36C26119R0002-011.pdf
PDF 9 MB Posted
- Attached to
- Upgrade Site for USP800 Compliant
- Solicitation number
- 36C26119R0002
About this file
36C26119R0002 Reference Document 2.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26119C0111-000.docx | DOCX document | |
| 36C26119R0002_0004.docx | DOCX document | |
| 36C26119R0002_0003.docx | DOCX document | |
| 36C26119R0002_0002.docx | DOCX document | |
| Pharmacy_Trailer_Salients_(002).pdf | ||
| 36C26119R0002_0001.docx | DOCX document | |
| 36C26119R0002-008.doc | DOC document | |
| 36C26119R0002-004.docx | DOCX document | |
| 36C26119R0002-013.docx | DOCX document | |
| 36C26119R0002-010.pdf | ||
| 36C26119R0002-005.docx | DOCX document | |
| 36C26119R0002-006.docx | DOCX document | |
| 36C26119R0002-009.doc | DOC document | |
| 36C26119R0002-014.pdf | ||
| 36C26119R0002-001.docx | DOCX document | |
| 36C26119R0002-003.docx | DOCX document | |
| 36C26119R0002-007.docx | DOCX document | |
| 36C26119R0002-012.docx | DOCX document | |
| 36C26119R0002-002.pdf | ||
| 36C26119R0002-000.docx | DOCX document |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FX
FX
FX
FX
FX
FX
FX
FX
VHAPALNGORY
Text Box
RADIOLOGY
VHAPALNGORY
Text Box
BLDG 100
VHAPALNGORY
Rectangle
VHAPALNGORY
Dimension 80'
VHAPALNGORY
Dimension 40'
VHAPALNGORY
Text Box
PHARMACY TRAILERS
VHAPALNGORY
Text Box
BLDG. 103 A / B
ADDENDUM #11
ADDENDUM #1 9/18/20131
C AV PAHCS
AV PAHCS
RSENIO RTEGA,
CONSULTING ENGINEER
5 Third Street, Suite 716 San Francisco, CA 94103
(415) 546-0490 tel -0491 fax
OA P.E.
C AV PAHCS
AV PAHCS
RSENIO RTEGA,
CONSULTING ENGINEER
5 Third Street, Suite 716
San Francisco, CA 94103
(415) 546-0490 tel -0491 fax
OA P.E.
3-500KCM, 1#2GF0350
4-500KCM, 1#2GF0350N
4-350KCM, 1#2G
3-350KCM, 1#2G
4-250KCM, 1#2G
3-250KCM, 1#2G
(NOTE: NOT ALL FEEDER TAGS MAY BE USED.)
FEEDER SCHEDULE
4#3/0, 1#6G
F0300N
F0300
F0250N
F0250
F0225N
F0225
F0200N
4#4/0, 1#4G
3#4/0, 1#4G
F0150N
F0200
F0175N
F0175
F0150
F0125N
F0125
4#1/0, 1#6G
3#3/0, 1#6G
4#2/0, 1#6G
3#2/0, 1#6G
3#1/0, 1#6G
4#1, 1#6G
3#1, 1#6G
CONDUIT
F0100N
F0100
F0070N
F0070
F0050N
F0050
TAG
4#2, 1#6G
3#2, 1#6G
4#4, 1#6G
3#4, 1#6G
4#6, 1#8G
CONDUCTORS
3#6, 1#8G
(2 SETS) 4-500KCM,
(2 SETS) 3-500KCM,
(2 SETS) 4-500KCM,
(2 SETS) 3-500KCM,
(3 SETS) 4-350KCM,
(3 SETS) 3-350KCM,
(3 SETS) 4-500KCM,
(3 SETS) 3-500KCM,
(4 SETS) 4-350KCM,
(4 SETS) 3-350KCM,
(4 SETS) 4-500KCM,
(4 SETS) 3-500KCM,
(5 SETS) 3-500KCM,
(5 SETS) 4-500KCM,
F1600N
F1600
F1400N
F1400
F1200N
F1200
F1000N
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#2/0G
F0800N
F1000
F0900N
F0900
F0700N
F0700
F0800
1#1/0G
1#2/0G
1#2/0G
1#2/0G
1#1/0G
1#1/0G
1#1/0G
(2 SETS) 4-250KCM,
(2 SETS) 3-250KCM,
(2 SETS) 4-350KCM,
(2 SETS) 3-350KCM,
CONDUIT
F0600N
F0600
F0500N
F0500
F0400N
F0400
TAG
1#1/0G
1#1/0G
1#1G
1#1G
3-500KCM, 1#2G
4-500KCM, 1#2G
CONDUCTORS
(5) 31/2"
(4) 31/2"
(4) 21/2"
(3) 31/2"
(3) 21/2"
31/2"
(2) 21/2"
(2) 21/2"
(2) 21/2"
(2) 31/2"
11/4"
11/4"
11/4"
11/2"
11/4"
11/2"
11/2"
11/2"
21/2"
21/2"
21/2"
31/2"
(2) 31/2"
F0040N
F0040
F0030N
F0030
4#8, 1#10G
3#8, 1#10G
4#10, 1#10G
3#10, 1#10G3/4"
3/4"
3/4"
3/4"
(NOTE: N = NEUTRAL CONDUCTOR INCLUDED)
F0020N
F0020
4#12, 1#12G
3#12, 1#12G3/4"
3/4"
1"
1"
2"
2"
2"
2"
2"
2"
3"
3"
3"
(2) 3"
(2) 3"
(2) 3"
(3) 3"
(3) 3"
(4) 3"
(4) 3"
(5) 3"
(4 SETS) 3-350KCM,
F1200 (E) 1#3/0G(4) 21/2"
(3 SETS) 4-400KCM,
F1000N (E) 1#2/0G(3) 3"
(2 SETS) 4-500KCM,
F0800N (E) 1#1/0G(2) 31/2"
(2 SETS) 3-500KCM,
F0800 (E) 1#1/0G
(2 SETS) 4-400KCM,
F0700N (E) 1#1/0G(2) 3"
(2 SETS) 4-350KCM,
F0600N (E) 1#1G
(2 SETS) 3-350KCM,
F0600 (E) 1#1G(2) 21/2"
(2 SETS) 4-250KCM,
F0500N (E) 1#2G(2) 21/2"
(2 SETS) 3-250KCM,
F0500 (E) 1#2G(2) 2"
F0400N (E) 4-500KCM, 1#2G31/2"
F0400 (E) 3-500KCM, 1#2G
3-350KCM, 1#4GF0300 (E) 21/2"
F0225N (E) 4#4/0, 1#4G21/2"
F0225 (E) 3#4/0, 1#4G
F0150N (E) 4#1/0, 1#6G11/2"
F0100 (E) 3#2, 1#8G11/4"
F0060N (E) 4#6, 1#10G11/4"
3#1 MV90 EPRHV-1 (E) (1) 4"
SWITCHBOARD NHS1001B (E)
4000A-277/480V-3PH-4W
CT'S
DMM
GFR
ST4000
GFR
800 ST
CT'S
F
N
E
PB
NBW1A
800A-3PH-4 W
SPACE SPACE
CT'S
ST 500 ST
CT'S
F
N
E
PB
CABLE
TAP
BOX
(E)
BUS RISER NBW6A (E)
600A-3PH-4 W
3 3
400 ST
CT'S
GFR GFR GFR
CT'S
GFR
ST
SWITCHBOARD NHS1001A (E)
4000A-277/480V-3PH-4W
CT'S
GFR
ST 500
CT'S
GFR
ST
CABLE TAP BOX (E)
RM E0.1
PANEL
NL01A
LHS
(E)
PANEL
NH01A
(E)
PANEL
NL01A
RHS
(E)
XFMR NTX01A (E)
45KV-480-120/208V-3PH-4W
ELEC RM E0.1
BASEMENT
ELEC RM E0.1
BASEMENT
ELEC RM E0.1
BASEMENT
100 AF
ELEC RM E0.1
BASEMENT
60 AF
ELEC RM E0.1
BASEMENT
PANEL
NL11A
LHS
(E)
PANEL
NH11A
(E)
XFMR NTX11A
112.5KVA-480-120/208V-3PH-4W
ELEC RM E1.1
1ST FLOOR
PANEL
NL11A
RHS
(E)
ELEC RM E1.1
1ST FLOOR
225 AF
ELEC RM E1.1
1ST FLOOR
225 AF
ELEC RM E1.1
1ST FLOOR
ELEC RM E1.1
1ST FLOOR
NBS01B (E)
NBS01A (E)
F0100 (E) F0175N (E)
F0060N (E)
NBS11B (E)
NBS11A (E)
F0225 (E)
F0225N (E)
F0400N (E)
F
N
E
PB
NBW2A
1000A-3PH-4 W
PANEL
NL02A
LHS
(E)
PANEL
NH02A
(E)
PANEL
NL02A
RHS
(E)
XFMR NTX02A (E)
150KV-480-120/208V-3PH-4W
ELEC RM E0.2
BASEMENT
ELEC RM E0.2
BASEMENT
ELEC RM E0.2
BASEMENT
300 AF
ELEC RM E0.2
BASEMENT
150 AF
ELEC RM E0.2
BASEMENT
PANEL
NL12A
LHS
(E)
PANEL
NH12A
(E)
XFMR NTX12A
112.5KVA-480-120/208V-3PH-4W
ELEC RM E1.2
1ST FLOOR
PANEL
NL12A
RHS
(E)
ELEC RM E1.2
1ST FLOOR
225 AF
ELEC RM E1.2
1ST FLOOR
60 AF
ELEC RM E1.2
1ST FLOOR
ELEC RM E1.2
1ST FLOOR
NBS02B (E)
NBS02A (E)
F0300 (E) F0600N (E)
F0150N (E)
NBS12B (E)
NBS12A (E)
F0225 (E)
F0060N (E)
F0400N (E)
400 ST
CT'S
GFR
800 ST
CT'S
GFR
MCC
NMCC00A
(E)
CHILLER
YARD
400AS
INFECTIOUS
WASTE
PROCESSOR
(LOADING DOCK)
F
E
PANEL
NH051A
(E)
F
E
PANEL
NH063A
(E)
F
E
E Q
U
IP
M
EN
T S
YS
TE
M R
O O
F
CT'S
DMM
GFR
ST4000
GFR
700 ST
CT'S
F
N
E
F
N
E
CT'S
ST 400 ST
CT'S
GFR GFRGFR
600 ST
CT'S
F
N
E
C R
IT
IC
A L
B R
A N
C H
C R
IT
IC
A L
B R
A N
C H
LI
F
E S
A F
E T
Y B
R A
N C
H
F
N
E
CT'S
ST
GFR
E Q
U
IP
M E
N T
S Y
S T
E M
S
F
E
CT'S
ST
GFR
EQ
U
IP
M
EN
T
SY
ST
EM
S
C O
O
LI
N G
T O
W
ER
Y
AR
D
F
E
CT'S
ST
GFR
E Q
U
IP
M E
N T
S Y
ST
EM
S R
O O
F
F
E
CT'S
ST
GFR
E Q
U
IP
M E
N T
S Y
ST
EM
S R
O O
F
F
N
E
PB
BUS RISER NBW4A (E)
400A-3PH-4W
CABLE TAP
BOX (E)
SATS
1001A
(E)
EP5.1.4
CATS
1001B
(E)
EP5.1.4
CATS
1001A
(E)
EP5.1.4
QATS
1001A
(E)
EP5.1.3
QATS
1001C
(E)
EP5.1.3
QATS
1001D
(E)
EP5.1.3
QATS
1001E
(E)
EP5.1.3
T1001A (E)
EP5.1.0
QATS
1001B
(E)
EP5.1.3
(2) SETS OF 4#250MCM WITH
1#2 PER SET IN 4" CONDUIT
(E)
TO
SECOND
FLOOR
TO
SECOND
FLOOR
#4 CU
CABLE TAP BOX (E)
RM E0.2
#2/0 CU
#3/0 CU
#2/0 CU
F0050 (E) 3#8, 1#10G3/4"
F0100N (E) 4#2, 1#8G11/4"
F0125N (E) 4#1, 1#6G11/2"
F0150 (E) 11/2" 3#1/0, 1#6G
F0175N (E) 4#2/0, 1#6G
4-350MCM, 1#4GF0300N (E)
4-400MCM, 1#2GF0350N (E)
2"
2"
3"
3"
3"
(2) 3"
(2) 3"
(E)
EATS
1031A (E)
EP5.1.1
T1001B (E)
EP5.1.0
33 33 3 3 33 3 33 33 3 33 3 F
N
F
F
TEMPORARY
SERVICE
TEMPORARY
SERVICE
5.01 5.015.015.04
5.05 5.05
5.06
5.05
5.06
5.06 5.065.04
5.03
5.02
LA
D
6/30/2015
L
No. E15435
TE
STA
AC
T R
EXP
OF
E L E C
L
ER
TE
I
G R E
AP
S U
J. O'
A
R
IN
I F
I C A
O
L
NE
E
ONN
LL
G R
NEE
I
S P
SOR FE ION
C
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
/1 0/
:0
1:
P M
SINGLE LINE DIAGRAM - NORMAL
POWER
EP5.1.2
HG VB01 FEB 2013
640-424
Radiology Consolidation
SCALE: NONE
54 SINGLE LINE DIAGRAM - NORMAL POWER
5.01 PROVIDE ALL NECESSARY COORDINATION AND PLANNING FOR
THE RELOCATION OF FEEDER. CONTRACTOR TO PROVIDE
TEMPORARY FEEDERS BEFORE CUTOVER. ADDITION OF
BREAKERS, LUGS, CABLE, CONDUIT OR TRENCHING MAY BE
REQUIRED IN ORDER TO SET UP TEMPORARY FEEDERS. FIELD
VERIFY EXISTING CONDUIT ROUTE, POWER SOURCES AND LOADS
AND PROVIDE WRITTEN PLAN FOR APPROVAL AND COMMENTS.
COORDINATE WITH VA RESIDENT ENGINEER AND FACILITIES
ENGINEER FOR TEMPORARY POWER CONNECTION, LOCATION OF
TEMPORARY GENERATORS AND ALL SHUTDOWNS. SEE SITE
PLAN SHEETS ES1.1.1 AND ES1.1.2 FOR MORE DETAILS.
5.02 PROVIDE TEMPORARY CABLING (800A) TO AND FROM ITEMS
INDICATED. SEE DRAWINGS ES1.1.1 & EP5.1.3.
5.03 PROVIDE TEMPORARY CABLING (400A) TO EATS1031A NORMAL
SOURCE FEEDER VIA DELTA-WYE TRANSFORMER. SEE
DRAWING EP5.1.1 FOR ADDITIONAL ONE LINE INFORMATION,
AND DRAWING ES1.1.1 FOR ESTIMATED LOCATIONS.
5.04 REMOVE EXISTING AND PROVIDE NEW CONDUCTORS FOR
ENTIRE FEEDER LENGTH (I.E. ONLY SMALL PORTION OF
EXISTING CONDUIT RUN REMAINS).
5.05 PROVIDE 4" CONDUIT SIZE FOR INDICATED FEEDER TO MATCH
EXISTING.
5.06 REMOVE EXISTING CONDUCTORS FROM SWBD NHS1001A TO
NEW PULL/SPLICE BOX LOCATION AT SOUTHEAST CORNER OF
BLDG 100. PULL IN NEW CONDUCTORS AND SPLICE.
1. RELOCATION OF ELECTRICAL FEEDERS OCCURS AT THE BEGINNING
OF THE PROJECT TO ALLOW FOR THE CONSTRUCTION OF THE NEW
RADIOLOGY ADDITION. DEMOLITION DRAWINGS TO BE USED AS
GUIDE. CONTRACTOR IS RESPONSIBLE FOR SCHEDULING AND
SEQUENCING ALL WORK IN ACCORDANCE WITH THE CONSTRUCTION
DOCUMENTS. CONTRACTORS ARE RESPONSIBLE FOR THE MEANS
AND METHODS OF PERFORMING THE REQUIRED DEMOLITION WORK.
CONTRACTOR SHALL SUBMIT DEMOLITION SEQUENCING PLAN AND
SCHEDULE TO THE VA RESIDENT ENGINEER FOR REVIEW.
2. COORDINATE ALL SHUTDOWNS WITH THE VA RESIDENT ENGINEER.
SEE DRAWING EP5.0.0 FOR ADDITIONAL INFORMATION.
1 ADDENDUM #1 9/18/2013
2 ADDENDUM #2 10/07/2013
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
KEY PLAN STAMP
ATTENTION:
ONLY WET SIGNED DOCUMENTS CONSTITUTE ADVANCE DESIGN CONSULTANTS, INC.
PROFESSIONAL WORK AND BECAUSE OTHER REPRODUCIBLE DOCUMENTS MAY BE EASILY
ALTERED WITHOUT THE CONSENT OF ADVANCE DESIGN CONSULTANTS, INC., THE WET
SIGNED DOCUMENTS MUST BE REFERRED TO FOR THE ORIGINAL AND CORRECT
INFORMATION. IF THERE ANY DIFFERENCES BETWEEN THE WET SIGNED DOCUMENTS AND
ANY O T H E R D O C U M E N T S , T H E W E T S I G N E D D O C U M E N T S S H A L L G O V E R N .
ADVANCE DESIGN CONSULTANTS, INC. IS NOT RESPONSIBLE FOR ANY MODIFICATIONS MADE
TO OUR DOCUMENTS BY ANYONE OTHER THAN AUTHORIZED REPRESENTATIVES OF
A D V A N C E D E S I G N C O N S U L T A N T S , I N C .
PRJ# 15-308-55
CONSTRUCTION DOCUMENTS
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
KEY PLAN STAMP
ATTENTION:
ONLY WET SIGNED DOCUMENTS CONSTITUTE ADVANCE DESIGN CONSULTANTS, INC.
PROFESSIONAL WORK AND BECAUSE OTHER REPRODUCIBLE DOCUMENTS MAY BE EASILY
ALTERED WITHOUT THE CONSENT OF ADVANCE DESIGN CONSULTANTS, INC., THE WET
SIGNED DOCUMENTS MUST BE REFERRED TO FOR THE ORIGINAL AND CORRECT
INFORMATION. IF THERE ANY DIFFERENCES BETWEEN THE WET SIGNED DOCUMENTS AND
ANY O T H E R D O C U M E N T S , T H E W E T S I G N E D D O C U M E N T S S H A L L G O V E R N .
ADVANCE DESIGN CONSULTANTS, INC. IS NOT RESPONSIBLE FOR ANY MODIFICATIONS MADE
TO OUR DOCUMENTS BY ANYONE OTHER THAN AUTHORIZED REPRESENTATIVES OF
A D V A N C E D E S I G N C O N S U L T A N T S , I N C .
PRJ# 15-308-55
CONSTRUCTION DOCUMENTS
(4) (4)
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
KEY PLAN STAMP
ATTENTION:
ONLY WET SIGNED DOCUMENTS CONSTITUTE ADVANCE DESIGN CONSULTANTS, INC.
PROFESSIONAL WORK AND BECAUSE OTHER REPRODUCIBLE DOCUMENTS MAY BE EASILY
ALTERED WITHOUT THE CONSENT OF ADVANCE DESIGN CONSULTANTS, INC., THE WET
SIGNED DOCUMENTS MUST BE REFERRED TO FOR THE ORIGINAL AND CORRECT
INFORMATION. IF THERE ANY DIFFERENCES BETWEEN THE WET SIGNED DOCUMENTS AND
ANY O T H E R D O C U M E N T S , T H E W E T S I G N E D D O C U M E N T S S H A L L G O V E R N .
ADVANCE DESIGN CONSULTANTS, INC. IS NOT RESPONSIBLE FOR ANY MODIFICATIONS MADE
TO OUR DOCUMENTS BY ANYONE OTHER THAN AUTHORIZED REPRESENTATIVES OF
A D V A N C E D E S I G N C O N S U L T A N T S , I N C .
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management
KEY PLAN STAMP
ATTENTION:
ONLY WET SIGNED DOCUMENTS CONSTITUTE ADVANCE DESIGN CONSULTANTS, INC.
PROFESSIONAL WORK AND BECAUSE OTHER REPRODUCIBLE DOCUMENTS MAY BE EASILY
ALTERED WITHOUT THE CONSENT OF ADVANCE DESIGN CONSULTANTS, INC., THE WET
SIGNED DOCUMENTS MUST BE REFERRED TO FOR THE ORIGINAL AND CORRECT
INFORMATION. IF THERE ANY DIFFERENCES BETWEEN THE WET SIGNED DOCUMENTS AND
ANY O T H E R D O C U M E N T S , T H E W E T S I G N E D D O C U M E N T S S H A L L G O V E R N .
ADVANCE DESIGN CONSULTANTS, INC. IS NOT RESPONSIBLE FOR ANY MODIFICATIONS MADE
TO OUR DOCUMENTS BY ANYONE OTHER THAN AUTHORIZED REPRESENTATIVES OF
A D V A N C E D E S I G N C O N S U L T A N T S , I N C .
25'-7 25__
(E)
(E)
(E)
(E)
BLDG 5
BLDG 100
HOSPITAL
BLDG 101
ADMINISTRATION
BLDG
102 DRC
LOADING
DOCK
AREA
CHILLER
YARD
MH
MH
MH
.7
MH
.3
M H
.2
MH
.5
C B
.9
C B
.9
C B
C B
.9
C B
.6
C B
.2
.0
.1
C B
.0
C B
.3
C B
.0
1.03
1.04
1.05
1.01
1.06
1.12 1.12
1.15
1.041.031.01
1.02
1.14
1.14
1.021.10
1.09
1.11
1.09
1.09
1.07
1.08
1.12
1.04
1.01
1.03 1.04 1.05
1.01 1.06
1.12
QLD01-6,81.16
1.17
1.12 1.18 1.19
1.12
1.07
1.03
1.18 1.19
MAIN ELECTRICAL SERVICE ROOM #1 (E)
(LOCATED AT FIRST FLOOR)
FOR ENLARGED PLAN
SEE DETAIL 54/EP4.1.2
NORMAL POWER PULLBOX
EMERGENCY POWER AND
CONTROL PULLBOX
EMERGENCY POWER AND CONTROL
PULLBOX
NORMAL POWER PULLBOX
EMERGENCY POWER AND CONTROL
PULLBOX
MAIN ELECTRICAL ROOM (E)
(LOCATED AT FIRST FLOOR)
CUSTOM ELECTRICAL MANHOLE
WITH DIVIDER FOR NORMAL AND
EMERGENCY POWER FEEDERS
1.13
MAIN ELECTRICAL SERVICE ROOM #2 (E)
(LOCATED AT FIRST FLOOR)
FOR ENLARGED PLAN, SEE DETAIL
51/EP4.1.2.
NORMAL SWBD NHS1001A (E)
EMERGENCY SWBD EHD1001A (E)
EMERGENCY EATS1031A (E)
EMERGENCY PARALLELING
DISTRIBUTION SWBD (E)
GENERATOR BLDG 103 (E)
BLDG 103
RADIOLOGY
ADDITION
EMERGENCY DISTR PANEL (E)
EMERGENCY PULLBOX (E)
ATS (E)
(E)
EMERGENCY SWBD EHD1002A (E)
1.01 800A-480V NORMAL POWER FEEDER (2-4"C) FROM BLDG 100
SERVICE #1 ROOM (NORMAL SWITCHBOARD "A") TO BLDG 103 ATS
NORMAL SIDE INPUT.
1.02 3000A-480V EMERGENCY POWER FEEDER (8-4", 2-4" SPARE) AND
CONTROL WIRING (1-2", 1-2" SPARE) FROM BLDG 103 EMERGENCY
SWITCHBOARD TO EMERGENCY DISTRIBUTION SWITCHBOARD AT
BLDG 100 SERVICE #2 ROOM.
1.03 3000A-480V EMERGENCY POWER FEEDER (8-4", 2-4" SPARE) AND
CONTROL WIRING (1-2", 1-2" SPARE) FROM BLDG 103 EMERGENCY
SWITCHBOARD TO EMERGENCY DISTRIBUTION SWITCHBOARD AT
BLDG 100 SERVICE #1 ROOM.
1.04 800A-480V EMERGENCY POWER FEEDER (2-4") AND CONTROL
WIRING (1-2") FROM BLDG 103 EMERGENCY SWITHBOARD TO
EMERGENCY DISTRIBUTION SWITCHBOARD AT BLDG 102 MAIN
ELEC. ROOM.
1.05 EMERGENCY POWER DUCT BANK APPROX. 28" HIGH AND 38"WIDE
OF CONCRETE CONSTRUCTION. (10) 4" CONDUITS, (3) 4"
CONDUITS (SPARE), (2) 2" CONDUITS CONTROLS, (1) 2" CONDUIT
(SPARE), AND (1) 1 1/4". APPROXIMATE DEPTH COVER OF 6 FEET.
1.06 NORMAL POWER DUCT BANK APPROX. 14" HIGH AND 18" WIDE OF
CONCRETE CONSTRUCTION, (2) 4" CONDUITS. APPROXIMATE
DEPTH COVER OF 3 FEET.
1.07 800A-480V EQUIPMENT EMERGENCY POWER FEEDER (2-4"C) FROM
BLDG 100 SERVICE #1 ROOM (EMERG SWBD EHD1001A) TO DIST
SWBD QHD00A AT BLDG 100 EXTERIOR EQUIPMENT YARD NEAR
LOADING DOCK.
1.08 MULTIPLE EXISTING NORMAL AND EMERGENCY POWER FEEDERS.
NEW BASEMENT LINK TUNNEL TO FUTURE ACC BLDG TO CLEAR
THIS FEEDER DUCTBANK.
1.09 FOR CONTINUATION - SEE BLDG 100 FLOOR PLAN SHEETS ES2.0.0
AND ES2.0.1.
1.10 EMERGENCY POWER DUCT BANK APPROX. 24"H x48"W OF
CONCRETE CONSTRUCTION. APPROXIMATE DEPTH OF COVER OF 6
FEET.
1.11 COORDINATE ENTRY POINT INTO BLDG 100 BASEMENT CEILING
SPACE WITH EXISTING CONDITIONS - ADJUST HEIGHT AND
SPACING OF CONDUITS AS NEEDED.
1.12 CLOSELY COORDINATE NEW DUCT BANK INSTALLATION WITH ALL
OTHER SITE UTILITIES IN THE AREA INCLUDING HIGH VOLTAGE,
FIRE ALARM AND SIGNAL SYSTEM DUCT BANKS. ADJUST ROUTING
AND DEPTH AS NEEDED.
1.13 EXCAVATE ENTIRE AREA WHERE NEW ELECTRICAL MANHOLE IS
LOCATED. PRIOR TO INSTALLATION OF NEW WORK. PROVIDE
TEMPORARY POWER FOR ALL DISTRUPTED FEEDERS. REMOVE
CONCRETE ENCASEMENT AROUND EXISTING CONDUITS.
EXPOSE SUFFICIENT LENGTH OF CONDUIT FOR
CONNECTION/EXTENSION TO NEW MANHOLE. ESTIMATED
MINIMUM MANHOLE SIZE IS 20'L x 8'W x20'D - CONTRACTOR TO
PROVIDE LARGER IF NEEDED. PROVIDE INTERNAL DIVIDER TO
CREATE TWO INDEPENDENT MANHOLE SECTIONS FOR NORMAL
POWER (EST. 8'L) AND EMERGENCY POWER (EST. 12'L). PROVIDE A
MINIMUM OF FOUR (4) TYPE KX1 LUMINAIRES. PROVIDE SUBMITTAL
OF MANHOLE AND ALL COMPONENTS AFTER EXCAVATION AND
REQUIREMENTS HAVE BEEN DETERMINED. MANHOLE TO HAVE
ALL SIMILAR COMPONENTS TO PRE-CAST MANHOLE - SEE
SPECIFICATION SECTION 26 05 41.
1.14 EXCAVATE ENTIRE AREA WHERE NEW ELECTRICAL PULLBOX IS
LOCATED. PRIOR TO INSTALLATION OF NEW WORK, PROVIDE
TEMPORARY POWER FOR ALL DISRUPTED FEEDERS. REMOVE
CONCRETE ENCASEMENT AROUND EXISTING CONDUITS TO
EXPOSE SUFFICIENT LENGTH OF CONDUIT FOR
CONNECTION/EXTENSION TO NEW PULLBOX.
1.15 EXTEND CONDUITS FROM NORMAL POWER PULLBOX UP SIDE OF
BLDG 103 TO APPROX. HEIGHT OF 18"-24", PENETRATE INTO BLDG
103, AND THEN INSTALL OVERHEAD TO ATS LOCATION AS SHOWN.
PROVIDE EITHER PULLBOXES OR CONDULETS AT INTERIOR AND
EXTERIOR OF BLDG 103 WHERE PENETRATING WALL. SEAL ALL
PENETRATIONS.
1.16 PROVIDE 2" CONDUIT WITH TWO (2) 20AMP-1POLE CIRCUITS FROM
PANEL QLD01 AT ELEC ROOM E0.4 IN BASEMENT OF NEW ADDITION.
CONNECT ONE CIRCUIT TO SUMP PUMP AND OTHER CIRCUIT TO
LIGHTS/RECEPTACLES IN BOTH SIDES OF MANHOLE.
1.17 INSTALL CONDUITS UNDERGROUND TO OUTSIDE EDGE OF BLDG
102 MAIN ELECTRICAL ROOM, EXTEND CONDUITS UP SIDE OF
BLDG 102 TO APPROX. HEIGHT OF 18"-24", PENETRATE INTO BLDG
102, AND THEN INSTALL OVERHEAD TO ATS LOCATION AS SHOWN.
PROVIDE EITHER PULLBOXES OR CONDULETS AT INTERIOR AND
EXTERIOR OF BLDG 102 WHERE PENETRATING WALL. SEAL ALL
PENETRATIONS.
1.18 800A-480V NORMAL POWER FEEDER (2-4"C) FROM BLDG 100
SERVICE #1 ROOM (NORM SWBD NHS1001A) TO MOTOR CONTROL
CENTER NMCC00A AT BLDG 100 EXTERIOR EQUIPMENT YARD
NEAR LOADING DOCK.
1.19 400A-480V NORMAL POWER FEEDER (1-4"C) FROM BLDG 100
SERVICE #1 ROOM (NORM SWBD NHS1001A) TO INFECTIONS
WASTE EQUIPMENT ROOM NEAR BLDG 100 BASEMENT LOADING
DOCK.
LA
D
6/30/2015
L
No. E15435
TE
STA
AC
T R
EXP
OF
E L E C
L
ER
TE
I
G R E
AP
S U
J. O'
A
R
IN
I F
I C A
O
L
NE
E
ONN
LL
G R
NEE
I
S P
SOR FE ION
C
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
Associate Architect:
TRUE NORTH
PROJ NORTH
Department of Veterans Affairs
PR
IN
TE
D
O N
/1 0/
:0
3:
P M
ENLARGED SITE PLAN - ELECTRICAL
FEEDERS - FINAL CONDITION
ES1.1.2
CO MV01 FEB 2013
640-424
Radiology Consolidation
SCALE: 1" = 30'-0"
54 ENLARGED SITE PLAN - ELECTRICAL FEEDERS - FINAL CONDITION
KEYNOTES
1. PROVIDE WATERPROOFING FOR ALL CONDUIT PENETRATIONS INTO
BUILDINGS, MANHOLES, PULLBOXES, ETC. REFER TO ARCHITECTURAL
SHEET AE5.3.1 FOR ADDITIONAL INFORMATION.
2. WHERE INTERCEPTING AND EXTENDING EXISTING FEEDERS, MATCH
EXISTING CONDUIT/CONDUCTOR SIZE AND QUANTITY.
3. COORDINATE ALL SHUTDOWNS WITH VA RESIDENT ENGINEER. SEE
DRAWING EP5.0.0 FOR ADDITIONAL INFORMATION.
1000KVA
12KV-480V
500KVA
12KV-480V
2000KVA
12KV-480V
2000KVA
12KV-480V
K K
2000KVA
12KV-480V
2000KVA
12KV-480V
K K
2000KVA
12KV-480V
2000KVA
12KV-480V
K
1500KVA
12KV-480V
K K
1500KVA
12KV-480V
1500KVA
12KV-480V
K K
1000KVA
12KV-480V
1000KVA
12KV-480V
K
500KVA
12KV-480V
K
500KVA
12KV-480V
K K
750KVA
12KV-480V
300KVA
12KV-208V
(E) SS-2 OUTDOOR ENCLOSURE
(SOUTH SUBSTATION LOCATED BY BLDG 6)
52 5252 52
F4 F5 F1 F3
NO
CITY OF PALO ALTO (FEEDER MB-22)
FROM CITY OF PALO ALTO
MAYBELL SUBSTATION (FEEDERS
MB-21 AND MB-22)
MB-21
FROM CITY OF PALO ALTO
HV-26
FROM CITY OF
PALO ALTO
NONCNCNO
(E) CITY OF PALO
ALTO SWITCH 1916X
CITY OF PALO ALTO (FEEDER MB-21)
CITY OF PALO ALTO FEEDER MB-21
(MAYBELL SUBSTATION)
FROM
SW 2553X
TO SS1
NCNCNCNC
(E) CITY OF PALO
ALTO SWITCH 1917X
F6 F2
(N) PMH-42
SS2S-F2
SS2S-F6
(N) PMH-41 (N) PMH-43 (N) PMH-40 (N) PMH-37 (N) PMH-36 (N) PMH-33
(N) PMH-39
COGEN BLDG
50 51
STB
50 51N
50 51
STB
50 51N
50 51
STB
50 51N
50 51
STB
50 51N
50 51
STB
50 51N
50 51
STB
50 51N
52 52
KWH
KQH
K KM2 M1
NC
INTERLOCK
STB DMMSTB DMM
TB
12KV-120V
MPT
A
L
P
PANEL
SS2
ATS SS2
12KV-120/240V
CPT
12KV-120/240V
CPT
12KV-120V
MPT
TB
KWH
KQH
(E) UTILITY
METERING
STRUCTURE
K
PEMPEMPEM
(N) PMH-34
SW4
ES5.1.3
SW3
ES5.1.3
(N) PMH-38
N.C.
N.C.N.C.N.C.N.C.N.C.N.C.
K
(E) BLDG 5
K
(E) BLDG 5
1500KVA
12KV-480V
300KVA
12KV-208V
(E) PMH-18 (E) PMH-19
K
(E) BLDG 102
600KVA
12KV-480V
(E) PMH-20 (E) PMH-21
(E) BLDG 101
SS2S-F4SS2S-F1SS2S-F5
SS2S-F3SS2S-F5
SS2S-F3
SS2S-F1
SS2S-F4
SS2S-F3 SS2S-F5
SS2S-F1 SS2S-F4 SS2S-F4SS2S-F1
SS2S-F2
SS2S-F6
SS2S-F2
SS2S-F6
SS2S-F2
SS2S-F6
SS2S-F2
SS2S-F6
SS2S-F2
SS2S-F6
SS2S-F2
SS2S-F6
SS2S-F2
SS2S-F6
SS2S-F2
SS2S-F6
SSPD
CPAU
SSPD
CPAU
(E) PMH-16
(E) ME BLDG (E) ME BLDG
(E) BLDG 7
ELECT ROOM
(E) SPINAL CORD
BLDG 7
(E) PMH-9
(E) BLDG 50/51
(E) PMH-17
SS2S-F2
(E) SPINAL CORD
BLDG 7
SS2S-F1
SS2S-F4
SS2S-F5 SS2S-F3
SS2S-F6 SS2S-F6
SS2S-F2
SS2S-F6
SS2S-F2
(E) PMH-16A
SS2S-F6
SS2S-F2
(E) PMH-16B
(E) DEFENDERS
LODGE
F2 F6 F2 F6
F2 F6 F2 F6 F2 F6 F2 F6
(E) ADMINISTRATIVE
BLDG-6
(E) ADMINISTRATIVE
BLDG-6
F2 F6 F2 F6
F3 F5 F3 F5 F1 F4 F3 F5 F1 F4 F1 F4
(E) UTILITY
METERING
STRUCTURE
SS2S-F2
BLDG 100
T1001A (E)
BLDG 100
T1001B (E)
BLDG 100
T1002A (E)
BLDG 100
T1002B (E)
SWBD
NHS1002B
(E)
SWBD
NHS1001A
(E)
EP5.1.5
SWBD
NHS1001B
(E)
EP5.1.2
SWBD
NHS1001A
(E)
EP5.1.2
K
VMU
(FUTURE)
1500KVA
12KV-480V
PS2
(FUTURE)
K
SS1N-F6
GENOMICS
(FUTURE)
K
ACC
(FUTURE)
K
ACC
(FUTURE)
K
SS1N-F6
LA
D
6/30/2015
L
No. E15435
TE
STA
AC
T R
EXP
OF
E L E C
L
ER
TE
I
G R E
AP
S U
J. O'
A
R
IN
I F
I C A
O
L
NE
E
ONN
LL
G R
NEE
I
S P
SOR FE ION
C
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
9/
/2
4:
:4
P
M SINGLE LINE DIAGRAM - SITE
NORMAL POWER SS-2 SUBSTATION
EP5.1.0
PO KG01 FEB 2013
640-424
Radiology Consolidation
SCALE: NONE
54 SINGLE LINE DIAGRAM - SITE NORMAL POWER SS-2 SUBSTATION
1. PARTIAL CAMPUS DISTRIBUTION SHOW FOR REFERENCE ONLY.
4-350KCM, 1#2G
3-350KCM, 1#2G
4-250KCM, 1#2G
3-250KCM, 1#2G
(NOTE: NOT ALL FEEDER TAGS MAY BE USED.)
FEEDER SCHEDULE
4#3/0, 1#6G
F0300N
F0300
F0250N
F0250
F0225N
F0225
F0200N
4#4/0, 1#4G
3#4/0, 1#4G
F0150N
F0200
F0175N
F0175
F0150
F0125N
F0125
4#1/0, 1#6G
3#3/0, 1#6G
4#2/0, 1#6G
3#2/0, 1#6G
3#1/0, 1#6G
4#1, 1#6G
3#1, 1#6G
CONDUIT
F0100N
F0100
F0070N
F0070
F0050N
F0050
TAG
4#2, 1#6G
3#2, 1#6G
4#4, 1#6G
3#4, 1#6G
4#6, 1#8G
CONDUCTORS
3#6, 1#8G
(2 SETS) 4-500KCM,
(2 SETS) 3-500KCM,
(2 SETS) 4-500KCM,
(2 SETS) 3-500KCM,
(3 SETS) 4-350KCM,
(3 SETS) 3-350KCM,
(3 SETS) 4-500KCM,
(3 SETS) 3-500KCM,
(4 SETS) 4-350KCM,
(4 SETS) 3-350KCM,
(4 SETS) 4-500KCM,
(4 SETS) 3-500KCM,
(5 SETS) 3-500KCM,
(5 SETS) 4-500KCM,
F1600N
F1600
F1400N
F1400
F1200N
F1200
F1000N
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#2/0G
F0800N
F1000
F0900N
F0900
F0700N
F0700
F0800
1#1/0G
1#2/0G
1#2/0G
1#2/0G
1#1/0G
1#1/0G
1#1/0G
(2 SETS) 4-250KCM,
(2 SETS) 3-250KCM,
(2 SETS) 4-350KCM,
(2 SETS) 3-350KCM,
CONDUIT
F0600N
F0600
F0500N
F0500
F0400N
F0400
TAG
1#1/0G
1#1/0G
1#1G
1#1G
3-500KCM, 1#2G
4-500KCM, 1#2G
CONDUCTORS
(5) 31/2"
(4) 31/2"
(4) 21/2"
(3) 31/2"
(3) 21/2"
31/2"
(2) 21/2"
(2) 21/2"
(2) 21/2"
(2) 31/2"
11/4"
11/4"
11/4"
11/2"
11/4"
11/2"
11/2"
11/2"
21/2"
21/2"
21/2"
31/2"
(2) 31/2"
F0040N
F0040
F0030N
F0030
4#8, 1#10G
3#8, 1#10G
4#10, 1#10G
3#10, 1#10G3/4"
3/4"
3/4"
3/4"
(NOTE: N = NEUTRAL CONDUCTOR INCLUDED)
F0020N
F0020
4#12, 1#12G
3#12, 1#12G3/4"
3/4"
1"
1"
2"
2"
2"
2"
2"
2"
3"
3"
3"
(2) 3"
(2) 3"
(2) 3"
(3) 3"
(3) 3"
(4) 3"
(4) 3"
(5) 3"
(4 SETS) 3-350KCM,
F1200 (E) 1#3/0G(4) 21/2"
(3 SETS) 4-400KCM,
F1000N (E) 1#2/0G(3) 3"
(2 SETS) 4-500KCM,
F0800N (E) 1#1/0G(2) 31/2"
(2 SETS) 3-500KCM,
F0800 (E) 1#1/0G
(2 SETS) 4-400KCM,
F0700N (E) 1#1/0G(2) 3"
(2 SETS) 4-350KCM,
F0600N (E) 1#1G
(2 SETS) 3-350KCM,
F0600 (E) 1#1G(2) 21/2"
(2 SETS) 4-250KCM,
F0500N (E) 1#2G(2) 21/2"
(2 SETS) 3-250KCM,
F0500 (E) 1#2G(2) 2"
F0400N (E) 4-500KCM, 1#2G31/2"
F0400 (E) 3-500KCM, 1#2G
3-350KCM, 1#4GF0300 (E) 21/2"
F0225N (E) 4#4/0, 1#4G21/2"
F0225 (E) 3#4/0, 1#4G
F0150N (E) 4#1/0, 1#6G11/2"
F0100 (E) 3#2, 1#8G11/4"
F0060N (E) 4#6, 1#10G11/4"
3#1 MV90 EPRHV-1 (E) (1) 4"
SWITCHBOARD NHS1001B (E)
4000A-277/480V-3PH-4W
CT'S
DMM
GFR
ST4000
GFR
800 ST
CT'S
F
N
E
PB
NBW1A
800A-3PH-4 W
SPACE SPACE
CT'S
ST 500 ST
CT'S
F
N
E
PB
CABLE
TAP
BOX
(E)
BUS RISER NBW6A (E)
600A-3PH-4 W
3 3
400 ST
CT'S
GFR GFR GFR
CT'S
GFR
ST
SWITCHBOARD NHS1001A (E)
4000A-277/480V-3PH-4W
CT'S
GFR
ST 500
CT'S
GFR
ST
CABLE TAP BOX (E)
RM E0.1
PANEL
NL01A
LHS
(E)
PANEL
NH01A
(E)
PANEL
NL01A
RHS
(E)
XFMR NTX01A (E)
45KV-480-120/208V-3PH-4W
ELEC RM E0.1
BASEMENT
ELEC RM E0.1
BASEMENT
ELEC RM E0.1
BASEMENT
100 AF
ELEC RM E0.1
BASEMENT
60 AF
ELEC RM E0.1
BASEMENT
PANEL
NL11A
LHS
(E)
PANEL
NH11A
(E)
XFMR NTX11A
112.5KVA-480-120/208V-3PH-4W
ELEC RM E1.1
1ST FLOOR
PANEL
NL11A
RHS
(E)
ELEC RM E1.1
1ST FLOOR
225 AF
ELEC RM E1.1
1ST FLOOR
225 AF
ELEC RM E1.1
1ST FLOOR
ELEC RM E1.1
1ST FLOOR
NBS01B (E)
NBS01A (E)
F0100 (E) F0175N (E)
F0060N (E)
NBS11B (E)
NBS11A (E)
F0225 (E)
F0225N (E)
F0400N (E)
F
N
E
PB
NBW2A
1000A-3PH-4 W
PANEL
NL02A
LHS
(E)
PANEL
NH02A
(E)
PANEL
NL02A
RHS
(E)
XFMR NTX02A (E)
150KV-480-120/208V-3PH-4W
ELEC RM E0.2
BASEMENT
ELEC RM E0.2
BASEMENT
ELEC RM E0.2
BASEMENT
300 AF
ELEC RM E0.2
BASEMENT
150 AF
ELEC RM E0.2
BASEMENT
PANEL
NL12A
LHS
(E)
PANEL
NH12A
(E)
XFMR NTX12A
112.5KVA-480-120/208V-3PH-4W
ELEC RM E1.2
1ST FLOOR
PANEL
NL12A
RHS
(E)
ELEC RM E1.2
1ST FLOOR
225 AF
ELEC RM E1.2
1ST FLOOR
60 AF
ELEC RM E1.2
1ST FLOOR
ELEC RM E1.2
1ST FLOOR
NBS02B (E)
NBS02A (E)
F0300 (E) F0600N (E)
F0150N (E)
NBS12B (E)
NBS12A (E)
F0225 (E)
F0060N (E)
F0400N (E)
400 ST
CT'S
GFR
800 ST
CT'S
GFR
MCC
NMCC00A
(E)
CHILLER
YARD
400AS
INFECTIOUS
WASTE
PROCESSOR
(LOADING DOCK)
F
E
PANEL
NH051A
(E)
F
E
PANEL
NH063A
(E)
F
E
E Q
U
IP
M
EN
T S
YS
TE
M R
O O
F
CT'S
DMM
GFR
ST4000
GFR
700 ST
CT'S
F
N
E
F
N
E
CT'S
ST 400 ST
CT'S
GFR GFRGFR
600 ST
CT'S
F
N
E
C R
IT
IC
A L
B R
A N
C H
C R
IT
IC
A L
B R
A N
C H
LI
F
E S
A F
E T
Y B
R A
N C
H
F
N
E
CT'S
ST
GFR
E Q
U
IP
M E
N T
S Y
S T
E M
S
F
E
CT'S
ST
GFR
EQ
U
IP
M
EN
T
SY
ST
EM
S
C O
O
LI
N G
T O
W
ER
Y
AR
D
F
E
CT'S
ST
GFR
E Q
U
IP
M E
N T
S Y
ST
EM
S R
O O
F
F
E
CT'S
ST
GFR
E Q
U
IP
M E
N T
S Y
ST
EM
S R
O O
F
F
N
E
PB
BUS RISER NBW4A (E)
400A-3PH-4W
CABLE TAP
BOX (E)
SATS
1001A
(E)
EP5.1.4
CATS
1001B
(E)
EP5.1.4
CATS
1001A
(E)
EP5.1.4
QATS
1001A
(E)
EP5.1.3
QATS
1001C
(E)
EP5.1.3
QATS
1001D
(E)
EP5.1.3
QATS
1001E
(E)
EP5.1.3
T1001A (E)
EP5.1.0
QATS
1001B
(E)
EP5.1.3
(2) SETS OF 4#250MCM WITH
1#2 PER SET IN 4" CONDUIT
(E)
TO
SECOND
FLOOR
TO
SECOND
FLOOR
#4 CU
CABLE TAP BOX (E)
RM E0.2
#2/0 CU
#3/0 CU
#2/0 CU
F0050 (E) 3#8, 1#10G3/4"
F0100N (E) 4#2, 1#8G11/4"
F0125N (E) 4#1, 1#6G11/2"
F0150 (E) 11/2" 3#1/0, 1#6G
F0175N (E) 4#2/0, 1#6G
4-350MCM, 1#4GF0300N (E)
4-400MCM, 1#2GF0350N (E)
2"
2"
3"
3"
3"
(2) 3"
(2) 3"
(E)
EATS
1031A (E)
EP5.1.1
T1001B (E)
EP5.1.0
33 33 3 3 33 3 33 33 3 33 3 F
N
F
F
TEMPORARY
SERVICE
TEMPORARY
SERVICE
5.01 5.015.015.04
5.05 5.05
5.06
5.05
5.06
5.06 5.065.04
5.03
5.02
LA
D
6/30/2015
L
No. E15435
TE
STA
AC
T R
EXP
OF
E L E C
L
ER
TE
I
G R E
AP
S U
J. O'
A
R
IN
I F
I C A
O
L
NE
E
ONN
LL
G R
NEE
I
S P
SOR FE ION
C
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
/1 0/
:0
1:
P M
SINGLE LINE DIAGRAM - NORMAL
POWER
EP5.1.2
HG VB01 FEB 2013
640-424
Radiology Consolidation
SCALE: NONE
54 SINGLE LINE DIAGRAM - NORMAL POWER
5.01 PROVIDE ALL NECESSARY COORDINATION AND PLANNING FOR
THE RELOCATION OF FEEDER. CONTRACTOR TO PROVIDE
TEMPORARY FEEDERS BEFORE CUTOVER. ADDITION OF
BREAKERS, LUGS, CABLE, CONDUIT OR TRENCHING MAY BE
REQUIRED IN ORDER TO SET UP TEMPORARY FEEDERS. FIELD
VERIFY EXISTING CONDUIT ROUTE, POWER SOURCES AND LOADS
AND PROVIDE WRITTEN PLAN FOR APPROVAL AND COMMENTS.
COORDINATE WITH VA RESIDENT ENGINEER AND FACILITIES
ENGINEER FOR TEMPORARY POWER CONNECTION, LOCATION OF
TEMPORARY GENERATORS AND ALL SHUTDOWNS. SEE SITE
PLAN SHEETS ES1.1.1 AND ES1.1.2 FOR MORE DETAILS.
5.02 PROVIDE TEMPORARY CABLING (800A) TO AND FROM ITEMS
INDICATED. SEE DRAWINGS ES1.1.1 & EP5.1.3.
5.03 PROVIDE TEMPORARY CABLING (400A) TO EATS1031A NORMAL
SOURCE FEEDER VIA DELTA-WYE TRANSFORMER. SEE
DRAWING EP5.1.1 FOR ADDITIONAL ONE LINE INFORMATION,
AND DRAWING ES1.1.1 FOR ESTIMATED LOCATIONS.
5.04 REMOVE EXISTING AND PROVIDE NEW CONDUCTORS FOR
ENTIRE FEEDER LENGTH (I.E. ONLY SMALL PORTION OF
EXISTING CONDUIT RUN REMAINS).
5.05 PROVIDE 4" CONDUIT SIZE FOR INDICATED FEEDER TO MATCH
EXISTING.
5.06 REMOVE EXISTING CONDUCTORS FROM SWBD NHS1001A TO
NEW PULL/SPLICE BOX LOCATION AT SOUTHEAST CORNER OF
BLDG 100. PULL IN NEW CONDUCTORS AND SPLICE.
1. RELOCATION OF ELECTRICAL FEEDERS OCCURS AT THE BEGINNING
OF THE PROJECT TO ALLOW FOR THE CONSTRUCTION OF THE NEW
RADIOLOGY ADDITION. DEMOLITION DRAWINGS TO BE USED AS
GUIDE. CONTRACTOR IS RESPONSIBLE FOR SCHEDULING AND
SEQUENCING ALL WORK IN ACCORDANCE WITH THE CONSTRUCTION
DOCUMENTS. CONTRACTORS ARE RESPONSIBLE FOR THE MEANS
AND METHODS OF PERFORMING THE REQUIRED DEMOLITION WORK.
CONTRACTOR SHALL SUBMIT DEMOLITION SEQUENCING PLAN AND
SCHEDULE TO THE VA RESIDENT ENGINEER FOR REVIEW.
2. COORDINATE ALL SHUTDOWNS WITH THE VA RESIDENT ENGINEER.
SEE DRAWING EP5.0.0 FOR ADDITIONAL INFORMATION.
SCALE: SCALE:
SCALE:
VFD VFD
VFDVFD
(4 SETS) 3-350KCM,
F1200 (E) 1#3/0G(4) 21/2"
(3 SETS) 4-400KCM,
F1000N (E) 1#2/0G(3) 3"
(2 SETS) 4-500KCM,
F0800N (E) 1#1/0G(2) 31/2"
(2 SETS) 3-500KCM,
F0800 (E) 1#1/0G
(2 SETS) 4-400KCM,
F0700N (E) 1#1/0G(2) 3"
(2 SETS) 4-350KCM,
F0600N (E) 1#1G
(2 SETS) 3-350KCM,
F0600 (E) 1#1G(2) 21/2"
(2 SETS) 4-250KCM,
F0500N (E) 1#2G(2) 21/2"
(2 SETS) 3-250KCM,
F0500 (E) 1#2G(2) 2"
F0400N (E) 4-500KCM, 1#2G31/2"
F0400 (E) 3-500KCM, 1#2G
3-350KCM, 1#4GF0300 (E) 21/2"
F0225N (E) 4#4/0, 1#4G21/2"
F0225 (E) 3#4/0, 1#4G
F0150N (E) 4#1/0, 1#6G11/2"
F0100 (E) 3#2, 1#8G11/4"
F0060N (E) 4#6, 1#10G11/4"
3#1 MV90 EPRHV-1 (E) (1) 4"
F0050 (E) 3#8, 1#10G3/4"
F0100N (E) 4#2, 1#8G11/4"
F0125N (E) 4#1, 1#6G11/2"
F0150 (E) 11/2" 3#1/0, 1#6G
F0175N (E) 4#2/0, 1#6G
4-350MCM, 1#4GF0300N (E)
4-400MCM, 1#2GF0350N (E)
2"
2"
3"
3"
3"
(2) 3"
(2) 3"
PARTIAL SWBD A (E)
2000A-277/480V-3PH-4W
NEMA 3R
ELECT EQMT YARD IN
FRONT OF ELECT RM 114
M/B
TO 1500KVA XFMR A (E)
12.47KV-277/480V-3PH-4W
(R)
SF-1 (E)
(ROOF)
(R
(R
40HP
CHILLER 3
CONTROL
PANEL
(R)
(E)
(E
(E
(R
XFMR C (R)
15KVA
480-120/208V-3PH-4W
PANEL
L
(R)
(R
CHILLER
YARD
LIGHTS &
POWER
NORTH CHILLER YARD
(R) (R)
(R
(R
10HP
CHWP-1
10HP
CHWP-2
CONTROL
PANEL
(R)
SPACE
DISTR PANEL M1 (R)
NORTH CHILLER YARD
(R
(R
) PANEL
(R
CONTROL
PANEL
CHILLER 1
(R)
PULLBOX (R) (R
15HP
(R)
(R
(R)
(R)(R)
PARTIAL MCC A (E)
600A-480V-3PH-3W
ELECT RM 114
WEST CHILLER YARD
(E)
(E
(E)
TO
ACC 1
(E)
(E
FIRE
PUMP
CONTROL
PANEL (R)
30HP
(R)
BLDG 5 NORTH
FIRE PUMP YARD
BLDG 5
NORTH
FIRE PUMP
YARD
FIRE
PUMP (R)
E N
TRANSFER SWITCH (E)
800A
ELECT RM 114
PARTIAL DISTR PANEL EM-2 (E)
800A-120/208V-3PH-4W
ELECT RM 114
EXISTING FEEDERS REFER
TO LRSU PACKAGE
(R
(R
(R
(E
(E
(E
PARTIAL SWBD A (E)
2000A-277/480V-3PH-4W
OUTDOOR NEMA 3R
ELECT EQMT YARD IN
FRONT OF ELECT RM 114
M/B
TO 1500KVA XFMR A (E)
12.47KV-277/480V-3PH-4W
PARTIAL MCC A (E)
600A-209V-3PH-3W
ELECT RM 114
(E)
(E
TO
ACC 1
(E)
(E
FIRE
PUMP
CONTROL
PANEL
30HP
BLDG 5 NORTH
FIRE PUMP YARD
BLDG 5
NORTH WEST
FIRE PUMP
YARD
FIRE
PUMP
E N
TRANSFER SWITCH (E)
800A
ELECT RM 114
PARTIAL DISTR PANEL EM-2 (E)
800A-120/208V-3PH-4W
ELECT RM 114
EXISTING FEEDERS REFER
TO LRSU PACKAGE
(E
(E
P/B
XFMR
(E)
RF-1 (E)
(ROOF)
50HP
(E)
(E
(E
(E)
SPACESPACESPACESPACE
(E)(E)
SF-1
AT ROOF
40HP(E)
RF-1
AT ROOF
50HP(E)
(E) (E)
E N
ATS (E)
ELECT RM 152
600KVA
XFMR
(E)
EP5.1.0
PART NORMAL MAIN DISTRIBUTION PANEL MDP (E)
1200A-277/480V-3PH-4W
ELECT RM 152
(E) (E)
EHS
1031A
(E)
EP5.1.1 (E)(E)(E)(E)
PANEL HP
(E)
PANEL HMP
(E)
MRI (E) XFMR TR
112.5KVA (E)
CHILLER
CH-1 (E)
CT (E)
(E) (E) (E) (E) (E) (E)
(E)
PART EMERGENCY DISTRIBUTION PANEL EDP (E)
600A-277/480V-3PH-4W
ELECT RM 152
(E)(E)(E)(E)(E)
PANEL EHP
(E)
PANEL EMP
(E)
XFMR TER
112.5KVA (E)
CRU-1
20HP (E)
(E) (E) (E) (E)
CHILLER
CH-2 (E)
(E)
(E)
(E)
(E)
PANEL
P/B
XFMR
(E)(E)
PULL/SPLICE BOX AT EXTERIOR
S/B
M/B
M/B
S/B
F0
F0
F0
F0
F0
F0
F0
0N
F0
F0
F0
F0
(2 ) 4
3#
0K
C M
, 1 #1
/0 G
SPARE
F0
F0
F0
F0
TEMPORARY SERVICE
3-500KCM, 1#2GF0350
4-500KCM, 1#2GF0350N
4-350KCM, 1#2G
3-350KCM, 1#2G
4-250KCM, 1#2G
3-250KCM, 1#2G
(NOTE: NOT ALL FEEDER TAGS MAY BE USED.)
FEEDER SCHEDULE
4#3/0, 1#6G
F0300N
F0300
F0250N
F0250
F0225N
F0225
F0200N
4#4/0, 1#4G
3#4/0, 1#4G
F0150N
F0200
F0175N
F0175
F0150
F0125N
F0125
4#1/0, 1#6G
3#3/0, 1#6G
4#2/0, 1#6G
3#2/0, 1#6G
3#1/0, 1#6G
4#1, 1#6G
3#1, 1#6G
CONDUIT
F0100N
F0100
F0070N
F0070
F0050N
F0050
TAG
4#2, 1#6G
3#2, 1#6G
4#4, 1#6G
3#4, 1#6G
4#6, 1#8G
CONDUCTORS
3#6, 1#8G
(2 SETS) 4-500KCM,
(2 SETS) 3-500KCM,
(2 SETS) 4-500KCM,
(2 SETS) 3-500KCM,
(3 SETS) 4-350KCM,
(3 SETS) 3-350KCM,
(3 SETS) 4-500KCM,
(3 SETS) 3-500KCM,
(4 SETS) 4-350KCM,
(4 SETS) 3-350KCM,
(4 SETS) 4-500KCM,
(4 SETS) 3-500KCM,
(5 SETS) 3-500KCM,
(5 SETS) 4-500KCM,
F1600N
F1600
F1400N
F1400
F1200N
F1200
F1000N
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#2/0G
F0800N
F1000
F0900N
F0900
F0700N
F0700
F0800
1#1/0G
1#2/0G
1#2/0G
1#2/0G
1#1/0G
1#1/0G
1#1/0G
(2 SETS) 4-250KCM,
(2 SETS) 3-250KCM,
(2 SETS) 4-350KCM,
(2 SETS) 3-350KCM,
CONDUIT
F0600N
F0600
F0500N
F0500
F0400N
F0400
TAG
1#1/0G
1#1/0G
1#1G
1#1G
3-500KCM, 1#2G
4-500KCM, 1#2G
CONDUCTORS
(5) 31/2"
(4) 31/2"
(4) 21/2"
(3) 31/2"
(3) 21/2"
31/2"
(2) 21/2"
(2) 21/2"
(2) 21/2"
(2) 31/2"
11/4"
11/4"
11/4"
11/2"
11/4"
11/2"
11/2"
11/2"
21/2"
21/2"
21/2"
31/2"
(2) 31/2"
F0040N
F0040
F0030N
F0030
4#8, 1#10G
3#8, 1#10G
4#10, 1#10G
3#10, 1#10G3/4"
3/4"
3/4"
3/4"
(NOTE: N = NEUTRAL CONDUCTOR INCLUDED)
F0020N
F0020
4#12, 1#12G
3#12, 1#12G3/4"
3/4"
1"
1"
2"
2"
2"
2"
2"
2"
3"
3"
3"
(2) 3"
(2) 3"
(2) 3"
(3) 3"
(3) 3"
(4) 3"
(4) 3"
(5) 3"
BUILDING 5 PART SINGLE LINE DIAGRAM - EXISTING - DEMO
NO SCALE
BUILDING 5 PART SINGLE LINE DIAGRAM - FINAL CONDITIONS
NO SCALE
BUILDING 102 - PART NON-ESSENTIAL POWER
ESSENTIAL POWER
BUILDING 102 EXISTING SINGLE LINE DIAGRAM
NO SCALE
PANEL: L SYSTEM: NORMAL LOCATION: BLDG 5, SOUTH CHILLER YARD
BUS SIZE: 50A VOLTAGE: 120/208V PHASE: 3 WIRE: 4+G MOUNTING: SURFACE AIC RATING: 22 KAIC
MAIN BREAKER OR LUGS: 50A M/B FEEDER INFO: REFER TO SINGLE LINE DIAGRAM
CKT
NO.
DESCRIPTION
Load in Volt-Amperes Circuit
LOAD TYPES
Circuit Load in Volt-Amperes
DESCRIPTION
CKT
NO.
per Phase Breaker Breaker per Phase
A B C Amp Pole Lts Rec Lts Rec Amp Pole A B C
1 50 CHILLER YARD LIGHTS 105 20 1 X 20 1 SPARE 2
3 50 CHILLER YARD REC 540 20 1 3 20 1 0 SPARE 4
5 SPARE 20 1 20 1 0 SPARE 6
7 SPARE 20 1 20 1 SPARE 8
9 SPARE 20 1 20 1 SPARE 10
11 SPARE 20 1 20 1 SPARE 12
13 SPARE 20 1 20 1 SPARE 14
15 SPARE 20 1 20 1 SPARE 16
17 SPARE 20 1 20 1 SPARE 18
19 SPACE SPACE 20
21 SPACE SPACE 22
23 SPACE SPACE 24
TOTAL 3 PHASE CONNECTED LOAD (VA): 645 TOTAL CONNECTED LOAD PER PHASE (VA): 105 540 0
TOTAL 3 PHASE CONNECTED LOAD (AMPS): 1.8 TOTAL CONNECTED LOAD PER PHASE (AMPS): 0.4 1.9 0.0
DEMAND LOAD CALCULATION:
LIGHTING LOADS 1.00 x 0.00 = 0.00 REMARKS:
RECEPTACLES (FIRST 10000VA) 1.00 x 0.00 = 0.00
RECEPTACLES (OVER 10000VA) 0.50 x 0.00 = 0.00
OTHER LOADS 1.00 x 0.00 = 0.00
TOTAL N.E.C. DEMAND LOAD (VA): 0.00 JOB NAME: VA PALO ALTO - RADIOLOGY CONSOLIDATION
TOTAL N.E.C. DEMAND LOAD (AMP): 0.00 JOB NUMBER: C&W #10061 DATE: 05-18-12 BY: PO
600/3
CHILLER 3
CONTROL
PANEL
XFMR C
15KVA
480-120/208V-3PH-4W
PANEL
L
CHILLER
YARD
LIGHTS &
POWER
SOUTH CHILLER YARD
15HP
CHWP-4
15HP
CHWP-5
SPACE
DISTR SWBD M1
600A-480V-3PH-3W
SOUTH CHILLER YARD
CHILLER 1
CONTROL
PANEL
15HP
60/3
NORTH WEST CHILLER YARD
SPACE SPACE SPACE
CHWP-6
400/3
5.061
5.07
5.07
5.07
5.07
5.01
5.03
5.02
5.015.01
5.04
5.02
5.015.01
5.01
5.01
5.01 5.01
5.07
5.07
5.05
LA
D
6/30/2015
L
No. E15435
TE
STA
AC
T R
EXP
OF
E L E C
L
ER
TE
I
G R E
AP
S U
J. O'
A
R
IN
I F
I C A
O
L
NE
E
ONN
LL
G R
NEE
I
S P
SOR FE ION
C
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
/1 6/
:1
8:
A M
SINGLE LINE DIAGRAM -
BUILDING 5 & 102
EP5.1.6
HG VB01 FEB 2013
640-424
Radiology Consolidation
5.01 INTERCEPT CONDUIT AND WIRE AT CRAWL SPACE AND EXTEND
TO NEW EQUIPMENT LOCATION. SEE SHEET EP4.4.4.
COORDINATE WITH CIVIL DRAWINGS.
5.02 COORDINATE WITH MECHANICAL FOR PHASING OF WORK.
5.03 COORDINATE WITH ARCHITECT AND CIVIL ENGINEER FOR FINAL
EQUIPMENT LOCATION.
5.04 PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE. FRAME AND
TYPE TO MATCH EXISTING.
5.05 COORDINATE WITH RESIDENT ENGINEER POINT OF CONNECTION
FOR TEMPORARY GENERATOR. SEE OTHER DRAWINGS
FOR ADDITIONAL INFORMATION.
5.06 FOR REFERENCE ONLY: EIXSITNG DISTRIBUTION SWITCHBOARD A
IS SIEMENS TYPE SB SWITCHBOARD RATED 2000AMPS WITH HLD
SERIES BREAKERS.
5.07 ALL EQUIPMENT AT EXTERIOR SHALL BE NEMA 3R RATED.
1. COORDINATE ALL SHUTDOWNS WITH VA RESIDENT ENGINEER. SEE
DRAWING EP5.0.0 FOR ADDITIONAL INFORMATION.
1 ADDENDUM #1 9/18/2013
4-350KCM, 1#2G
3-350KCM, 1#2G
4-250KCM, 1#2G
3-250KCM, 1#2G
(NOTE: NOT ALL FEEDER TAGS MAY BE USED.)
FEEDER SCHEDULE
4#3/0, 1#6G
F0300N
F0300
F0250N
F0250
F0225N
F0225
F0200N
4#4/0, 1#4G
3#4/0, 1#4G
F0150N
F0200
F0175N
F0175
F0150
F0125N
F0125
4#1/0, 1#6G
3#3/0, 1#6G
4#2/0, 1#6G
3#2/0, 1#6G
3#1/0, 1#6G
4#1, 1#6G
3#1, 1#6G
CONDUIT
F0100N
F0100
F0070N
F0070
F0050N
F0050
TAG
4#2, 1#6G
3#2, 1#6G
4#4, 1#6G
3#4, 1#6G
4#6, 1#8G
CONDUCTORS
3#6, 1#8G
(2 SETS) 4-500KCM,
(2 SETS) 3-500KCM,
(2 SETS) 4-500KCM,
(2 SETS) 3-500KCM,
(3 SETS) 4-350KCM,
(3 SETS) 3-350KCM,
(3 SETS) 4-500KCM,
(3 SETS) 3-500KCM,
(4 SETS) 4-350KCM,
(4 SETS) 3-350KCM,
(4 SETS) 4-500KCM,
(4 SETS) 3-500KCM,
(5 SETS) 3-500KCM,
(5 SETS) 4-500KCM,
F1600N
F1600
F1400N
F1400
F1200N
F1200
F1000N
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#4/0G
1#2/0G
F0800N
F1000
F0900N
F0900
F0700N
F0700
F0800
1#1/0G
1#2/0G
1#2/0G
1#2/0G
1#1/0G
1#1/0G
1#1/0G
(2 SETS) 4-250KCM,
(2 SETS) 3-250KCM,
(2 SETS) 4-350KCM,
(2 SETS) 3-350KCM,
CONDUIT
F0600N
F0600
F0500N
F0500
F0400N
F0400
TAG
1#1/0G
1#1/0G
1#1G
1#1G
3-500KCM, 1#2G
4-500KCM, 1#2G
CONDUCTORS
(5) 31/2"
(4) 31/2"
(4) 21/2"
(3) 31/2"
(3) 21/2"
31/2"
(2) 21/2"
(2) 21/2"
(2) 21/2"
(2) 31/2"
11/4"
11/4"
11/4"
11/2"
11/4"
11/2"
11/2"
11/2"
21/2"
21/2"
31/2"
(2) 31/2"
F0040N
F0040
F0030N
F0030
4#8, 1#10G
3#8, 1#10G
4#10, 1#10G
3#10, 1#10G3/4"
3/4"
3/4"
3/4"
(NOTE: N = NEUTRAL CONDUCTOR INCLUDED)
F0020N
F0020
4#12, 1#12G
3#12, 1#12G3/4"
3/4"
1"
1"
2"
2"
2"
2"
2"
2"
3"
3"
3"
(2) 3"
(2) 3"
(2) 3"
(3) 3"
(3) 3"
(4) 3"
(4) 3"
(5) 3"
(4 SETS) 3-350KCM,
F1200 (E) 1#3/0G(4) 21/2"
(3 SETS) 4-400KCM,
F1000N (E) 1#2/0G(3) 3"
(2 SETS) 4-500KCM,
F0800N (E) 1#1/0G(2) 31/2"
(2 SETS) 3-500KCM,
F0800 (E) 1#1/0G
(2 SETS) 4-400KCM,
F0700N (E) 1#1/0G(2) 3"
(2 SETS) 4-350KCM,
F0600N (E) 1#1G
(2 SETS) 3-350KCM,
F0600 (E) 1#1G(2) 21/2"
(2 SETS) 4-250KCM,
F0500N (E) 1#2G(2) 21/2"
(2 SETS) 3-250KCM,
F0500 (E) 1#2G(2) 2"
F0400N (E) 4-500KCM, 1#2G31/2"
F0400 (E) 3-500KCM, 1#2G
3-350KCM, 1#4GF0300 (E) 21/2"
F0225N (E) 4#4/0, 1#4G21/2"
F0225 (E) 3#4/0, 1#4G
F0150N (E) 4#1/0, 1#6G11/2"
F0100 (E) 3#2, 1#8G11/4"
F0060N (E) 4#6, 1#10G11/4"
3#1 MV90 EPRHV-1 (E) (1) 4"
SWITCHBOARD NHS1001B (E)
4000A-277/480V-3PH-4W
CT'S
DMM
GFR
ST4000
GFR
800 ST
CT'S
F0
0N (E
PB
NBW1A
800A-3PH-4 W
CT'S
ST 500 ST
CT'S
F0
0N (E
PB
CABLE
TAP
BOX
(E)
BUS RISER NBW6A (E)
600A-3PH-4 W
400 ST
CT'S
GFR GFR GFR
CT'S
GFR
ST
SWITCHBOARD NHS1001A (E)
4000A-277/480V-3PH-4W
CT'S
GFR
ST 500
CT'S
GFR
ST
CABLE TAP BOX (E)
RM E0.1
PANEL
NL01A
LHS
(E)
PANEL
NH01A
(E)
PANEL
NL01A
RHS
(E)
XFMR NTX01A (E)
45KV-480-120/208V-3PH-4W
ELEC RM E0.1
BASEMENT
ELEC RM E0.1
BASEMENT
ELEC RM E0.1
BASEMENT
100 AF
ELEC RM E0.1
BASEMENT
60 AF
ELEC RM E0.1
BASEMENT
PANEL
NL11A
LHS
(E)
PANEL
NH11A
(E)
XFMR NTX11A
112.5KVA-480-120/208V-3PH-4W
ELEC RM E1.1
1ST FLOOR
PANEL
NL11A
RHS
(E)
ELEC RM E1.1
1ST FLOOR
225 AF
ELEC RM E1.1
1ST FLOOR
225 AF
ELEC RM E1.1
1ST FLOOR
ELEC RM E1.1
1ST FLOOR
NBS01B (E)
NBS01A (E)
F0100 (E) F0175N (E)
F0060N (E)
NBS11B (E)
NBS11A (E)
F0225 (E)
F0225N (E)
F0400N (E)
F1
0N (E
PB
NBW2A
1000A-3PH-4 W
PANEL
NL02A
LHS
(E)
PANEL
NH02A
(E)
PANEL
NL02A
RHS
(E)
XFMR NTX02A (E)
150KV-480-120/208V-3PH-4W
ELEC RM E0.2
BASEMENT
ELEC RM E0.2
BASEMENT
ELEC RM E0.2
BASEMENT
300 AF
ELEC RM E0.2
BASEMENT
150 AF
ELEC RM E0.2
BASEMENT
PANEL
NL12A
LHS
(E)
PANEL
NH12A
(E)
XFMR NTX12A
112.5KVA-480-120/208V-3PH-4W
ELEC RM E1.2
1ST FLOOR
PANEL
NL12A
RHS
(E)
ELEC RM E1.2
1ST FLOOR
225 AF
ELEC RM E1.2
1ST FLOOR
60 AF
ELEC RM E1.2
1ST FLOOR
ELEC RM E1.2
1ST FLOOR
NBS02B (E)
NBS02A (E)
F0300 (E) F0600N (E)
F0150N (E)
NBS12B (E)
NBS12A (E)
F0225 (E)
F0060N (E)
F0400N (E)
400 ST
CT'S
GFR
800 ST
CT'S
GFR
MCC
NMCC00A
(E)
CHILLER
YARD
400AS
INFECTIOUS
WASTE
PROCESSOR
(LOADING DOCK)
F0
(E
PANEL
NH051A
(E)
F0
(E
PANEL
NH063A
(E)
F0
(E
EQ
U
IP
M
EN
T
SY
S
TE
M
R O
O F
CT'S
DMM
GFR
ST4000
GFR
700 ST
CT'S
F0
0N (E
F0
5N (E
CT'S
ST 400 ST
CT'S
GFR GFRGFR
600 ST
CT'S
F0
0N (E
C R
IT
IC
AL
B
R A
N C
H
C R
IT
IC
AL
B
R A
N C
H
LI
FE
S
AF
ET
Y
B R
A N
C H
F0
0N (E
CT'S
ST
GFR
EQ
U
IP
M
E N
T S
YS
TE
M S
F0
(E
CT'S
ST
GFR
EQ
U
IP
M
E N
T S
YS
TE
M S
C O
O
LI
N G
T O
W
ER
Y
AR
D
F0
(E
CT'S
ST
GFR
EQ
U
IP
M
E N
T S
YS
TE
M S
R O
O F
F0
(E
CT'S
ST
GFR
EQ
U
IP
M
E N
T S
YS
TE
M S
R O
O F
F0
0N (E
PB
BUS RISER NBW4A (E)
400A-3PH-4W
CABLE TAP
BOX (E)
SATS
1001A
(E)
EP5.1.9
CATS
1001B
(E)
EP5.1.9
CATS
1001A
(E)
EP5.1.9
QATS
1001A
(E)
EP5.1.7
QATS
1001C
(E)
EP5.1.7
QATS
1001D
(E)
EP5.1.7
QATS
1001E
(E)
EP5.1.7
T1001A (E)
EP5.1.0
QATS
1001B
(E)
EP5.1.7
TO
SECOND
FLOOR
#4 CU
CABLE TAP BOX (E)
RM E0.2
#3/0 CU
#2/0 CU
F0050 (E) 3#8, 1#10G3/4"
F0100N (E) 4#2, 1#8G11/4"
F0125N (E) 4#1, 1#6G11/2"
F0150 (E) 11/2" 3#1/0, 1#6G
F0175N (E) 4#2/0, 1#6G
4-350MCM, 1#4GF0300N (E)
4-400MCM, 1#2GF0350N (E)
2"
2"
3"
3"
3"
(2) 3"
(2) 3"
(E)
EATS
1031A (E)
EP5.1.1
T1001B (E)
EP5.1.0
33 33 3 3 33 3 33 33 3 33 3
F0
0N (E
F0
(E
F0
(E
#2/0 CU
F0
0N
F0
0N
QATS
EP5.1.7
1001G (N)
CATS
EP5.1.9
1001D (N)
TO
SECOND
FLOOR
XFMR NTX11B (N)
75kVA
480-208Y/120V-3PH-4W
ELEC RM E1.2
1ST FLOOR
125 A
1ST FLOOR
NBS12C (N)
F0125 F0100N
#2 CU
200 A
F0
0N
PANEL
(E)
CL01A2
NL01B
(N)
F0
0N
PANEL
(E)
CL11A3
NL11B
(N)
F0100N
3"
CT'S
GFR
ST
CT'S
GFR
ST
TO
SECOND
FLOOR
TO
SECOND
FLOOR
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
SHEET NOTES
KEYNOTES
Department of Veterans Affairs
PR
IN
TE
D
O N
640-424
CONSTRUCTION DOCUMENTS
9/
/2
:5 9:
A
M
SINGLE LINE DIAGRAM - NORMAL
POWER
EP5.1.10
JHT AJV18 SEPTEMBER
Radiology Consolidation Electrical EM Power Revisions
SCALE: NONE
1 SINGLE LINE DIAGRAM - NORMAL POWER
PROVIDE NEW SQUARE D MEF36800LSG CIRCUIT BREAKER, 800A,
600V, 65KA, 100%, WITH ADJUSTABLE LONG-TIME, SHORT-TIME,
INSTANTANEOUS, AND GROUND-FAULT SETTINGS. INSTALL IN
EXISTING SPACE. REFER TO PHOTOS 2 & 3 ON EP6.1.11.
UPDATE PANELBOARD NAMEPLATES AND ALL DOWNSTREAM
JUNCTION BOXES AND WIRING DEVICES TO INDICATE NEW
PANELBOARD NAME.
PROVIDE NEW BUS PLUG AND INSTALL IN EXISTING SPACE IN
EXISTING BUS DUCT. REFER TO PHOTO 5 ON DP6.1.11.
E504
E5XX
E504 E504
E505
E505 E505
E506
E506
A. DARK LINEWEIGHT INDICATES NEW WORK. DIAGONAL CROSS-
HATCHING INDICATES DEMOLITION WORK.
B. PROVIDE ADDITIONAL PULL BOXES AND SPLICES AS REQUIRED
WHEN INTERCEPTING EXISTING CONDUITS/FEEDERS.
C. REFER TO ES0.1.0 FOR SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
D. UPDATE THE ELECTRICAL SYSTEM PROTECTIVE DEVICE STUDY
PERFORMED FOR THE RADIOLOGY ADDITION PROJECT TO REFLECT
THE CHANGES INDICIATED ON THESE SINGLE LINE DIAGRAMS. REFER
TO SPECIFICATION SECTION 260571 FOR ALL REQUIREMENTS. SUBMIT
THE REVISED REPORT TO THE OWNER, CONTRACTOR, AND
ARCHITECT FOR REVIEW AND COMMENT.
E. SET ALL FIELD-ADJUSTABLE CIRCUIT BREAKER SETTINGS PER THE
UPDATED SHORT-CIRCUIT/ARC-FLASH/COORDINATION STUDY.
F. COORDINATE ALL REQUIRED SHUTDOWNS WITH THE OWNER. DO NOT
PROCEED WITHOUT WRITTEN APPROVAL. PROVIDE THE OWNER A
MINIMUM OF 14 DAYS NOTICE.
G. REFER TO SPEC SECTION 262416 FOR REQUIREMENTS FOR NEW
PANELBOARDS AND CIRCUIT BREAKERS.
H. REFER TO SPEC SECTION 262200 FOR REQUIREMENTS FOR NEW
TRANSFORMER.
I. REFER TO SPEC SECTION 265111 FOR REQUIREMENTS FOR NEW BUS
PLUG.
J. REFER TO SPEC SECTION 260521 FOR REQUIREMENTS FOR NEW
LOW VOLTAGE POWER CONDUCTORS.
ASI-022.1R 9/18/2017