About this file

This document is a Monthly Eyewash and Shower Inspection Report for July 2024, covering multiple buildings and locations within a Veterans Health Administration facility. The comprehensive inspection checklist details 56 different eyewash stations, shower/eye stations, and sink eye stations across buildings numbered 1-590, tracking critical safety equipment parameters including water clarity, obstructions, condition of unit, and tepid water requirements.

The inspection reveals several notable observations: multiple units were noted as having low pressure (Buildings 1, 6, and 14), some units had broken caps or positioning issues not meeting six-inch clearance requirements, and specific locations like the Pharmacy/Chemo Room, Vet Clinic, and Hazmat area had unique comments. Two eyewash ports in Building 2 were marked as "Surplus - Not functional," and the Hazmat 38 eyewash port was found at 0 PSI and subsequently refilled to 100 PSI. Most units were marked as "Good" condition with clear water and no obstructions, indicating generally maintained safety equipment across the facility.

View the file

Other files

File Type Posted
36C25925Q0223 0003_1.docx DOCX document
36C25925Q0223 0003.docx DOCX document
Questions asked in reference to Solicitation 36C25925Q0223.docx DOCX document
36C25925Q0223 0002_1.docx DOCX document
36C25925Q0223 0002.docx DOCX document
AED Locations 2025_0103.docx DOCX document
36C25925Q0223 0001_1.docx DOCX document
January 2025.xlsx XLSX spreadsheet
36C25925Q0223 0001.docx DOCX document
36C25925Q0223.docx DOCX document
36C25925Q0223_1.docx DOCX document
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INSPECTED CLARITY CONDITION TEPID

✔ ROOM BLDG. TYPE OF WATER OBSTRUCTIONS OF UNIT Y/N COMMENTS

✔ GB01B-1 1 Eyewash Clear None Good Y Pharmacy

✔ GB01D-1 1 Eyewash Clear None Poor Y Pharmacy/Chemo Room - No Pressure

✔ GC04A-1 1 Eyewash Clear None Good Y Biomed

✔ 3B01B-1 1 Sink Eye Clear None Poor Y Paddle Broken

✔ 3B01C-1 1 Sink Eye Clear None Poor Y No Pressure

✔ 4D27A-1 1 Sink Eye Clear None Poor Y No Pressure

✔ 4D27B-1 1 Sink Eye Clear None Poor Y No Pressure

✔ 4D28-1 1 Eyewash Clear None Good Y

✔ GA04-2 2 Shower/Eye Clear None Good Y

✔ GA10-2 2 Eyewash-Port Clear None Good Y

✔ GA22-2 2 Shower/Eye Clear None Good Y

✔ GC05-2 2 Shower/Eye Clear None Good Y Low Pressure

✔ GC09-2 2 Eyewash-Port Clear None Good Y PSI 70, refilled to 80

✔ GC15-2 2 Shower/Eye Clear None Good Y Hits Ceiling, Not 6 inches

✔ GC27 2 Eyewash/Port Clear None Good Y

✔ GC27-2 2 Shower/Eye Clear None Good Y

✔ 1C42-2 2 Shower/Eye Clear None Good Y

✔ 1D17-2 (Hall) 2 Shower/Eye Clear None Good Y Not 6 inches away from drinking fountain

MONTHLY EYEWASH AND SHOWER

Jul-24

MONTHLY EYEWASH AND SHOWER

Jul-24

✔ 1D17-2 2 Eyewash-Port NA None Good Y PSI 69, refilled to 80

✔ 1D23-2 2 Eyewash Clear None Good Y

✔ 1D29-2 2 Eyewash-Port NA None Good Y

✔ 1D24-2 2 Shower/Eye Clear None Good Y Need six inches of clearance/cap broken

✔ 1D30 2 Eyewash-Port NA None Good Y

✔ 2A09-2 2 Shower/Eye Clear None Good Y

✔ 2A12-2 2 Shower/Eye Clear None Good Y Broken Cap

✔ 2A19-2 2 Eyewash-Port NA None Good Y

✔ 2A17-2 2 Shower/Eye Clear None Good Y

✔ 2A17-2 2 Eyewash-Port NA None Good Y PSI 72, refilled to 80

✔ 2A33-2 2 Shower/Eye Clear None Good Y

✔ 2C40-2 2 Shower/Eye Clear None Good Y

✔ 2C43 2 Shower/Eye Clear None Good Y

✔ 2D15-2 2 Shower/Eye Clear None Good Y

✔ 2D27-2 2 Shower/Eye Clear None Good Y

✔ 2D23 2 Eyewash-Port NA None Good Y PSI 64, refilled to 80

✔ 2D25-2 2 Eyewash-Port NA None Good Y PSI 74, refilled to 80

MONTHLY EYEWASH AND SHOWER

Jul-24

✔ 1A07-5 5 Shower/Eye Clear None Good Y

✔ 1A16-5 - Kit 5 Shower/Eye Clear None Good Y

✔ 1A33 5 Eyewash-Port Clear None Good Y

✔ 1B01-SW-6 6 Eyewash Clear None Good Y Low Pressure

✔ 1B01-SE-6 6 Shower/Eye Clear None Good Y Low Pressure

✔ 1A31-6 6 Shower/Eye Clear None Good Y

✔ 1C05-6 6 Shower/Eye Clear None Good Y Not 6 inches from cabinet or other obstruction.

✔ 1C04-6 6 Eyewash Clear None Good Y

✔ Warehouse-7 7 Shower/Eye Clear None Good Y

✔ Warehouse-7 7 Eyewash Clear None Good Y

✔ 1A01 7 Sink/Eye Clear None Good Y Vet Clinic - Broken Cap

✔ 1A15-7 7 Shower/Eye Clear None Good Y Vet Clinic - Not 6 inches away from ceiling

✔ 1A30 7 Eyewash-Port NA None Good Y Vet Clinic

✔ 1A02B 8 Sink/Eye Clear None Good Y In Canteen

✔ G03A-8 8 Shower/Eye Clear None Good Y

✔ BA040 14 Eyewash Clear None Good Y Morgue-Basement

✔ BC02 14 Eyewash-Port NA None Good Y Pesticide Room - Solution Changed

✔ 1B15-14 14 Eyewash Clear None Good Y

MONTHLY EYEWASH AND SHOWER

Jul-24

✔ 1B24-14 14 Shower/Eye Clear None Good Y Hematology

✔ 1A12 14 Shower/Eye Clear None Good Y Blocked

✔ 1A06C-14 14 Eyewash Clear None Good Y

✔ 1A06A-14 14 Eyewash Clear None Good Y

✔ 1A04A-14 14 Eyewash-Port Clear None Good Y

✔ 1B18A-14 14 Eyewash Clear None Good Y

✔ 1B20-14 14 Eyewash Clear None Good Y

✔ 2B41B 14 Eyewash-Port NA None Good Y

✔ 2B42B 14 Eyewash-Port NA None Good Y

✔ 2B26 14 Eyewash-Port NA None Good Y Solution Changed

✔ 2C08-14 14 Eyewash Clear None Poor Y Low Pressure

✔ 2C28-14 14 Eyewash Clear None Good Y

3B36-14 14 Eyewash Clear None Good Y

3B38-14 14 Eyewash Clear None Good Y

✔ 1A00-27 27 Shower/Eye Clear None Good Y

✔ 106-38 38 Shower/Eye Clear None Good Y

✔ Hazmat 38 38 Eyewash-Port NA None Poor Y 0 PSI - Refilled to 100psi

MONTHLY EYEWASH AND SHOWER

Jul-24

✔ 100-42 42 Shower/Eye Clear None Good Y

✔ GA15-45 45 Shower/Eye Clear None Good Y

✔ GA08 45 Eyewash-Port NA None Good Y

✔ 1A17 47 Eyewash Clear None Good Y

✔ 1A18 47 Eyewash Clear None Good Y

✔ Dental Lab 590 Eyewash Clear None Good Y

✔ GB09 2 Eyewash-Port Clear None Good Y Surplus - Not functional

✔ GB09 2 Eyewash-Port Clear None Good Y Surplus - Not functional

✔ 18 18 3x Eyewash-Por Clear None Good Y Solution Changed

SUBMITTED BY: _________________________