Fire Protection_amend_2_Semi-Annual Halon Preaction 200501.pdf
PDF 77 KB Posted
- Solicitation number
- 36C26120Q1110
About this file
This file contains a fire protection system inspection report and a pre-solicitation notice for a related federal contract opportunity. The inspection report documents the results of a semi-annual inspection of a clean agent fire suppression system at a Department of Veterans Affairs facility in Reno, Nevada. All devices passed inspection, including the clean agent suppression system, cylinders, control panel, and battery.
The related pre-solicitation notice announces that the Department of Veterans Affairs Network Contracting Office 21 will be issuing a Request for Quote for fire protection testing, inspection, and maintenance/repair services in Reno, Nevada. The solicitation will be a total SDVOSB (Service Disabled Veteran Owned Small Business) set aside. The government intends to award one firm fixed-priced contract. Questions must be submitted in writing by the date specified in the forthcoming solicitation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Fire Protection_amend 2_Quarterly Preaction 200713.pdf | ||
| 36C26120Q1110 0002 - AMENDMENT_2.docx | DOCX document | |
| Fire Protection_amend_2_SemiAnnual Ansul 200518.pdf | ||
| Fire Protection _amend _2_ attachment _1_Annual FWP 191121.pdf | ||
| 36C26120Q1110 0001.docx | DOCX document | |
| 36C26120Q1110_FIRE PROTECTION_ Performance Work Statement.docx | DOCX document | |
| 36C26120Q1110_Solicitation_rfq.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CUSTOMER NAME: Department of Veterans Affairs BUILDING NAME: Department of Veterans Affairs BUILDING ADDRESS: 975 Kirman Ave, Reno, NV, 89502 INSPECTION TYPE: Clean Agent Suppression System FREQUENCY: Semi-Annual
WORK ORDER: 46958476
INSPECTION END DATE: 05/01/2020
INSPECTOR (s): Arkie DeVenuto
INSPECTOR LICENSE: 13107
ACCOUNT NAME: Johnson Controls North America OFFICE ADDRESS: 1105 S Rock Blvd RENO NV 89502
OFFICE PHONE: 775 412 4581
OFFICE LICENSE:
TIMEZONE: GMT-07:00
FIRE ALARM INSPECTION REPORT
General Inspection Notes
1. Inspected by Paul Johnson 2189
DEVICE DEFICIENCIES
No device deficiencies in this inspection.
INSPECTION RESULTS SUMMARY
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Clean Agent Suppression System 1 1 0 0
Clean Agent Cylinder 2 2 0 0
Clean Agent Control Panel 1 1 0 0
Clean Agent Battery 1 1 0 0
Clean Agent Suppression System
INSPECTION RESULTS SUMMARY
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Clean Agent Suppression System 1 1 0 0
CLEAN AGENT SUPPRESSION INSPECTION
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Server Room Clean Agent
Suppression System
— Arkie DeVenuto 05/01/2020 Passed
Type Of System Halon 1301
System Manufacturer Siemens
Releasing Panel Manufacturer Siemens
Releasing Panel Model Siemens
Quantity Of Cylinders 2
All Solenoids / Actuators Removed No
Pneumatic Actuators Removed N/A
All Solenoids, Actuators, and Mechanical Pull Stations Reconnected N/A
System Returned to Normal Yes
Clean Agent Suppression System–Semi-Annual
Customer: Department of Veterans Affairs Building: Department of Veterans Affairs
Address: 975 Kirman Ave, Reno, NV, 89502
Clean Agent Suppression System | 05/01/2020 Page 1 of 4
Clean Agent Devices
INSPECTION RESULTS SUMMARY
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT
Clean Agent Cylinder 2 2 0 0
Clean Agent Control Panel 1 1 0 0
Clean Agent Battery 1 1 0 0
CLEAN AGENT BATTERY
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Server Room Clean Agent Battery — Arkie DeVenuto 05/01/2020 Passed
Quantity (Enter 2 if answering for a set) 2
AMP Hour Rating 18
Visual Inspection Pass
Battery Install Date 10-2019
Batteries less than 5 Years Pass
Manufacture Date Code 10-2019
Voltage with charger N/A
Voltage without charger N/A
Load Voltage Test Results N/A
Load Voltage Test Results (%) N/A
CLEAN AGENT CONTROL PANEL
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — OINT Server Room Clean Agent Control
Panel
— Arkie DeVenuto 05/01/2020 Passed
System Returned to Normal Upon Inspection Completion Yes
Clean Agent Suppression System–Semi-Annual
Customer: Department of Veterans Affairs Building: Department of Veterans Affairs
Clean Agent Suppression System | 05/01/2020 Page 2 of 4
Clean Agent Devices
CLEAN AGENT CYLINDER
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 — Next to pre-action Siemens Clean Agent Cylinder — Arkie DeVenuto 05/01/2020 Passed
Specify Agent Type Halon 1301
Cylinder Size 150
Cylinder Number 0090
Is This Cylinder Part Of Main Or Reserve Bank Reserve
Cylinder is Properly Tagged Yes
Design PSI 360
Current PSI 360
Design Weight 90
Current Weight 90
Agent Quantity Weight Less Than 5% Loss Yes
Agent PSI Less Than 10% Loss Yes
Inergen - Agent Psi Less Than 5% N/A
What is the Liquid Level Measurement on this Tank 9.25
Current Room Temperature 68
Cylinder Hose Assembly Date N/A
Cylinder Hose Date N/A
Date of Last Hydrotest 10-2014
2 — Next to pre-action Siemens Clean Agent Cylinder — Arkie DeVenuto 05/01/2020 Passed
Specify Agent Type Halon 1301
Cylinder Size 560
Cylinder Number 0305
Is This Cylinder Part Of Main Or Reserve Bank Main
Cylinder is Properly Tagged Yes
Design PSI 370
Current PSI 370
Design Weight 305
Current Weight 305
Agent Quantity Weight Less Than 5% Loss Yes
Agent PSI Less Than 10% Loss Yes
Inergen - Agent Psi Less Than 5% N/A
What is the Liquid Level Measurement on this Tank 14.25
Current Room Temperature 68
Cylinder Hose Assembly Date N/A
Cylinder Hose Date N/A
Date of Last Hydrotest 7-2013
Clean Agent Suppression System–Semi-Annual
Customer: Department of Veterans Affairs Building: Department of Veterans Affairs
Clean Agent Suppression System | 05/01/2020 Page 3 of 4
Inspector Signature
Inspector Name Arkie DeVenuto Date 05/01/2020
Signature of the
Maintenance Lead
Printed name of the Maintenance
Lead Robert Hunter Date 05/01/2020
Clean Agent Suppression System–Semi-Annual
Customer: Department of Veterans Affairs Building: Department of Veterans Affairs
Clean Agent Suppression System | 05/01/2020 Page 4 of 4