5. PROJECT NUMBER (if applicable)

CODE

7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer) 09-03-2019 Date of Amed #2 n/a 36C259 Department of Veterans Affairs Network Contracting Office

NCO 19

1011 Honor Heights Drive Muskogee

OK

74401 36C259 Department of Veterans Affairs Network Contracting Office

NCO 19

1011 Honor Heights Drive Muskogee

OK

74401 To all Offerors/Bidders

36C25919Q0555 08-27-2019

X X X

See below Vendor's question(s) and VA's responces.

The Performance Work Statement (PWS) has been adjusted, see and use below PWS to provide quote.

The closing date and time is still 9-6-2019 at 1:00 PM (CST).

All other terms & conditions remain unchanged.

Lance Davis Contracting Officer

NCO1616L2-5045

See below Vendor questions with the VA’s responses in Red.

Vendor’s Question(s)

For the 4 York Chillers (i., ii., iii., iv. On Page 8), would it be possible to add the following wording on the following 3 annual tasks to ensure all bidding parties are meeting the manufacturer specifications:

1- Clean or backflush VSD heat exchanger and strainer-There is no VSD on these chillers, VSDs are on the lower voltage chillers. The 4 York chillers are 4160 volt.

2- Replace VSD starter coolant and ensure proper levels- There is no VSD on these chillers, VSDs are on the lower voltage chillers. The 4 York chillers are 4160 volt.

3- Perform oil analysis on compressor lube oil (“This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK equipment”) This will be done annually as stated Page 6 item 4. Oil Analysis.

Also, If the customer will be removing the heads of the 4 chillers for the annual visual tube inspection, can you clarify if the contractor will be able to brush the tubes at that time? This would reduce costs. Currently the scope of work seems to say the customer will remove the chiller head for the visual inspection, however, for the tube brushing the contractor must replace and remove the head. If we are able to do the brushing at the same time as the head removal for the inspection it seems that would be more efficient. (see attached Head removal.pdf) Yes when the head is removed (by the contractor) the tubes are to be brushed (by the contractor).

End of Vendor’s Question(s)

PWS has been adjusted to state that the Head(s) are to be removed by the Contractor.

Various other items of the PWS have also been adjusted, please ensure to re-read and adhere to the attached PWS.

Performance Work Statement Chiller Preventive Maintenance Service Oklahoma City VAMC

The contractor shall provide Chiller Preventive Maintenance Services in accordance with the terms and conditions stated within this Performance Work Statement (PWS). All work shall be coordinated with the Oklahoma City VA Health Care System’s COR.

1. INSPECTION SERVICES:

a. General:

i. Contractor shall provide scheduled quarterly and annual preventive maintenance services of chillers and associated equipment as specified within all updated manufacturer specifications and requirements.

ii. Chillers are located on 2 campuses:

1. Oklahoma City VAMC 921 NE 13th St Oklahoma City, OK 73014

2. Lawton Outpatient Clinic 4303 Pitman Street Fort Sill, OK 73503

iii. Contractor shall provide all labor, materials, and equipment necessary for protection of VAMC personnel, furnishings, equipment and buildings from damage, and shall replace or repair any damage due to work performed under this contract equal to its original construction and finish. Contractor must have adequate insurance protection against negligent work and other forms and follow all federal, state, local regulations related to this requirement.

iv. All gauging and measurement equipment used shall be calibrated prior to use (within 1 calendar year) according to manufacturer’s specifications or a standard traceable to the National Bureau of Standards.

b. Deliverables and Performance:

i. Preventive Maintenance services are to be performed during the following time periods:

1st Quarter: October thru December of contract year.

2nd Quarter: January thru March of contract year.

3rd Quarter: April thru June of contract year.

4th Quarter: July thru September of contract year.

Note: Annuals shall occur in 1st or 2nd quarter and the same quarter of each following option year (if exercised).

ii. Maintenance Procedures for York 1000 Ton (2 ea.) & 600 Ton (2 ea.) Chillers:

1. Quarterly Inspection/Service:

a. Check chilled water temperature and pressure.

b. Check condensing water temperature and pressure.

c. Complete required maintenance checklists

d. Check for proper water flow.

e. Check oil heater.

f. Check operation of purge (if applicable).

g. Check for unusual noise and vibration.

h. Check with appropriate customer representative for operational deficiencies.

i. Check refrigerant charge.

j. Check compressor oil level(s).

k. Visually inspect for refrigerant and oil leaks.

l. Check surface condenser and hot well.

m. Check condensate pump and starter (if applicable) and lubricate bearings as required.

n. Check overall condition of unit.

o. Clean area around equipment.

p. Check capacity control and linkage.

2. Annual Inspection:

a. Change oil filter(s).

b. Inspect starter.

c. Check oil heater.

d. Check drive coupling.

e. Lubricate motor bearings.

f. Check overall condition of unit.

g. Check capacity control and linkage.

h. Check safeties.

i. Verify drive alignment.

j. Complete any required maintenance checklists

k. Check compressor oil level(s)

l. Reset purge counter (if applicable)

m. Check and tighten electrical connections.

n. Check with appropriate customer representative for operational deficiencies.

o. Check operating controls.

p. Check speed increaser (if applicable)

q. Check for unusual noise and vibration

r. Clean area around equipment

s. Conduct refrigerant leak check

t. Conduct visual inspection of condenser tubes (head to be removed by Contractor)

u. Change purge filter(s) (if applicable)

3. Chiller Tube Brushing (Annual):

a. Check with appropriate customer representative for operational deficiencies

b. Mechanically brush tubes.

c. Replace head

d. Clean area around equipment

e. Remove head (head to be removed by Contractor)

f. Isolate tubes

g. Drain water from tubes

h. Replace gasket

4. Oil Analysis (Annual):

a. Remove sample in approved container.

b. Label and complete paperwork indicating present operating conditions

c. Send for analysis.

iii. Maintenance Procedures for Carrier 160 Ton (2 ea.) and Trane 100 Ton (1 ea.) Chillers:

1. Cooling season start up preparation and inspection (Quarterly):

a. Check auxiliary equipment operation

b. Check refrigerant levels

c. Perform oil analysis.

d. Check the compressor heater, oil temperatures and lube system

e. Check and test all operating and safety controls

f. Check for proper voltage and starter operation

g. Start the chilled and condenser water pumps

h. Start the unit and calibrate controls and transducers

i. Check the proper settings for sub cooling and super heat

j. Log operating conditions after the unit stabilizes

k. Review operating procedures with the operator

l. Remove debris from inside and around the unit

m. Inspect condensing coils for blockage and clean lines

n. Inspect and tighten electrical connections

o. Check the fan and fan motor operation after start up

2. Operating Season Inspections (Quarterly):

a. Check general condition and operation.

b. Log operating conditions and identify inconsistencies

c. Adjust operating controls if required

d. Check for proper oil level and refrigerant charge

e. Check the oil temperature and compressor heater

f. Inspect starter, relays and controls

g. Inspect the air-cooled condenser fans and motor operations

h. Remove debris from inside and around the unit.

i. Review operating procedures and the owner’s log with operator

3. Annual Equipment Shutdown Inspection and PM:

a. Meggering and record motor winding resistance

b. Change oil filter

c. Check oil level in lube system; add additional oil as required and conduct an oil acidity test

d. Conduct a leak check; correct leaks; add refrigerant as necessary.

e. Change the filter-dryer

f. Check the crankcase heater for proper operation

g. Tighten power wiring on contactors and in the motor terminal box

h. Clean all contactors and recommend replacement if needed.

i. Check all relays, operating controls and safeties

j. Check and calibrate all controls, safeties, unloaders, and external interlocks

k. Clean condenser coil.

iv. Maintenance Procedures for York 50 ton and 25 Ton (1 ea.) Chiller:

1. Cooling season start-up preparation and inspection:

a. Check auxiliary equipment operation

b. Check refrigerant levels

c. Check the crankcase heater

d. Check and test all operating and safety controls

e. Check for proper voltage and starter operation

f. Start the chilled and condenser water pumps where applicable

g. Start the unit and calibrate controls and transducers

h. Check the proper settings for sub cooling and super heat

i. Log operating conditions after the unit stabilizes

j. Review operating procedures with the operator

k. Remove debris from inside and around the unit

l. Inspect condenser coils for blockage and clean lines

m. Inspect and tighten electrical connections

n. Check the fan and fan motor operation after start-up

2. Operating Season Inspection:

a. Check general condition and operation.

b. Log operating conditions and identify inconsistencies

c. Adjust operating controls if required

d. Check for proper oil level and refrigerant charge

e. Check the oil temperature and compressor heater

f. Inspect starter, relays and controls

g. Inspect the air-cooled condenser fans and motor operations

h. Remove debris from inside and around the unit.

i. Review operating procedures and the owner’s log with operator

3. Annual:

a. Meggering and record motor winding resistance

b. Check oil level in lube system; add additional oil as required and conduct an oil acidity test

c. Conduct a leak check; correct leaks; add refrigerant as necessary.

d. Change the filter-dryer

e. Check the crankcase heater for proper operation

f. Tighten power wiring on contactors and in the motor terminal box

g. Clean all contactors and recommend replacement if needed.

h. Check all relays, operating controls and safeties

i. Check and calibrate all controls, safeties, unloaders, and external interlocks

j. Check the suction and discharge compressor valves

k. Clean condenser coil.

2. CHILLER INVENTORY AND LOCATION:

a. Oklahoma City Campus:

i. York 1000 Ton Chiller Model #: YKKPK4H9 Serial #: SEWM-591880

ii. York 1000 Ton Chiller Model #: YKKPK4H9 Serial #: SEWM-591730

iii. York 600 Ton Chiller Model #: YKGQEP8 Serial #: SAXM-831760

iv. York 600 Ton Chiller Model #: YKGQEP8 Serial #: SAXM-831910

v. Carrier 160 Ton Chiller Model #: 30HXA161RZE661KA Serial #: 5105Q05873

vi. Carrier 160 Ton Chiller Model #: 30HXA161RZE661KA Serial #: 5105Q05874

vii. York 50 Ton Chiller Model #: YCAL0080SC46XAA Serial #: RCJM4480AA

b. Lawton Outpatient Clinic:

i. Trane 100 Ton Chiller Model #: RTAA1004XFO1A1COB Serial #: U94K24511

ii. York 25 Ton Chiller Model #: YCAL0028EE46XEBSXTX Serial #: YCAL028

3. SCHEDULING ARRANGEMENTS: Except by special alternative arrangement, scheduled work will be performed only during VAMC’s normal working hours (8:00 a.m. to 4:30 p.m. Monday through Friday excluding federal holidays). Contractor shall schedule all work within 1 week of contract award, approved by VA HCS COR. Vendor shall provide at least two weeks’ notice to the Contracting Officer’s Representative (COR) prior to performing the work. Work cannot be scheduled during heavy cooling load periods. Only one chiller at a time can be out of service for the inspection, testing, and calibration procedures. Work must be conducted when the COR or his/her designate is available on site to monitor the work.

Check in/out procedures: Prior to commencement of and immediately after each service visit, the contractor and/or contractor’s authorized repair technician must check in and out with the VAMC Boiler Plant staff. Due to heightened security requirements, the contractor and/or contractor’s authorized service representative will be required to wear an ID Badge which will be signed for upon arrival and turned in when leaving.

4. FEDERAL HOLIDAYS: Federal holidays are any calendar days designated by statute or executive order as federal holidays. Federal holidays consist of New Year’s Day, Martin Luther King Jr.’s Birthday, Presidents Day, Memorial Day, Independence Day, Labor Day, Columbus Day, Veterans Day, Thanksgiving Day, and Christmas.

5. DOCUMENTATION: Contractor shall provide this VA HCS with individual service reports, which describes the inspection services performed on the equipment.

a. Provide complete written report of the inspection fully describing all tests performed, all findings, and recommendations. The report shall contain copies of York and Carrier preventive maintenance procedures used along with any logs taken.

b. Furnish report within two weeks of each facility inspection by email to the COR.

c. All safety-related deficiencies shall be immediately reported to the COR, during the inspection visit.

6. PROTECTION FROM DAMAGE: Contractor shall provide all labor, materials, and equipment necessary for protection of VA HCS personnel, furnishings, equipment and buildings from damage, and shall replace or repair any damage due to work performed under this contract equal to its original construction and finish.

7. RESPONSE REQUESTS: Contractor shall only respond to requests for service from VA HCS CO or COR. If service is requested from any other source the Contractor is to advise the caller of this requirement and refuse to respond. Any billing resulting from unauthorized service will not be paid by the government.

8. CHECK IN/OUT PROCEDURES: Prior to commencement of, and immediately after each service visit, the Contractor or his authorized repair technician must check in and out with the VA HCS COR (during normal working hours). Contractor will be required to obtain contractor badges provided by the VA HCS.

9. LIABILITY INSURANCE: Contractor must provide this VA HCS with written confirmation that Contractor has adequate insurance protection against negligent work and other forms of liability. The nature and level of protection must be acceptable to this VA HCS.

10. INFORMATION SECURITY: The C&A requirements do not apply, and a Security Accreditation Package is not required.

File details come from the government source that posted it. Updated .