S05 - RFIs and Responses FINAL.pdf

PDF 163 KB Posted

Attached to
Z2DA--VETERANS HEALTH-PRIVACY AND DECENCY
Solicitation number
36C25923R0084
Issued by

View the file

Other files

File Type Posted
36C25923R0084 0005.docx DOCX document
36C25923R0084 0004.docx DOCX document
S06 - ICRA Template.pdf PDF
36C25923R0084 0003.docx DOCX document
Veterans Health Sheridan VAMC Takeoff 06142023.pdf PDF
S05 - RFI for Curtain Fabrics_Color.pdf PDF
36C25923R0084 0002.docx DOCX document
S04 - Site Visit Sign-In Roster 06142023.pdf PDF
S04 - Site Visit Meeting Doc_Vet Health.pdf PDF
36C25923R0084 0001.docx DOCX document
S05 - RFIs and Responses 2023.pdf PDF
S02 - Design Alert.pdf PDF
S02 - Specifications.pdf PDF
S02 - Drawings.pdf PDF
36C25923R0084_1.docx DOCX document
S22 - Blank LOS Cert.docx DOCX document
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project: 666-19-104 Veteran’s Health-Privacy and Decency Sheridan VAMC RFI’s

Solicitation: 36C25923R0084

1. Drawing A-106 shows that we have to build walls with bifold doors. During the walk through today we noticed that there are walls already built. Do you know what the construction of the walls are? Do we just cut the existing walls and install the bifold doors?

Also do you know what is behind the walls?

A: Prior to submittal and after design the VA changed the purpose of the room in question.

Per the VA the work to install a closet and bifold door in that room is omitted from the project.

2. On the same drawing in the same room there is a blank cover on the wall under the lavatory. Do you know if there is power behind the blank cover or what is the blank cover for? The sink that is called to be installed takes power and we need to know if we have to run new power or if we can tie into whatever is behind the blank cover? If there is no power close can we run exposed conduit on the wall to provide power?

A: Due to the change in the purpose of that room, an electrically controlled RADA faucet cannot be installed. Omit the installation of a new sink and faucet in this room. A new sink with an anti-ligature faucet will be added by the VA at a later date.