A3. Panels_Annunciators_Redacted.pdf

PDF 78 KB Posted

Attached to
Fire Protection & Life Safety Inspection, Testing, and Certification (ITC) for Spokane WA VAMC
Solicitation number
36C26024Q0901
Issued by

About this file

This document is a fire alarm system inspection report for the VA MED CENTRE CAMPUS in Spokane, Washington. It provides details on the monthly fire alarm system inspection conducted on July 8, 2023, including the types of equipment tested, the test results, and the system performance. All tests were reported as satisfactory. The report is signed by the fire alarm firm representative.

The related federal contract opportunity is a solicitation for Fire Protection & Life Safety Inspection, Testing, and Certification (ITC) services for the Mann-Grandstaff (Spokane) VAMC. It is a base plus four option year contract, and is a 100% Small Business Set-aside. Interested vendors are required to submit quotes in four parts as specified in Section E.2., and the award will be based on the criteria outlined in Section E.6. The solicitation number is 36C26024Q0901, and the contract is planned to begin in FY25, subject to availability of funds.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM SYSTEM

Report of Inspection

Date 7-8-23 of facility VA MED CENTRE CAMPUS

Occupied as _HOSPITAL

Address 4815 N ASSEMBLY_____________________ City _____SPOKANE_________

County __SPOKANE_____________ Zip __99205________ Telephone ___________________

Building designation (if more than one building) _____________________________

_________________ Title __service tech_______________

Date of inspection 7-9-22_______

1. Type of test: monthly [ ] quarterly [ ] semi-annual [ ] annual [X ]

2. Type of system: non-coded [X ] common coded [ ] selective coded [ ] dual coded [ ]

3. Local Fire Department ______

4. Fire Department official contacted ________

5. Comments, explanation of unsatisfactory results, action taken, repairs made, etc.

______ALL TEST GOOD

Type of Equipment

# of Units

Tested

Test Date

Satisfactory Check

Yes No N/A

Type and Manufacturer

6. Control panel 17 7-8-23 X EST 3

7. Manual station 187 7-8-23 X SIGA-278

8. Heat detectors 44 7-8-23 X SIGA HRS HFC

9. Smoke detectors 474 7-8-23 X SIGA -PS

10. Audible alarms 176 7-8-23 X EST-GIRF/G4RF

11. Visual alarms 188 7-8-23 X EST

12. Duct detectors 119 7-8-23 X EST

13. Auto. Security door releases

14. Trouble indicators 21 7-8-23 X FACP

15. Charger 47 7-8-23 X FACP/BPS

16. Generator

17. Ventilation control relays

18. Fire door holders

19. Central station interconnection 1 7-8-23 X TELCO

20. Exterior sprinkler electric alarm bell

21. Sprinkler water flow switch TESTED BY

22. Sprinkler gate valve tamper switch

OTHERS

23. Annunciators 4 7-8-23 X EST3

Tested battery % or

System Demand Design total

Load Test

Satisfactory

Battery description, size, and how many

Amp Draw

Standby or test %

Batt. #1

Amp Draw

Alarm or test %

Batt. #2

Load Test

Type.

Amp Hour

Available

Yes

No

24. BATT 18VOLT .241 .248 NO AC 18 HOUR X

25. Automatic time delay of general alarm _____0_____ minutes. None installed [X ]

26. Test of alarm system on emergency power satisfactory? Yes [x ] No [ ]

27. This is to certify that this fire alarm system has been properly inspected and functions as designed covering the times listed in this report and is consistent with local and NFPA Fire Alarm Maintenance Standards.

A. Signature of owner or representative ________________________________________________________

B. Signature of fire alarm firm representative

28. Smoke detector sensitivity testing provided:

A. Yes, service form attached and copy filed with owner. Comments:_________________________________

B. No, owner refused. Comments: ___________________________________________________________

C. NA (not applicable or not due). Comments: ___not due____________________________________ a:servfrms.doc rev. 12/21/2011

File details come from the government source that posted it. Updated .