
4A-108
MECH ROOM
4-A107
STAIR
DIRECTOR'S
CONFERENCE
RM
4-A105
F
F
F
F
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
F
F S
F
UP
DN
DN
UP
DD
+6'
F
S
F
S
F
S
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
E-WING FOURTH FLOOR FIRE
ALARM PLAN
NORTH
PLAN
0 4 8 161 E-WING FOURTH FLOOR FIRE ALARM PLAN
SCALE: 1/8" = 1' 0"
JWBRSB
MATCH LINE, SEE EWFA108
EWFA109
T1-EW
1. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
2. EXISTING FIRE ALARM PULL BOX WITH CONDUIT
TO BE REUSED.
3. EXISTING SPRINKLER TAMPER AND FLOW
SWITCH FIRE PROTECTION DEVICES
(SPRINKLER DEVICES) TO REMAIN, PROVIDE
NEW MONITORING MODULARS AND CONNECT
TO NEW FIRE ALARM SYSTEM.
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
40 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED FOURTH FLOOR.
DN
STORAGE
STAIR
NO-1
MECH RM
ELEVATOR RM
HD
SD
F
SD
F S
HD
SD
F
HD
SD
F
S
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of
Construction and Facilities
Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
P
M
HONOLULU VA,
UPGRADE FIRE ALARM
PANELS AND SENSORS
459 PATTERSON ROAD,
HONOLULU, HI 96819
MAY 19, 2022
100% CONSTRUCTION DOCUMENTS
459-16-106
19-148
KEY NOTES:
SHEET NOTES:
FULLY SPRINKLERED
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL DESCRIPTION
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM PHOTOELECTRIC SMOKE
DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
DD
FIRE ALARM DUCT SMOKE DETECTOR W/
ADDRESSABLE RELAY
FIRE ALARM HEAT DETECTOR
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
NAC
FAAP
F
S
F
S
HD
SD
FIRE ALARM GRAPHIC ANNUNCIATOR PANELFAGAP
FLOW SWITCH
TAMPER SWITCH
PIV
REMOTE LIGHT/TEST SWITCH FOR
DUCT DETECTORS
F FIRE ALARM BELL
FIRE ALARM CONTROL PANELFACP
RADIO FIRE ALARM TRANSMITTERRFAT
KEYPLAN
= AREA OF WORK
POST INDICATOR VALVE WITH TAMPER
SWITCH AND MONITOR MODULES
F
C
FIRE ALARM PULL STATION WITH STOPPER II
COVERS WITH 9 VOLT DC BATTERIES
E-WING PENTHOUSE FIRE
ALARM PLAN
NORTH
PLAN
0 4 8 161 E-WING PENTHOUSE FIRE ALARM PLAN
SCALE: 1/8" = 1' 0"
JWBRSB
1. PROVIDE ELEVATOR RECALL FIRE ALARM
MODULES AND CONNECT TO ELEVATOR
CONTROLLER AND FIRE ALARM PANEL. SEE
DETAIL OF SHEET FA501 FOR MORE INFO.
2. PROVIDE NEW FIRE ALARM DEVICES,
RACEWAYS AND WIRING AND CONNECT TO
NEW FIRE ALARM SYSTEM.
3. PROVIDE NEW ADDRESSABLE HEAT
DETECTORS WITHIN 2 FT OF ALL SPRINKLER
HEADS.
4. EXISTING ELEVATOR CONTROLLERS.
5. EXISTING SPRINKLER TAMPER AND FLOW
SWITCH FIRE PROTECTION DEVICES
(SPRINKLER DEVICES) TO REMAIN, PROVIDE
NEW MONITORING MODULARS AND CONNECT
TO NEW FIRE ALARM SYSTEM.
6. CONTRACTOR TO HIRE ELEVATOR
CONTRACTOR TO HELP WITH ELEVATOR
RECALL AND SHUNT TRIP FOR FUNCTIONAL
SYSTEM.
EWFA110
T1-EW
A. REPLACE ALL EXISTING FIRE ALARM DEVICES WIRING
WITH NEW FIRE ALARM DEVICES AND NEW WIRING
AND CONNECT TO NEW FIRE ALARM SYSTEM.
B. EXISTING FIRE ALARM CONDUIT BOXES THAT ARE
NOT PAINTED "RED" SHALL BE PAINTED "RED" AND
SHALL BE LABELED ACCORDING WITH NFPA, AND VA
FIRE PROTECTION DESIGN MANUAL.
C. PROVIDE BLANK COVER PLATES FOR ALL EXISTING
FIRE ALARM DEVICES THAT ARE NOT REPLACED.
D. ALL CIRCUIT BREAKER SERVING THE FIRE ALARM
EQUIPMENT SHALL BE PAINTED RED AND SHALL
HAVE LOCKING DEVICES (ELOCK-FA-E SERIES).
41 66
FIRE ALARM NOTIFICATIONS
ZONES - CODE RED PENTHOUSE.
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED
OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS
IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL
CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH
NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)
WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE
GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS
SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF
OPENING IS 26 IN. (660 MM).
2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR
ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY
OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE
RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN.
(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL
ELECTRICAL METALLIC TUBING
D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING
E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL GAS
PIPING MAY BE USED:
1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
OMEGA FLEX INC
2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
TITEFLEX CORP
A BUNDY CO
3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
WARD MFG INC
3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM) THICKNESS
OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES
OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT
LOCATION ON BOTH SIDES OF WALL.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN
WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.
THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND
THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,
*BEARING THE UL CLASSIFICATION MARKING
SYSTEM NO.W-L-1001
JUNE 15, 2005
F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)
T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
MAX PIPE OR
CONDUIT DIAM
IN. (mm)
1 (25)
1 (25)
4 (102)
6 (152)
12 (305)
F RATING
HR
1 OR 2
3 OR 4
1 OR 2
3 OR 4
1 OR 2
T RATING
HR
0+, 1 OR 2
3 OR 4
SECTION A-A
1B
1A
A
A
DUCT
DETECTOR
WITH
ADDRESABLE
RELAY
FACP
AIR HANDLING
STARTER / VFD
DUCT SENSOR / PROBE
DD
6'+
HD
INTERFACE RELAYS INSTALL WITHIN 3' OF
ELEVATOR CONTROLLER
R1
EQL
R2
EQL
R3
EQL
SHUNT TRIP
BREAKER
R4
EQL
HOT NEUTRAL
120 VAC CIRCUIT
(POWER TO OPERATE
SHUNT TRIP BREAKER)
FROM EMERGENCY
POWER SOURCE
R5
EQL
FIRE ALARM CONTROL UNIT
SCC1 SCC2 SCC3 SCC4
ACTUARION
CAUSES
RECALL TO
ALTERNATE
LEVEL
ACTUARION
CAUSES
RECALL TO
DESIGNATED
LEVEL
ACTUARION
CAUSES
FLASHING
OF
WARNING
SIGNAL
ACTUARION
CAUSES
DISCONNECT
OF MAIN LINE
ELEVATOR
POWER
1DC1
(SUPERVISORY)
ACTUARION
CAUSES
SUPERVISORY
SIGNAL
CONVENTIONAL OR
ADDRESSABLE
ZONE / CIRCUIT
MODULE
HD
ELEVATOR
HOISTWAY HEAT
DETECTOR(S)
ELEVATOR
MACHINE ROOM
HEAT DETECTOR(S)
SD
ELEVATOR
HOISTWAY SMOKE
DETECTOR(S)
ELEVATOR MACHINE
ROOM SMOKE
DETECTOR(S)
SD SD
ELEVATOR LOBBY
SMOKE DETECTOR
5TH FLOOR
SD
ELEVATOR LOBBY
SMOKE DETECTOR
4TH FLOOR
SD
ELEVATOR LOBBY
SMOKE DETECTOR
3RD FLOOR
SD
ELEVATOR LOBBY
SMOKE DETECTOR
2ND FLOOR
(ALTERNATE LEVEL)
SD
ELEVATOR LOBBY
SMOKE DETECTOR
GROUND FLOOR
(DESIGNATED LEVEL)
SD
ELEVATOR LOBBY
SMOKE DETECTOR
BASEMENT
1.
NOTE:
FIRE ALARM CIRCUITS ARE TO BE DESIGNED AND
INSTALLED IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE
ALARM CODE AND NEC 70, NATIONAL ELECTRICAL CODE
R1 SIGNAL TO ELEVATOR CONTROLLER FOR RECALL TO DESIGNATED LEVEL.
R2 SIGNAL TO ELEVATOR CONTROLLER TO RECALL TO ALTERNATE LEVEL.
R3 SIGNAL TO ELEVATOR CONTROLLER FOR RECALL TO ALTERNATE LEVEL.
R4 SIGNAL TO ACTIVATE SHUNT TRIP RELAY.
R5 SUPERVISORY RELAY TO MONITOR PRESENCE OF VOLTAGE (POWER) TO OPERATE SHUNT
TRIP BREAKER
SCC1 SUPERVISED CONTROL CIRCUIT FOR OPERATING R1.
SCC2 SUPERVISED CONTROL CIRCUIT FOR OPERATING R2.
SCC3 SUPERVISED CONTROL CIRCUIT FOR OPERATING R3.
SCC4 SUPERVISED CONTROL CIRCUIT FOR OPERATING R4.
IDC1 INITIATING DEVICE CIRCUIT TO SUPERVISE R5 CONTACTS (MONITORING POWER TO OPERATE
SHUNT TRIP BREAKER).
COMPONENT FUNCTION
FIRE ALARM CONDUIT
FIRE ALARM BOX
CKT NO.: XXX
FIRE ALARM FIBER CABLE
TYPE: XXX
LOOP: XXX
FROM: XXX
T…