RFI for Temp Sensors 12 20 2023.docx
DOCX document 25 KB Posted
- Solicitation number
- 36C25924Q0041
About this file
This request for information (RFI) concerns a federal solicitation to convert temperature sensors to wireless thermostats at various Department of Veterans Affairs locations. The solicitation number is 36C25924Q0041 for project Z2DA--666-24-122 B64. The RFI clarifies that not all temperature sensors listed in the project plans need replacement, excluding those in rooms 152 and 237. It also confirms the existing controllers are Trane Tracer Ensemble models compatible with Trane Tracer Ensemble thermostats. The RFI additionally requires that any wiring abandoned in place during sensor removal must be labeled on both ends to indicate its origin and destination locations using printed stickers.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S04 - Site Visit Meeting Doc 12.12.docx | DOCX document | |
| 36C25924Q0041 0001.docx | DOCX document | |
| Sign in Sheet B64 Wireless Temp Sensors.pdf | ||
| 36C25924Q0041_1.docx | DOCX document | |
| 6 Drawings B64 Temp Sensor.pdf | ||
| Past Performance Questionnaire.docx | DOCX document | |
| P02_ Specifications666-24-122 B64.pdf | ||
| S22- 852.219-75 LOS Certificaiton.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1) During the site visit it was brought to our attention that not all the temperature sensors called out for replacement actually needed to be replaced as some were within the 18" of the knob side of the door as required. However the plans list ALL the thermostats.
Can you please have the plans updated or give us an updated count needed.
Replace all temperature sensors indicated on the plans except the one in rooms 152, and 237 on the rock walls. Disregard general note 2.
2) Concerning solicitation 36C25924Q0041 convert to wireless thermostats, could you please confirm that the current VAV controllers are the Trane Tracer Ensemble Controllers?
The existing thermostats are Trane Tracer Ensemble compatible.
3) Where temperature sensors are removed, and control wiring is abandoned in place do the wires need labeled. Answer – Yes label the wires on each end to where they go such as BC-1 on the room side, and room ### on the BC or controller side. Label with typed printed sticker.