This solicitation is seeking general contractor firms to provide construction services for upgrading an existing fire alarm system at the Oklahoma City Veterans Affairs Medical Center. The scope of work includes modifying and upgrading the facility's fire alarm system to bring it into compliance with NFPA 72, and involves construction items such as adding, modifying, and replacing fire alarm system components in various buildings and areas. Key requirements include furnishing all labor, materials, equipment and supervision to meet upgrade needs; complying with all applicable safety codes and standards; coordinating work to minimize interference with medical center operations; and obtaining any necessary licenses and certifications. The period of performance is 300 days from the notice to proceed.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BOILER PLANT BASEMENT
HAS NO EXISTING AUDIBLE
OR VISUAL NOTIFICATION.
SUBBASEMENT HAS NO
EXISTING AUDIBLE OR
VISUAL NOTIFICATION.
SUBBASEMENT HAS NO
EXISTING AUDIBLE OR
VISUAL NOTIFICATION.
SUBBASEMENT HAS NO
EXISTING AUDIBLE OR
VISUAL NOTIFICATION.
SUBBASEMENT HAS NO
EXISTING AUDIBLE OR
VISUAL NOTIFICATION.
SUBBASEMENT HAS NO
EXISTING AUDIBLE OR
VISUAL NOTIFICATION.
FA10SB
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
SUBBASEMENT NOTES:
THE SUB-BASEMENT IS CURRENTLY ON THE OLD SPECTRONICS SYSTEM. WORK ON THIS
LEVEL INCLUDES THE FOLLOWING:
1. CONVERT ALL EXISTING DEVICES FROM THE SPECTRONICS SYSTEM TO THE
FCI/GAMEWELL SYSTEM.
2. REPLACE 8 EXISTING MONITOR MODULES WITH NEW TO SUPERVISE 8 EXISTING TAMPER
SWITCHES. SPECTRONICS ADDRESSES FOR THESE 8 TAMPERS ARE: 01-28-29, 01-28-30,
01-28-32, 01-28-34, 01-28-36, 01-28-91, 01-28-92, & 01-28-93
3. INSTALL MONITOR MODULES TO SUPERVISE THE EXISTING FIRE PUMP (QUANTITIES AND
DETAILS TO BE PROVIDED AT 65%)
4. REPLACE 4 SPECTRONICS RELAY MODULES WITH NEW FCI/GAMEWELL MODULES
5. REPLACE PULL STATION AT STAIRWELL 4 WITH NEW
6. REPLACE THE FOLLOWING SPECTRONICS MONITORING POINTS WITH NEW
FCI/GAMEWELL MODULES:
6.1. DISCHARGE WATERFLOW - 01.28.33
6.2. WEST WALL BELOW LAUNDRY - 01.28.31
6.3. CENTER OF SUB-BASEMENT - 01.28.35
6.4. WATER FLOW 28 - 01.28.28
7. INSTALL AUDIBLE AND VISUAL NOTIFICATION THROUGHOUT LEVEL
8. CONVERT LOCKED TAMPER SWITCHES TO ELECTRONICALLY SUPERVISED TAMPER
SWITCHES, CONNECT TO FIRE ALARM SYSTEM
OVERALL SUB-BASEMENT PLAN
FA10SB
OVERALL SUB-BASEMENT PLAN
1/32" = 1'-0"
NOTE: OVERALL FLOORPLAN IS INTENDED TO ILLUSTRATE SCOPE OF WORK AREAS FOR
THIS PROJECT. REFER TO INDIVIDUAL AREAS FOR MORE DETAILS ON FIRE ALARM WORK.
PERFORMANCE CRITERIA FOR OCCUPANT NOTIFICATIONS:
1. AUDIBILITY SHALL BE IN ACCORDANCE WITH NFPA 72.
2. FOR PUBLIC MODE AREAS, AUDIBILITY SHALL BE 15 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL. PUBLIC
MODE AREAS ARE NON-PATIENT AREAS AND INCLUDE
LOBBIES, WAITING ROOMS, CAFETERIA, OFFICE
SUITES AND COMMON AREAS OPEN TO THE PUBLIC.
AUDIBILITY SHALL BE BASED ON AVERAGE LEVELS
DEFINED BY NFPA 72, NOTED IN TABLE #1 BELOW.
3. IN PRIVATE MODE AREAS, AUDIBILITY SHALL BE 10 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL.
PRIVATE MODE AREAS INCLUDE PATIENT WING
CORRIDORS, NURSE STATIONS, AREAS EXCLUSIVELY
FOR MEDICAL STAFF AND AREAS WHERE PATIENTS
MAY BE PRESENT ALONG WITH STAFF (I.E. DAY
ROOMS). AUDIBILITY SHALL BE BASED ON AVERAGE
LEVELS DEFINED BY NFPA 72, NOTED IN TABLE #1
BELOW.
4. PATIENT ROOMS ARE NOT TO BE PROVIDED WITH
NOTIFICATION IN ACCORDANCE WITH THE
ALLOWANCES OF PRIVATE MODE.
5. INTELLIGIBILITY SHALL BE ACHIEVED PER NFPA 72.
MEASURABLE INTELLIGIBILITY LEVELS ARE NOTED IN
TABLE #2 BELOW.
TABLE #1: AVERAGE AUDIBILITY LEVELS
TABLE #2: RECOMMENDED INTELLIGIBILITY LEVELS
95CD
1W
95CD
1W
95CD
1W
95CD
1W
110CD
1W
W
15CD
1W
15CD
1W
CIRCUITS IN
NEW NAC & VOICE
N,V
2N,2V
TO ABOVE
FROM/RETURN
CIRCUITS IN
NEW NAC & VOICE
V EOLR
N EOLR
N,V
N V 2L
CO
INSTALL CARBON
MONOXIDE DETECTOR
ON CEILING IN
BASEMENT.
RETURN TO ABOVE
EXISTING SLC IN/
2L
FA10SBa
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
SUBBASEMENT NOTES:
THE SUB-BASEMENT IS CURRENTLY ON THE OLD SPECTRONICS SYSTEM. WORK ON THIS
LEVEL INCLUDES THE FOLLOWING:
1. CONVERT ALL EXISTING DEVICES FROM THE SPECTRONICS SYSTEM TO THE
FCI/GAMEWELL SYSTEM.
2. REPLACE 8 EXISTING MONITOR MODULES WITH NEW TO SUPERVISE 8 EXISTING TAMPER
SWITCHES. SPECTRONICS ADDRESSES FOR THESE 8 TAMPERS ARE: 01-28-29, 01-28-30,
01-28-32, 01-28-34, 01-28-36, 01-28-91, 01-28-92, & 01-28-93
3. INSTALL MONITOR MODULES TO SUPERVISE THE EXISTING FIRE PUMP (QUANTITIES AND
DETAILS TO BE PROVIDED AT 65%)
4. REPLACE 4 SPECTRONICS RELAY MODULES WITH NEW FCI/GAMEWELL MODULES
5. REPLACE PULL STATION AT STAIRWELL 4 WITH NEW
6. REPLACE THE FOLLOWING SPECTRONICS MONITORING POINTS WITH NEW
FCI/GAMEWELL MODULES:
6.1. DISCHARGE WATERFLOW - 01.28.33
6.2. WEST WALL BELOW LAUNDRY - 01.28.31
6.3. CENTER OF SUB-BASEMENT - 01.28.35
6.4. WATER FLOW 28 - 01.28.28
7. INSTALL AUDIBLE AND VISUAL NOTIFICATION THROUGHOUT LEVEL
8. CONVERT LOCKED TAMPER SWITCHES TO ELECTRONICALLY SUPERVISED TAMPER
SWITCHES, CONNECT TO FIRE ALARM SYSTEM
SUB-BASEMENT FIRE ALARM PLAN -
AREA A
FA10SBa
SUB-BASEMENT FIRE ALARM PLAN - AREA A
1/8" = 1'-0"
ADD ONE MONITOR MODULE TO
SUPERVISE EXISTING LOCKED
TAMPER SWITCH. INSTALL ONE
TAMPER SWITCH ON SPRINKLER
CONTROL VALVE.
ADD ONE MONITOR MODULE TO SUPERVISE
EXISTING LOCKED TAMPER SWITCH. INSTALL ONE
TAMPER SWITCH ON SPRINKLER CONTROL VALVE.
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
15CD
1W
INSTALL NEW MODULES TO SUPERVISE
EXISTING FIRE PUMP. APPROXIMATE
COUNT = 20 MONITOR MODULES.
N,V
CIRCUITS IN
NEW NAC & VOICE
N,V
N,V
V EOLR
N EOLR
N,V
N,V
MM
MM
MM
N,V
N,V
N,V
N,V
N,V N,V
N,V
(20)
NEAREST DEVICE
SLC IN FROM
OR FROM FACP
2L 2L 2L
2L
PROVIDE 4 MONITOR MODULES TO
SUPERVISE TAMPER SWITCHES ON
2 BACKFLOW PREVENTERS. (FIELD
LOCATE)
MM (4)
FA10SBb
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
SUBBASEMENT NOTES:
THE SUB-BASEMENT IS CURRENTLY ON THE OLD SPECTRONICS SYSTEM. WORK ON THIS
LEVEL INCLUDES THE FOLLOWING:
1. CONVERT ALL EXISTING DEVICES FROM THE SPECTRONICS SYSTEM TO THE
FCI/GAMEWELL SYSTEM.
2. REPLACE 8 EXISTING MONITOR MODULES WITH NEW TO SUPERVISE 8 EXISTING TAMPER
SWITCHES. SPECTRONICS ADDRESSES FOR THESE 8 TAMPERS ARE: 01-28-29, 01-28-30,
01-28-32, 01-28-34, 01-28-36, 01-28-91, 01-28-92, & 01-28-93
3. INSTALL MONITOR MODULES TO SUPERVISE THE EXISTING FIRE PUMP (QUANTITIES AND
DETAILS TO BE PROVIDED AT 65%)
4. REPLACE 4 SPECTRONICS RELAY MODULES WITH NEW FCI/GAMEWELL MODULES
5. REPLACE PULL STATION AT STAIRWELL 4 WITH NEW
6. REPLACE THE FOLLOWING SPECTRONICS MONITORING POINTS WITH NEW
FCI/GAMEWELL MODULES:
6.1. DISCHARGE WATERFLOW - 01.28.33
6.2. WEST WALL BELOW LAUNDRY - 01.28.31
6.3. CENTER OF SUB-BASEMENT - 01.28.35
6.4. WATER FLOW 28 - 01.28.28
7. INSTALL AUDIBLE AND VISUAL NOTIFICATION THROUGHOUT LEVEL
8. CONVERT LOCKED TAMPER SWITCHES TO ELECTRONICALLY SUPERVISED TAMPER
SWITCHES, CONNECT TO FIRE ALARM SYSTEM
SUB-BASEMENT FIRE ALARM PLAN -
AREA B
FA10SBb
SUB-BASEMENT FIRE ALARM PLAN - AREA B
95CD
1W
95CD
1W
95CD
1W
95CD
1W
95CD
1W
CIRCUITS IN
NEW NAC & VOICE
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
FA10SBc
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
SUBBASEMENT NOTES:
THE SUB-BASEMENT IS CURRENTLY ON THE OLD SPECTRONICS SYSTEM. WORK ON THIS
LEVEL INCLUDES THE FOLLOWING:
1. CONVERT ALL EXISTING DEVICES FROM THE SPECTRONICS SYSTEM TO THE
FCI/GAMEWELL SYSTEM.
2. REPLACE 8 EXISTING MONITOR MODULES WITH NEW TO SUPERVISE 8 EXISTING TAMPER
SWITCHES. SPECTRONICS ADDRESSES FOR THESE 8 TAMPERS ARE: 01-28-29, 01-28-30,
01-28-32, 01-28-34, 01-28-36, 01-28-91, 01-28-92, & 01-28-93
3. INSTALL MONITOR MODULES TO SUPERVISE THE EXISTING FIRE PUMP (QUANTITIES AND
DETAILS TO BE PROVIDED AT 65%)
4. REPLACE 4 SPECTRONICS RELAY MODULES WITH NEW FCI/GAMEWELL MODULES
5. REPLACE PULL STATION AT STAIRWELL 4 WITH NEW
6. REPLACE THE FOLLOWING SPECTRONICS MONITORING POINTS WITH NEW
FCI/GAMEWELL MODULES:
6.1. DISCHARGE WATERFLOW - 01.28.33
6.2. WEST WALL BELOW LAUNDRY - 01.28.31
6.3. CENTER OF SUB-BASEMENT - 01.28.35
6.4. WATER FLOW 28 - 01.28.28
7. INSTALL AUDIBLE AND VISUAL NOTIFICATION THROUGHOUT LEVEL
8. CONVERT LOCKED TAMPER SWITCHES TO ELECTRONICALLY SUPERVISED TAMPER
SWITCHES, CONNECT TO FIRE ALARM SYSTEM
SUB-BASEMENT FIRE ALARM PLAN -
AREA C
FA10SBc
SUB-BASEMENT FIRE ALARM PLAN - AREA C
95CD
1W
95CD
1W
N EOLR
V EOLR
N,V
N,V
N,V
FA10SBd
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
SUBBASEMENT NOTES:
THE SUB-BASEMENT IS CURRENTLY ON THE OLD SPECTRONICS SYSTEM. WORK ON THIS
LEVEL INCLUDES THE FOLLOWING:
1. CONVERT ALL EXISTING DEVICES FROM THE SPECTRONICS SYSTEM TO THE
FCI/GAMEWELL SYSTEM.
2. REPLACE 8 EXISTING MONITOR MODULES WITH NEW TO SUPERVISE 8 EXISTING TAMPER
SWITCHES. SPECTRONICS ADDRESSES FOR THESE 8 TAMPERS ARE: 01-28-29, 01-28-30,
01-28-32, 01-28-34, 01-28-36, 01-28-91, 01-28-92, & 01-28-93
3. INSTALL MONITOR MODULES TO SUPERVISE THE EXISTING FIRE PUMP (QUANTITIES AND
DETAILS TO BE PROVIDED AT 65%)
4. REPLACE 4 SPECTRONICS RELAY MODULES WITH NEW FCI/GAMEWELL MODULES
5. REPLACE PULL STATION AT STAIRWELL 4 WITH NEW
6. REPLACE THE FOLLOWING SPECTRONICS MONITORING POINTS WITH NEW
FCI/GAMEWELL MODULES:
6.1. DISCHARGE WATERFLOW - 01.28.33
6.2. WEST WALL BELOW LAUNDRY - 01.28.31
6.3. CENTER OF SUB-BASEMENT - 01.28.35
6.4. WATER FLOW 28 - 01.28.28
7. INSTALL AUDIBLE AND VISUAL NOTIFICATION THROUGHOUT LEVEL
8. CONVERT LOCKED TAMPER SWITCHES TO ELECTRONICALLY SUPERVISED TAMPER
SWITCHES, CONNECT TO FIRE ALARM SYSTEM
SUB-BASEMENT FIRE ALARM PLAN -
AREA D
FA10SBd
SUB-BASEMENT FIRE ALARM PLAN - AREA D
BOILER PLANT NEEDS AUDIBLE
AND VISUAL NOTIFICATION AND
CARBON MONOXIDE DETECTION.
AREA IS MISSING AUDIBLE AND
VISUAL NOTIFICATION IN SOME
ROOMS.
ADD AUDIBLE & VISUAL
NOTIFICATION BASED ON
ROOM USE.
MAIN FIRE ALARM CONTROL
PANEL LOCATED HERE.
EXISTING COVERAGE IS
LACKING IN THIS SPACE.
SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW
DEVICES AS SHOWN.
EXISTING COVERAGE IS LACKING IN
THIS AREA. SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW DEVICES
AS SHOWN. EXAM ROOMS REQUIRE
COVERAGE PER NFPA 101.
STAIR IS MISSING PULL STATION.
ADD PULL STATION TO MATCH
OTHER FLOORS.
ADD AUDIBLE & VISUAL
NOTIFICATION BASED ON
ROOM USE.
FA10B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
OVERALL BASEMENT FIRE ALARM
PLAN
FA10B
OVERALL BASEMENT FLOOR PLAN
1/32" = 1'-0"
NOTE: OVERALL FLOORPLAN IS INTENDED TO ILLUSTRATE SCOPE OF WORK AREAS FOR
THIS PROJECT. REFER TO INDIVIDUAL AREAS FOR MORE DETAILS ON FIRE ALARM WORK.
PERFORMANCE CRITERIA FOR OCCUPANT NOTIFICATIONS:
1. AUDIBILITY SHALL BE IN ACCORDANCE WITH NFPA 72.
2. FOR PUBLIC MODE AREAS, AUDIBILITY SHALL BE 15 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL. PUBLIC
MODE AREAS ARE NON-PATIENT AREAS AND INCLUDE
LOBBIES, WAITING ROOMS, CAFETERIA, OFFICE
SUITES AND COMMON AREAS OPEN TO THE PUBLIC.
AUDIBILITY SHALL BE BASED ON AVERAGE LEVELS
DEFINED BY NFPA 72, NOTED IN TABLE #1 BELOW.
3. IN PRIVATE MODE AREAS, AUDIBILITY SHALL BE 10 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL.
PRIVATE MODE AREAS INCLUDE PATIENT WING
CORRIDORS, NURSE STATIONS, AREAS EXCLUSIVELY
FOR MEDICAL STAFF AND AREAS WHERE PATIENTS
MAY BE PRESENT ALONG WITH STAFF (I.E. DAY
ROOMS). AUDIBILITY SHALL BE BASED ON AVERAGE
LEVELS DEFINED BY NFPA 72, NOTED IN TABLE #1
BELOW.
4. PATIENT ROOMS ARE NOT TO BE PROVIDED WITH
NOTIFICATION IN ACCORDANCE WITH THE
ALLOWANCES OF PRIVATE MODE.
5. INTELLIGIBILITY SHALL BE ACHIEVED PER NFPA 72.
MEASURABLE INTELLIGIBILITY LEVELS ARE NOTED IN
TABLE #2 BELOW.
CO
INSTALL CARBON MONOXIDE
DETECTOR ON CEILING
WITHIN 25' OF BOILERS.
110CD
2W
W
110CD
1W
W
110CD
1W
W
75CD
1W
W
75CD
1W
W
110CD
1W
W
15CD
.5W
15CD
.5W
110CD
1W
W
75CD
2W
W
15CD
15CD
.5W15CD
.5W N,V
N,V
N,V
N,V
N,V
110CD
1W
W N,V
CO
INSTALL CARBON MONOXIDE
DETECTOR ON CEILING
WITHIN 25' OF BOILERS.
L
L
LLL
L
N,V
N EOLR
V EOLR
CIRCUITS IN
NEW NAC & VOICE
NEAREST DEVICE
SLC IN FROM
NAC/VOICE CKT
IN FROM EXISTING NAC/VOICE CKT
RETURN TO EXISTING
N,V
N,V
N,V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
N EOLR
V EOLR
N,V
S S
S
S
S
S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA10Ba
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
BASEMENT FIRE ALARM PLAN -
AREA A
FA10Ba
BASEMENT LEVEL FIRE ALARM PLAN - AREA A
EXISTING FIRE ALARM CONTROL
PANELS. FCI-GAMEWELL PANEL
TO REMAIN. SPECTRONICS
PANEL TO BE DEMOLISHED
UNDER THIS SCOPE OF WORK.
15CD
.5W
110CD
1W
W
75CD
1W
W
75CD
1W
W
75CD
1W
W
EXISTING COVERAGE IS LACKING IN THIS
SPACE. SUPPLEMENT EXISTING COVERAGE
BY ADDING NEW DEVICES AS SHOWN.
110CD
2W
W
75CD
2W
W
110CD
2W
W
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
N EOLR
V EOLR
CIRCUITS IN
NEW NAC & VOICE
N,V
N,V
N,V
FACP
NEW AMPLIFIER AND POWER
SUPPLY. CONNECT TO SPARE
CIRCUIT ON EMERGENCY POWER
PANEL.
FACP
S
SSS
S
S
S
S
S
S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA10Bb
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
BASEMENT FIRE ALARM PLAN -
AREA B
FA10Bb
BASEMENT LEVEL FIRE ALARM PLAN - AREA B
135CD
2W
W
2N,2V
FACPFACP
S
S
S
S
S
S
S
S
S S
S
S
S
S
SSS
S
S
S
S
S
SS
S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA10Bc
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
BASEMENT FIRE ALARM PLAN -
AREA C
FA10Bc
BASEMENT LEVEL FIRE ALARM PLAN - AREA C
135CD
2W
W
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
S
S
SS
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA10Bd
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
BASEMENT FIRE ALARM PLAN -
AREA D
FA10Bd
BASEMENT LEVEL FIRE ALARM PLAN - AREA D
NEW MANUAL PULL
STATION
15CD
.25W
15CD
.25W
30CD
.5W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
CIRCUITS IN
NEW NAC & VOICE
V EOLR
N EOLR
N,V N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V N,V
N,V
N,V
N,V
2L
EXISTING SLC CKT
IN FROM/RETURN TO
S
S
S
S
S
S
S
S
S
S
S
S
S S
SS
S S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA10Be
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
BASEMENT FIRE ALARM PLAN -
AREA E
FA10Be
BASEMENT LEVEL FIRE ALARM PLAN - AREA E
2L
EXISTING SLC CKT
IN FROM/RETURN TO
S
S
S
S
S
S
S
S
S S
S
SS
S
SUBSTATION #4 IS UNDERNEATH ER OVERHANG.
INSTALL 2 SPEAKER/STROBES, 4 SMOKE DETECTORS,
2 PULL STATIONS. PULL WIRE FROM ER AREA
THROUGH CEILING OF PORTECOCHERE.
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA10Bf
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
BASEMENT FIRE ALARM PLAN -
AREA F
FA10Bf
BASEMENT LEVEL FIRE ALARM PLAN - AREA F
ADD AUDIBLE & VISUAL
NOTIFICATION BASED ON
ROOM USE.
ADD AUDIBLE & VISUAL
NOTIFICATION BASED ON
ROOM USE.
ADD AUDIBLE & VISUAL
NOTIFICATION BASED ON
ROOM USE.
STAIR IS MISSING PULL STATION.
ADD PULL STATION TO MATCH
OTHER FLOORS.
EXISTING COVERAGE IS LACKING IN
THIS AREA. SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW DEVICES
AS SHOWN. EXAM ROOMS REQUIRE
COVERAGE PER NFPA 101.
FA100
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
OVERALL GROUND LEVEL
FIRE ALARM PLAN
FA100
OVERALL GROUND LEVEL FLOOR PLAN
1/32" = 1'-0"
PERFORMANCE CRITERIA FOR OCCUPANT NOTIFICATIONS:
1. AUDIBILITY SHALL BE IN ACCORDANCE WITH NFPA 72.
2. FOR PUBLIC MODE AREAS, AUDIBILITY SHALL BE 15 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL. PUBLIC
MODE AREAS ARE NON-PATIENT AREAS AND INCLUDE
LOBBIES, WAITING ROOMS, CAFETERIA, OFFICE
SUITES AND COMMON AREAS OPEN TO THE PUBLIC.
AUDIBILITY SHALL BE BASED ON AVERAGE LEVELS
DEFINED BY NFPA 72, NOTED IN TABLE #1 BELOW.
3. IN PRIVATE MODE AREAS, AUDIBILITY SHALL BE 10 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL.
PRIVATE MODE AREAS INCLUDE PATIENT WING
CORRIDORS, NURSE STATIONS, AREAS EXCLUSIVELY
FOR MEDICAL STAFF AND AREAS WHERE PATIENTS
MAY BE PRESENT ALONG WITH STAFF (I.E. DAY
ROOMS). AUDIBILITY SHALL BE BASED ON AVERAGE
LEVELS DEFINED BY NFPA 72, NOTED IN TABLE #1
BELOW.
4. PATIENT ROOMS ARE NOT TO BE PROVIDED WITH
NOTIFICATION IN ACCORDANCE WITH THE
ALLOWANCES OF PRIVATE MODE.
5. INTELLIGIBILITY SHALL BE ACHIEVED PER NFPA 72.
MEASURABLE INTELLIGIBILITY LEVELS ARE NOTED IN
TABLE #2 BELOW.
15CD
.5W
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
S
S
S
S
S
S
S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA100a
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
GROUND LEVEL FIRE ALARM PLAN -
AREA A
FA100a
GROUND LEVEL FIRE ALARM PLAN - AREA A
75CD
1W
75CD
1W
110CD
1W
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
S
S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA100b
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
GROUND LEVEL FIRE ALARM PLAN -
AREA B
FA100b
GROUND LEVEL FIRE ALARM PLAN - AREA B
75CD
75CD
1W
15CD
.5W
15CD
.5W
15CD
.5W
15CD
1W
15CD
.25W
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V2N,2V
2N,2V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
NEW AMPLIFIER AND POWER
SUPPLY. CONNECT TO SPARE
CIRCUIT ON EMERGENCY POWER
PANEL.
S
S
S
15CD
.25W
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA100c
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
GROUND LEVEL FIRE ALARM PLAN -
AREA C
FA100c
GROUND LEVEL FIRE ALARM PLAN - AREA C
15CD
.25W
2L
EXISTING SLC CKT
IN FROM/RETURN TO
S S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA100d
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
GROUND LEVEL FIRE ALARM PLAN -
AREA D
FA100d
GROUND LEVEL FIRE ALARM PLAN - AREA D
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.2515CD
.25
15CD
.25
15CD
.2515CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25 15CD
.25
15CD
.2515CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.2515CD
.25
15CD
.25
15CD
.25 15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
CIRCUITS IN
NEW NAC & VOICE
V EOLR
N EOLR
CIRCUITS IN
NEW NAC & VOICE
N EOLR
V EOLR
CIRCUITS IN
NEW NAC & VOICE
N EOLR
V EOLR
N EOLR
V EOLR
CIRCUITS IN
NEW NAC & VOICE
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V N,V
N,V
N,V
N,VN,VN,V
N,V
N,V N,V N,V
N,V
N,V
N,VN,VN,VN,VN,VN,VN,VN,V
N,V
N,V
N,V N,V
N,V
S
S
S
S
S
S S
S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA100e
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
GROUND LEVEL FIRE ALARM PLAN -
AREA E
FA100e
GROUND LEVEL FIRE ALARM PLAN - AREA E
.25
15CD
.25
15CD
.25 15CD
.2515CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
15CD
.25
N EOLR
V EOLR
CIRCUITS IN
NEW NAC & VOICE
N,V
N,VN,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA100f
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
GROUND LEVEL FIRE ALARM PLAN -
AREA F
FA100f
GROUND LEVEL FIRE ALARM PLAN - AREA F
NOTIFICATION BASED ON
ROOM USE.
ADD AUDIBLE & VISUAL
NOTIFICATION BASED ON
ROOM USE.
EXISTING COVERAGE IS LACKING IN
THIS AREA. SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW DEVICES
AS SHOWN. EXAM ROOMS REQUIRE
COVERAGE PER NFPA 101.
EXISTING COVERAGE IS LACKING IN
THIS AREA. SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW DEVICES
AS SHOWN. EXAM ROOMS REQUIRE
COVERAGE PER NFPA 101.
EXISTING COVERAGE IS LACKING IN
THIS AREA. SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW DEVICES
AS SHOWN. EXAM ROOMS REQUIRE
COVERAGE PER NFPA 101.
EXISTING COVERAGE IS LACKING IN
THIS AREA. SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW DEVICES
AS SHOWN. EXAM ROOMS REQUIRE
COVERAGE PER NFPA 101.
FA101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
OVERALL 1ST FLOOR PLAN
FA101
OVERALL FIRST FLOOR PLAN
1/32" = 1'-0"
NOTE: OVERALL FLOORPLAN IS INTENDED TO ILLUSTRATE SCOPE OF WORK AREAS FOR
THIS PROJECT. REFER TO INDIVIDUAL AREAS FOR MORE DETAILS ON FIRE ALARM WORK.
PERFORMANCE CRITERIA FOR OCCUPANT NOTIFICATIONS:
1. AUDIBILITY SHALL BE IN ACCORDANCE WITH NFPA 72.
2. FOR PUBLIC MODE AREAS, AUDIBILITY SHALL BE 15 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL. PUBLIC
MODE AREAS ARE NON-PATIENT AREAS AND INCLUDE
LOBBIES, WAITING ROOMS, CAFETERIA, OFFICE
SUITES AND COMMON AREAS OPEN TO THE PUBLIC.
AUDIBILITY SHALL BE BASED ON AVERAGE LEVELS
DEFINED BY NFPA 72, NOTED IN TABLE #1 BELOW.
3. IN PRIVATE MODE AREAS, AUDIBILITY SHALL BE 10 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL.
PRIVATE MODE AREAS INCLUDE PATIENT WING
CORRIDORS, NURSE STATIONS, AREAS EXCLUSIVELY
FOR MEDICAL STAFF AND AREAS WHERE PATIENTS
MAY BE PRESENT ALONG WITH STAFF (I.E. DAY
ROOMS). AUDIBILITY SHALL BE BASED ON AVERAGE
LEVELS DEFINED BY NFPA 72, NOTED IN TABLE #1
BELOW.
4. PATIENT ROOMS ARE NOT TO BE PROVIDED WITH
NOTIFICATION IN ACCORDANCE WITH THE
ALLOWANCES OF PRIVATE MODE.
5. INTELLIGIBILITY SHALL BE ACHIEVED PER NFPA 72.
MEASURABLE INTELLIGIBILITY LEVELS ARE NOTED IN
TABLE #2 BELOW.
15CD
.5W
15CD
.25W
15CD
.25W 15CD
.25W
15CD
.25W 15CD
.25W
15CD
.25W
15CD
.25W
75CD
1W
110CD
1W
W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W 15CD
.25W
75CD
.5W
N,V
N,V
N,VN,VN,V N,VN,V
N,V
N,V
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
CIRCUITS IN
NEW NAC & VOICE
N,VN,VN,VN,VN,V
N,V
N,V
N,V
N EOLR
V EOLR
S
S
CIRCUITS IN
NEW NAC & VOICE
N,V
N EOLR
V EOLR
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA101a
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
1ST FLOOR FIRE ALARM PLAN -
AREA A
FA101a
1ST FLOOR FIRE ALARM PLAN - AREA A
.25W
15CD
.25W 15CD
.25W
15CD
.25W 15CD
.25W75CD
1W
75CD
1W
N,V
N,VN,VN,V N,VN,V
N,VEXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
2N,2V
S
S
S
S
S
S
SS
S
15CD
.5W15CD
.5W
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
2N,2V
15CD
.5W 2N,2V
15CD
.5W15CD
.5W 2N,2V
2N,2V
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA101b
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
1ST FLOOR FIRE ALARM PLAN -
AREA B
FA101b
1ST FLOOR FIRE ALARM PLAN - AREA B
N EOLR
V EOLR
15CD
.25W
15CD
.25W
15CD
.25W
EXISTING NAC/VOICE CKT
IN FROM/RETURN TO
15CD
.25W
2N,2V
2N,2V
2N,2V 2N,2V 2N,2V
NEW AMPLIFIER AND POWER
SUPPLY. CONNECT TO SPARE
CIRCUIT ON EMERGENCY POWER
PANEL.
S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA101c
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
1ST FLOOR FIRE ALARM PLAN -
AREA C
FA101c
1ST FLOOR FIRE ALARM PLAN - AREA C
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA101d
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
1ST FLOOR FIRE ALARM PLAN -
AREA D
FA101d
1ST FLOOR FIRE ALARM PLAN - AREA D
15CD
.25W
15CD
.25W 15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W 75CD
1W
N EOLR
V EOLR
15CD
.25W
30CD
.5W
30CD
.5W
30CD
.5W
30CD
.5W
15CD
.25W
15CD
.25W15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W 15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W 15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
75CD
.5W
15CD
.25W
15CD
.25W 15CD
.25W
15CD
.25W
15CD
.25W 2N,2V
CIRCUITS IN
NEW NAC & VOICE
15CD
.25W
N,V
N,V
N,V N,V
N,V
N,V
N,V N,V
N,V
N,V N,V
N,V
N,V N,V
N,V
CIRCUITS IN
NEW NAC & VOICE
N EOLR
V EOLR
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,VN,V
N,V
N,V
N,V
N,V
N,V
S
S
S
S
S
S
15CD
.25W
15CD
.25W
15CD
.25W 15CD
.25W
15CD
.25W 15CD
.25W
15CD
.25W
V EOLR
N EOLR
15CD
.25W
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA101e
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
1ST FLOOR FIRE ALARM PLAN -
AREA E
FA101e
1ST FLOOR FIRE ALARM PLAN - AREA E
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.25W
15CD
.5W
15CD
.25W
15CD
.25W 15CD
.25W
15CD
.25W
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
N,V
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA101f
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
1ST FLOOR FIRE ALARM PLAN -
AREA F
FA101f
1ST FLOOR FIRE ALARM PLAN - AREA F
SPR
SPR
SPR
SPR
EXISTING COVERAGE IS LACKING IN
THIS AREA. SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW DEVICES
AS SHOWN.
EXISTING COVERAGE IS LACKING IN
THIS AREA. SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW DEVICES
AS SHOWN. EXAM ROOMS REQUIRE
COVERAGE PER NFPA 101.
ADD AUDIBLE & VISUAL
NOTIFICATION BASED ON
ROOM USE.
EXISTING COVERAGE IS LACKING IN
THIS AREA. SUPPLEMENT EXISTING
COVERAGE BY ADDING NEW DEVICES
AS SHOWN.
ADD AUDIBLE & VISUAL
NOTIFICATION BASED ON
ROOM USE.
STAIR IS MISSING PULL STATION.
ADD PULL STATION TO MATCH
OTHER FLOORS.
FA102
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO 80443
(970) 409-9082
DEBORAH SHANER
UPGRADE EXISTING FIRE
ALARM SYSTEM PHASE II
VAMC OKLAHOMA CITY, OKLAHOMA
635-20-101
OKCVAMC
Project Director
4/21/21 RD DSRevisions: Date: 4F PROJECT NO: 15.2226.A24
100% CONSTRUCTION
DOCUMENTS
Phase
1/8" = 1' (UNLESS OTHERWISE NOTED)
NO SCALE
N O
R
TH
F
E
A
B
C D
OVERALL 2ND FLOOR PLAN
FA102
OVERALL SECOND FLOOR PLAN
1/32" = 1'-0"
NOTE: OVERALL FLOORPLAN IS INTENDED TO ILLUSTRATE SCOPE OF WORK AREAS FOR
THIS PROJECT. REFER TO INDIVIDUAL AREAS FOR MORE DETAILS ON FIRE ALARM WORK.
PERFORMANCE CRITERIA FOR OCCUPANT NOTIFICATIONS:
1. AUDIBILITY SHALL BE IN ACCORDANCE WITH NFPA 72.
2. FOR PUBLIC MODE AREAS, AUDIBILITY SHALL BE 15 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL. PUBLIC
MODE AREAS ARE NON-PATIENT AREAS AND INCLUDE
LOBBIES, WAITING ROOMS, CAFETERIA, OFFICE
SUITES AND COMMON AREAS OPEN TO THE PUBLIC.
AUDIBILITY SHALL BE BASED ON AVERAGE LEVELS
DEFINED BY NFPA 72, NOTED IN TABLE #1 BELOW.
3. IN PRIVATE MODE AREAS, AUDIBILITY SHALL BE 10 DB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL.
PRIVATE MODE AREAS INCLUDE PATIENT WING
CORRIDORS, NURSE STATIONS, AREAS EXCLUSIVELY
FOR MEDICAL STAFF AND AREAS WHERE PATIENTS
MAY BE PRESENT ALONG WITH STAFF (I.E. DAY
ROOMS). AUDIBILITY SHALL BE BASED ON AVERAGE
LEVELS DEFINED BY NFPA 72, NOTED IN TABLE #1
BELOW.
4. PATIENT ROOMS ARE NOT TO BE PROVIDED WITH
NOTIFICATION IN ACCORDANCE WITH THE
ALLOWANCES OF PRIVATE MODE.
5. INTELLIGIBILITY SHALL BE ACHIEVED PER NFPA 72.
MEASURABLE INTELLIGIBILITY LEVELS ARE NOTED IN
TABLE #2 BELOW.
15CD
.25W
75CD
1W
15CD
.5W
15CD
.25W
15CD
.25W
15CD
.5W
CIRCUITS IN
NEW NAC & VOICE
N EOLR
V EOLR
N,V N,V
N,V N,V
N,V
N,V
N,V
N,V
S
S
S
REPLACE EXISTING NOTIFICATION APPLIANCE
ON A ONE-FOR-ONE BASIS. REFER TO
LEGEND BELOW.
FLAG NOTES
S
S WALL MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER/STROBE
CEILING MOUNTED SPEAKER ONLY
CEILING MOUNTED SPEAKER ONLY
S
FIRE ALARM STANDARD
DUAL CONE IN-TILE
DRAWING PACKAGE INCLUDES ONLY DEVICES THAT
ARE BEING IMPACTED BY THIS SCOPE OF WORK.
EXISTING DEVICES THAT ARE NOT PART OF THIS
SCOPE ARE NOT SHOWN.
GENERAL NOTE
FA102a
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
ScaleARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOURFRONT DESIGN, INC.
517 SEVENTH STREET
RAPID CITY, SOUTH DAKOTA 57701
(605) 342-9470
RAY DAWES
FIRE PROTECTION:
SHANER LIFE SAFETY
PO BOX 1073
FRISCO, COLORADO…