36C26119B0017-0003003.pdf
PDF 136 KB Posted
- Solicitation number
- 36C26119B0017
About this file
36C26119B0017 0003 26 09 23 Lighting Control.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26119B0017-0005000.docx | DOCX document | |
| 36C26119B0017-0004034.pdf | ||
| 36C26119B0017-0004035.pdf | ||
| 36C26119B0017-0004033.docx | DOCX document | |
| 36C26119B0017-0003002.pdf | ||
| 36C26119B0017-0003001.pdf | ||
| 36C26119B0017-0003006.pdf | ||
| 36C26119B0017-0003004.pdf | ||
| 36C26119B0017-0003005.pdf | ||
| 36C26119B0017-0003000.docx | DOCX document | |
| 36C26119B0017-0002001.pdf | ||
| 36C26119B0017-0002000.docx | DOCX document | |
| 36C26119B0017-0001000.docx | DOCX document | |
| 36C26119B0017-064.pdf | ||
| 36C26119B0017-066.pdf | ||
| 36C26119B0017-058.pdf | ||
| 36C26119B0017-060.pdf | ||
| 36C26119B0017-068.pdf | ||
| 36C26119B0017-062.pdf | ||
| 36C26119B0017-059.pdf | ||
| 36C26119B0017-061.pdf | ||
| 36C26119B0017-057.pdf | ||
| 36C26119B0017-067.docx | DOCX document | |
| 36C26119B0017-063.pdf | ||
| 36C26119B0017-065.pdf | ||
| 36C26119B0017-056.docx | DOCX document | |
| 36C26119B0017-001.docx | DOCX document | |
| 36C26119B0017-000.docx | DOCX document |
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Northern California Health Care System VA Project: 612-17-111 McClellan Park (Sacramento), California Renovate Bldg. 209 at McClellan
LIGHTING CONTROLS
26 09 23 – 1
SECTION 26 09 23
PART 1 - GENERAL
1.1 DESCRIPTION
This section specifies the furnishing, installation and connection of the lighting controls.
1.2 RELATED WORK
A. Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC: Interface of lighting controls with HVAC control systems.
B. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General requirements that are common to more than one section of Division 26.
C. Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND
CABLES (600 VOLTS AND BELOW): Cables and wiring.
D. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:
Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents.
E. Section 26 24 16, PANELBOARDS: Panelboard enclosure and interior bussing used for lighting control panels.
F. Section 26 27 26, WIRING DEVICES: Wiring devices used for control of the lighting systems.
G. Section 26 51 00, INTERIOR LIGHTING: Luminaire and drivers used in control of lighting systems.
1.3 QUALITY ASSURANCE
A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS
(PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR
ELECTRICAL INSTALLATIONS.
1.4 SUBMITTALS
A. Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:
1. Shop Drawings:
a. Submit the following information for each type of lighting controls.
b. Material and construction details.
c. Physical dimensions and description.
26 09 23 – 2
d. Wiring schematic and connection diagram.
e. Installation details.
2. Manuals:
a. Submit, simultaneously with the shop drawings, complete maintenance and operating manuals, including technical data sheets, wiring diagrams, and information for ordering replacement parts.
b. If changes have been made to the maintenance and operating manuals originally submitted, submit updated maintenance and operating manuals two weeks prior to the final inspection.
3. Certifications: Two weeks prior to final inspection, submit the following.
a. Certification by the Contractor that the lighting control systems have been properly installed and tested.
1.5 APPLICABLE PUBLICATIONS
A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only.
B. National Electrical Manufacturer's Association (NEMA):
C136.10-10 ........................... American National Standard for Roadway and Area Lighting
Equipment—Locking-Type Photocontrol Devices and
Mating Receptacles—Physical and Electrical
Interchangeability and Testing
ICS-1-15 ................................ Standard for Industrial Control and Systems General
Requirements
ICS-2-05 ................................ Standard for Industrial Control and Systems: Controllers, Contractors, and Overload Relays Rated Not More than
2000 Volts AC or 750 Volts DC: Part 8 - Disconnect
Devices for Use in Industrial Control Equipment
ICS-6-16 ................................ Standard for Industrial Controls and Systems Enclosures
C. National Fire Protection Association (NFPA):
70-17 ..................................... National Electrical Code (NEC)
D. Underwriters Laboratories, Inc. (UL):
20-10 ..................................... Standard for General-Use Snap Switches
98-16 ..................................... Enclosed and Dead-Front Switches
26 09 23 – 3
773-16 ................................... Standard for Plug-In Locking Type Photocontrols for Use with Area Lighting
773A-16 ................................. Nonindustrial Photoelectric Switches for Lighting Control
916-15 ................................... Standard for Energy Management Equipment Systems
917-06 ................................... Clock Operated Switches
924-16 ................................... Emergency Lighting and Power Equipment (for use when controlling emergency circuits).
PART 2 - PRODUCTS
2.1 ELECTRONIC TIME SWITCHES
A. Electronic, solid-state programmable units with alphanumeric display; complying with
UL 916 and or 917.
1. Contact Configuration: SPST
2. Contact Rating: 20-A load, 120-277 volt.
2.2 CEILING-MOUNTED PHOTOELECTRIC SWITCHES
A. Solid-state, light-level sensor unit, with separate relay unit.
1. Sensor Output: Contacts rated to operate the associated relay. Sensor shall be powered from the relay unit.
2. Relay Unit: Dry contacts rated for 20A load at 120 volt.
3. Monitoring Range: 10 to 200 fc [108 to 2152 lx], with an adjustment for turn-on and turn-off levels.
4. Time Delay: Adjustable from 5 to 300 seconds, with deadband adjustment.
5. Indicator: Two LEDs to indicate the beginning of on-off cycles.
2.3 INDOOR OCCUPANCY SENSORS
A. Wall- or ceiling-mounting, solid-state units with a power supply and relay unit, suitable for the environmental conditions in which installed.
1. Operation: Unless otherwise indicated, turn lights on when covered area is occupied and off when unoccupied; with a 1 to 10 minute adjustable time delay for turning lights off.
2. Sensor Output: Contacts rated to operate the connected relay. Sensor shall be powered from the relay unit.
3. Relay Unit: Dry contacts rated for 20A load at 120 volt.
4. Mounting:
a. Sensor: Suitable for mounting in any position on a standard outlet box.
26 09 23 – 4
b. Time-Delay and Sensitivity Adjustments: Recessed and concealed behind hinged door.
5. Indicator: LED, to show when motion is being detected during testing and normal operation of the sensor.
6. Bypass Switch: Override the on function in case of sensor failure.
7. Manual/automatic selector switch.
8. Automatic Light-Level Sensor: Adjustable from 2 to 200 fc [21.5 to 2152 lx]; keep lighting off when selected lighting level is present.
9. Faceplate for Wall-Switch Replacement Type: Refer to wall plate material and color requirements for toggle switches, as specified in Section 26 27 26, WIRING
DEVICES.
B. Dual-technology Type: Ceiling mounting; combination PIR and ultrasonic detection methods, field-selectable.
1. Sensitivity Adjustment: Separate for each sensing technology.
2. Detector Sensitivity: Detect occurrences of 6 inch [150 mm] minimum movement of any portion of a human body that presents a target of not less than 36 sq. inches
[232 sq. cm], and detect a person of average size and weight moving not less than
305 mm (12 inches) in either a horizontal or a vertical manner at an approximate speed of 12 inches [305 mm/s].
C. Detection Coverage: Shall be sufficient to provide coverage as required by sensor locations shown on drawing.
2.4 LIGHTING CONTROL SYSTEM – RELAY PANEL TYPE (STAND ALONE)
A. System Description:
1. The lighting control system shall be with lighting relay panels. Lighting control devices connect to the relay panels and communicate via the panel controller.
System includes all interfaces and wiring, relay panels, control modules, input modules, panel processors, relays, photocells, switches, dimmers, time clock, and occupancy sensors.
2. System shall include the capability of BACnet IP communication with other systems as described. System communication protocol shall be compatible with the building automation system specified in Section 23 09 23, DIRECT-DIGITAL CONTROL
SYSTEM FOR HVAC.
26 09 23 – 5
3. Panel Controller shall provide programmable operation of lights connected via system relays and controlled with system devices. System software shall provide control of relays and control devices, time and sequence scheduling, timed out and blink light operation and monitoring and reporting of system events and components.
Initial programming shall be as shown on plans and schedules.
B. Panel Controller: Comply with UL 508; programmable, solid-state, astronomic 365-day control unit with non-volatile memory, mounted in preassembled relay panel with low-voltage-controlled, latching-type, single-pole lighting circuit relays. Controller shall be capable of receiving inputs from control devices and other sources. Where indicated, a limited number of digital or analog, low-voltage control-circuit outputs shall be supported by control unit and circuit boards associated with relays.
C. Cabinet: Steel with hinged, locking door. Barriers separate low-voltage and line-voltage components.
D. Directory: Identifies each relay as to load controlled.
E. System Power Supply: Transformer and full-wave rectifier with filtered dc output for panel, controllers and control devices. Feed from an equipment emergency circuit at a minimum.
F. Single-Pole Relays: Mechanically held unless otherwise indicated; split-coil, momentary-pulsed type, rated 20 A, 125 volt AC for tungsten filaments and 20 A, 277 volt AC for electronic ballasts, 50,000 cycles at rated capacity.
G. Control Devices: All occupancy sensors (Ultrasonic, IR and Dual Technology type), shall be provided with system and designed to operate on system network.
Supplemental power packs shall be provided as required for multiple control devices.
This equipment shall be identified in shop drawing submission.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Installation shall be in accordance with the NEC, manufacturer's instructions, as shown on the drawings, and as specified.
B. Aiming for wall-mounted and ceiling-mounted motion sensor switches shall be per manufacturer’s recommendations.
C. Set occupancy sensor "on" duration to 10 minutes.
D. Program lighting control panels per schedule on drawings.
26 09 23 – 6
3.2 ACCEPTANCE CHECKS AND TESTS
A. Perform in accordance with the manufacturer's recommendations.
B. Upon completion of installation, conduct an operating test to show that equipment operates in accordance with requirements of this section.
C. Test for full range of dimming ballast and dimming controls capability. Observe for visually detectable flicker over full dimming range.
D. Test occupancy sensors for proper operation. Observe for light control over entire area being covered.
E. Upon completion of the installation, the system shall be commissioned by the manufacturer’s factory-authorized technician who will verify all adjustments and sensor placements.
3.3 FOLLOW-UP VERIFICATION
Upon completion of acceptance checks and tests, the Contractor shall show by demonstration in service that the lighting control devices are in good operating condition and properly performing the intended function in the presence of COR.
3.4 INSTRUCTION
A. Furnish the services of a factory-trained technician for one 4-hour training period for instructing personnel in the maintenance and operation of the lighting control system on the dates requested by the COR.
B. Contractor shall submit written instructions on training and maintenance as reviewed in training session.
- - - E N D - - -
File details come from the government source that posted it.