TORQUE ALL BOLTS PER TABLE BELOW:
FRAMING, FITTINGS AND FASTENERS EXPOSED TO WEATHER SHALL BE HOT-DIPPED GALVANIZED
GREEN EPOXY PAINT. FASTENERS SHALL HAVE STANDARD ELECTRO-PLATED ZINC FINISH.
5. CHANNEL MATERIAL AND FITTINGS SHALL HAVE STANDARD FINISH OF PERMA GREEN OR DURA
7. WHERE FRAMING SYSTEM IS USED FOR SUPPORT OF EQUIPMENT, VERIFY ALL ASPECTS OF INSTALLATION
BOLT SIZE (DIA.) 1/4" 5/16" 3/8" 1/2" 5/8" 3/4"
TORQUE (FT. LBS.) 6 11 19 50 100 125
WITH EQUIPMENT MANUFACTURER AND ARCHITECTURAL LAYOUT.
AFTER FABRICATION.
BOLT TORQUE TABLE:
1. METAL FRAMING SYSTEM SHALL BE B-LINE, UNISTRUT OR APPROVED EQUAL AS SPECIFIED ON
4. ALL BOLTS SHALL BE A307 WITH CHANNEL NUTS CONFORMING TO ASTM A675 OR ASTM A36.
3. ALL FITTINGS SHALL BE MADE FROM HOT ROLLED, PICKLED AND OILED PLATE OR STRIP STEEL
GRADE 33, HAVE A NOMINAL OVERALL WIDTH OF 1 5/8" AND HAVE A 7/8" SLOT FACE OPENING.
2. ALL CHANNELS SHALL BE COLD FORMED FROM 12 GA. STEEL, CONFORMING TO ASTM A570,
HARDWARE AS DEFINED IN THE METAL FRAMING MANUFACTURERS ASSOCIATION STANDARD
PLANS AND DETAILS. THE METAL FRAMING SYSTEM SHALL CONSIST OF CHANNELS, FITTINGS AND
PUBLICATION MFMA-1. ALL FITTINGS AND ACCESSORIES SHALL BE FROM THE SAME
CONFORMING TO ASTM A635.
MANUFACTURER, WITH NO EXCEPTIONS.
CONTINUOUS SLOT METAL FRAMING SYSTEM
GRADE C, PICKLED AND OILED. FINISH SHALL BE PER NOTE 5 ABOVE. INNER TUBE SHALL BE 1-1/2" SQ.
6. TELESPAR DROP TUBING SHALL BE ROLLED FROM 12 GA. HOT ROLLED STEEL, CONFORMING TO ASTM 570, AND OUTER TUBE 1-3/4" SQ.
ADHESIVE ANCHOR RODS, DOWELS AND REBARS
1. CHEMICAL ANCHOR SYSTEMS:
CONCRETE: USE ONLY ADHESIVE ANCHOR SYSTEMS THAT HAVE BEEN ISSUED AN ICC-ES REPORT IN
ACCORDANCE WITH THE PROVISIONS OF ICC-ES AC308. ANCHOR SYSTEM SHOULD BE APPROVED FOR
USE IN CRACKED CONCRETE AND SEISMIC DESIGN CATEGORIES A-F PER SECTION 2.0 OF THE ICC-ES
EVALUATION SERVICES REPORT. ANCHOR SYSTEMS SHALL BE INSTALLED PER THE REQUIREMENTS OF THE
ICC-ES EVALUATION SERVICES REPORT FOR THE SPECIFIC ANCHOR AND AS REQUIRED BY THE
MANUFACTURER.
2. ANCHOR RODS:
ALL RODS SHALL BE ASTM A36 THREADED RODS WITH ASTM A 563 GRADE A NUTS AND ANSI
B18.22.1 TYPE A WASHERS, UNLESS OTHERWISE NOTED. ANCHORS DESIGNATED AS ASTM A193 GRADE
B7 THREADED RODS SHALL USE ASTM 563 GRADE DH HEAVY HEX NUTS AND ASTM F436 WASHERS.
3. DOWELS: ASTM A615 GRADE 60 REINFORCING STEEL.
4. REMOVE GREASE, OIL, RUST AND ANY OTHER LAITANCE FROM RODS AND DOWELS PRIOR TO INSTALLATION.
5. SPECIAL INSPECTION REQUIREMENTS WILL BE DICTATED BY SECTION 4.0 OF THE ICC-ES EVALUATION
SERVICES REPORT. ANY SPECIAL INSPECTION SHALL VERIFY ANCHOR TYPE ANCHOR DIMENSIONS, CONCRETE
TYPE, CONCRETE COMPRESSIVE STRENGTH, HOLE DIMENSIONS, ANCHOR SPACINGS, EDGE DISTANCES, SLAB
THICKNESS, ANCHOR EMBEDMENT, AND TIGHTENING TORQUE.
6. THE TENSION TESTING OF THE CHEMICAL ANCHORS SHALL BE DONE IN THE PRESENCE OF THE SPECIAL
INSPECTOR AND A REPORT OF THE TEST RESULTS SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY. IF
ANY ANCHORS FAIL THE TENSION-TESTING REQUIREMENTS, THE ADDITIONAL TESTING REQUIREMENTS SHALL
BE ACCEPTABLE TO THE ENFORCEMENT AGENCY.
7. TEST QUANTITY OF ANCHORS AS NOTED BELOW:
APPLICATION QUANTITY
STRUCTURAL 100% OF BOLTS
NON-STRUCTURAL 50% OF BOLTS
SILL PLATE BOLTING 10% OF BOLTS
8. ANCHORS TO BE TESTED SHALL BE SELECTED AT RANDOM BY THE SPECIAL INSPECTOR.
9. WHERE ADHESIVE ANCHOR SYSTEMS ARE USED TO INSTALL REINFORCING DOWEL BARS IN HARDENED
CONCRETE, ONLY 25% OF THE DOWELS NEED BE TESTED IF THE FOLLOWING CONDITIONS ARE MET:
A. THE DOWELS ARE USED EXCLUSIVELY TO TRANSMIT SHEAR FORCES ACROSS JOINTS BETWEEN EXISTING
AND NEW CONCRETE;
B. THE NUMBER OF DOWELS IN ANY ONE MEMBER EQUALS OR EXCEEDS 12;
C. THE DOWELS ARE UNIFORMLY DISTRIBUTED ACROSS SEISMIC FORCE RESISTING MEMBERS (SUCH AS
SHEAR WALLS, COLLECTORS AND DIAPHRAGMS).
10. TESTING OF SHEAR DOWELS ACROSS COLD JOINTS IN SLABS ON GRADE WHERE THE SLAB IS NOT PART OF
THE LATERAL FORCE-RESISTING SYSTEM IS NOT REQUIRED.
11. REPLACE ANCHORS AND DOWELS THAT FAIL DURING TESTING AND RETEST. IF MORE THAN 10% OF THE
TESTED DOWELS AND ANCHORS FAIL TO ACHIEVE THE SPECIFIED TEST LOAD, TEST 100% OF THE DOWELS
AND ANCHORS INSTALLED WITHIN THE LAST 2 DAYS OF ANCHOR INSTALLATION.
12. A HYDRAULIC CYLINDER SHALL BE USED TO APPLY THE TENSION TEST LOAD TO THE ANCHOR WITH THE
CYLINDER SUPPORTED ON A LOADING PLATE HAVING A HOLE DIAMETER EQUAL TO 1.5 TO 2.0 TIMES THE
ANCHOR HOLE DIAMETER (CONFINED CONFIGURATION) UNLESS OTHERWISE APPROVED BY ENFORCEMENT
AGENCY.
13. THE FOLLOWING CRITERIA APPLY FOR THE ACCEPTANCE OF INSTALLED ANCHORS:
A. HYDRAULIC RAM METHOD: THE ANCHOR SHALL HAVE NO OBSERVABLE MOVEMENT AT THE
APPLICABLE TEST LOAD.
14. IF ANY ANCHOR FAILS TESTING, TEST ALL ANCHORS OF THE SAME TYPE, INSTALLED BY THE SAME
TRADE, NOT PREVIOUSLY TESTED UNTIL TWENTY (20) CONSECUTIVE ANCHORS PASS, THEN RESUME THE
INITIAL TEST FREQUENCY.
15. ALL HOLES FOR POST-INSTALLED ANCHORS SHALL BE DRILLED, CLEANED AND PREPARED IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS AND THE APPLICABLE ICC-ESR. WHERE AN ANCHOR DOES
NOT SET PROPERLY, OR FAILS A TENSION TEST, OR REINFORCEMENT IS ENCOUNTERED DURING DRILLING, THE
DRILLED HOLE MAY NOT BE REUSED. ABANDONED HOLES SHALL BE FILLED WITH NON-SHRINK GROUT. THE
MINIMUM SPACING BETWEEN AN ABANDONED HOLE AND A DRILLED HOLE USED FOR A POST-INSTALLED
ANCHOR SHALL NOT BE LESS THAN 1-1/2 ANCHOR DIAMETERS UNLESS OTHERWISE APPROVED BY THE
ENFORCEMENT AGENCY. IF THE ANCHOR OR DOWEL MAY NOT BE SHIFTED AS NOTED ABOVE, THE
STRUCTURAL ENGINEER OF RECORD WILL DETERMINE A NEW LOCATION.
16. LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES ATTACHED WITH ADHESIVE ANCHORS.
17. REQUIRED TEST LOADS ARE CALLED OUT AT EACH DETAIL. TEST ACCEPTANCE CRITERIA SHALL BE
PER IBC 2015 REQUIREMENTS
STRUCTURAL GENERAL NOTES:
GENERAL
WRITTEN APPROVAL OF THE ARCHITECT OR STRUCTURAL ENGINEER AND COR.
BE REPORTED SO THAT PROPER CLARIFICATION MAY BE MADE. MODIFICATION OF DETAILS OF CONSTRUCTION SHALL NOT BE MADE WITHOUT
SUPPLIED BY THE OWNER, BUT WITHOUT GUARANTEE OF ACCURACY. WHERE ACTUAL CONDITIONS CONFLICT WITH THE DRAWINGS, THEY SHALL
9. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS GIVEN AS THE BEST PRESENT KNOWLEDGE FROM PLANS
APPROVED BY THE STRUCTURAL ENGINEER.
8. NO HOLES, NOTCHES, BLOCKOUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS UNLESS DETAILED ON THE STRUCTURAL DRAWINGS OR
RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITIES FOR THE ABOVE.
THE SITE BY THE ARCHITECT OR STRUCTURAL ENGINEER SHALL NOT INCLUDED INSPECTION OF THE ABOVE ITEMS AND DOES NOT IN ANY WAY
SHALL INCLUDED BUT NOT BE LIMITED TO, BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC. OBSERVATION VISITS TO
SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE AND SAFETY OF WORKMEN DURING CONSTRUCTION. SUCH MEASURES
7. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR
6. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED DRAWINGS AND LARGE SCALE OVER SMALL.
5. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR OF ADJACENT EXISTING SURFACES ADJACENT EXISTING
DEVELOP NOT COVERED BY THE CONTRACT DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
SHOP DRAWINGS, START OF CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE ENCOUNTERED, OR CONDITIONS
4. ALL DIMENSIONS AND THE SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE JOB SITE PRIOR TO BID SUBMITTAL, START OF
REQUIRED, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
3. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE CONSTRUCTION STANDARDS. IF CLARIFICATION IS
HIS OWN EXPENSE AND AT NO EXPENSE TO THE OWNER OR ARCHITECT.
PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT
THE ATTENTION OF THE ARCHITECT PRIOR TO THE START OF CONSTRUCTION SO THAT A CLARIFICATION CAN BE ISSUED. ANY WORK
AND COORDINATION OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES THAT OCCUR SHALL BE BROUGHT TO
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW
1. ALL WORK SHALL COMPLY TO MEET VA DOCUMENT H-18-8 DATED OCTOBER 2016, INTERNATIONAL BUILDING CODE (IBC) 2015 AND
DESIGN PARAMETERS
1. STRUCTURE HAS BEEN DESIGNED IN COMPLIANCE WITH 2015 IBC AND ASCE 7-10
2. SEISMIC
SITE CLASS: D
SEISMIC DESIGN CATEGORY: D
SD : 1.047
OCCUPANCY CATEGORY IV
I = 1.5 p
COMPONENT IMPORTANCE FACTOR
s
EVALUATION SERVICES REPORT FOR THE SPECIFIC ANCHOR, AND AS REQUIRED BY THE MANUFACTURER. ALL EXPANSION ANCHORS
SHALL BE HILTI KB-TZ (ESR-1917) AS SPECIFIED ON DETAILS. ANY SUBSTITUTION MUST BE APPROVED BY SEOR AND AGENCIES
HAVING JURISDICTION OVER THIS PROJECT.
2. WHERE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS OR APPLICABLE ICC-ES EVALUATION SERVICES REPORT CALL FOR THE
APPLICATION OF AN INSTALLATION TORQUE, THE SPECIFIED TORQUE SHALL BE APPLIED WITH A CALIBRATED TORQUE WRENCH. THE
SPECIFIED INSTALLATION TORQUE SHALL NOT BE EXCEEDED. CALIBRATION MUST BE WITHIN 12 MONTHS.
3. ANCHORS ARE TYPICALLY AVAILABLE IN ELECTRO-GALVANIZED CARBON STEEL,HOT-DIPPED GALVANIZED CARBON STEEL, AND STAINLESS
STEEL. USE OF ELECTRO-GALVANIZED CARBON STEEL ANCHORS IS TYPICALLY LIMITED TO DRY, INTERIOR LOCATIONS, UNLESS OTHERWISE
NOTED. STAINLESS STEEL OR HOT-DIPPED GALVANIZED ANCHORS SHALL BE USED APPLICATIONS EXPOSED TO EXTERIOR WEATHER CONDITIONS.
FINAL AUTHORITY ON THE TYPE OF ANCHOR COATING UTILIZED RESTS WITH THE STRUCTURAL ENGINEER OF RECORD AND MUST BE APPROVED
BY SUCH.
4. EXPANSION ANCHORS FOR NON-VIBRATION ISOLATED MECHANICAL EQUIPMENT RATED OVER 10HP ARE NOT PERMITTED BY ASCE 7-10
SECTION 13.6.5.5.ANCHORS INSTALLED IN OVERHEAD CONDITIONS FOR NON-VIBRATION ISOLATED EQUIPMENT WITH RECIPROCATING OR
ROTATING MECHANISMS SHALL BE UNDERCUT ANCHORS.
5. THE SPECIAL INSPECTOR SHALL BE ON THE JOBSITE CONTINUOUSLY DURING ANCHOR INSTALLATIONS, UNLESS OTHERWISE NOTED IN ICC-ES
ESR,TO VERIFY ANCHOR TYPE, ANCHOR DIMENSIONS, CONCRETE TYPE, CONCRETE COMPRESSIVE STRENGTH, HOLE DIMENSIONS, ANCHOR
SPACINGS, EDGE DISTANCES, SLAB THICKNESS, ANCHOR EMBEDMENT, AND TIGHTENING TORQUE.
6. THE TESTING OF THE EXPANSION ANCHORS SHALL BE DONE IN THE PRESENCE OF THE SPECIAL INSPECTOR AND A REPORT OF THE TEST
RESULTS SHALL BE SUBMITTED TO THE COR.
7. TEST QUANTITY OF ANCHORS AS NOTED BELOW:
APPLICATION QUANTITY
STRUCTURAL 100% OF BOLTS
NON-STRUCTURAL 50% OF BOLTS
8. ANCHORS TO BE TESTED SHALL BE SELECTED AT RANDOM BY THE SPECIAL INSPECTOR.
9. UNDERCUT ANCHORS THAT ALLOW VISUAL CONFIRMATION OF FULL SET NEED NOT BE TESTED, UNLESS OTHERWISE NOTED BY ENFORCEMENT
AGENCY OR ENGINEER OR RECORD.
10. THE TEST LOAD MAY BE APPLIED BY USING OF A CALIBRATED TORQUE WRENCH FOR TORQUE-CONTROLLED EXPANSION ANCHORS.
11. THE FOLLOWING CRITERIA APPLY FOR THE ACCEPTANCE OF INSTALLED ANCHORS:
A. TORQUE WRENCH METHOD: THE APPLICABLE TEST TORQUE MUST BE REACHED WITHIN ONE-HALF (1/2) TURN OF THE NUT.
12. IF ANY ANCHOR FAILS TESTING, TEST ALL ANCHORS OF THE SAME TYPE, INSTALLED BY THE SAME TRADE, NOT PREVIOUSLY TESTED
UNTIL TWENTY (20) CONSECUTIVE ANCHORS PASS, THEN RESUME THE INITIAL TEST FREQUENCY.
13. WHEN INSTALLING DRILLED-IN ANCHORS IN EXISTING NON-PRESTRESSED REINFORCED CONCRETE, USE CARE AND CAUTION TO AVOID CUTTING
OR DAMAGING THE EXISTING REINFORCING BARS. WHEN INSTALLING THEM INTO EXISTING PRESTRESSED CONCRETE (PRE- OR POST-TENSIONED), LOCATE THE PRESTRESSED TENDONS BY USING A NON-DESTRUCTIVE METHOD PRIOR TO INSTALLATION. EXERCISE EXTREME CARE AND CAUTION
14. IF REBAR IS ENCOUNTERED DURING THE DRILLING, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE DRILLING AND CONTACT THE ENGINEER
OF RECORD.
15. LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES
ATTACHED WITH MECHANICAL ANCHORS.
16. IF THE CONCRETE CRACKS DURING THE INSTALLATION OF THE ANCHOR, THE ANCHOR SHALL BE REMOVED OR ABANDONED.
17. UNLESS OTHERWISE NOTED, PROVIDE MINIMUM EMBEDMENT OF ANCHORS AS FOLLOWS:
ANCHOR BOLT DIAMETER ANCHOR BOLT EMBEDMENT *
KB-TZ
* EMBEDMENTS BASED ON ICC-ES ESR 1917.
18. FOR REQUIRED TEST TORQUE VALUES REFER TO ICC-ESR EVALUATION SERVICE REPORT AND TORQUE VALUES AS FALLOWS:
TO AVOID CUTTING OR DAMAGING THE TENDONS DURING INSTALLATION. MAINTAIN A MINIMUM CLEARANCE OF ONE BETWEEN THE REINFORCEMENT
AND THE DRILLED-IN ANCHOR.
MECHANICAL ANCHORS
1. EXPANSION ANCHOR SYSTEMS:
A. CONCRETE: USE ONLY EXPANSION ANCHOR SYSTEMS THAT HAVE BEEN ISSUED AN ICC-ES REPORT IN ACCORDANCE WITH THE
OF ICC-ES AC193. ANCHOR SYSTEMS SHOULD BE APPROVED FOR USE IN CRACKED CONCRETE AND SEISMIC DESIGN CATEGORIES
A-F PER ICC EVALUATIONS SERVICES REPORT. ANCHOR SYSTEMS SHALL BE INSTALLED PER THE REQUIREMENTS OF THE ICC-ES
3/8"
1/2"
ANCHOR BOLT DIAMETER TORQUE (ft-lb)
KB-TZ
3/8"
1/2"
2"
2"
SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT OF NEW WORK.
STRUCTURAL STEEL
COMPLETE PENETRATION GROOVE WELDS AND BY TENSION TEST SECTION 6.2.5 AWS.
7. ALL COMPLETE PENETRATION GROOVE WELDS CONTAINED IN JOINTS AND SPLICES SHALL BE TESTED BY ULTRASONIC TESTING OF
6. ALL FIELD WELDING, EXCEPT TACK WELDING, SHALL BE CONTINUOUSLY INSPECTED BY APPROVED WELDING INSPECTOR.
ERECTION OF STEEL BUILDINGS AND THE AISC CODE OF STANDARD PRACTICE AND THE REQUIREMENTS OF PROJECT SPECIFICATIONS.
5. ALL STRUCTURAL STEEL SHALL BE FABRICATED IN ACCORDANCE WITH THE AISC SPECIFICATIONS FOR THE DESIGN FABRICATION AND
TOUCHED UP WITH GALVALOY. ALL HSS SECTIONS SHALL HAVE WELDED CAP PLATES TO SEAL EXPOSED ENDS.
4. ALL STEEL EXPOSED TO WEATHER SHALL BE HOT-DIPPED GALVANIZED G90 AFTER FABRICATION. ABRADED AREAS TO BE
TABLE J.2.4 & CHAPTER 22 OF THE IBC 2015.
WITHOUT INDICATION OF SIZE, USE MINIMUM SIZE WELDS AS SPECIFIED IN AISC MANUAL OF STEEL CONSTRUCTION, 14TH EDITION,
3. WELD LENGTHS CALLED FOR ON THE PLANS ARE THE NET EFFECTIVE LENGTH REQUIRED. WHERE FILLET WELD SYMBOL IS GIVEN
CERTIFIED WELDERS USING E70XX ELECTRODES (U.N.O.) AND THE SHIELDED METAL ELECTRIC ARC PROCESS.
2. ALL WELDING SHALL CONFORM TO THE SPECIFICATIONS OF THE AMERICAN WELDING SOCIETY AND SHALL BE PERFORMED BY
- ALL STRUCTURAL STEEL W10X AND LARGER U.N.O. A-992 OR A-572 (GR. 50)
1. STRUCTURAL STEEL SHALL CONFORM TO ASTM SPECIFICATIONS AS NOTED BELOW AND TO THE AISC SPECIFICATIONS FOR
- RECTANGULAR OR SQUARE HSS SECTIONS: A-500, GRADE B. F~SY=46 KSI
- AROUND HSS SECTIONS: A-500, GRADE B. F~SY=42 KSI
- CONNECTION PLATES, ANGLES, CHANNELS AND MISC. A-36 (UNLESS NOTED OTHERWISE)
FABRICATION AND ERECTION:
8. ALL HEADED ANCHORS AND EXPANSION ANCHORS EXPOSED TO WEATHER SHALL BE STAINLESS STEEL.
CONCRETE
ALL NEW CONCRETE BESIDES ROOF TOP CONCRETE PAD SHALL BE 3000 PSI (U.N.O.), HAVE AIR-DRY UNIT WEIGHT OF 145 P.C.F. WITH 4" SLUMP.
2. CONCRETE DESIGN MIXES SHALL BE PREPARED BY AN INDEPENDENT TESTING LAB AND APPROVED BY THE STRUCTURAL ENGINEER (CONCRETE
PROPORTIONED BY METHOD "B").
PLACING OF ALL CONCRETE SHALL BE INSPECTED BY THE JOB INSPECTOR. INSPECTOR TO VERIFY THAT REINFORCING STEEL AS DETAILED IS
SECURELY SUPPORTED IN PLACE DURING THE POUR.
3.
ANCHOR BOLTS, DOWELS, REINFORCING STEEL, INSERTS, ETC., SHALL BE SECURELY TIED IN PLACE PRIOR TO POURING CONCRETE. CONCRETE
BLOCKS ONLY SHALL BE USED TO SUPPORT REINFORCING OFF GRADE.
PROVIDE 3/4" CHAMFER ON ALL EXPOSED CONCRETE CORNERS. CHAMFER NOT SHOWN ON DETAILS FOR CLARITY.
ALL CONCRETE SHALL BE VIBRATED IN PLACE DURING PLACING OF CONCRETE.
NO STAKES, STEEL OR WOOD, SHALL BE PERMITTED IN ANY CONCRETE POUR. SUSPEND FORMS FROM ABOVE GRADE.
4.
5.
6.
7.
8.
SURFACE; MINIMUM F'c = 7,000 PSI, PLASTIC STATE. NUBUMUM F'c = 7,000 PSI, PLASTIC STATE.
DRY PACK SHALL BE NON-SHRINKING, NON-METALLIC GROUT WITH SUFFICIENT WATER TO ALLOW A SMALL AMOUNT OF PASTE TO COME TO THE
9.
GROUT SHALL BE 1:3:2 PORTLAND CEMENT TO SAND TO PEA GRAVEL WITH A MINIMUM 28 DAY STRENGTH OF 4,000 PSI.
10. CONCRETE GROUT SHALL BE NON-SHRINKING, NON-METALLIC GROUT WITH SUFFICIENT WATER TO ALLOW POURING.
11.
ANCHOR BOLTS SHALL CONFORM TO ASTM F1554 UNLESS GRADE A36 OR ANY OTHER GRADE NOTED.
CORED HOLES AND DRILLED HOLES FOR EXPANSION ANCHOR INSTALLATIONS SHALL BE MADE SO AS NOT TO CUT ANY EXISTING REINFORCING BARS.
12.
REINFORCING
ALL REINFORCING SHALL CONFORM TO ASTM A615, GRADE 60, UNLESS NOTED OTHERWISE HEREIN. WELDED WIRE FABRIC SHALL CONFORM TO ASTM
A185. ANY NEW REINFORCEMENT TO BE WELDED SHALL ALSO CONFORM TO THE CHEMICAL REQUIREMENTS OF ASTM A615 REINFORCING STEEL.
2. REINFORCING BARS SHALL BE SPLICED AND BENT IN STRICT ACCORDANCE WITH THE DRAWINGS AND DETAILS AND C.R.S.I. PUBLICATIONS. NO KINKS
ALLOWED. ALL BARS SHALL BE CLEAN PRIOR TO CONCRETE PLACEMENT. SPLICE SHALL BE STAGGERED AT LEAST 24".
3.
LAPS TO BE IN ACCORDANCE WITH THE DRAWINGS AND DETAILS. DOWELS SHALL BE CLEANED AFTER POUR.
PROVIDE DOWELS OF SAME SIZE AND NUMBER FROM ADJACENT POUR, BOTH VERTICALLY & HORIZONTALLY TO MATCH TYPICAL REINFORCING SHOWN.
WHEN CONCRETE IS PLACED AGAINST PREVIOUSLY HARDENED CONCRETE, THE INTERFACE SHALL BE CLEAN AND FREE OF LAITANCE. THE INTERFACE
SHALL BE ROUGHENED TO A FULL AMPLITUDE OF APPROXIMATELY 1/4 INCH PRIOR TO FRESH CONCRETE PLACEMENT.
REINFORCEMENT SHALL BE SUCH THAT HE SPLICES IN ALTERNATE BARS WITHIN A CURTAIN OF REINFORCEMENT IS STAGGERED A MINIMUM OF
WHERE LAP SPLICES FOR REINFORCING INTENDED TO BE CONTINUOUS ARE REQUIRED, SUCH SPLICES SHALL CONFORM TO A CLASS "B" SPLICE
UNLESS NOTED OTHERWISE. SPLICES IN ALTERNATE BARS SHALL BE OFFSET 36 INCHES MINIMUM. ALL SPLICES SHALL BE SHOWN ON THE
REINFORCING SHOP DRAWINGS. LAP SPLICES SHALL BE MADE AWAY FROM POINTS OF MAXIMUM STRESS WHEREVER POSSIBLE. SPLICES IN WALL
24 INCHES, AND SPLICES OF REINFORCEMENT IN ADJACENT CURTAINS SHALL ALSO BE STAGGERED A MINIMUM OF 24 INCHES SO AS NOT TO
OCCUR IN THE SAME LOCATION. MINIMUM SPLICE LENGTHS SHALL BE AS SHOWN ON DETAILS.
8.
9.
ALL REINFORCING BENDING DETAILS SHALL BE IN ACCORDANCE WITH SECTION 1907 IBC 2015 AND AC1 318-14.
WELDED WIRE FABRIC SHALL COMPLY TO ASTM A-185 SPECIFICATIONS.
ALL REINFORCING IN CONCRETE USED FOR THE CONTAINMENT OF WATER SHALL BE HOT-DIPPED GALVANIZED OR EPOXY COATED AFTER FABRICATION. 10.
11.
12.
1.
SHOP DRAWINGS FOR REINFORCING STEEL SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER OF RECORD (SEOR) FOR APPROVAL PRIOR TO
FABRICATION.
4.
1.
5. FIELD WELDING OR BENDING OF REINFORCING IS NOT PERMITTED EXCEPT AS INDICATED ON THE DRAWINGS OR AS APPROVED BY THE STRUCTURAL
ENGINEER (SEOR) & THE AGENCIES HAVING JURISDICTION OVER THIS PROJECT.
6. BARS SHALL NOT BE RE-BENT.
7. WELDING OF STIRRUPS, TIES, INSERTS OR OTHER SIMILAR ELEMENTS TO LONGITUDINAL REINFORCEMENT IS NOT PERMITTED.
5/8" 60
5/8" 3 1/8"
9. HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM A-325 UNLESS NOTED OTHERWISE, OTHER BOLTS, AS NOTED, SHALL CONFORM TO ASTM A307.
A-490 BOLTS.
10. ALL HIGH STRENGTH BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH "SPECIFICATION FOR STRUCTURAL JOINTS" USING ASTM A-325 OR
11. PROVIDE BEVELED WASHERS ON ALL CONNECTION TO SLOPING FLANGES OF W SECTION AND CHANNELS WHERE SLOPE EXCEEDS 1:20.
BASED ON ACI 318-14 SPECIFIED MIX DESIGN METHOD. ROOF TOP CONCRETE PAD TO BE LIGHT WEIGHT AGGREGATE UNLESS NOTED
OTHERWISE. L.W. AGGREGATE TO BE EXPANDED CLAY OR SHALE CONFORMING TO ASTM C-330. AIR-DRY UNIT WEIGHT SHALL BE 110 PCF
ALL CONCRETE STRENGTHS SHOWN ARE ULTIMATE 28 DAY COMPRESSIVE STRENGTHS. SELECTION OF CONCRETE PROPORTIONS SHALL BE
WITH A TOLERANCE OF ± 5 PCF.
REQUIREMENTS OF PROJECT SPECIFICATIONS.
10. UNLESS OTHERWISE NOTED, ALL ELEMENTS SHOWN ON PLANS AND DETAILS ARE NEW ELEMENTS.
MECHANICAL ANCHORS (Cont.)
3/4" 3 1/4"
3/4" 110
AV PAHCS
Veterans Affairs Veterans Affairs• tel: 626.793.9805 fax: 626.793.9807
48 east holly street, pasadena, ca 91103
SWA Architect
SWA 20170024
PH: 626.463.2800
FAX: 626.463.2801
www.ttgcorp.com
300 N. LAKE AVENUE
14TH FLOOR
PASADENA, CA
91101 Project No.
d/b/a
17001385.00
Exp. 09/30/18
C
O
F
E
S
S
T
A
T
T
R
U
C A
L
I
F
A
L
T
U
R
O
R
N
I
A
R
No.5145
E
E
R
E
R E G
I S
T
D
P
R
O
F
E
N
G
I
N
E E
A
L
SS
I O
N
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Professional Seal
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Check-by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Architects
AutoCAD SHX Text Drawn-by:
AutoCAD SHX Text Office of Facilities Management
AutoCAD SHX Text Engineers/Consultants
AutoCAD SHX Text \\AD.KJWW.COM\KJWW\KJWW\PROJECTS\2017\17001385.00\CAD-BIM FOLDERS\AUTOCAD\_STR\17001385_SS1.DWG - 2/12/2018 2:04 PM - 2/12/2018 2:04 PM2/12/2018 2:04 PM
AutoCAD SHX Text Design Development ONLY-NOT for Construction
AutoCAD SHX Text Building Number:
AutoCAD SHX Text Drawing Number:
AutoCAD SHX Text Project Number:
AutoCAD SHX Text B126
AutoCAD SHX Text 600-17-102
AutoCAD SHX Text Location:
AutoCAD SHX Text Project Title
AutoCAD SHX Text
5901- EAST SEVENTH STREET
AutoCAD SHX Text
LONG BEACH, CALIFORNIA, 90822
AutoCAD SHX Text
DEPARTMENT OF VETERANS AFFAIRS
AutoCAD SHX Text
TIBOR RUBIN VA MEDICAL CENTER
AutoCAD SHX Text
B126 RENOVATE HOSPITAL
AutoCAD SHX Text
ROOM SERVICE KITCHEN
AutoCAD SHX Text
AM
AutoCAD SHX Text
AS
AutoCAD SHX Text
100%%% FINAL CONSTRUCTION DOCUMENT
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text SD 35%%% Submission
AutoCAD SHX Text 08-22-2017
AutoCAD SHX Text DD 65%%% Submission
AutoCAD SHX Text 10-27-2017
AutoCAD SHX Text CD 95%%% Submission
AutoCAD SHX Text 02-19-2018
AutoCAD SHX Text CD 100%%% Submission
AutoCAD SHX Text 04-06-2018
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text See Revisions Date
AutoCAD SHX Text
SS-1
AutoCAD SHX Text
GENERAL NOTES
STRUCTURAL GENERAL NOTES (Cont.):
METAL STUDS
1. STUDS SHALL CONFORM TO STANDARDS OF THE STEEL STUD MANUFACTURERS ASSOCIATION (SSMA) ICC
ER 3064-P. STUDS SHALL CONFORM TO ASTM A653 SS GRADE 33 FOR 18 GAGE AND LIGHTER AND
A653 SS GRADE 50 CLASS 1 FOR 16 GAGE AND HEAVIER. TRACK STUDS SHALL BE OF THE SAME GAGE
AND GRADE AS THE SUPPORTED STUD.
2. STUD FRAMING SHALL BE IN ACCORDANCE WITH AISI, "SPECIFICATIONS FOR DESIGN OF COLD
FORMED STEEL STRUCTURAL MEMBERS".
3. STUDS SHALL BE PAINTED OR GALVANIZED PER SPECIFICATIONS.
4. CONFIRMATION SHALL BE MADE THAT THE COLD-FORMED STEEL MEMBERS BEING INSTALLED MATCH THE
PROJECT'S SPECIFIED SIZE, TYPE, MECHANICAL PROPERTIES AND SPACING.
5. SCREW CONNECTIONS:
A. SCREWS LARGER THAN SPECIFIED MAY BE USED, PROVIDED THE MINIMUM SPACING
AND EDGE DISTANCE REQUIREMENTS ARE MET.
B. SCREWS SHALL BE FULLY DRIVEN AND HAVE A MINIMUM PENETRATION OF THREE THREADS
THROUGH THE LAST MATERIAL JOINED.
C. SCREWS SHALL HAVE PROTECTIVE COATING TO COMPLY WITH RECOGNIZED DESIGN STANDARD
FOR THE PROJECT ENVIRONMENTAL CONDITIONS.
6. WELDING: ALL WELDING SHALL COMPLY WITH RECOGNIZED STANDARDS AND STRUCTURAL WELDING
CODE AWS D1.1 (WHEN WELDING SHEET STEEL TO STRUCTURAL STEEL 1/8" AND THICKER) AND
STRUCTURAL WELDING CODE SHEET STEEL, AWS D1.3-98 (WHEN WELDING SHEET STEEL TO SHEET STEEL).
7. WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS. SUBMIT WRITTEN WELDING PROCEDURE SPECIFICATIONS
FOR REVIEW PRIOR TO FABRICATION. USE LOW HYDROGEN ELECTRODES FOR WELDING TO STRUCTURAL STEEL.
8. BOLTED CONNECTIONS: BOLTS SHALL MEET OR EXCEED THE REQUIREMENTS OF ASTM A307 AND
SHALL BE INSTALLED WITH NUTS AND WASHERS AT SPACING PER RECOGNIZED DESIGN STANDARD.
9. BEARING SURFACES: UNIFORM BEARING SURFACE SHALL BE PROVIDED WITH A MAXIMUM 1/4" GAP
BETWEEN BOTTOM TRACK AND THE FOUNDATION OR SLAB. IT SHALL BE ACCOMPLISHED BY THE USE OF
LOAD BEARING SHIMS AND/OR GROUT PROVIDED BETWEEN THE UNDERSIDE OF THE WALL BOTTOM TRACK
AND THE TOP OF THE FOUNDATION OR SLAB AT EACH STUD.
10. TYPICAL DETAILS SHOWN SHALL BE INCORPORATED INTO THE PROJECT AT ALL APPROVED LOCATIONS
WHETHER SPECIFICALLY CALLED OUT OR NOT.
11. STUDS SHALL HAVE THE FOLLOWING PRODUCT IDENTIFICATION:
600S137-68
MEMBER DEPTH (6"=600X1/100 IN) MATERIAL THICKNESS (MILS)
STYLE: FLANGE WIDTH
S= STUD OR JOIST
T= TRACK
12. THICKNESS OF SECTIONS PER SSMA DESIGNATION:
THICKNESS DISIGN THICKNESS GAUGE NO.
(MILS) (IN) (REFERENCE ONLY)
33 0.0346 20-STRUCTURAL
43 0.0451 18
54 0.0566 16
68 0.0713 14
97 0.1017 12
SEISMIC BRACING OF MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS
1. SHOP DRAWINGS OF THE SUPPORTS AND BRACING SYSTEMS IN ACCORDANCE WITH THE
PRE-APPROVAL SHALL BE SUBMITTED TO THE DISCIPLINE IN RESPONSIBLE CHARGE OF THE
PROJECT FOR REVIEW TO VERIFY THAT THE DETAILS ARE IN CONFORMANCE WITH ALL CODE
ASCE 7-10 SECTION 13.6 & VA DOCUMENT H-18-8 DATED OCTOBER 2016.
A) THE STRUCTURAL ENGINEER OF RECORD (SEOR) SHALL VERIFY THAT THE SUPPORTING
STRUCTURE IS ADEQUATE FOR THE LOADS IMPOSED ON IT BY THE SUPPORTS AND BRACES
INSTALLED IN ACCORDANCE WITH THE PRE-APPROVAL IN ADDITION TO ALL OTHER LOADS.
B) THE SEOR WILL FORWARD THE ANCHORAGE AND BRACING DRAWINGS (INCLUDING
APPROVED CHANGE ORDERS FOR SUPPLEMENTARY FRAMING WHERE REQUIRED) TO THE
DISCIPLINE IN RESPONSIBLE CHARGE WITH A NOTATION INDICATING THAT THE DRAWINGS
HAVE BEEN REVIEWED AND ARE IN GENERAL CONFORMANCE WITH THE OPM
1. MASON SEISMIC RESTRAINT GUIDELINES, OSHPD OPM-0043-13
C) A "SHOP DRAWING STAMP" MAY BE USED TO INDICATE COMPLIANCE WITH THIS
REQUIREMENT.
D) THE REGISTERED DESIGN PROFESSIONAL (OTHER THAN SEOR) MAY PROVIDE THE
SHOP DRAWING STAMP FOR SMALL PROJECTS AT THE DISCRETION OF THE DISTRICT
STRUCTURAL ENGINEER.
2. THE SHOP DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE SUBMITTED TO THE
DISTRICT STRUCTURAL ENGINEER TO REVIEW THE FP FOR PRE-APPROVED SYSTEM.
3. THE SHOP DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE KEPT ON THE JOBSITE
AND CAN THEN BE USED FOR INSTALLATION OF THE SUPPORT AND BRACING.
- VA FIELD STAFF WILL REVIEW THE INSTALLATION.
4. A COPY OF THE CHOSEN BRACING SYSTEM(S) INSTALLATION GUIDE/MANUAL SHALL BE ON
THE JOBSITE PRIOR TO STARTING THE INSTALLATION OF HANGERS AND/OR BRACES.
- IT IS THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN COPIES OF VA PRE-APPROVALS
AND FURNISH THE IOR WITH ONE COPY OF EACH.
5. COMPONENTS OF TWO OR MORE PRE-APPROVED BRACING SYSTEMS SHALL NOT BE MIXED.
ONLY ONE PRE-APPROVED BRACING SYSTEM MAY BE USED FOR A RUN OF PIPE,
DUCT OR CONDUIT.
2. B-LINE/TOLCO OPM-0052-13 AND THE DESIGN OF THE PROJECT.
DEMOLITION
1. ALL DEMOLITION SHALL BE CARRIED ON IN SUCH A WAY AS NOT TO DAMAGE EXISTING ELEMENTS
WHICH ARE TO REMAIN.
2. ALL ELEMENTS WHICH ARE TO REMAIN AND WHICH ARE DAMAGED DURING DEMOLITION WORK
SHALL BE REPLACED AT NO ADDED COST. EXISTING ELEMENTS TO BE PROTECTED TO THE FULLEST
EXTENT POSSIBLE TO REDUCE SUCH DAMAGE TO A MINIMUM.
SCREW INSTALLATION INTO ELECTRICAL, MECHANICAL, MEDICAL OR ANY EQUIPMENT
1. CONTRACTOR SHALL PROVIDE MAXIMUM CARE AND COORDINATION, WHEN INSTALLATION OF THE SCREWS
INTO ELECTRICAL & MECHANICAL EQUIPMENTS IS REQUIRED.
2. CONTRACTOR MUST VERIFY EACH LOCATION OF SCREW TO BE INSTALLED, PRIOR TO ANY PENETRATION, REGARDLESS OF LENGTH OF PROTRUSION.
3. PENETRATION OF SCREWS THROUGH JOINED MATERIAL SHOULD NOT BE LESS THAN 3 EXPOSED THREADS.
CONTRACTOR SHALL VERIFY AT EACH CASE, SO AS NOT TO DAMAGE THE CONTENT AND OR FUNCTION
OF THE EQUIPMENT.
4. CONTRACTOR SHALL PROVIDE EPOXY, REZIN COVER, OR ANY OTHER REQUIRED ITEM AS PART OF THEIR
MEANS & METHODS TO PROTECT THE SHARP EDGES OF THE SCREW DURING THE USAGE FUTURE
AND/OR MAINTENANCE OF THE EQUIPMENT.
5. THE MINIMUM SPACING BETWEEN CENTERS OF FASTENERS SHALL NOT BE LESS THAN 3X FASTENER
DIAMETER. THE MINIMUM EDGE DISTANCE FROM THE CENTER OF A FASTENER TO THE EDGE OF
ANY PART SHALL NOT BE LESS THAN 1.5X FASTENER DIAMETER.
6. USE ONLY SCREWS THAT HAS BEEN ISSUED ON ICC-ES REPORT IN ACCORDANCE WITH PROVISIONS
OF ICC-ES-AC-118.
7. SCREWS SHALL HAVE VALID ICC REPORT SUCH AS ICC-2196, ICC-1408 OR ICC-1730. ANY
SUBSTITUTION MUST BE APPROVED BY SEOR.
8. 1/4" THRU BOLT MAY BE USED IN LIEU OF SCREW FOR ELECTRICAL EQUIPMENT ANCHORAGE AS SHOWN
ON DETAIL.
SHORING
1. WHERE THERE IS NOT SUFFICIENT SPACE FOR SLOPED EMBANKMENTS, SHORING WILL BE REQUIRED
(SEE CONTRACT DRAWINGS).
2. REFER TO THE SOILS REPORT FOR INFORMATION REGARDING THE DESIGN AND INSTALLATION OF THE
SHORING. SHORING THAT IS NOT PART OF THE PERMANENT BUILDING SUPPORT IS THE CONTRACTOR'S
RESPONSIBILITY AND OUTSIDE THIS PERMIT.
ABBREVIATIONS
# Number or pounds
@ At
CL Center line
-3" Slab Depression
A.B. Anchor Bolt
APG Auger Pressure Grouted
AISC American Institute of Steel Construction
Anch. Anchor
BF Brace Frame
Bm.
Bottom of Footing
Bott.
Beam
Btwn.
Bottom
CIDH
Between
Clr.
Cast In Drilled Hole
Col.
Clear
Conc.
Column
Cont.
Concrete
Det.
Continuous
Dia.
Detail
Dim.
Diameter
Dwg.
Dimension
Dwl.
Drawing
(E)
Dowel
E.F.
Existing
E.W.
Each Face
Ea.
Each Way
EL
Each
Electl.
Elevation
Elev.
Electrical
E.O.S.
Elevator
Exp.
Edge of Slab
Extr.
Expansion
F.O.C.
Exterior
F.O.S.
Face of Concrete
F.O.W.
Face of Stud
Fdn.
Face of Wall
Fin.
Foundation
Flr.
Finish
Frmg.
Floor
Ftg.
Framing
Ga.
Footing
Galv.
Gage
Gr. Bm.
Galvanized
HI
Grade Beam
H.S.B.
High
Horiz.
High Strength Bolt
Intr.
Horizontal
B.O.F.
Interior
LO Low
Lt. Wt. Lightweight
M.B. Machine Bolt
Max. Maximum
Mechl. Mechanical
Mfr. Manufacturer
Minimum
Mtl. Metal
(N) New
N.T.S.
Not in Contract
No.
Not to Scale
O.C.
Number
O.H.
On Center
Pc
Opposite Hand
P.H.
Piece
Pl.
Penthouse
Plcs.
Plate
Reinf.
Places
S
Reinforcing
S.A.
Strut/Drag Steel Beam
SCBF
Stud Anchor
Sched.
Special Concentric Brace Frame
Sect.
Schedule
Sep'n.
Section
Sim.
Separation
S.L.R.S.
Similar
SOG
Seismic Load Resisting System
SOMD
Slab on Grade
Spec.
Slab on Metal Deck
Sq.
Specification
Std.
Square
Stiff.
Standard
Stl.
Stiffener
STMS
Steel
Suppt.
Self Tapping Machine Screws
Sym.
Support
T.O.
Symmetrical
T.O.S.
Top of
T.O.W.
Top of Steel
Thk.
Top of Wall
Typ.
Thick
U.N.O.
Typical
V.O.J.
Unless Noted Otherwise
V.O.S.
Verify on Job
Vert.
Verify on Site
W.P.
Vertical
Wt.
Work Point
N.I.C.
Weight
Min.
W/ With
N.WT. Normal Weight
Jt. Joint
AV PAHCS
Veterans Affairs Veterans Affairs• tel: 626.793.9805 fax: 626.793.9807
48 east holly street, pasadena, ca 91103
SWA Architect
SWA 20170024
PH: 626.463.2800
FAX: 626.463.2801
www.ttgcorp.com
300 N. LAKE AVENUE
14TH FLOOR
PASADENA, CA
91101 Project No.
d/b/a
17001385.00
Exp. 09/30/18
C
O
F
E
S
S
T
A
T
T
R
U
C A
L
I
F
A
L
T
U
R
O
R
N
I
A
R
No.5145
E
E
R
E
R E G
I S
T
D
P
R
O
F
E
N
G
I
N
E E
A
L
SS
I O
N
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Professional Seal
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Check-by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Architects
AutoCAD SHX Text Drawn-by:
AutoCAD SHX Text Office of Facilities Management
AutoCAD SHX Text Engineers/Consultants
AutoCAD SHX Text \\AD.KJWW.COM\KJWW\KJWW\PROJECTS\2017\17001385.00\CAD-BIM FOLDERS\AUTOCAD\_STR\17001385_SS2.DWG - 2/14/2018 1:44 PM - 2/14/2018 1:44 PM2/14/2018 1:44 PM
AutoCAD SHX Text Design Development ONLY-NOT for Construction
AutoCAD SHX Text Building Number:
AutoCAD SHX Text Drawing Number:
AutoCAD SHX Text Project Number:
AutoCAD SHX Text B126
AutoCAD SHX Text 600-17-102
AutoCAD SHX Text Location:
AutoCAD SHX Text Project Title
AutoCAD SHX Text
5901- EAST SEVENTH STREET
AutoCAD SHX Text
LONG BEACH, CALIFORNIA, 90822
AutoCAD SHX Text
DEPARTMENT OF VETERANS AFFAIRS
AutoCAD SHX Text
TIBOR RUBIN VA MEDICAL CENTER
AutoCAD SHX Text
B126 RENOVATE HOSPITAL
AutoCAD SHX Text
ROOM SERVICE KITCHEN
AutoCAD SHX Text
AM
AutoCAD SHX Text
AS
AutoCAD SHX Text
100%%% FINAL CONSTRUCTION DOCUMENT
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text SD 35%%% Submission
AutoCAD SHX Text 08-22-2017
AutoCAD SHX Text DD 65%%% Submission
AutoCAD SHX Text 10-27-2017
AutoCAD SHX Text CD 95%%% Submission
AutoCAD SHX Text 02-19-2018
AutoCAD SHX Text CD 100%%% Submission
AutoCAD SHX Text 04-06-2018
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text See Revisions Date
AutoCAD SHX Text
SS-2
GENERAL NOTES
NONE
TYPICAL REINFORCING DETAILS
NONE
TYPICAL OPENING IN EXISTING FLOOR
NONE
NEW CONCRETE PAD ON EXISTING SLAB
NONE
DEPRESSED SLAB INFILL
NONE
EXTENDED CONCRETE PAD DETAIL
DO NOT OVER CUT CORNERS
SAWCUT ONLY TO CORED HOLES
CHIP OUT CORNER AS REQUIRED
FOR SQUARE OPENING
CORE 6" DIAMETER HOLE
IN EACH CORNER OF
OPENING PRIOR TO
SAWCUTTING OPENING
EXISTING MASONRY OR
CONCRETE
SAWCUT OPENING
IN EXISTING CONC.
OR MASONRY
CLEAN & ROUGHEN
(E) MIN. 7 1/2" CONC.
1/4" AMPLITUDE
(ICC ESR-3814)-TYP.
HIT-RE 500-V3 ADHESIVE
HOLE WITH HILTI
PLACE BAR IN DRILLED
#4 @ 18" O.C. EA. WAY
C L R
M A
X
SURFACE TO
#4 @ 18" O.C.
3 MIN.
T Y
P
8"
TYP.
EXP. ANCHOR
SLAB (3000 PSI)
TOOLED
RADIUS-TYP.
6" MIN.
TYP. U.N.O.
NOTE:
FOR OPENING LOCATION SEE ARCH'L AND MEP DRAWINGS.
NOTE:
FOR NEW CONC. PAD LOCATION AND SIZE SEE ARCH'L AND MEP DRAWINGS.
(N) N.WT. CONC. PAD
(TENSION TEST = 2000#)
SEE SCHEDULE FOR
THE BARS, EXCEPT IN WALLS.
OF CONCRETE CAST BELOW
BARS WITH MORE THAN 12"
BY 1.3 FOR HORIZONTAL
* MULTIPLY LENGTHS SHOWN
#8 5'-11"
#7 5'-2"
#6 3'-7"
#5 3'-0"
#4 2'-4"
#3 1'-9"
SPLICE LENGTH *
ALL HOOKS, BENDS & LAPS SHALL BE AS INDICATED, U.N.O.
NOTE:
MAX. SLOPE
135 DEG. BEND
LAP SPLICE
180 DEG. BEND OFFSET 90 DEG. BEND
'd' BAR DIAMETER d
TOGETHER - TYP.
WIRE REINFORCING
'd'
'd' BAR DIAMETER
CONCRETE SPLICE LENGTH
BAR DIAMETER
6d FOR #3 THRU #8
'D' = BAR BEND DIAMETER2 1/2"
4d d
D
D
D
D
M
I N
50 d - 2'-0" MIN. MASONRY d4
M
I
N
EACH SIDE
4"
TYP.
(E) 7 1/2" CONC. SLAB
LT.WT CONC. SLAB
#4 REBAR @ 18" O.C.
EACH WAY-TYP.
SET BAR WITH
HILTI HIT RE 500-V3
ADHESIVE
(MIN. 2 REBAR EA. WAY)
NOTE:
1. FOR THE INFILL AREA AND DIMENSIONS SEE ARCH'L.
CLEAN & ROUGHEN
1/4" AMPLITUDE
SURFACE TO
(4000psi)
(ICC ESR-3814)-TYP.
#4 @ 18" O.C.
E.W., TYP. MIN.
SET BAR WITH HILTI
HIT RE 500-V3 ADHESIVE
(ICC ESR-3814)-TYP.
2 REBAR EA. WAY
CLEAN & ROUGHEN
SURFACE TO 1/4"
AMPLITUDE
(E) 4" CONC. PAD
SEE MECH'L FOR DIMENSION
(MIN. 3000psi)
(N) EXTENDED
N.WT. CONC. PAD
T Y
P
6"
DOWELED
#4x2'-0" @ 18" O.C.
(ICC ESR-3814)
6" MIN.
(E) 7 1/2" N.WT. CONC.
(MIN. 3000psi)
M I N
TYP. U.N.O.
MIN.
2 1/2" STRUCTURAL
STYROFOAM
2'-0"
PREFAB. TRENCH AND
BY MFR. (WHERE OCCURS)
CONNECTION TO CONC.
2. FOR TRENCH LOCATION-SEE ARCH'L.
(TENSION TEST = 2000#)
T Y
P
NEW OPENING
NONE
PIPE/CONDUIT THRU CONCRETE SLAB
(E) CONCRETE SLAB
PIPE OR CONDUIT
NOTE:
1. VERIFY LOCATION OF (E) REBAR PRIOR OF ANY CORING.
2. DO NOT CUT (E) REBAR.
3. PROVIDE 2" MINIMUM DISTANCE BETWEEN (E) REBAR AND (N) CORE.
W
(E) OR (N) CORE
4 1/2"
MAX.
SEE NOTE 4
4. W = 13 1/2" MIN. OR 3D WHICHEVER IS BIGGER.
D
NONE
TYPICAL CONCRETE PAD ON ROOF SLAB
6'-0"
M
A X
RIGID STYROFOAM
(4000psi)
SURFACE TO 1/4"
AMPLITUDE-TYP.
#4-TYP.
(E) 7 1/2" N.WT. CONC.
N.WT. CONC. PAD
W/ COMPRESSIVE
STRENGTH=100psf
CLEAN & ROUGHEN
(ICC ESR-3814)-TYP.
W/ 4" EMBED.
W/ HILTI RE 500 V3 ADHESIVE
PLACE BAR IN DRILLED HOLE
(TENSION TEST=2000#)
#4 @ 18" O.C.-TYP.
LEVEL
(MIN. 3000psi)
MAX.
6"
TYP.
EQ.
TYP.
EQ.
TYP.
M
I N
C L R
EACH WAY-TYP.
#4 @ 18" O.C.
AV PAHCS
Veterans Affairs Veterans Affairs• tel: 626.793.9805 fax: 626.793.9807
48 east holly street, pasadena, ca 91103
SWA Architect
SWA 20170024
PH: 626.463.2800
FAX: 626.463.2801
www.ttgcorp.com
300 N. LAKE AVENUE
14TH FLOOR
PASADENA, CA
91101 Project No.
d/b/a
17001385.00
Exp. 09/30/18
C
O
F
E
S
S
T
A
T
T
R
U
C A
L
I
F
A
L
T
U
R
O
R
N
I
A
R
No.5145
E
E
R
E
R E G
I S
T
D
P
R
O F
E
N
G
I N
E E
A
L
SS
I O
N
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Professional Seal
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Check-by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Architects
AutoCAD SHX Text Drawn-by:
AutoCAD SHX Text Office of Facilities Management
AutoCAD SHX Text Engineers/Consultants
AutoCAD SHX Text \\AD.KJWW.COM\KJWW\KJWW\PROJECTS\2017\17001385.00\CAD-BIM FOLDERS\AUTOCAD\_STR\17001385_SS3.DWG - 4/5/2018 10:18 AM - 4/5/2018 10:18 AM4/5/2018 10:18 AM
AutoCAD SHX Text Design Development ONLY-NOT for Construction
AutoCAD SHX Text Building Number:
AutoCAD SHX Text Drawing Number:
AutoCAD SHX Text Project Number:
AutoCAD SHX Text B126
AutoCAD SHX Text 600-17-102
AutoCAD SHX Text Location:
AutoCAD SHX Text Project Title
AutoCAD SHX Text
5901- EAST SEVENTH STREET
AutoCAD SHX Text
LONG BEACH, CALIFORNIA, 90822
AutoCAD SHX Text
DEPARTMENT OF VETERANS AFFAIRS
AutoCAD SHX Text
TIBOR RUBIN VA MEDICAL CENTER
AutoCAD SHX Text
B126 RENOVATE HOSPITAL
AutoCAD SHX Text
ROOM SERVICE KITCHEN
AutoCAD SHX Text
AM
AutoCAD SHX Text
AS
AutoCAD SHX Text
100%%% FINAL CONSTRUCTION DOCUMENT
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text SD 35%%% Submission
AutoCAD SHX Text 08-22-2017
AutoCAD SHX Text DD 65%%% Submission
AutoCAD SHX Text 10-27-2017
AutoCAD SHX Text CD 95%%% Submission
AutoCAD SHX Text 02-19-2018
AutoCAD SHX Text CD 100%%% Submission
AutoCAD SHX Text 04-06-2018
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text See Revisions Date
AutoCAD SHX Text
SS-3
SECTIONS AND DETAILS
TYPICAL BACKING SUPPORT
OVER 3 STUDS MIN. (U.N.O.)
(N) 6x16GA. OR 4x16GA.
(E) METAL STUD
3-#12 S.M.S.SEE DETAILS
NON-PUNCHED TRACK-TYP.
1/4" MAX.
TYP.
EXTEND BACKING TRACK ONE STUD BAY BEYOND
THE EDGE OF THE SUPPORTED EQUIPMENT OR CABINET.
NOTE:
NONE
STEAM JACKETED KETTLE ANCHORAGE
NONE
FLANGED FOOT MOUNTED EQUIPMENT DETAIL
NONE
HOOD HANGER & BRACE CONNECTION DETAILS
1/2"Ø A36 ALL THREAD
ROD STIFFENER CLAMP,
MASON, OPM-0043-13
SUSPENDED
EQUIPMENT
ROD STIFFENER, *
UNISTRUT P1000
(E) 7 1/2" N.WT. CONC.
(MIN. 3000psi)
1/2"Ø HILTI KB-TZ
W/ 3 1/4" EMBED.
(ICC-ESR 1917)-TYP.
115"
PLAN
ELEVATION
WT.=831#
MAX.
1/2"Ø HANGER ROD
(4 PER SECTION)-TYP.
MAX.
* USE ROD STIFFENER
WHERE BRACE OCCURS.
P1843W TOP AND BOTT.
W/ 1/2"Ø BOLT-TYP.
EQUIPMENT MOUNTING
BRACKET (BY MFR)
5° MAX. SWAY
ALLOWED TO SIDES
TYP. EACH BRACE
ALTERNATIVE LONGITUDINAL
BRACE LOCATION-TYP.
P1000 BRACE
1/2"Ø HILTI KB-TZ
(ICC ESR-1917)
W/ 3 1/4" EMBED.
(L=10'-0' MAX.)
T Y
P
ALL-THREAD
VERTICAL
SUPPORT
TYP.
A
C
A
3'-0" MAX.
OBSTRUCTION
UNISTRUT TRAPEZE AT OBSTRUCTION
P1000 BRACE
SEE FOR CONN.
PLAN AT BASE
FRONT VIEW
WT=1000#
MAX.
C.G.
H
D
"W"
2-1/2"Ø HILTI KB-TZ S.S.
W/ 2" EMBED.
(ICC ESR-1917)
FLANGED LEG
(E) 7 1/2" N.WT. CONC.
(MIN. 3000psi)
3"
DETAIL -A-
A
BY VENDOR
FOR DIMENSIONS AND EXACT WEIGHT-SEE ARCH'L.
NOTE:
H
COUPLER NUT
@ 12" MAX. SPACING
ROD HANGER
A
FOR: 41, 82, 84, 87, 154, 157, 161, 182, 188, 226, 228, 341, 343, 366
FOR: 81A, 81B, 153A, 153B, 218A, 218B, 236A, 236B, 344, 362
2-5/8"Ø HILTI KB-TZ S.S.
W/ 2" EMBED.
(ICC ESR-1917) FLANGED LEG
4"
DETAIL -A-
BY VENDOR
FOR: 221, 223
PLAN VIEW
FRONT VIEW
FOR DIMENSIONS AND EXACT WEIGHT-SEE ARCH'L.
NOTE:
A
WT=1130#
MAX.
C.G.
TYP.
TYP.
TYP.
M I N
35"
MIN.
M I N
M I N
MIN.
C.G.
ALTERNATIVE TRANSVERSE
BRACE LOCATION-TYP.
LONGITUDINAL BRACE
(2 PER SECTION)
TRANSVERSE BRACE
(2 PER SECTION)
P1001 AW
CHANNEL
WASHER AND NUT
TOP AND BOTTOM
TYP.
CHANNEL WASHER
AND NUT-TYP.
A
NONE
FLIGHT TYPE WAREWASHER ANCHORAGE
2-1/2"Ø HILTI KB-TZ S.S.
W/ 2" EMBED.
(ICC ESR-1917)
FLANGED LEG
2.5"
DETAIL -A-
FRONT VIEW
SIDE VIEW
A TYP.
MAX.
C.G.
WT=4085#
(E) 7 1/2" N.WT. CONC.
(MIN. 3000psi)
BY MFR.
FOR: 361
(E) 7 1/2" N.WT. CONC.
(MIN. 3000psi)
QUARRY TILE
W/ MORTAR BED
W/ 2" MAX. THK.
T Y
P
AV PAHCS
Veterans Affairs Veterans Affairs• tel: 626.793.9805 fax: 626.793.9807
48 east holly street, pasadena, ca 91103
SWA Architect
SWA 20170024
PH: 626.463.2800
FAX: 626.463.2801
www.ttgcorp.com
300 N. LAKE AVENUE
14TH FLOOR
PASADENA, CA
91101 Project No.
d/b/a
17001385.00
Exp. 09/30/18
C
O
F
E
S
S
T
A
T
T
R
U
C A
L
I
F
A
L
T
U
R
O
R
N
I
A
R
No.5145
E
E
R
E
R E G
I S
T
D
P
R
O F
E
N
G
I N
E E
A
L
SS
I O
N
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Professional Seal
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Check-by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Architects
AutoCAD SHX Text Drawn-by:
AutoCAD SHX Text Office of Facilities Management
AutoCAD SHX Text Engineers/Consultants
AutoCAD SHX Text \\AD.KJWW.COM\KJWW\KJWW\PROJECTS\2017\17001385.00\CAD-BIM FOLDERS\AUTOCAD\_STR\17001385_SS4.DWG - 4/2/2018 11:41 AM - 4/2/2018 11:41 AM4/2/2018 11:41 AM
AutoCAD SHX Text Design Development ONLY-NOT for Construction
AutoCAD SHX Text Building Number:
AutoCAD SHX Text Drawing Number:
AutoCAD SHX Text Project Number:
AutoCAD SHX Text B126
AutoCAD SHX Text 600-17-102
AutoCAD SHX Text Location:
AutoCAD SHX Text Project Title
AutoCAD SHX Text
5901- EAST SEVENTH STREET
AutoCAD SHX Text
LONG BEACH, CALIFORNIA, 90822
AutoCAD SHX Text
DEPARTMENT OF VETERANS AFFAIRS
AutoCAD SHX Text
TIBOR RUBIN VA MEDICAL CENTER
AutoCAD SHX Text
B126 RENOVATE HOSPITAL
AutoCAD SHX Text
ROOM SERVICE KITCHEN
AutoCAD SHX Text
AM
AutoCAD SHX Text
AS
AutoCAD SHX Text
100%%% FINAL CONSTRUCTION DOCUMENT
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text SD 35%%% Submission
AutoCAD SHX Text 08-22-2017
AutoCAD SHX Text DD 65%%% Submission
AutoCAD SHX Text 10-27-2017
AutoCAD SHX Text CD 95%%% Submission
AutoCAD SHX Text 02-19-2018
AutoCAD SHX Text CD 100%%% Submission
AutoCAD SHX Text 04-06-2018
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text See Revisions Date
AutoCAD SHX Text
SS-4
COMBI-OVEN ANCHORAGE
NONE
COUNTERTOP ICE/WATER DISPENSER WITH ICEMAKER ANCHORAGE
NONE
ALTERNATIVE MOBILE WIRE RACK ANCHORAGE
NONE
WIRE RACK ANCHORAGE
NONE
PASS-THRU CART WASHER ANCHORAGE DETAIL
FRONT VIEW SIDE VIEW
42 3/8" 38 1/2"
(E) 7 1/2" N. WT. CONC.
(MIN. 3000psi)
3-#12 S.M.S. S.S.
AT ANGLE VERT. LEG
TO EQUIP. ENCLOSURE
AS SHOWN-TYP.
EQ.
TYP.
3/4"
TYP.
1/2"Ø HILTI KB-TZ S.S.
W/ 3 1/4" EMBED.
(ICC ESR-1917)
ANGLE
ALTERNATE
DIRECTION
L7x4x3/8x0'-3" S.S.
TYP.
DETAIL -A-
28"
MIN.
M
A X
V O
S
C.G.
WT.=750#
MAX.
FRONT VIEW
PL2x3 STAINLESS STEEL
DOUBLE STUDDED W/ 3M VHB
ADHESIVE BACKING BY MFR.
3"x6"x16GA.
STAINLESS STEEL
BRACKET BY MFR.
WING NUT
BY MFR.-TYP.
(EA. SIDE, TOTAL 2)
(TYP., TOTAL 2, 1 PER
BRACKET VERT. LEG)
2-1/4"Ø THRU BOLT
BY CONTRACTOR
(2 PER BRACKET)
SIDE VIEW
SEE ARCH'L
ALTERNATE BRACKET
ORIENTATION
LB2236S BRACKET
BY WORKSAFE MFR.
'W'
'D'
H
C.G.
WT.=150#
MAX.
AT PROVIDED HOLES
(TOTAL 2)
FOR: 107, 134, 142, 146
FRONT VIEW
C.G.
WT.=1400#
MAX.
H
C.G.
WT.=1400#
MAX.
DETAIL -A- SECTION B-B
A
B
B
UNISTRUT
UNISTRUT PIPE CLAMP
TO MATCH SHELF POST
CONT. P1000
W/ 1/4"Ø SCREW
METAL STUD WALL
1" MAX.
TYP.
@ 6" O.C.
TO BACKING
H
M A
X
H
M A
X
4"
MIN.
DIAMETER
1/4"Ø SCREW
EACH SIDE
OF PIPE CLAMP
AS SHOWN
SHELF REAR POST
WHERE OCCURS
BACKING TRACK
NOTES:
1. FOR EQUIPMENT DIMENSIONS SEE ARCHITECTURAL DRAWINGS.
2. PROVIDE BUSHING FOR HOLES PROVIDED BY MFR AS REQUIRED.
2. WHERE WHEELS OCCUR AT POSTS-SEE .
FRONT VIEWSIDE VIEW
DETAIL -B-
BASE PLATE BRACKET
BY MFR.
1/2"Ø HILTI KB-TZ S.S.
W/ 3 1/4" EMBED.
(ICC ESR-1917)-TYP.
C.G.
WT.=1550#
MAX.
A
DETAIL -A-
POST
SEISMIC KIT
BY MFR.
TYP.
18"-24" 24"-60"
M
A X
TOP OF LOADED SHELF
NO LOAD ON COVER ALLOWED
FOR: 12, 18, 26, 33, 56, 57, 64, 72, 76, 306, 312, 317, 347
FOR: 91, 242
A
TYP.
TYP.
60"
(E) 7 1/2" N. WT. CONC.
(MIN. 3000psi)
COUNTER
NOTE:
FOR DIMENSIONS-SEE ARCH'L.
SEE ARCH'L
SS4
BASE PLATE BRACKET
BY MFR.
ALTERNATIVE DETAIL -B-
NONE
COUNTERTOP RAPID COOK OVEN ANCHORAGE
SIDE VIEW
PLAN AT BASE
1/4" A307 BOLT
W/ WASHER & NUT
MAX.
C.G.
WT=190#
COUNTERTOP
FOR: 92, 165
26"
AT EA. PROVIDED
LEG HOLE
C.G.
WT.=8500#
MAX.
FRONT VIEW
SIDE VIEW
148 3/8" 88 11/16"
3/4"Ø HILTI KB-TZ S.S.
W/ 3 3/4" EMBED.
(ICC ESR-1917) AT
EA. SEISMIC BRACKET
WELD SEISMIC
ANCHOR BRACKET
BY MFR.
(E) 7 1/2" N. WT. CONC.
(MIN. 3000psi)
FOR: 374
AV PAHCS
Veterans Affairs Veterans Affairs• tel: 626.793.9805 fax: 626.793.9807
48 east holly street, pasadena, ca 91103
SWA Architect
SWA 20170024
PH: 626.463.2800
FAX: 626.463.2801
www.ttgcorp.com
300 N. LAKE AVENUE
14TH FLOOR
PASADENA, CA
91101 Project No.
d/b/a
17001385.00
Exp. 09/30/18
C
O
F
E
S
S
T
A
T
T
R
U
C A
L
I
F
A
L
T
U
R
O
R
N
I
A
R
No.5145
E
E
R
E
R E G
I S
T
D
P
R
O F
E
N
G
I N
E E
A
L
SS
I O
N
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Professional Seal
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Check-by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Architects
AutoCAD SHX Text Drawn-by:
AutoCAD SHX Text Office of Facilities Management
AutoCAD SHX Text Engineers/Consultants
AutoCAD SHX Text \\AD.KJWW.COM\KJWW\KJWW\PROJECTS\2017\17001385.00\CAD-BIM FOLDERS\AUTOCAD\_STR\17001385_SS5.DWG - 3/12/2018 11:22 AM - 3/12/2018 11:22 AM3/12/2018 11:22 AM
AutoCAD SHX Text Design Development ONLY-NOT for Construction
AutoCAD SHX Text Building Number:
AutoCAD SHX Text Drawing Number:
AutoCAD SHX Text Project Number:
AutoCAD SHX Text B126
AutoCAD SHX Text 600-17-102
AutoCAD SHX Text Location:
AutoCAD SHX Text Project Title
AutoCAD SHX Text
5901- EAST SEVENTH STREET
AutoCAD SHX Text
LONG BEACH, CALIFORNIA, 90822
AutoCAD SHX Text
DEPARTMENT OF VETERANS AFFAIRS
AutoCAD SHX Text
TIBOR RUBIN VA MEDICAL CENTER
AutoCAD SHX Text
B126 RENOVATE HOSPITAL
AutoCAD SHX Text
ROOM SERVICE KITCHEN
AutoCAD SHX Text
AM
AutoCAD SHX Text
AS
AutoCAD SHX Text
100%%% FINAL CONSTRUCTION DOCUMENT
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text SD 35%%% Submission
AutoCAD SHX Text 08-22-2017
AutoCAD SHX Text DD 65%%% Submission
AutoCAD SHX Text 10-27-2017
AutoCAD SHX Text CD 95%%% Submission
AutoCAD SHX Text 02-19-2018
AutoCAD SHX Text CD 100%%% Submission
AutoCAD SHX Text 04-06-2018
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text See Revisions Date
AutoCAD SHX Text
SS-5
PREP/WORK TABLE, DISHTABLE WITH SINK ANCHORAGE
NONE
FLOOR MIXER ANCHORAGE
NONE
REACH-IN REFRIGERATOR ANCHORAGE
FRONT ELEVATION
142"
FLANGED LEG
DETAIL -A-
3"
SIDE VIEW
PLAN AT BASE
3/8"Ø HILTI KB-TZ S.S.
W/ 2" EMBED.
ICC ESR-1917
(TOTAL 4)
MAX.
C.G.
WT=600#
BY VENDOR
2-1/2"Ø HILTI KB-TZ S.S.
W/ 2" EMBED.
(ICC ESR-1917)
(E) 7 1/2" N.WT. CONC.
(MIN. 3000psi)
(E) 7 1/2" N.WT. CONC.
(MIN. 3000psi)
NONE
REACH-IN FREEZER ANCHORAGE
NONE
SANDWICH/SALAD PREP REFRIGERATOR ANCHORAGE
NONE
COUNTERTOP MIXER ANCHORAGE
C.G.
PLAN AT BASE
(E) SWIVEL
WHEEL
TYP.
2-1/2"Ø THRU BOLT S.S.
W/ NUT AND WASHER
DETAIL -A-
(E) EQUIP. FRAMING
PL3/8"xV.O.S.x0'-5 1/2" S.S.
W/ 4-1/4"Ø SCREWS S.S.
TO EQUIP. FRAMING
L4x4x3/8x0'-5 1/2" S.S.
W/ 2-1/2"Ø HILTI KB-TZ S.S.
W/ 3 1/4" EMBED.
(ICC ESR-1917)
(TOTAL 4)
SIDE VIEW
1/2" 1/2"
EQ.
52 5/8"
M A
X
2"
A
FRONT VIEW
1"
TYP.
4"…