Atch. 2_36C26027R0002 0007_Drawing E501-rv_531-25-102 Expand ED.pdf

PDF 1 MB Posted

Attached to
Y1DA--CON NRM 531-25-102 | Expand Emergency Room
Solicitation number
36C26027R0002-0007
Issued by

About this file

This document is a set of architectural and engineering construction drawings for the Expand Emergency Room project at Boise Veterans Affairs Medical Center (VAMC), located at 500 W Fort Street, Boise, Idaho 83702. The drawings are dated October 30, 2025, and represent a 100% Construction Documents (CD) submittal for Project Number 531-25-102, Building 85.

The drawings include comprehensive architectural details for doors, frames, windows, and interior elevations. Sheet AE701 contains a door and frame types schedule with 68 door entries specifying room locations, door sizes ranging from 2'-0" x 7'-0" to 8'-0" x 7'-2½", hardware configurations, door materials (wood, metal, aluminum, glass), door finishes, frame types (hollow metal or aluminum), and fire ratings (ranging from 45-minute to 90-minute ratings). Notable specialized requirements include blast-resistant and bullet-resistant doors for security-sensitive areas (waiting area, police lobby, vestibule), anti-barricade and anti-ligature features for mental health spaces, and self-closing mechanisms for utility rooms. Glass type specifications include security glass with glass-clad polycarbonate (1.25" thickness) and tempered float glass (6mm). The electrical sheets (E500, E501) document the existing and new electrical one-line diagrams, including transformer configurations, panelboard ratings up to 1600A, automatic transfer switches, and equipment connections. The project is fully sprinklered and involves coordination with mechanical systems, variable frequency drives, and hospital-essential power requirements. The design team includes Alesia Architecture P.C. (Elkhorn, Nebraska), Specialized Engineering Solutions (Omaha, Nebraska), Morrison-Maierle (Bozeman, Montana), and Crux Consulting (Omaha, Nebraska), with the U.S. Department of Veterans Affairs Office of Construction and Facilities Management as the contracting agency.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IL#1

8"

6" 6"

F

FLUSH

FG

FULL GLASS

8"

LG#132

8"

6" 6"

HG

HALD GLASS

S1

MANUAL SLIDING DOOR

LG#1

LG#1

CR1

OVERHEAD COILING DOOR

IL#2

8"

6" 6"

FG1

FULL GLASS

8"

2"

SCHEDULE

SEE DOOR 2" 2"

SCHEDULE

SEE DOOR 2" 2"

SCHEDULE

SEE DOOR 2"

4" S

E E

D O

O R

S C

H E

D U

LE

HOSPITAL

STOPS @

INTERIOR

DOORS

ONLY

EMERGENCY

RELEASE

STOPS 1H

HOLLOW METAL

HOLLOW METAL

HOLLOW METAL

2" S

E E

D O

O R

S C

H E

D U

LE

2" S

E E

D O

O R

S C

H E

D U

LE HOLLOW METAL FRAME

BOTTOM OF FRAME

4" MATCH EXISTING FRAMES

45°

TYP.

4"

HOLLOW METAL FRAME

WALL - SEE

PLAN FOR TYPE

WALL (WHERE OCCURS)

- SEE PLAN FOR TYPE

3' -6

W1

POLICE LOBBY WINDOW

16'-2"

2" 3'

-1 0"4' -0

W3

RECEPTION WINDOW

2" 3'

-2

2"

3' -6

W2

POLICE VESTIBULE WINDOW

2" 3'

-2

2"

3'-0"

2" 2'-8" 2"

5'-0"

2" 4'-8" 2"

T O

F

LO

O R

3' -0

T O

F

LO

O R

2' -7

T O

F

LO

O R

3' -0

3'-10" 2" 3'-10" 2" 3'-10" 2" 3'-10" 2"2"

1'-3 1/2" 1'-4" 1'-2 1/2"

4"

1/

2"

2' -0

IL#2 IL#2

IL#1

IL#1

IL#1

IL#1

IL#1

IL#1

IL#1

IL#1

AE701

AE701

2" 2'

-8

2"

3' -0

W4

ISOLATION VIEWING WINDOW

2'-0"

2" 1'-8" 2"

T O

F

LO

O R

3' -6

LG#1

AE701

AE701

AE701

4' -0

THREAT

SIDE

SECURE

SIDE

2' -0

1/

2"

ALUMINUM TUBE

ALUMINUM 2-PC CHANNEL

U.L RATED BULLET RESISTANT GLAZING

ARCH WINDOW

ALUMINUM U-CHANNEL

S/S RECESSED CURRENCY DEAL TRAY

COUNTER TOP

THREAT SIDE

SECURE SIDE 4"

1'-3" 1'-4" 1'-3"

3'-10"

4'-2"

2"2"

ALUMINUM TUBE

SCREWS TO SECURE

FRAME IN OPENING

U.L. RATED BULLET

RESISTANT GLAZING

ALUMINUM 2-PC CHANNEL

SEE PLAN

VARIES

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND - TYP.

HOLLOW METAL

FRAME

GLAZING

REMOVABLE STOP

LEAD

10/30/2025

S T

A

T E

O F G EOR

G I A

C E

R T

I F I C A T E N O . R A 0

1 5

R E

G I S T E R E D A R C H

I T E

C T

EDWIN SANTOS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

NE COA NUMBER: CA-0721

on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

EXPAND EMERGENCY ROOM

BOISE VAMC

531-25-102

500 W FORT ST, BOISE, ID 83702

A

B

C

D

E

F

EYS IJM

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050

Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590

A u to d e s k D o c s /1

-2

-1

E x p a n d

E m e rg e n c y R o o m V

A M

C B o is e /5

-2

-1

.A rc h

R

-E x p

E m e rg

R m

B o is e

V A

M C

.r v t

/1 /2

:2

:5

P

M

AE701

DOOR AND FRAME TYPES, DETAILS

AND DOOR SCHEDULE

2025.10.30

100% CD SUBMITTAL

DOOR SCHEDULE

DOOR NUMBER ROOM NAME DOOR SIZE HARDWARE DOOR MATERIAL DOOR TYPE DOOR FINISH FRAME TYPE

FRAME

MATERIAL FRAME FINISH FIRE RATING REMARKS

851000 WAITING PR 3'-6" x 7'-0" 1 MTL F P-1 1H HM P-1 S CR/DO, BLAST & BULLET

RESISTANT

851000A POLICE 3'6" x 7'-0" 3 MTL FG1 P-1 1H HM P-1 CR, BULLET & BLAST

RESISTANT

851002 RECEPTION 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

851003 RNOD OFFICE 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

851003B RECEPTION 8'-0" x 7'-2 1/2" 8 AL S1 P-1 1H AL P-1

851004 TRIAGE 8'-0" x 7'-2 1/2" 8 AL S1 AN - AL AN

851005 A1 - GENERAL EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN - AL AN

851006 A2- GENERAL EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN - AL AN

851007 A3 - GENERAL EXAM 3'-6" x 7'-0" 5 WD HG WD-1 1H HM P-1

851008 A4 - FAST TRACK EXAM 3'-6" x 7'-0" 5 WD HG WD-1 1H HM P-1

851009 A5 - MENTAL HEALTH 4'-0" x 7'-0" 13 WD HG WD-1 1H HM P-1 ANTI-BARRICADE, ANTI-LIGATURE

851009A A5 - MENTAL HEALTH 3'-10" X 7'-0" 11 STL CR1 AN - -

851009B A5 - MENTAL HEALTH 6'-0"x 7'-0" 11 STL CR1 AN - -

851011 SECLUSION ROOM 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR, ANTI-BARRICADE, ANTI-LIGATURE

851012 A6 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN

851013 TOILET 3'-6" x 7'-0" 7 WD F WD-1 3 HM P-1

851015 CLEAN UTILITY 3'-6" x 7'-0"

45-MIN

3 WD F WD-1 1H HM P-1 45MIN CR, SELF CLOSING &

LATCHING

851016 B8 - GEN EXAM 8'-0" x 7'-2 1/2" 8 GL S1 AN 1H AL P-1

851017 SOILED UTILITY 3'-6" x 7'-0"

45-MIN

3 WD F WD-1 1H HM P-1 45MIN CR, SELF CLOSING &

LATCHING

851018 B7 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN

851019 B4 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN

851020 B6 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN

851021 B5 - GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN

851023 HAC 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

851024 PHYS WORK 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

851025 PHYSICIAN WORK 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

851026 MEDICATION ROOM 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

851028A RESUSCITATION 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN

851028B RESUSCITATION 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN

851029 C2 - GYN EXAM 4'-0" x 7'-0" 5 WD F WD-1 1H HM P-1

851029A GYN TOILET 3'-6" x 7'-0" 7 WD F WD-1 3 HM P-1

851030 TOILET 3'-6" x 7'-0" 7 WD F WD-1 3 HM P-1

851031 ANTE 4'-0" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

851031A C3 - AIRBORNE INFECTION ISO 4'-0" x 7'-0" 6 WD F WD-1 3 HM P-1

851031B ISO TOILET 3'-6" x 7'-0" 7 WD F WD-1 1H HM P-1

851032 CORRIDOR 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN

851033 B1 GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL P-1

851036 B2 GEN EXAM 8'-0" x 7'-2 1/2" 8 AL S1 AN 1H AL AN

851037A DECONTAMINATION 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

851037B DECONTAMINATION 3'-6" x 7'-0" 2 MTL F P-1 4 HM P-1 CR

851038 BREAKROOM 3'-6" x 7'-0" 6 WD F WD-1 1H HM P-1

851040 OFFICE 3'-6" x 7'-0" 5 WD F WD-1 1H HM P-1

851041 OFFICE 3'-6" x 7'-0" 5 WD F WD-1 1H HM P-1

851042 OFFICE/SLEEP 3'-6" x 7'-0" 5 WD F WD-1 1H HM P-1

851044 VEST. PR 7'-0" x 7'-0" 12 MTL F P-1 1H HM P-1 CR/DO, BLAST RESISTANT, 14 GA STEEL

851050 FAMILY CONSULT 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

851051 STORAGE 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

C002 CORRIDOR 3'-6" x 7'-0" 3 WD F WD-1 1H HM P-1 CR

C004 CORRIDOR PR 3'-0" x 7'-0" 1 WD F WD-1 1H HM P-1 CR/DO

C004B CORRIDOR 3'-6" x 7'-0" 2 WD F WD-1 1H HM P-1 CR

C16B VEST. 4'-0" x 7'-0" 1 MTL FG FG 1H HM P-1 DO,CR, BULLET & BLAST

RESISTANT

E851014 ELEC PR 3'-0" x 7'-0" 4 WD F WD-1 1H HM P-1

E851027B ELEC PR 3'-0" x 7'-0"

45MIN

10 MTL F P-1 4 HM P-1 45MIN CR, SELF CLOSING &

LATCHING

E851034 ELEC 2'-0" x 7'-0" 3 WD F WD-1 1H HM P-1 45MIN CR

ST14 STAIR 3'-0" x 7'-0" 90MIN 2 WD F MTL 1H HM P-1 90MIN CR

1/4" = 1'-0"1

DOOR TYPES

FRAME TYPES

GLASS TYPE SCHEDULE

REF TYPE Description Thickness Remarks

IL#1 TYPE IL#1 SECURITY GLASS, GLASS CLAD POLYCARBONATE CLEAR 1.25" A,B

IL#2 TYPE IL#2 SECURITY GLASS, GLASS CLAD POLYCARBONATE CLEAR, TINTED 1.25" A,B

LG#1 TYPE LG#1 CLR, TEMPERED TONGLESS FLOAT 6MM (0.23") C

GLASS TYPE SCHEDULE NOTES:

A: COMPLY W/ VA-PSDM/UFC 4-0110-01 FORCE PROTECTION REQUIREMENTS

B: SEE SPECIFICATION SECTION 08 80 00: INSULATED LAMINATED GLASS SCHEDULE (FORCE PROTECTION AND PHYS SAFETY)

C: SEE SPECIFICATION SECTION 08 80 00: GLAZING

D: DOOR UNIT ASSEMBLY, COORDINATE WITH DOOR & HARDWARE SCHEDULE

1 1/2" = 1'-0"4

HOSPITAL STOPS

1 1/2" = 1'-0"3

DOOR FRAME OFFSET

1" = 1'-0"5

WINDOW FRAME TYPES

1" = 1'-0"6

RECEPTION WINDOW SECTION

1" = 1'-0"7

RECEPTION WINDOW PLAN

CR = CARD READER

DO = DOOR OPERATOR

3" = 1'-0"8

WINDOW FRAME DETAIL

Mark Revisions: Date:

2 Revision 2 2026/10/30

4 Revision 4 2026/11/18

FIRST FLOOR

100' - 0"

J.9 J.7 J.1 J

A5077

F3200

M3150

851026

RB-1

FIRST FLOOR

100' - 0"

G

F0206

F2000

F0410

E0703

M1801

A1015

F0275

RB-1

FIRST FLOOR

100' - 0"

3.8

F0275

M1801

E0703

F0410851050

RB-1

FIRST FLOOR

100' - 0"

G

F0410 F0205

RB-1

FIRST FLOOR

100' - 0"

3.8

F0205

F0206

F2000

RB-1

FIRST FLOOR

100' - 0"

32.8

M3150

A5077

F3200

E0945

R6200

RB-1

CG-1

FIRST FLOOR

100' - 0"

J.9J.7J.1J

R6200 A5106

F2010

E0945

RB-1

CG-1

AE904

FIRST FLOOR

100' - 0"

3 2.8

E0945

A5145

A5145

A5077

RB-1

FIRST FLOOR

100' - 0"

F3200

851011

WSF-1

FIRST FLOOR

100' - 0"

H

M7011

F3200

WSF-1

FIRST FLOOR

100' - 0"

H

M7011

WSF-1

FIRST FLOOR

100' - 0"

M7011

WSF-1

10/30/2025

S T

A

T E

O F G EOR

G I A

C E

R T

I F I C A T E N O . R A 0

1 5

R E

G I S T E R E D A R C H

I T E

C T

EDWIN SANTOS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

NE COA NUMBER: CA-0721

on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

EXPAND EMERGENCY ROOM

BOISE VAMC

531-25-102

500 W FORT ST, BOISE, ID 83702

A

B

C

D

E

F

EYS IJM

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050

Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590

A u to d e s k D o c s /1

-2

-1

E x p a n d

E m e rg e n c y R o o m V

A M

C B o is e /5

-2

-1

.A rc h

R

-E x p

E m e rg

R m

B o is e

V A

M C

.r v t

/1 /2

:0

:0

P M

AE913

INTERIOR ELEVATIONS

2025.10.30

100% CD SUBMITTAL

3/8" = 1'-0"4

MEDICATION ROOM 851026 - WEST ELEVATION

3/8" = 1'-0"6

FAMILY CONSULT 851050 - EAST ELEVATION

3/8" = 1'-0"7

FAMILY CONSULT 851050 - SOUTH ELEVATION

3/8" = 1'-0"8

FAMILY CONSULT 851050 - WEST ELEVATION

3/8" = 1'-0"5

FAMILY CONSULT 851050 - NORTH ELEVATION

3/8" = 1'-0"1

MEDICATION ROOM 851026 - NORTH ELEVATION

3/8" = 1'-0"2

MEDICATION ROOM 851026 - EAST ELEVATION

3/8" = 1'-0"3

MEDICATION ROOM 851026 - SOUTH ELEVATION

3/8" = 1'-0"11

SECLUSION 851011 - SOUTH ELEVATION

3/8" = 1'-0"10

SECLUSION 851011 - EAST ELEVATION

3/8" = 1'-0"12

SECLUSION 851011 - WEST ELEVATION

3/8" = 1'-0"9

SECLUSION 851011 - NORTH ELEVATION

Mark Revisions: Date:

4 Revision 4 2026/11/18

FEC

F E

C

N C

NC

N C

C R

CR

CR

D

NC

NC

Z Z

N C

N C

N

CD

D

D

CR

NC

D

T V

AC

AC

AC

N C

S

S

S

S

C

C

C C

CR

C

C

C

C R

NC

AC CR

C

P M

P M

P M

P M

PM

PM

AC

C R

A C A C

P M

C

C

N C

VI

DO

AC

AC

CR

CR

AC

N C

NC

AC CR

J

J

J.1

J.1

J.7

J.7

J.9

J.9

K.4

K.4

L.1

L.1

N

N

O

O

0.9 0.9

1 1

1.9 1.9

2 2

2.8 2.8

3 3

3.8 3.8

4 4

K.6

K.6

CORRIDOR

C002

C3 - AIRBORNE

INFECTION

ISO-1

851031A-1

ANTE

851031 NURSE ALC

C010

GYN TOILET

851029A

ISO TOILET

851031B

GEN EXAM

851033

ELEC

E851027

OMNI BANK

RESUSCITATION

851028

B3 - EXAM-1

851032-1

OFFICE/SLEEP

851042

OFFICE

851041

TOILET

851039

MEDICATION

ROOM

851026

MECH SHAFT

C2 - GYN EXAM

851029

TOILET

851030

EQUIPMENT

OFFICE

851040

BREAKROOM

851038

DECONTAMINATION

851037

GEN EXAM

851036

CORRIDOR

C001

PHYSICIAN

WORK

851025

BSID-STF/CODE

BSID-STF/CODE

APULL

APULL

DUTY

APULL

BSID-STF/CODE

BSID-STF/CODE

BSID-STF/CODE

W

CONS

44"

WAP

WAP

WAP

WAP

WAP

WAP

WAP

VEST.

C16B

CORRIDOR

C005

72"

BSID-STF/CODE

E

E300

AC

AC AC

E E

2D

W 2D

2D

W

W

2D

2D

W

2D

2D

2D

2D 2D

2D

2D

W 2D

4D

2D

2D

W

E

E

W

CONS

44"

W

2D

4D

2D

2D

DUTY

DED

MON

DED

MON

DED

MON

DED

MON

DED

MON

DED

MON

2D

2D

2D

2D

2D

2D

WS

STF/CODE

STF/CODE2

SYMBOL

FIRE WALL LEGEND

DESCRIPTION

1-HOUR FIRE BARRIER

2-HOUR FIRE BARRIER

SMOKE PARTITIONS S S S S

INSTALL GREEN INSULATED

GROUND WIRE WITH

LIGHTING, RECEPTACLE AND

EQUIPMENT BRANCH CIRCUITS.

INSTALL INDIVIDUAL (DEDICATED)

NEUTRAL CONDUCTORS FOR

EACH 120V OR 277V PHASE

CONDUCTOR SERVED FROM A

SINGLE POLE CIRCUIT BREAKER

TRUE

NORTH

PLAN

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

NE COA NUMBER: CA-0721

on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

EXPAND EMERGENCY ROOM

BOISE VAMC

531-25-102

500 W FORT ST, BOISE, ID 83702

A

B

C

D

E

F

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050

10/29/2025Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590

A u to d e s k D o c s /1

-2

-1

E x p a n d E m e rg e n c y R o o m V

A M

C B o is e /2

V

A B o is e E x p a n d E m e rg e n c y R o o m

S

E S

.r v t

/1 /2

:4

:0

A

M

EV103

FIRST FLOOR - ENLARGED LOW

VOLTAGE PLAN 2

MLW CRD2025.10.30

100% CD SUBMITTAL

1/4" = 1'-0"EV103

ENLARGED LV PLAN 21

SHEET NOTES:

1. PROVIDE NURSE CALL STATION AS WEATHERPROOF CORROSION RESISTANT TYPE.

Mark Revisions: Date:

1 Revision 1 2026/10/08

2 Revision 2 2026/10/30

4 Revision 4 2026/11/18

250AF

225AT

100AF/AT 400AF/AT

I

EDP1

480Y/277V

400A 3P/4W

DE

NDP1

480Y/277V

1200A 3P/4W

250AF/AT

LSI

E

250AF/AT

LSI

E

250AF/AT

LSI

D

400AF/AT

LSI

E

250AF/AT

LSI

D

250AF/AT

LSI

E

1200AF/AT

LSIG

E

480Y/277V

225A MCB

3P/4W E

CHILLER 3

480V 600A

E

PH2

480Y/277V

225A MCB

3P/4W E

E16 480Y/277V

100A MCB

3P/4W

E24 480Y/277V

100A MCB

3P/4W

EPH2

480Y/277V

100A MCB

3P/4W

E

E

E

E17 480Y/277V

400A MCB

3P/4W

EPH3

480Y/277V

225A MCB

3P/4W

E25 480Y/277V

400A MLO

3P/4W

E18 208Y/120V

225A MCB

3P/4W

EPH5

208Y/120V

225A MLO

3P/4W

EPH4

208Y/120V

225A MCB

3P/4W

T21

75KVA

480:208Y/120V

T14

75KVA

480:208Y/120V

E

E

EE

E

E

E

E

208Y/120V

175A MCB

3P/4W E

E

T10N

1000KVA

12.47KV:480/277V

T19

30KVA

480:208Y/120V

EDP3

480Y/277V

400A 3P/4W

E E

100AF/AT

E

70AF/AT

E

125AF/AT

E

100A E

E

D

E

D

E

E13A 208Y/120V

60A MCB

3P/4W

E13 208Y/120V

100A MCB

3P/4W

E11 208Y/120V

225A MCB

3P/4W

E12 208Y/120V

90A MCB

3P/4W

T3

30KVA

480:208Y/120V

150AF/AT

LSI

E

400AF

200AT

LSI

E

400AF/AT

LSI

E

SPARE

400AF/AT

LSI

E

400AF/AT

LSI

D

400AF/AT

LSI

E

CT

SCANNER

E

CT

SCANNER

/NM

E

XRAY

NO.1

E

XRAY

NO.2

E

XRAY

NO.4

E

400AF/AT

LSIG

E

150AF/AT

LSIG

E

400AF

200AT

LSIG

E

600AF/AT

LSIG

E

400AF

200AT

LSIG

E

400AF/AT

LSIG

E

400AF

300AT

LSIG

E

1200AF/AT

LSIG

E

EQ

ATS5

200A E

EXTERIOR

TEMP

POWER

E

T1

45KVA

480:208Y/120V

D

SHUNT TRIP

UROLOGY

GENERATOR

E (DISC.)

EQ

ATS2

400A

CR

ATS1

400A

LS

ATS3

150A

E EE

600AF/AT

LSI

E

T18

3KVA

277:120V

E19 120V

70A MLO

1P/2W

E

E

EMDP1

480Y/277V 1600A 3P/4W

NMDP1

480Y/277V

1600A 3P/4W

XRAY

NO.3

E

E E

150AF

100AT

LSIG

E

150AF

100AT

LSIG

E

E

T10E

1000KVA

12.47KV:480/277V

250AF

200AT

I E

400AF

300AT

I E

250AF

110AT

I E

400AF

400AT

I E

SPARE

EDP2

480Y/277V 400A 3P/4W E

40AF/AT

E

50AF/AT

E

SPARE

40AF/AT

E

60AF/AT

E

80A E

80AF/AT

E

70AF/AT

E

125AF/AT

E

EDP4

480Y/277V

400A MLO

3P/4W E

150AF

125AT

LSIG

E

150AF

125AT

LSIG

E

400AF/AT

LSIG

E

SPARE

400AF

200AT

LSIG

N.O.

E

150AF

125AT

E

SPARE

150AF

100AT

LSIG

E

1600AF/AT

LSIG, N.C.

E

"SERVICE ENTRANCE"

1600AF/AT

LSIG, N.C.

E

"SERVICE ENTRANCE"

1600AF/AT

LSIG, N.O.

E

EPH1

480Y/277V

225A MCB

3P/4W E

TO

BASEMENT,

T10/EG2

TO 3RD

FLOOR,

T8/31

TO

BASEMENT,

EG1

TO 2ND

FLOOR, E21

TO 2ND

FLOOR 24

TO 3RD

FLOOR, OR

PANEL E34

TO 3RD

FLOOR, OR

PANEL E35

E

T2

30KVA

480:208Y/120V

TO RM 140,

E14

400AF/AT

LSI

E

SPARE

TO

BASEMENT,

T11

TO

BASEMENT,

EMCC1

TO OLD

PENTHOUSE,

EMCC2

TO (7) 20A,

277V 1P

LIGHTING

CIRCUITS

TO OLD

PENTHOUSE,

EPH6

TO

BASEMENT,

T13

TO OLD

PENTHOUSE,

NMCC2

TO

BASEMENT,

NMCC1

TO 3RD

FLOOR, 31

TO 2ND

FLOOR, 21

TIEESSENTIAL

MAIN

NORMAL

MAIN

CR

ATS8

400A E

LS

ATS7

100A E

EQ

ATS6

225A

D

T15

75KVA

480:208Y/120V E

208Y/120V

225A MCB

3P/4W E

T20

75KVA

480:208Y/120V E

PH3A

208Y/120V

225A MCB

3P/4W E

PH3B

208Y/120V

225A MLO

3P/4W E

E23 480Y/277V

225A MCB

3P/4W E

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

NE COA NUMBER: CA-0721

on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

EXPAND EMERGENCY ROOM

BOISE VAMC

531-25-102

500 W FORT ST, BOISE, ID 83702

A

B

C

D

E

F

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050

10/29/2025Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590

A u to d e s k D o c s /1

-2

-1

E x p a n d E m e rg e n c y R o o m V

A M

C B o is e /2

V

A B o is e E x p a n d E m e rg e n c y R o o m

S

E S

.r v t

/1 /2

:4

:0

A

M

E500

DEMO ELECTRICAL ONE-LINE

DIAGRAM

MJF MLW2025.10.30

100% CD SUBMITTAL

NO SCALEE500

DEMO ELECTRICAL ONE-LINE1

SHEET NOTES:

1. REPLACE EXISTING BREAKER OR TRIP UNIT. SEE NEW ELECTRICAL ONE-LINE AND/OR PANEL SCHEDULES

FOR FURTHER INFORMATION.

2. DEMOLISH CONDUIT AND WIRE FROM SECOND FLOOR PANEL E23 TO PENTHOUSE ELECTRICAL PANEL EPH1.

3. CONDUIT AND WIRE TO REMAIN FOR RE-CONNECTION TO NEW.

4. REPLACE EXISTING PANEL WITH NEW, USING EXISTING CONDUIT AND WIRE. RE-CONNECT EXISTING CONDUIT

AND WIRE.

5. REPLACE EXISTING TRANSFORMER WITH NEW, USING EXISTING CONDUIT AND WIRE ON PRIMARY AND

INSTALLING NEW ON SECONDARY. SEE NEW ELECTRICAL ONE-LINE FOR FURTHER INFORMATION.

6. PULL EXISTING WIRE BACK TO CEILING TO BE SPLICED INTO NEW FEED. SEE NEW ONE-LINE DIAGRAM FOR

FURTHER INFORMATION.

11 1

3 3

4 4

GENERAL NOTES:

A. WHERE EXISTING CONDUIT AND WIRE IS EXPLICITLY STATED OR SHOWN AS TO BE RE-USED AND IT IS NOT

FEASIBLE TO RE-CONNECT TO THE NEW TERMINALS DUE TO SITE CONDITIONS:

• FOR 120V 20A CIRCUITS: PROVIDED THAT THE EXISTING CONDITION MEETS THE REQUIREMENTS SET

FORTH IN ALL GUIDING DOCUMENTS APPLICABLE TO THIS JOB (SUCH AS THE ELECTRICAL DESIGN MANUAL, NFPA 70 (2023), AND THE PROJECT SPECIFICATIONS), THE CONTRACTOR MAY CHOOSE TO SPLICE A CIRCUIT EXTENSION OF THE SAME CONFIGURATION, SIZE, AND INSULATION OF WIRE THROUGH

THE USE OF AN APPROVED JUNCTION BOX TO REACH THE NEW TERMINALS.

• FOR ALL OTHER CIRCUITS: SUBMIT RFI WITH REASONING, PROPOSED SOLUTION (IF DETERMINED), AND

ANY PROJECT IMPACTS FOR EVALUATION ON A CASE BY CASE BASIS.

B. WORK ON ELECTRICAL PANELS AND EQUIPMENT INCLUDING BUT NOT LIMITED TO EMDP1, NMDP1, EDP1, NDP1, AND ANY ITEMS ON THE EQUIPMENT BRANCH CIRCUIT WILL REQUIRE OUTAGES WHICH EXTEND BEYOND THE LIMITS OF THE PHYSICAL PROJECT AREA. CONTRACTOR SHALL COORDINATE WITH BOISE VAMC STAFF, COR, AND A/E TO MINIMIZE THE DURATION AND IMPACT OF THESE OUTAGES DURING PRE- CONSTRUCTION MEETINGS. THE WORK SHALL OCCUR DURING OFF PEAK HOURS. CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO LOADS ESSENTIAL TO THE SAFE OPERATION OF THE HOSPITAL FOR THE

DURATION OF THE OUTAGE.

Mark Revisions: Date:

2 Revision 2 2026/10/30

4 Revision 4 2026/11/18

400AF/AT

LSI

150AF

100AT

LSI

400AF/AT

LSI

EDP1

480Y/277V

800A 3P/4W

400AF/AT

LSI

E1-20 208Y/120V

125A MLO

3P/4W

E

NDP1

480Y/277V

1200A 3P/4W

250AF/AT

LSI

E

250AF/AT

LSI

E

400AF/AT

LSI

E

250AF/AT

LSI

E

1200AF/AT

LSIG

E

480Y/277V

225A MCB

3P/4W E

CHILLER 3

480V 600A

E

T15

75KVA

480:208Y/120V E

208Y/120V

225A MCB

3P/4W E

PH2

480Y/277V

225A MCB

3P/4W E

T20

75KVA

480:208Y/120V E

PH3A

208Y/120V

225A MCB

3P/4W E

E23 480Y/277V

225A MCB

3P/4W

E16 480Y/277V

100A MCB

3P/4W

E24 480Y/277V

100A MCB

3P/4W

EPH2

480Y/277V

100A MCB

3P/4W

E

E

E

E

E17 480Y/277V

400A MCB

3P/4W

EPH3

480Y/277V

225A MCB

3P/4W

E25 480Y/277V

400A MLO

3P/4W

E18 208Y/120V

225A MCB

3P/4W

EPH5

208Y/120V

225A MLO

3P/4W

EPH4

208Y/120V

225A MCB

3P/4W

T21

75KVA

480:208Y/120V

T14

75KVA

480:208Y/120V

E

E

EE

E

E

E

E

208Y/120V

225A MCB

3P/4W E

E

T10N

1000KVA

12.47KV:480/277V

T19

30KVA

480:208Y/120V

EDP3

480Y/277V

400A 3P/4W

E E

100AF/AT

E

70AF/AT

E

125AF/AT

E

100A E

E

E

E

E13A 208Y/120V

60A MCB

3P/4W

E11 208Y/120V

225A MCB

3P/4W

T3

30KVA

480:208Y/120V

150AF/AT

LSI

E

400AF

200AT

LSI

E

400AF/AT

LSI

E

SPARE

400AF/AT

LSI

E

800AF/AT

LSI

400AF/AT

LSI

E

CT

SCANNER

E

CT

SCANNER

/NM

E

XRAY

NO.1

E

XRAY

NO.2

E

XRAY

NO.4

E

400AF/AT

LSIG

E

150AF/AT

LSIG

E

400AF

200AT

LSIG

E

600AF/AT

LSIG

E

400AF

200AT

LSIG

E

400AF/AT

LSIG

E

400AF

300AT

LSIG

E

1200AF/AT

LSIG

E

EQ

ATS5

200A E

EXTERIOR

TEMP

POWER

E

T1

75KVA

480:208Y/120V

NEMA 1

SHUNT TRIP

UROLOGY

GENERATOR

E (DISC.)

EQ

ATS2

400A

CR

ATS1

400A

LS

ATS3

150A

E EE

600AF/AT

LSI

E

T18

3KVA

277:120V

E19 120V

70A MLO

1P/2W

E

E

EMDP1

480Y/277V 1600A 3P/4W

NMDP1

480Y/277V

1600A 3P/4W

XRAY

NO.3

E

E E

150AF

100AT

LSIG

E

150AF

100AT

LSIG

E

E

T10E

1000KVA

12.47KV:480/277V

250AF

200AT

I E

400AF

300AT

I E

250AF

110AT

I E

400AF

400AT

I E

SPARE

EDP2

480Y/277V 400A 3P/4W E

40AF/AT

E

50AF/AT

E

SPARE

40AF/AT

E

60AF/AT

E

80A E

80AF/AT

E

70AF/AT

E

125AF/AT

E

EDP4

480Y/277V

400A MLO

3P/4W E

150AF

125AT

LSIG

E

150AF

125AT

LSIG

E

400AF/AT

LSIG

E

SPARE

400AF

200AT

LSIG

N.O.

E

150AF

70AT

LSIG

E

150AF

100AT

LSIG

E

1600AF/AT

LSIG, N.C.

E

"SERVICE ENTRANCE"

1600AF/AT

LSIG, N.C.

E

"SERVICE ENTRANCE"

1600AF/AT

LSIG, N.O.

E

EPH1

480Y/277V

225A MCB

3P/4W E

TO

BASEMENT,

T10/EG2

TO 3RD

FLOOR,

T8/31

TO

BASEMENT,

EG1

TO 2ND

FLOOR, E21

TO 2ND

FLOOR 24

TO 3RD

FLOOR, OR

PANEL E34

TO 3RD

FLOOR, OR

PANEL E35

E

T2

30KVA

480:208Y/120V

TO RM 140,

E14

400AF/AT

LSI

E

SPARE

TO

BASEMENT,

T11

TO

BASEMENT,

EMCC1

TO OLD

PENTHOUSE,

EMCC2

TO (7) 20A,

277V 1P

LIGHTING

CIRCUITS

TO OLD

PENTHOUSE,

EPH6

TO

BASEMENT,

T13

TO OLD

PENTHOUSE,

NMCC2

TO

BASEMENT,

NMCC1

TO 3RD

FLOOR, 31

TO 2ND

FLOOR, 21

TIEESSENTIAL

MAIN

NORMAL

MAIN

CR

ATS8

400A E

LS

ATS7

100A E

EQ

ATS6

400A

NEMA 1

800AF/AT

LSI

208Y/120V

125A MLO

3P/4W

E12

PANEL

125A MCB

3P/4W

E13 208Y/120V

125A MCB

3P/4W

150AF

100AT

LSI

208Y/120V

125A MCB

3P/4W

T17

45KVA

480:208Y/120V

NEMA 1

40N 40N

80N

45T 75T

12N12N

AHU-18

480V

SF-18

7.5HP

HRCP-1

2HP

VFD-HRCP-1VFD-SF-18

EF-32A

2HP

VFD-EF-32A

EF-32B

2HP

VFD-EF-32B

30A/3P NF

NEMA 3R

CP-AHU-8

480V

60A MCB

SF-8

15HP

EF-8

7.5HP

30A/3P NF

NEMA 3R

3 6

2 2

PH3B

208Y/120V

225A MLO

3P/4W E

40N

22N 22N

225AF/AT

LSI

225AF/AT

LSI

E1-21 480Y/277V

400A 3P/4W

35KAIC

9 9 9 9 9 2

9 9 9

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

NE COA NUMBER: CA-0721

on e ei gh th in ch o ne f oo t th re e in ch es o ne f oo t

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs in ch o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

EXPAND EMERGENCY ROOM

BOISE VAMC

531-25-102

500 W FORT ST, BOISE, ID 83702

A

B

C

D

E

F

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Morrison-Maierle 2880 Technology BLVD Bozeman, Montana 59718 Phone: (406)442-3050

10/29/2025Crux Consulting 663 N 132nd St #7373 Omaha, NE 68154 Phone: (402)208-9590

A u to d e s k D o c s /1

-2

-1

E x p a n d E m e rg e n c y R o o m V

A M

C B o is e /2

V

A B o is e E x p a n d E m e rg e n c y R o o m

S

E S

.r v t

/1 /2

:4

:0

A

M

E501

NEW ELECTRICAL ONE-LINE DIAGRAM

MJF MLW2025.10.30

100% CD SUBMITTAL

NO SCALEE501

NEW ELECTRICAL ONE-LINE1

SHEET NOTES:

1. REPLACE EXISTING BREAKER WITH NEW BREAKER OF SAME MAKE AND MODEL WITH NEW RATING AS

INDICATED.

2. CONTROL PANEL/ELECTRICAL PANEL TO BE SUPPLIED WITH AHU-18. SEE 'EQUIPMENT CONNECTION

SCHEDULE' SHEET E700.

3. NEMA 4X SST CONTROL PANEL WITH VFD'S INTERNAL AND NEMA 4X SST ATTACHED AC UNIT. SEE "VARIABLE

FREQUENCY DRIVE SCHEDULE" SHEET M600 FOR FURTHER INFORMATION ON CP-AHU-18.

4. SIZE CONDUCTOR TO BE RATED TO NO LESS THAN 115% OF THE MAXIMUM OUTPUT AMPS OF THE DRIVE AND IN ACCORDANCE WITH THE NEC, NO SMALLER THAN #10. SIZE CONDUIT TO MEET THE CONDUIT FILL REQUIREMENTS SET FORTH IN THE NEC, NO SMALLER THAN 1". RUN UNBROKEN GROUND OF SAME SIZE AS

PHASE CONDUCTOR BETWEEN DRIVE OUTPUT AND MOTOR.

5. SPLICE NEW FEED ONTO EXISTING USING APPROVED METHODS SET FORTH IN THE PROJECT

SPECIFICATIONS. SUBMIT PRODUCT DATA AND EQUIPMENT INFORMATION FOR APPROVAL.

6. NEW 18 POLE/6 SLOT 400A MLO PANELBOARD WITH FULLY ADJUSTABLE ELECTRONIC TRIP FEEDER BREAKERS AS SHOWN. PROVIDE (1) SPARE BREAKER OF MATCHING TYPE TO THE OTHER (2) BEING

PROVIDED.

7. SEE DRY TYPE TRANSFORMER GROUNDING DETAIL SHEET E601.

8. REPLACE EXISTING TRIP UNIT WITH NEW, RATED AS INDICATED.

9. THE SCOPE OF THE POWER SYSTEM STUDY MAY END EARLY IN THE CIRCUIT AT THIS LOCATION WHICH

SHALL BE MODELED AS A BUS.

11 1

FEEDER SCHEDULE - COPPER

FEEDER NOMINAL SIZE WIRE AND CONDUIT

2 20 A 3-#12 CU, #12 CU GND - 3/4" C.

3 30 A 3-#10 CU, #10 CU GND - 3/4" C.

6 60 A 3-#4 CU, #10 CU GND - 1" C.

7 70 A 3-#4 CU, #8 CU GND - 1-1/4" C.

12N 125 A 4-#1/0 CU, #6 CU GND - 2" C.

22N 225 A 4-250 KCMIL CU, #4 CU GND - 3" C.

40N 400 A 4-#4/0 CU, #3 CU GND - 2-1/2" C. (2 SETS)

45T 150 A 4-#2/0 CU, #4 CU GND - 2"C.

75T 250 A 4-300 KCMIL CU, #2 CU GND - 3"C.

80N 800 A 4-350 KCMIL CU, #1/0 CU GND - 3" C. (3 SETS)

A. WHERE EXISTING CONDUIT AND WIRE IS EXPLICITLY STATED AS TO BE RE-USED AND IT IS NOT FEASIBLE

TO RE-CONNECT TO THE NEW TERMINALS:

• FOR 120V 20A CIRCUITS: PROVIDED THAT THE EXISTING CONDITION MEETS THE REQUIREMENTS SET

FORTH IN ALL GUIDING DOCUMENTS APPLICABLE TO THIS JOB (SUCH AS THE ELECTRICAL DESIGN MANUAL, NFPA 70 (2023), AND THE PROJECT SPECIFICATIONS), THE CONTRACTOR MAY CHOOSE TO SPLICE A CIRCUIT EXTENSION OF THE SAME CONFIGURATION, SIZE, AND INSULATION OF WIRE

THROUGH THE USE OF AN APPROVED JUNCTION BOX TO REACH THE NEW TERMINALS.

• FOR ALL OTHER CIRCUITS: SUBMIT RFI WITH REASONING, PROPOSED SOLUTION (IF DETERMINED), AND

ANY PROJECT IMPACTS FOR EVALUATION ON A CASE BY CASE BASIS.

B. FURTHER INFORMATION REGARDING ELECTRICAL PANELS AND CIRCUITS CAN BE FOUND IN THE

ELECTRICAL PANEL SCHEDULES ON SHEETS E701 THROUGH E705.

C. NOT ALL ELECTRICAL OR MECHANICAL EQUIPMENT IS SHOWN ON THIS ONE LINE DIAGRAM. FOR READABILITY, THE ENGINEER HAS OMITTED PORTIONS OF THE DISTRIBUTION SYSTEM ASSOCIATED WITH

THE FACILITY.

D. THE ENGINEER HAS INCLUDED ON THIS SHEET SELECTED 480V MECHANICAL EQUIPMENT WHICH HAS CIRCUITING WHICH WOULD BE OTHERWISE DIFFICULT TO DEPICT. VERIFY THE WIRING AND CONDUIT REQUIREMENTS ON THIS SHEET WITH THE ELECTRICAL REQUIREMENTS OF THE EQUIPMENT AS SHOWN IN

THE 'EQUIPMENT CONNECTION SCHEDULE' ON SHEET E700 AND ON THE MECHANICAL SHEETS.

REGARDLESS OF THE LOCATION OF THE INFORMATION, THE CONTRACTOR IS REQUIRED TO PROVIDE CONDUIT AND WIRE FROM SOURCE TO LOAD IN ACCORDANCE WITH THE PROJECT DOCUMENTS AND NEC

INCLUDING WHERE EQUIPMENT SUPPLIED UNDER THE MECHANICAL SCOPE (SUCH AS VFDS AND

MANUFACTURER PROVIDED PANELS) EXIST IN THE MIDDLE OF THE CIRCUIT.

E. WORK ON ELECTRICAL PANELS AND EQUIPMENT INCLUDING BUT NOT LIMITED TO EMDP1, NMDP1, EDP1, NDP1, AND ANY ITEMS ON THE EQUIPMENT BRANCH CIRCUIT WILL REQUIRE OUTAGES WHICH EXTEND BEYOND THE LIMITS OF THE PHYSICAL PROJECT AREA. CONTRACTOR SHALL COORDINATE WITH BOISE VAMC STAFF, COR, AND A/E TO MINIMIZE THE DURATION AND IMPACT OF THESE OUTAGES DURING PRE- CONSTRUCTION MEETINGS. THE WORK SHALL OCCUR DURING OFF PEAK HOURS. CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO LOADS ESSENTIAL TO THE SAFE OPERATION OF THE HOSPITAL FOR THE

DURATION OF THE OUTAGE.

F. THE EXISTING POWER SYSTEM STUDY FOR THE CAMPUS IS TO BE PROVIDED TO THE CONTRACTOR FOR

UPDATING BASED ON THESE PROJECT DOCUMENTS AND THE CONDITIONS IN THE FIELD. THE

CONTRACTOR SHALL INCLUDE ALL FIELD INVESTIGATION AND MODELING REQUIRED TO EXECUTE THE REQUIREMENTS OF SPECIFICATION 26 05 73 IN THE BID. THE STUDY SHALL BEGIN AT T10E/T10N AND EXTEND THROUGH THE LAST BRANCH BREAKER EXCEPT WHERE THE STUDY MAY END EARLY IN THE CIRCUIT WHERE EXPLICITLY SHOWN. AVAILABLE FAULT CONTRIBUTION SHALL BE MODELED AS INFINITE BUS AT EACH OF THE TRANSFORMERS UNLESS TRUE KNOWN CONTRIBUTION DATA IS AVAILABLE.

TRANSFER SWITCHES AND TIES ARE OPEN TRANSITION UNLESS EXPLICITLY NOTED OTHERWISE OR

FOUND TO BE OTHERWISE IN THE FIELD.

GENERAL NOTES:

4 4 4

4 4

AUTOMATIC TRANSFER SWITCH SCHEDULE

NAME AMPS VOLTAGE PHASE

NUMBER

OF POLES

NUMBER OF

WIRES BRANCH

BYPASS

ISOLATION

TRANSITION

TYPE

MIN. 3 CYCLE

WCR

MIN. 30 CYCLE

WCR MODEL PRIORITY REMARKS

ATS6 400 A 480 V 3 4 4 EQUIPMENT Yes OPEN 35KAIC - - 3 REPLACE IN

KIND

Mark Revisions: Date:

2 Revision 2 2026/10/30

4 Revision 4 2026/11/18

AE701 - DOOR AND FRAME TYPES, DETAILS AND DOOR SCHEDULE
AE913 - INTERIOR ELEVATIONS
EV103 - FIRST FLOOR -ENLARGED LOW VOLTAGE PLAN 2
E500 - DEMO ELECTRICAL ONE-LINE DIAGRAM
E501 - NEW ELECTRICAL ONE-LINE DIAGRAM

File details come from the government source that posted it. Updated .