Fire Protection_amend_2_Semi-Annual Halon Preaction 200501.pdf

PDF 77 KB Posted

Attached to
H142--Fire Protection Testing, Inspection, and Maintenance/Repair Service
Solicitation number
36C26120Q1110
Issued by

About this file

This file contains a fire protection system inspection report and a pre-solicitation notice for a related federal contract opportunity. The inspection report documents the results of a semi-annual inspection of a clean agent fire suppression system at a Department of Veterans Affairs facility in Reno, Nevada. All devices passed inspection, including the clean agent suppression system, cylinders, control panel, and battery.

The related pre-solicitation notice announces that the Department of Veterans Affairs Network Contracting Office 21 will be issuing a Request for Quote for fire protection testing, inspection, and maintenance/repair services in Reno, Nevada. The solicitation will be a total SDVOSB (Service Disabled Veteran Owned Small Business) set aside. The government intends to award one firm fixed-priced contract. Questions must be submitted in writing by the date specified in the forthcoming solicitation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CUSTOMER NAME: Department of Veterans Affairs BUILDING NAME: Department of Veterans Affairs BUILDING ADDRESS: 975 Kirman Ave, Reno, NV, 89502 INSPECTION TYPE: Clean Agent Suppression System FREQUENCY: Semi-Annual

WORK ORDER: 46958476

INSPECTION END DATE: 05/01/2020

INSPECTOR (s): Arkie DeVenuto

INSPECTOR LICENSE: 13107

ACCOUNT NAME: Johnson Controls North America OFFICE ADDRESS: 1105 S Rock Blvd RENO NV 89502

OFFICE PHONE: 775 412 4581

OFFICE LICENSE:

TIMEZONE: GMT-07:00

FIRE ALARM INSPECTION REPORT

General Inspection Notes

1. Inspected by Paul Johnson 2189

DEVICE DEFICIENCIES

No device deficiencies in this inspection.

INSPECTION RESULTS SUMMARY

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT

Clean Agent Suppression System 1 1 0 0

Clean Agent Cylinder 2 2 0 0

Clean Agent Control Panel 1 1 0 0

Clean Agent Battery 1 1 0 0

Clean Agent Suppression System

INSPECTION RESULTS SUMMARY

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT

Clean Agent Suppression System 1 1 0 0

CLEAN AGENT SUPPRESSION INSPECTION

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 — Server Room Clean Agent

Suppression System

— Arkie DeVenuto 05/01/2020 Passed

Type Of System Halon 1301

System Manufacturer Siemens

Releasing Panel Manufacturer Siemens

Releasing Panel Model Siemens

Quantity Of Cylinders 2

All Solenoids / Actuators Removed No

Pneumatic Actuators Removed N/A

All Solenoids, Actuators, and Mechanical Pull Stations Reconnected N/A

System Returned to Normal Yes

Clean Agent Suppression System–Semi-Annual

Customer: Department of Veterans Affairs Building: Department of Veterans Affairs

Address: 975 Kirman Ave, Reno, NV, 89502

Clean Agent Suppression System | 05/01/2020 Page 1 of 4

Clean Agent Devices

INSPECTION RESULTS SUMMARY

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT

Clean Agent Cylinder 2 2 0 0

Clean Agent Control Panel 1 1 0 0

Clean Agent Battery 1 1 0 0

CLEAN AGENT BATTERY

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 — Server Room Clean Agent Battery — Arkie DeVenuto 05/01/2020 Passed

Quantity (Enter 2 if answering for a set) 2

AMP Hour Rating 18

Visual Inspection Pass

Battery Install Date 10-2019

Batteries less than 5 Years Pass

Manufacture Date Code 10-2019

Voltage with charger N/A

Voltage without charger N/A

Load Voltage Test Results N/A

Load Voltage Test Results (%) N/A

CLEAN AGENT CONTROL PANEL

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 — OINT Server Room Clean Agent Control

Panel

— Arkie DeVenuto 05/01/2020 Passed

System Returned to Normal Upon Inspection Completion Yes

Clean Agent Suppression System–Semi-Annual

Customer: Department of Veterans Affairs Building: Department of Veterans Affairs

Clean Agent Suppression System | 05/01/2020 Page 2 of 4

Clean Agent Devices

CLEAN AGENT CYLINDER

# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 — Next to pre-action Siemens Clean Agent Cylinder — Arkie DeVenuto 05/01/2020 Passed

Specify Agent Type Halon 1301

Cylinder Size 150

Cylinder Number 0090

Is This Cylinder Part Of Main Or Reserve Bank Reserve

Cylinder is Properly Tagged Yes

Design PSI 360

Current PSI 360

Design Weight 90

Current Weight 90

Agent Quantity Weight Less Than 5% Loss Yes

Agent PSI Less Than 10% Loss Yes

Inergen - Agent Psi Less Than 5% N/A

What is the Liquid Level Measurement on this Tank 9.25

Current Room Temperature 68

Cylinder Hose Assembly Date N/A

Cylinder Hose Date N/A

Date of Last Hydrotest 10-2014

2 — Next to pre-action Siemens Clean Agent Cylinder — Arkie DeVenuto 05/01/2020 Passed

Specify Agent Type Halon 1301

Cylinder Size 560

Cylinder Number 0305

Is This Cylinder Part Of Main Or Reserve Bank Main

Cylinder is Properly Tagged Yes

Design PSI 370

Current PSI 370

Design Weight 305

Current Weight 305

Agent Quantity Weight Less Than 5% Loss Yes

Agent PSI Less Than 10% Loss Yes

Inergen - Agent Psi Less Than 5% N/A

What is the Liquid Level Measurement on this Tank 14.25

Current Room Temperature 68

Cylinder Hose Assembly Date N/A

Cylinder Hose Date N/A

Date of Last Hydrotest 7-2013

Clean Agent Suppression System–Semi-Annual

Customer: Department of Veterans Affairs Building: Department of Veterans Affairs

Clean Agent Suppression System | 05/01/2020 Page 3 of 4

Inspector Signature

Inspector Name Arkie DeVenuto Date 05/01/2020

Signature of the

Maintenance Lead

Printed name of the Maintenance

Lead Robert Hunter Date 05/01/2020

Clean Agent Suppression System–Semi-Annual

Customer: Department of Veterans Affairs Building: Department of Veterans Affairs

Clean Agent Suppression System | 05/01/2020 Page 4 of 4