Atch. 2_36C26027R0002 0007_Drawing E501-rv_531-25-102 Expand ED.pdf
PDF 1 MB Posted
- Attached to
- Y1DA--CON NRM 531-25-102 | Expand Emergency Room
- Solicitation number
- 36C26027R0002-0007
About this file
This document is a set of architectural and engineering construction drawings for the Expand Emergency Room project at Boise Veterans Affairs Medical Center (VAMC), located at 500 W Fort Street, Boise, Idaho 83702. The drawings are dated October 30, 2025, and represent a 100% Construction Documents (CD) submittal for Project Number 531-25-102, Building 85.
The drawings include comprehensive architectural details for doors, frames, windows, and interior elevations. Sheet AE701 contains a door and frame types schedule with 68 door entries specifying room locations, door sizes ranging from 2'-0" x 7'-0" to 8'-0" x 7'-2½", hardware configurations, door materials (wood, metal, aluminum, glass), door finishes, frame types (hollow metal or aluminum), and fire ratings (ranging from 45-minute to 90-minute ratings). Notable specialized requirements include blast-resistant and bullet-resistant doors for security-sensitive areas (waiting area, police lobby, vestibule), anti-barricade and anti-ligature features for mental health spaces, and self-closing mechanisms for utility rooms. Glass type specifications include security glass with glass-clad polycarbonate (1.25" thickness) and tempered float glass (6mm). The electrical sheets (E500, E501) document the existing and new electrical one-line diagrams, including transformer configurations, panelboard ratings up to 1600A, automatic transfer switches, and equipment connections. The project is fully sprinklered and involves coordination with mechanical systems, variable frequency drives, and hospital-essential power requirements. The design team includes Alesia Architecture P.C. (Elkhorn, Nebraska), Specialized Engineering Solutions (Omaha, Nebraska), Morrison-Maierle (Bozeman, Montana), and Crux Consulting (Omaha, Nebraska), with the U.S. Department of Veterans Affairs Office of Construction and Facilities Management as the contracting agency.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Atch. 1_36C26027R0002 0007_RFI Log No. 2_531-25-102 Expand ER.xlsx | XLSX spreadsheet | |
| 36C26027R0002 0007.pdf | ||
| Atch. 3_36C26027R0002 0007_Specs. Sec. 080671-rv_531-25-102 Expand ED.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IL#1
8"
6" 6"
F
FLUSH
FG
FULL GLASS
8"
LG#132
8"
6" 6"
HG
HALD GLASS
S1
MANUAL SLIDING DOOR
LG#1
LG#1
CR1
OVERHEAD COILING DOOR
IL#2
8"
6" 6"
FG1
FULL GLASS
8"
2"
SCHEDULE
SEE DOOR 2" 2"
SCHEDULE
SEE DOOR 2" 2"
SCHEDULE
SEE DOOR 2"
4" S
E E
D O
O R
S C
H E
D U
LE
HOSPITAL
STOPS @
INTERIOR
DOORS
ONLY
EMERGENCY
RELEASE
STOPS 1H
HOLLOW METAL
HOLLOW METAL
HOLLOW METAL
2" S
E E
D O
O R
S C
H E
D U
LE
2" S
E E
D O
O R
S C
H E
D U
LE HOLLOW METAL FRAME
BOTTOM OF FRAME
4" MATCH EXISTING FRAMES
45°
TYP.
4"
HOLLOW METAL FRAME
WALL - SEE
PLAN FOR TYPE
WALL (WHERE OCCURS)
- SEE PLAN FOR TYPE
3' -6
W1
POLICE LOBBY WINDOW
16'-2"
2" 3'
-1 0"4' -0
W3
RECEPTION WINDOW
2" 3'
-2
2"
3' -6
W2
POLICE VESTIBULE WINDOW
2" 3'
-2
2"
3'-0"
2" 2'-8" 2"
5'-0"
2" 4'-8" 2"
T O
F
LO
O R
3' -0
T O
F
LO
O R
2' -7
T O
F
LO
O R
3' -0
3'-10" 2" 3'-10" 2" 3'-10" 2" 3'-10" 2"2"
1'-3 1/2" 1'-4" 1'-2 1/2"
4"
1/
2"
2' -0
IL#2 IL#2
IL#1
IL#1
IL#1
IL#1
IL#1
IL#1
IL#1
IL#1
AE701
AE701
2" 2'
-8
2"
3' -0
W4
ISOLATION VIEWING WINDOW
2'-0"
2" 1'-8" 2"
T O
F
LO
O R
3' -6
LG#1
AE701
AE701
AE701
4' -0
THREAT
SIDE
SECURE
SIDE
2' -0
1/
2"
ALUMINUM TUBE
ALUMINUM 2-PC CHANNEL
U.L RATED BULLET RESISTANT GLAZING
ARCH WINDOW
ALUMINUM U-CHANNEL
S/S RECESSED CURRENCY DEAL TRAY
COUNTER TOP
THREAT SIDE
SECURE SIDE 4"
1'-3" 1'-4" 1'-3"
3'-10"
4'-2"
2"2"
ALUMINUM TUBE
SCREWS TO SECURE
FRAME IN OPENING
U.L. RATED BULLET
RESISTANT GLAZING
ALUMINUM 2-PC CHANNEL
SEE PLAN
VARIES
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND - TYP.
HOLLOW METAL
FRAME
GLAZING
REMOVABLE STOP
LEAD
10/30/2025
S T
A
T E
O F G EOR
G I A
C E
R T
I F I C A T E N O . R A 0
1 5
R E
G I S T E R E D A R C H
I T E
C T
EDWIN SANTOS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
EXPAND EMERGENCY ROOM
BOISE VAMC
531-25-102
500 W FORT ST, BOISE, ID 83702
A
B
C
D
E
F
EYS IJM
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050
Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590
A u to d e s k D o c s /1
-2
-1
E x p a n d
E m e rg e n c y R o o m V
A M
C B o is e /5
-2
-1
.A rc h
R
-E x p
E m e rg
R m
B o is e
V A
M C
.r v t
/1 /2
:2
:5
P
M
AE701
DOOR AND FRAME TYPES, DETAILS
AND DOOR SCHEDULE
2025.10.30
100% CD SUBMITTAL
DOOR SCHEDULE
DOOR NUMBER ROOM NAME DOOR SIZE HARDWARE DOOR MATERIAL DOOR TYPE DOOR FINISH FRAME TYPE
FRAME
MATERIAL FRAME FINISH FIRE RATING REMARKS
851000 WAITING PR 3'-6" x 7'-0" 1 MTL F P-1 1H HM P-1 S CR/DO, BLAST & BULLET
RESISTANT
851000A POLICE 3'6" x 7'-0" 3 MTL FG1 P-1 1H HM P-1 CR, BULLET & BLAST
RESISTANT
851002 RECEPTION 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
851003 RNOD OFFICE 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
851003B RECEPTION 8'-0" x 7'-2 1/2" 8 AL S1 P-1 1H AL P-1
851004 TRIAGE 8'-0" x 7'-2 1/2" 8 AL S1 AN - AL AN
851005 A1 - GENERAL EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN - AL AN
851006 A2- GENERAL EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN - AL AN
851007 A3 - GENERAL EXAM 3'-6" x 7'-0" 5 WD HG WD-1 1H HM P-1
851008 A4 - FAST TRACK EXAM 3'-6" x 7'-0" 5 WD HG WD-1 1H HM P-1
851009 A5 - MENTAL HEALTH 4'-0" x 7'-0" 13 WD HG WD-1 1H HM P-1 ANTI-BARRICADE, ANTI-LIGATURE
851009A A5 - MENTAL HEALTH 3'-10" X 7'-0" 11 STL CR1 AN - -
851009B A5 - MENTAL HEALTH 6'-0"x 7'-0" 11 STL CR1 AN - -
851011 SECLUSION ROOM 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR, ANTI-BARRICADE, ANTI-LIGATURE
851012 A6 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN
851013 TOILET 3'-6" x 7'-0" 7 WD F WD-1 3 HM P-1
851015 CLEAN UTILITY 3'-6" x 7'-0"
45-MIN
3 WD F WD-1 1H HM P-1 45MIN CR, SELF CLOSING &
LATCHING
851016 B8 - GEN EXAM 8'-0" x 7'-2 1/2" 8 GL S1 AN 1H AL P-1
851017 SOILED UTILITY 3'-6" x 7'-0"
45-MIN
3 WD F WD-1 1H HM P-1 45MIN CR, SELF CLOSING &
LATCHING
851018 B7 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN
851019 B4 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN
851020 B6 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN
851021 B5 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN
851023 HAC 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
851024 PHYS WORK 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
851025 PHYSICIAN WORK 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
851026 MEDICATION ROOM 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
851028A RESUSCITATION 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN
851028B RESUSCITATION 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN
851029 C2 - GYN EXAM 4'-0" x 7'-0" 5 WD F WD-1 1H HM P-1
851029A GYN TOILET 3'-6" x 7'-0" 7 WD F WD-1 3 HM P-1
851030 TOILET 3'-6" x 7'-0" 7 WD F WD-1 3 HM P-1
851031 ANTE 4'-0" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
851031A C3 - AIRBORNE INFECTION ISO 4'-0" x 7'-0" 6 WD F WD-1 3 HM P-1
851031B ISO TOILET 3'-6" x 7'-0" 7 WD F WD-1 1H HM P-1
851032 CORRIDOR 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN
851033 B1 GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL P-1
851036 B2 GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN
851037A DECONTAMINATION 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
851037B DECONTAMINATION 3'-6" x 7'-0" 2 MTL F P-1 4 HM P-1 CR
851038 BREAKROOM 3'-6" x 7'-0" 6 WD F WD-1 1H HM P-1
851040 OFFICE 3'-6" x 7'-0" 5 WD F WD-1 1H HM P-1
851041 OFFICE 3'-6" x 7'-0" 5 WD F WD-1 1H HM P-1
851042 OFFICE/SLEEP 3'-6" x 7'-0" 5 WD F WD-1 1H HM P-1
851044 VEST. PR 7'-0" x 7'-0" 12 MTL F P-1 1H HM P-1 CR/DO, BLAST RESISTANT, 14 GA STEEL
851050 FAMILY CONSULT 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
851051 STORAGE 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
C002 CORRIDOR 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR
C004 CORRIDOR PR 3'-0" x 7'-0" 1 WD F WD-1 1H HM P-1 CR/DO
C004B CORRIDOR 3'-6" x 7'-0" 2 WD F WD-1 1H HM P-1 CR
C16B VEST. 4'-0" x 7'-0" 1 MTL FG FG 1H HM P-1 DO,CR, BULLET & BLAST
RESISTANT
E851014 ELEC PR 3'-0" x 7'-0" 4 WD F WD-1 1H HM P-1
E851027B ELEC PR 3'-0" x 7'-0"
45MIN
10 MTL F P-1 4 HM P-1 45MIN CR, SELF CLOSING &
LATCHING
E851034 ELEC 2'-0" x 7'-0" 3 WD F WD-1 1H HM P-1 45MIN CR
ST14 STAIR 3'-0" x 7'-0" 90MIN 2 WD F MTL 1H HM P-1 90MIN CR
1/4" = 1'-0"1
DOOR TYPES
FRAME TYPES
GLASS TYPE SCHEDULE
REF TYPE Description Thickness Remarks
IL#1 TYPE IL#1 SECURITY GLASS, GLASS CLAD POLYCARBONATE CLEAR 1.25" A,B
IL#2 TYPE IL#2 SECURITY GLASS, GLASS CLAD POLYCARBONATE CLEAR, TINTED 1.25" A,B
LG#1 TYPE LG#1 CLR, TEMPERED TONGLESS FLOAT 6MM (0.23") C
GLASS TYPE SCHEDULE NOTES:
A: COMPLY W/ VA-PSDM/UFC 4-0110-01 FORCE PROTECTION REQUIREMENTS
B: SEE SPECIFICATION SECTION 08 80 00: INSULATED LAMINATED GLASS SCHEDULE (FORCE PROTECTION AND PHYS SAFETY)
C: SEE SPECIFICATION SECTION 08 80 00: GLAZING
D: DOOR UNIT ASSEMBLY, COORDINATE WITH DOOR & HARDWARE SCHEDULE
1 1/2" = 1'-0"4
HOSPITAL STOPS
1 1/2" = 1'-0"3
DOOR FRAME OFFSET
1" = 1'-0"5
WINDOW FRAME TYPES
1" = 1'-0"6
RECEPTION WINDOW SECTION
1" = 1'-0"7
RECEPTION WINDOW PLAN
CR = CARD READER
DO = DOOR OPERATOR
3" = 1'-0"8
WINDOW FRAME DETAIL
Mark Revisions: Date:
2 Revision 2 2026/10/30
4 Revision 4 2026/11/18
FIRST FLOOR
100' - 0"
J.9 J.7 J.1 J
A5077
F3200
M3150
851026
RB-1
FIRST FLOOR
100' - 0"
G
F0206
F2000
F0410
E0703
M1801
A1015
F0275
RB-1
FIRST FLOOR
100' - 0"
3.8
F0275
M1801
E0703
F0410851050
RB-1
FIRST FLOOR
100' - 0"
G
F0410 F0205
RB-1
FIRST FLOOR
100' - 0"
3.8
F0205
F0206
F2000
RB-1
FIRST FLOOR
100' - 0"
32.8
M3150
A5077
F3200
E0945
R6200
RB-1
CG-1
FIRST FLOOR
100' - 0"
J.9J.7J.1J
R6200 A5106
F2010
E0945
RB-1
CG-1
AE904
FIRST FLOOR
100' - 0"
3 2.8
E0945
A5145
A5145
A5077
RB-1
FIRST FLOOR
100' - 0"
F3200
851011
WSF-1
FIRST FLOOR
100' - 0"
H
M7011
F3200
WSF-1
FIRST FLOOR
100' - 0"
H
M7011
WSF-1
FIRST FLOOR
100' - 0"
M7011
WSF-1
10/30/2025
S T
A
T E
O F G EOR
G I A
C E
R T
I F I C A T E N O . R A 0
1 5
R E
G I S T E R E D A R C H
I T E
C T
EDWIN SANTOS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
EXPAND EMERGENCY ROOM
BOISE VAMC
531-25-102
500 W FORT ST, BOISE, ID 83702
A
B
C
D
E
F
EYS IJM
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050
Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590
A u to d e s k D o c s /1
-2
-1
E x p a n d
E m e rg e n c y R o o m V
A M
C B o is e /5
-2
-1
.A rc h
R
-E x p
E m e rg
R m
B o is e
V A
M C
.r v t
/1 /2
:0
:0
P M
AE913
INTERIOR ELEVATIONS
2025.10.30
100% CD SUBMITTAL
3/8" = 1'-0"4
MEDICATION ROOM 851026 - WEST ELEVATION
3/8" = 1'-0"6
FAMILY CONSULT 851050 - EAST ELEVATION
3/8" = 1'-0"7
FAMILY CONSULT 851050 - SOUTH ELEVATION
3/8" = 1'-0"8
FAMILY CONSULT 851050 - WEST ELEVATION
3/8" = 1'-0"5
FAMILY CONSULT 851050 - NORTH ELEVATION
3/8" = 1'-0"1
MEDICATION ROOM 851026 - NORTH ELEVATION
3/8" = 1'-0"2
MEDICATION ROOM 851026 - EAST ELEVATION
3/8" = 1'-0"3
MEDICATION ROOM 851026 - SOUTH ELEVATION
3/8" = 1'-0"11
SECLUSION 851011 - SOUTH ELEVATION
3/8" = 1'-0"10
SECLUSION 851011 - EAST ELEVATION
3/8" = 1'-0"12
SECLUSION 851011 - WEST ELEVATION
3/8" = 1'-0"9
SECLUSION 851011 - NORTH ELEVATION
Mark Revisions: Date:
4 Revision 4 2026/11/18
FEC
F E
C
N C
NC
N C
C R
CR
CR
D
NC
NC
Z Z
N C
N C
N
CD
D
D
CR
NC
D
T V
AC
AC
AC
N C
S
S
S
S
C
C
C C
CR
C
C
C
C R
NC
AC CR
C
P M
P M
P M
P M
PM
PM
AC
C R
A C A C
P M
C
C
N C
VI
DO
AC
AC
CR
CR
AC
N C
NC
AC CR
J
J
J.1
J.1
J.7
J.7
J.9
J.9
K.4
K.4
L.1
L.1
N
N
O
O
0.9 0.9
1 1
1.9 1.9
2 2
2.8 2.8
3 3
3.8 3.8
4 4
K.6
K.6
CORRIDOR
C002
C3 - AIRBORNE
INFECTION
ISO-1
851031A-1
ANTE
851031 NURSE ALC
C010
GYN TOILET
851029A
ISO TOILET
851031B
GEN EXAM
851033
ELEC
E851027
OMNI BANK
RESUSCITATION
851028
B3 - EXAM-1
851032-1
OFFICE/SLEEP
851042
OFFICE
851041
TOILET
851039
MEDICATION
ROOM
851026
MECH SHAFT
C2 - GYN EXAM
851029
TOILET
851030
EQUIPMENT
OFFICE
851040
BREAKROOM
851038
DECONTAMINATION
851037
GEN EXAM
851036
CORRIDOR
C001
PHYSICIAN
WORK
851025
BSID-STF/CODE
BSID-STF/CODE
APULL
APULL
DUTY
APULL
BSID-STF/CODE
BSID-STF/CODE
BSID-STF/CODE
W
CONS
44"
WAP
WAP
WAP
WAP
WAP
WAP
WAP
VEST.
C16B
CORRIDOR
C005
72"
BSID-STF/CODE
E
E300
AC
AC AC
E E
2D
W 2D
2D
W
W
2D
2D
W
2D
2D
2D
2D 2D
2D
2D
W 2D
4D
2D
2D
W
E
E
W
CONS
44"
W
2D
4D
2D
2D
DUTY
DED
MON
DED
MON
DED
MON
DED
MON
DED
MON
DED
MON
2D
2D
2D
2D
2D
2D
WS
STF/CODE
STF/CODE2
SYMBOL
FIRE WALL LEGEND
DESCRIPTION
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
SMOKE PARTITIONS S S S S
INSTALL GREEN INSULATED
GROUND WIRE WITH
LIGHTING, RECEPTACLE AND
EQUIPMENT BRANCH CIRCUITS.
INSTALL INDIVIDUAL (DEDICATED)
NEUTRAL CONDUCTORS FOR
EACH 120V OR 277V PHASE
CONDUCTOR SERVED FROM A
SINGLE POLE CIRCUIT BREAKER
TRUE
NORTH
PLAN
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
EXPAND EMERGENCY ROOM
BOISE VAMC
531-25-102
500 W FORT ST, BOISE, ID 83702
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050
10/29/2025Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590
A u to d e s k D o c s /1
-2
-1
E x p a n d E m e rg e n c y R o o m V
A M
C B o is e /2
V
A B o is e E x p a n d E m e rg e n c y R o o m
S
E S
.r v t
/1 /2
:4
:0
A
M
EV103
FIRST FLOOR - ENLARGED LOW
VOLTAGE PLAN 2
MLW CRD2025.10.30
100% CD SUBMITTAL
1/4" = 1'-0"EV103
ENLARGED LV PLAN 21
SHEET NOTES:
1. PROVIDE NURSE CALL STATION AS WEATHERPROOF CORROSION RESISTANT TYPE.
Mark Revisions: Date:
1 Revision 1 2026/10/08
2 Revision 2 2026/10/30
4 Revision 4 2026/11/18
250AF
225AT
100AF/AT 400AF/AT
I
EDP1
480Y/277V
400A 3P/4W
DE
NDP1
480Y/277V
1200A 3P/4W
250AF/AT
LSI
E
250AF/AT
LSI
E
250AF/AT
LSI
D
400AF/AT
LSI
E
250AF/AT
LSI
D
250AF/AT
LSI
E
1200AF/AT
LSIG
E
480Y/277V
225A MCB
3P/4W E
CHILLER 3
480V 600A
E
PH2
480Y/277V
225A MCB
3P/4W E
E16 480Y/277V
100A MCB
3P/4W
E24 480Y/277V
100A MCB
3P/4W
EPH2
480Y/277V
100A MCB
3P/4W
E
E
E
E17 480Y/277V
400A MCB
3P/4W
EPH3
480Y/277V
225A MCB
3P/4W
E25 480Y/277V
400A MLO
3P/4W
E18 208Y/120V
225A MCB
3P/4W
EPH5
208Y/120V
225A MLO
3P/4W
EPH4
208Y/120V
225A MCB
3P/4W
T21
75KVA
480:208Y/120V
T14
75KVA
480:208Y/120V
E
E
EE
E
E
E
E
208Y/120V
175A MCB
3P/4W E
E
T10N
1000KVA
12.47KV:480/277V
T19
30KVA
480:208Y/120V
EDP3
480Y/277V
400A 3P/4W
E E
100AF/AT
E
70AF/AT
E
125AF/AT
E
100A E
E
D
E
D
E
E13A 208Y/120V
60A MCB
3P/4W
E13 208Y/120V
100A MCB
3P/4W
E11 208Y/120V
225A MCB
3P/4W
E12 208Y/120V
90A MCB
3P/4W
T3
30KVA
480:208Y/120V
150AF/AT
LSI
E
400AF
200AT
LSI
E
400AF/AT
LSI
E
SPARE
400AF/AT
LSI
E
400AF/AT
LSI
D
400AF/AT
LSI
E
CT
SCANNER
E
CT
SCANNER
/NM
E
XRAY
NO.1
E
XRAY
NO.2
E
XRAY
NO.4
E
400AF/AT
LSIG
E
150AF/AT
LSIG
E
400AF
200AT
LSIG
E
600AF/AT
LSIG
E
400AF
200AT
LSIG
E
400AF/AT
LSIG
E
400AF
300AT
LSIG
E
1200AF/AT
LSIG
E
EQ
ATS5
200A E
EXTERIOR
TEMP
POWER
E
T1
45KVA
480:208Y/120V
D
SHUNT TRIP
UROLOGY
GENERATOR
E (DISC.)
EQ
ATS2
400A
CR
ATS1
400A
LS
ATS3
150A
E EE
600AF/AT
LSI
E
T18
3KVA
277:120V
E19 120V
70A MLO
1P/2W
E
E
EMDP1
480Y/277V 1600A 3P/4W
NMDP1
480Y/277V
1600A 3P/4W
XRAY
NO.3
E
E E
150AF
100AT
LSIG
E
150AF
100AT
LSIG
E
E
T10E
1000KVA
12.47KV:480/277V
250AF
200AT
I E
400AF
300AT
I E
250AF
110AT
I E
400AF
400AT
I E
SPARE
EDP2
480Y/277V 400A 3P/4W E
40AF/AT
E
50AF/AT
E
SPARE
40AF/AT
E
60AF/AT
E
80A E
80AF/AT
E
70AF/AT
E
125AF/AT
E
EDP4
480Y/277V
400A MLO
3P/4W E
150AF
125AT
LSIG
E
150AF
125AT
LSIG
E
400AF/AT
LSIG
E
SPARE
400AF
200AT
LSIG
N.O.
E
150AF
125AT
E
SPARE
150AF
100AT
LSIG
E
1600AF/AT
LSIG, N.C.
E
"SERVICE ENTRANCE"
1600AF/AT
LSIG, N.C.
E
"SERVICE ENTRANCE"
1600AF/AT
LSIG, N.O.
E
EPH1
480Y/277V
225A MCB
3P/4W E
TO
BASEMENT,
T10/EG2
TO 3RD
FLOOR,
T8/31
TO
BASEMENT,
EG1
TO 2ND
FLOOR, E21
TO 2ND
FLOOR 24
TO 3RD
FLOOR, OR
PANEL E34
TO 3RD
FLOOR, OR
PANEL E35
E
T2
30KVA
480:208Y/120V
TO RM 140,
E14
400AF/AT
LSI
E
SPARE
TO
BASEMENT,
T11
TO
BASEMENT,
EMCC1
TO OLD
PENTHOUSE,
EMCC2
TO (7) 20A,
277V 1P
LIGHTING
CIRCUITS
TO OLD
PENTHOUSE,
EPH6
TO
BASEMENT,
T13
TO OLD
PENTHOUSE,
NMCC2
TO
BASEMENT,
NMCC1
TO 3RD
FLOOR, 31
TO 2ND
FLOOR, 21
TIEESSENTIAL
MAIN
NORMAL
MAIN
CR
ATS8
400A E
LS
ATS7
100A E
EQ
ATS6
225A
D
T15
75KVA
480:208Y/120V E
208Y/120V
225A MCB
3P/4W E
T20
75KVA
480:208Y/120V E
PH3A
208Y/120V
225A MCB
3P/4W E
PH3B
208Y/120V
225A MLO
3P/4W E
E23 480Y/277V
225A MCB
3P/4W E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
EXPAND EMERGENCY ROOM
BOISE VAMC
531-25-102
500 W FORT ST, BOISE, ID 83702
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050
10/29/2025Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590
A u to d e s k D o c s /1
-2
-1
E x p a n d E m e rg e n c y R o o m V
A M
C B o is e /2
V
A B o is e E x p a n d E m e rg e n c y R o o m
S
E S
.r v t
/1 /2
:4
:0
A
M
E500
DEMO ELECTRICAL ONE-LINE
DIAGRAM
MJF MLW2025.10.30
100% CD SUBMITTAL
NO SCALEE500
DEMO ELECTRICAL ONE-LINE1
SHEET NOTES:
1. REPLACE EXISTING BREAKER OR TRIP UNIT. SEE NEW ELECTRICAL ONE-LINE AND/OR PANEL SCHEDULES
FOR FURTHER INFORMATION.
2. DEMOLISH CONDUIT AND WIRE FROM SECOND FLOOR PANEL E23 TO PENTHOUSE ELECTRICAL PANEL EPH1.
3. CONDUIT AND WIRE TO REMAIN FOR RE-CONNECTION TO NEW.
4. REPLACE EXISTING PANEL WITH NEW, USING EXISTING CONDUIT AND WIRE. RE-CONNECT EXISTING CONDUIT
AND WIRE.
5. REPLACE EXISTING TRANSFORMER WITH NEW, USING EXISTING CONDUIT AND WIRE ON PRIMARY AND
INSTALLING NEW ON SECONDARY. SEE NEW ELECTRICAL ONE-LINE FOR FURTHER INFORMATION.
6. PULL EXISTING WIRE BACK TO CEILING TO BE SPLICED INTO NEW FEED. SEE NEW ONE-LINE DIAGRAM FOR
FURTHER INFORMATION.
11 1
3 3
4 4
GENERAL NOTES:
A. WHERE EXISTING CONDUIT AND WIRE IS EXPLICITLY STATED OR SHOWN AS TO BE RE-USED AND IT IS NOT
FEASIBLE TO RE-CONNECT TO THE NEW TERMINALS DUE TO SITE CONDITIONS:
• FOR 120V 20A CIRCUITS: PROVIDED THAT THE EXISTING CONDITION MEETS THE REQUIREMENTS SET
FORTH IN ALL GUIDING DOCUMENTS APPLICABLE TO THIS JOB (SUCH AS THE ELECTRICAL DESIGN MANUAL, NFPA 70 (2023), AND THE PROJECT SPECIFICATIONS), THE CONTRACTOR MAY CHOOSE TO SPLICE A CIRCUIT EXTENSION OF THE SAME CONFIGURATION, SIZE, AND INSULATION OF WIRE THROUGH
THE USE OF AN APPROVED JUNCTION BOX TO REACH THE NEW TERMINALS.
• FOR ALL OTHER CIRCUITS: SUBMIT RFI WITH REASONING, PROPOSED SOLUTION (IF DETERMINED), AND
ANY PROJECT IMPACTS FOR EVALUATION ON A CASE BY CASE BASIS.
B. WORK ON ELECTRICAL PANELS AND EQUIPMENT INCLUDING BUT NOT LIMITED TO EMDP1, NMDP1, EDP1, NDP1, AND ANY ITEMS ON THE EQUIPMENT BRANCH CIRCUIT WILL REQUIRE OUTAGES WHICH EXTEND BEYOND THE LIMITS OF THE PHYSICAL PROJECT AREA. CONTRACTOR SHALL COORDINATE WITH BOISE VAMC STAFF, COR, AND A/E TO MINIMIZE THE DURATION AND IMPACT OF THESE OUTAGES DURING PRE- CONSTRUCTION MEETINGS. THE WORK SHALL OCCUR DURING OFF PEAK HOURS. CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO LOADS ESSENTIAL TO THE SAFE OPERATION OF THE HOSPITAL FOR THE
DURATION OF THE OUTAGE.
Mark Revisions: Date:
2 Revision 2 2026/10/30
4 Revision 4 2026/11/18
400AF/AT
LSI
150AF
100AT
LSI
400AF/AT
LSI
EDP1
480Y/277V
800A 3P/4W
400AF/AT
LSI
E1-20 208Y/120V
125A MLO
3P/4W
E
NDP1
480Y/277V
1200A 3P/4W
250AF/AT
LSI
E
250AF/AT
LSI
E
400AF/AT
LSI
E
250AF/AT
LSI
E
1200AF/AT
LSIG
E
480Y/277V
225A MCB
3P/4W E
CHILLER 3
480V 600A
E
T15
75KVA
480:208Y/120V E
208Y/120V
225A MCB
3P/4W E
PH2
480Y/277V
225A MCB
3P/4W E
T20
75KVA
480:208Y/120V E
PH3A
208Y/120V
225A MCB
3P/4W E
E23 480Y/277V
225A MCB
3P/4W
E16 480Y/277V
100A MCB
3P/4W
E24 480Y/277V
100A MCB
3P/4W
EPH2
480Y/277V
100A MCB
3P/4W
E
E
E
E
E17 480Y/277V
400A MCB
3P/4W
EPH3
480Y/277V
225A MCB
3P/4W
E25 480Y/277V
400A MLO
3P/4W
E18 208Y/120V
225A MCB
3P/4W
EPH5
208Y/120V
225A MLO
3P/4W
EPH4
208Y/120V
225A MCB
3P/4W
T21
75KVA
480:208Y/120V
T14
75KVA
480:208Y/120V
E
E
EE
E
E
E
E
208Y/120V
225A MCB
3P/4W E
E
T10N
1000KVA
12.47KV:480/277V
T19
30KVA
480:208Y/120V
EDP3
480Y/277V
400A 3P/4W
E E
100AF/AT
E
70AF/AT
E
125AF/AT
E
100A E
E
E
E
E13A 208Y/120V
60A MCB
3P/4W
E11 208Y/120V
225A MCB
3P/4W
T3
30KVA
480:208Y/120V
150AF/AT
LSI
E
400AF
200AT
LSI
E
400AF/AT
LSI
E
SPARE
400AF/AT
LSI
E
800AF/AT
LSI
400AF/AT
LSI
E
CT
SCANNER
E
CT
SCANNER
/NM
E
XRAY
NO.1
E
XRAY
NO.2
E
XRAY
NO.4
E
400AF/AT
LSIG
E
150AF/AT
LSIG
E
400AF
200AT
LSIG
E
600AF/AT
LSIG
E
400AF
200AT
LSIG
E
400AF/AT
LSIG
E
400AF
300AT
LSIG
E
1200AF/AT
LSIG
E
EQ
ATS5
200A E
EXTERIOR
TEMP
POWER
E
T1
75KVA
480:208Y/120V
NEMA 1
SHUNT TRIP
UROLOGY
GENERATOR
E (DISC.)
EQ
ATS2
400A
CR
ATS1
400A
LS
ATS3
150A
E EE
600AF/AT
LSI
E
T18
3KVA
277:120V
E19 120V
70A MLO
1P/2W
E
E
EMDP1
480Y/277V 1600A 3P/4W
NMDP1
480Y/277V
1600A 3P/4W
XRAY
NO.3
E
E E
150AF
100AT
LSIG
E
150AF
100AT
LSIG
E
E
T10E
1000KVA
12.47KV:480/277V
250AF
200AT
I E
400AF
300AT
I E
250AF
110AT
I E
400AF
400AT
I E
SPARE
EDP2
480Y/277V 400A 3P/4W E
40AF/AT
E
50AF/AT
E
SPARE
40AF/AT
E
60AF/AT
E
80A E
80AF/AT
E
70AF/AT
E
125AF/AT
E
EDP4
480Y/277V
400A MLO
3P/4W E
150AF
125AT
LSIG
E
150AF
125AT
LSIG
E
400AF/AT
LSIG
E
SPARE
400AF
200AT
LSIG
N.O.
E
150AF
70AT
LSIG
E
150AF
100AT
LSIG
E
1600AF/AT
LSIG, N.C.
E
"SERVICE ENTRANCE"
1600AF/AT
LSIG, N.C.
E
"SERVICE ENTRANCE"
1600AF/AT
LSIG, N.O.
E
EPH1
480Y/277V
225A MCB
3P/4W E
TO
BASEMENT,
T10/EG2
TO 3RD
FLOOR,
T8/31
TO
BASEMENT,
EG1
TO 2ND
FLOOR, E21
TO 2ND
FLOOR 24
TO 3RD
FLOOR, OR
PANEL E34
TO 3RD
FLOOR, OR
PANEL E35
E
T2
30KVA
480:208Y/120V
TO RM 140,
E14
400AF/AT
LSI
E
SPARE
TO
BASEMENT,
T11
TO
BASEMENT,
EMCC1
TO OLD
PENTHOUSE,
EMCC2
TO (7) 20A,
277V 1P
LIGHTING
CIRCUITS
TO OLD
PENTHOUSE,
EPH6
TO
BASEMENT,
T13
TO OLD
PENTHOUSE,
NMCC2
TO
BASEMENT,
NMCC1
TO 3RD
FLOOR, 31
TO 2ND
FLOOR, 21
TIEESSENTIAL
MAIN
NORMAL
MAIN
CR
ATS8
400A E
LS
ATS7
100A E
EQ
ATS6
400A
NEMA 1
800AF/AT
LSI
208Y/120V
125A MLO
3P/4W
E12
PANEL
125A MCB
3P/4W
E13 208Y/120V
125A MCB
3P/4W
150AF
100AT
LSI
208Y/120V
125A MCB
3P/4W
T17
45KVA
480:208Y/120V
NEMA 1
40N 40N
80N
45T 75T
12N12N
AHU-18
480V
SF-18
7.5HP
HRCP-1
2HP
VFD-HRCP-1VFD-SF-18
EF-32A
2HP
VFD-EF-32A
EF-32B
2HP
VFD-EF-32B
30A/3P NF
NEMA 3R
CP-AHU-8
480V
60A MCB
SF-8
15HP
EF-8
7.5HP
30A/3P NF
NEMA 3R
3 6
2 2
PH3B
208Y/120V
225A MLO
3P/4W E
40N
22N 22N
225AF/AT
LSI
225AF/AT
LSI
E1-21 480Y/277V
400A 3P/4W
35KAIC
9 9 9 9 9 2
9 9 9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
NE COA NUMBER: CA-0721
on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t
6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t
6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t
EXPAND EMERGENCY ROOM
BOISE VAMC
531-25-102
500 W FORT ST, BOISE, ID 83702
A
B
C
D
E
F
Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520
Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050
10/29/2025Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590
A u to d e s k D o c s /1
-2
-1
E x p a n d E m e rg e n c y R o o m V
A M
C B o is e /2
V
A B o is e E x p a n d E m e rg e n c y R o o m
S
E S
.r v t
/1 /2
:4
:0
A
M
E501
NEW ELECTRICAL ONE-LINE DIAGRAM
MJF MLW2025.10.30
100% CD SUBMITTAL
NO SCALEE501
NEW ELECTRICAL ONE-LINE1
SHEET NOTES:
1. REPLACE EXISTING BREAKER WITH NEW BREAKER OF SAME MAKE AND MODEL WITH NEW RATING AS
INDICATED.
2. CONTROL PANEL/ELECTRICAL PANEL TO BE SUPPLIED WITH AHU-18. SEE 'EQUIPMENT CONNECTION
SCHEDULE' SHEET E700.
3. NEMA 4X SST CONTROL PANEL WITH VFD'S INTERNAL AND NEMA 4X SST ATTACHED AC UNIT. SEE "VARIABLE
FREQUENCY DRIVE SCHEDULE" SHEET M600 FOR FURTHER INFORMATION ON CP-AHU-18.
4. SIZE CONDUCTOR TO BE RATED TO NO LESS THAN 115% OF THE MAXIMUM OUTPUT AMPS OF THE DRIVE AND IN ACCORDANCE WITH THE NEC, NO SMALLER THAN #10. SIZE CONDUIT TO MEET THE CONDUIT FILL REQUIREMENTS SET FORTH IN THE NEC, NO SMALLER THAN 1". RUN UNBROKEN GROUND OF SAME SIZE AS
PHASE CONDUCTOR BETWEEN DRIVE OUTPUT AND MOTOR.
5. SPLICE NEW FEED ONTO EXISTING USING APPROVED METHODS SET FORTH IN THE PROJECT
SPECIFICATIONS. SUBMIT PRODUCT DATA AND EQUIPMENT INFORMATION FOR APPROVAL.
6. NEW 18 POLE/6 SLOT 400A MLO PANELBOARD WITH FULLY ADJUSTABLE ELECTRONIC TRIP FEEDER BREAKERS AS SHOWN. PROVIDE (1) SPARE BREAKER OF MATCHING TYPE TO THE OTHER (2) BEING
PROVIDED.
7. SEE DRY TYPE TRANSFORMER GROUNDING DETAIL SHEET E601.
8. REPLACE EXISTING TRIP UNIT WITH NEW, RATED AS INDICATED.
9. THE SCOPE OF THE POWER SYSTEM STUDY MAY END EARLY IN THE CIRCUIT AT THIS LOCATION WHICH
SHALL BE MODELED AS A BUS.
11 1
FEEDER SCHEDULE - COPPER
FEEDER NOMINAL SIZE WIRE AND CONDUIT
2 20 A 3-#12 CU, #12 CU GND - 3/4" C.
3 30 A 3-#10 CU, #10 CU GND - 3/4" C.
6 60 A 3-#4 CU, #10 CU GND - 1" C.
7 70 A 3-#4 CU, #8 CU GND - 1-1/4" C.
12N 125 A 4-#1/0 CU, #6 CU GND - 2" C.
22N 225 A 4-250 KCMIL CU, #4 CU GND - 3" C.
40N 400 A 4-#4/0 CU, #3 CU GND - 2-1/2" C. (2 SETS)
45T 150 A 4-#2/0 CU, #4 CU GND - 2"C.
75T 250 A 4-300 KCMIL CU, #2 CU GND - 3"C.
80N 800 A 4-350 KCMIL CU, #1/0 CU GND - 3" C. (3 SETS)
A. WHERE EXISTING CONDUIT AND WIRE IS EXPLICITLY STATED AS TO BE RE-USED AND IT IS NOT FEASIBLE
TO RE-CONNECT TO THE NEW TERMINALS:
• FOR 120V 20A CIRCUITS: PROVIDED THAT THE EXISTING CONDITION MEETS THE REQUIREMENTS SET
FORTH IN ALL GUIDING DOCUMENTS APPLICABLE TO THIS JOB (SUCH AS THE ELECTRICAL DESIGN MANUAL, NFPA 70 (2023), AND THE PROJECT SPECIFICATIONS), THE CONTRACTOR MAY CHOOSE TO SPLICE A CIRCUIT EXTENSION OF THE SAME CONFIGURATION, SIZE, AND INSULATION OF WIRE
THROUGH THE USE OF AN APPROVED JUNCTION BOX TO REACH THE NEW TERMINALS.
• FOR ALL OTHER CIRCUITS: SUBMIT RFI WITH REASONING, PROPOSED SOLUTION (IF DETERMINED), AND
ANY PROJECT IMPACTS FOR EVALUATION ON A CASE BY CASE BASIS.
B. FURTHER INFORMATION REGARDING ELECTRICAL PANELS AND CIRCUITS CAN BE FOUND IN THE
ELECTRICAL PANEL SCHEDULES ON SHEETS E701 THROUGH E705.
C. NOT ALL ELECTRICAL OR MECHANICAL EQUIPMENT IS SHOWN ON THIS ONE LINE DIAGRAM. FOR READABILITY, THE ENGINEER HAS OMITTED PORTIONS OF THE DISTRIBUTION SYSTEM ASSOCIATED WITH
THE FACILITY.
D. THE ENGINEER HAS INCLUDED ON THIS SHEET SELECTED 480V MECHANICAL EQUIPMENT WHICH HAS CIRCUITING WHICH WOULD BE OTHERWISE DIFFICULT TO DEPICT. VERIFY THE WIRING AND CONDUIT REQUIREMENTS ON THIS SHEET WITH THE ELECTRICAL REQUIREMENTS OF THE EQUIPMENT AS SHOWN IN
THE 'EQUIPMENT CONNECTION SCHEDULE' ON SHEET E700 AND ON THE MECHANICAL SHEETS.
REGARDLESS OF THE LOCATION OF THE INFORMATION, THE CONTRACTOR IS REQUIRED TO PROVIDE CONDUIT AND WIRE FROM SOURCE TO LOAD IN ACCORDANCE WITH THE PROJECT DOCUMENTS AND NEC
INCLUDING WHERE EQUIPMENT SUPPLIED UNDER THE MECHANICAL SCOPE (SUCH AS VFDS AND
MANUFACTURER PROVIDED PANELS) EXIST IN THE MIDDLE OF THE CIRCUIT.
E. WORK ON ELECTRICAL PANELS AND EQUIPMENT INCLUDING BUT NOT LIMITED TO EMDP1, NMDP1, EDP1, NDP1, AND ANY ITEMS ON THE EQUIPMENT BRANCH CIRCUIT WILL REQUIRE OUTAGES WHICH EXTEND BEYOND THE LIMITS OF THE PHYSICAL PROJECT AREA. CONTRACTOR SHALL COORDINATE WITH BOISE VAMC STAFF, COR, AND A/E TO MINIMIZE THE DURATION AND IMPACT OF THESE OUTAGES DURING PRE- CONSTRUCTION MEETINGS. THE WORK SHALL OCCUR DURING OFF PEAK HOURS. CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO LOADS ESSENTIAL TO THE SAFE OPERATION OF THE HOSPITAL FOR THE
DURATION OF THE OUTAGE.
F. THE EXISTING POWER SYSTEM STUDY FOR THE CAMPUS IS TO BE PROVIDED TO THE CONTRACTOR FOR
UPDATING BASED ON THESE PROJECT DOCUMENTS AND THE CONDITIONS IN THE FIELD. THE
CONTRACTOR SHALL INCLUDE ALL FIELD INVESTIGATION AND MODELING REQUIRED TO EXECUTE THE REQUIREMENTS OF SPECIFICATION 26 05 73 IN THE BID. THE STUDY SHALL BEGIN AT T10E/T10N AND EXTEND THROUGH THE LAST BRANCH BREAKER EXCEPT WHERE THE STUDY MAY END EARLY IN THE CIRCUIT WHERE EXPLICITLY SHOWN. AVAILABLE FAULT CONTRIBUTION SHALL BE MODELED AS INFINITE BUS AT EACH OF THE TRANSFORMERS UNLESS TRUE KNOWN CONTRIBUTION DATA IS AVAILABLE.
TRANSFER SWITCHES AND TIES ARE OPEN TRANSITION UNLESS EXPLICITLY NOTED OTHERWISE OR
FOUND TO BE OTHERWISE IN THE FIELD.
GENERAL NOTES:
4 4 4
4 4
AUTOMATIC TRANSFER SWITCH SCHEDULE
NAME AMPS VOLTAGE PHASE
NUMBER
OF POLES
NUMBER OF
WIRES BRANCH
BYPASS
ISOLATION
TRANSITION
TYPE
MIN. 3 CYCLE
WCR
MIN. 30 CYCLE
WCR MODEL PRIORITY REMARKS
ATS6 400 A 480 V 3 4 4 EQUIPMENT Yes OPEN 35KAIC - - 3 REPLACE IN
KIND
Mark Revisions: Date:
2 Revision 2 2026/10/30
4 Revision 4 2026/11/18
| AE701 - DOOR AND FRAME TYPES, DETAILS AND DOOR SCHEDULE |
| AE913 - INTERIOR ELEVATIONS |
| EV103 - FIRST FLOOR -ENLARGED LOW VOLTAGE PLAN 2 |
| E500 - DEMO ELECTRICAL ONE-LINE DIAGRAM |
| E501 - NEW ELECTRICAL ONE-LINE DIAGRAM |