Sheet T0.01.pdf
PDF 293 KB Posted
- Attached to
- Y1DA--36C257-26-AP-0163 | NEW CON FY26 | CTX 674-16-016 - Remodel Amphitheater (VA-26-00003450)
- Solicitation number
- 36C25726R0011
About this file
This document is an Addendum (No. 001) for the Remodel Amphitheater project for Central Texas Veterans, issued on 12/16/2025. The addendum, prepared by ELK Consortium + WestEast Design Group JV, LLC, updates the technology documentation by adding an Audio Visual Responsibility Matrix to Sheet T0.01. The document specifies that bidders must incorporate this addendum into their bids and acknowledge its receipt, with the changes taking precedence over original contract documents. The project involves technology systems integration, including detailed specifications for communications, security systems, audio-visual equipment, and network infrastructure, with a comprehensive responsibility matrix delineating the scope of work for various technological components.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 18708 Final Report Bldg 163.pdf | ||
| 36C25726R0011 0004.docx | DOCX document | |
| 36C25726R0011 0003.docx | DOCX document | |
| 36C25726R0011 0002.docx | DOCX document | |
| Sign-in Sheet.pdf | ||
| 36C25726R0011 0001_1.docx | DOCX document | |
| 36C25726R0011 0001.docx | DOCX document | |
| 36C25726R0011.pdf | ||
| Attachment 4 - Itemized Cost Breakdown.xlsx | XLSX spreadsheet | |
| Attachment 1 - 67416016 Remodel Amphitheater 100 percent CD Drawings.pdf | ||
| Attachment 5 - VHA Pre-Construction Risk Assessment.pdf | ||
| Attachment 3 - 67416016 Remodel Amphitheater 100 percent CD Material Board.pdf | ||
| Attachment 2 - 6716016 Remodel Amphitheater 100 percent CD Specs.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELK Consortium + WestEast Design Group JV, LLC 2797 Valencia Lane Schertz, Texas 78154 M 940.642.9158
Addendum PROJECT Remodel Amphitheater
674-16-016 PROJECT No. WestEast Design Group, LLC:
22480
TO COR, Mr. Tyrone Bennett Central Texas Veterans 1901 Veterans Memorial Drive, Temple, TX 76504
ADD No. 001
ISSUE DATE 12/16/2025
ISSUED FOR: Bidding
VIA EMAIL
FROM Jon Quebe West East Design Group, LLC 200 E. Grayson Street, Suite 207 San Antonio, TX 78215 210.530.0755
This addendum shall be considered part of the Contract Documents and is issued to change or delete from or otherwise explain the drawings and specifications. Where provisions of this addendum differ from those of the original contract documents, this addendum shall have precedence over the original drawings and specifications and shall govern.
Bidders are hereby notified that they shall incorporate this addendum in their bids, and it shall be construed that the Contractor's Bid shall reflect with full knowledge, all items, changes and modifications to the contract documents herein specified. Bidders shall acknowledge receipt of this addendum in the space provided on the contractor’s bid form.
Description
Technology Audio Visual Responsibility Matrix added to Sheet T0.01.
Drawing
1. Sheet T0.01 (Updated 12-16-2025)
END OF ADDENDUM No.1
9990 Richmond Avenue
South Building, Suite 300
Houston, TX 77042 v 713.914.0888
ADDENDUM 1
www.dbrinc.com TBPE Firm Registration No. 2234
DATE
December 16, 2025
ISSUE TITLE
ADDENDUM 1
PROJECT 240006.000 CISD VA Ampitheater
The work described herein shall be added to the scope of work defined by the contract documents or it shall modify the scope of work defined by the contract documents as described. This work shall become a part of the contract documents by addendum.
DRAWINGS
TECHNOLOGY
ITEM 1. T0.01 – TECHNOLOGY SYMBOL LEGEND
a. Added Responsibility matrix to sheet.
END OF ADDENDUM 1
D E
V
IC
E S
TECHNOLOGY LEGEND
DESCRIPTIONSYMBOLG
R O
U P
'D#'
INDICATES THE LOCATION OF A NEW TECHNOLOGY OUTLET. CONTRACTOR TO PROVIDE FACEPLATE
WITH A MINIMUM OF 4-PORTS AT EACH LOCATION UNLESS OTHERWISE NOTED. ELECTRICAL
CONTRACTOR TO PROVIDE A DOUBLE GANG BACK BOX WITH A SINGLE GANG REDUCER RING AND A 1" EMT CONDUIT FROM THE BOX TO THE NEAREST ACCESSIBLE CEILING. SOME EXISTING BUILDINGS
MAY REQUIRE SURFACE MOUNTED RACEWAY. ELECTRICAL CONTRACTOR TO PROVIDE AND
INSTALL RACEWAY AS SPECIFIED AND DESIGNATE IN THE ELECTRICAL CONTRACT DOCUMENTS.
SYSTEM INSTALLER TO PROVIDE AND INSTALL A PLASTIC PROTECTIVE BUSHING, ON EACH CONDUIT
STUB-OUT, TO PREVENT CABLE DAMAGE.
INDICATES THE LOCATION OF A FLOOR MOUNTED TECHNOLOGY OUTLET. ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL A FLOOR BOX WITH (1) 1" CONDUIT PER EVERY (6) CABLES INSTALLED. ALL CONDUITS SHALL ROUT FROM THE FLOOR BOX, DIRECTLY TO THE WALL INDICATED AND STUB-UP
INTO THE NEAREST ACCESSIBLE PLENUM CEILING
INDICATES THE LOCATION OF A CEILING MOUNTED OUTLET. CONTRACTOR SHALL MOUNT THIS
OUTLET AT +12" ABOVE THE CEILING AND COORDINATE ALL FINAL LOCATIONS WITH OTHER TRADES ON THE PROJECT TO VERIFY THAT THE LOCATION OF THE OUTLET MAINTAINS 12" OF CLEARANCE
FROM THE FRONT OF THE FACEPLATE FOR OWNER ACCESS. ELECTRICAL CONTRACTOR SHALL
ROUTE (1) 1" CONDUIT FROM THE BUILDING STRUCTURE TO A SINGLE GANG BACK BOX MOUNTED AT 5' OR LESS ABOVE THE FINISHED CEILING. SECURE CONDUIT AND BACK BOX TO INSURE MINIMAL
SWAY MOVEMENT.
DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE USE OF A
NETWORK CONNECTION. THE '#' SHALL BE REPLACED WITH NUMERIC TEXT THAT IDENTIFIES THE
TOTAL NUMBER OF CATEGORY 6, NETWORK CABLES THAT ARE TO BE INSTALLED AT THE
TECHNOLOGY OUTLET LOCATION. CONTRACTOR TO PROVIDE AND INSTALL CATEGORY 6 NETWORK
CABLES, CATEGORY 6 CONNECTORS, STAINLESS STEEL FACEPLATES WITH IDENTIFICATION
WINDOWS, LABELS, BLANK INSERTS, AND ANY OTHER MATERIALS REQUIRED TO FURNISH A
COMPLETE FUNCTIONAL AND TESTED OUTLET LOCATION. ALL FACEPLATES PROVIDED SHALL
CONTAIN A MINIMUM 4-PORTS AND SHALL BE APPROPRIATELY SIZED TO ACCOMMODATE THE
NUMBER OF CIRCUITS BEING INSTALLED AT THIS TECHNOLOGY OUTLET LOCATION. MAXIMUM OF
SIX(6) DATA CABLES PER OUTLET.
DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE USE OF A WALL
MOUNTED TELEPHONE CONNECTION. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6
NETWORK CABLE, (1) CATEGORY 6 CONNECTOR, STAINLESS STEEL WALL TELEPHONE FACEPLATE, LABELS, AND ANY OTHER MATERIALS REQUIRED TO FURNISH A COMPLETE FUNCTIONAL AND
TESTED CIRCUIT AT EACH LOCATION SHOWN. CONTRACTOR SHALL MOUNT THIS OUTLET AT +42" AFF AND COORDINATE ALL FINAL LOCATIONS WITH OTHER TRADES ON THE PROJECT TO VERIFY THAT THE LOCATION OF THE OUTLET MAINTAINS 8" OF CLEARANCE ON ALL FOUR SIDES OF THE BACK BOX.
OUTLETS SHALL REMAIN CLEAR OF ROOM DOORS, CABINET DOORS, APPLIANCE DOORS, AND
SLIDING DRAWERS.
DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE USE OF A
WIRELESS ACCESS POINT CONNECTION. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6
NETWORK CABLE, (1) CATEGORY 6 CONNECTOR, STAINLESS STEEL FACEPLATE WITH
IDENTIFICATION WINDOWS, LABELS, AND ANY OTHER MATERIALS REQUIRED TO FURNISH A
COMPLETE FUNCTIONAL AND TESTED CIRCUIT AT EACH LOCATION SHOWN. REFERENCE
SPECIFICATIONS FOR PATCH CABLE REQUIREMENTS.
INDICATES THE LOCATION OF AN IP VIDEO SURVEILLANCE CAMERA. CONTRACTOR TO PROVIDE AND
INSTALL CATEGORY 6 NETWORK CABLES, CATEGORY 6 CONNECTORS, STAINLESS STEEL
FACEPLATES WITH IDENTIFICATION WINDOWS, LABELS, BLANK INSERTS, AND ANY OTHER
MATERIALS REQUIRED TO FURNISH A COMPLETE FUNCTIONAL AND TESTED OUTLET LOCATION. ALL
FACEPLATES PROVIDED SHALL SHALL BE APPROPRIATELY SIZED TO ACCOMMODATE THE NUMBER
OF CIRCUITS BEING INSTALLED AT THIS OUTLET LOCATION. REFERENCE SPECIFICATIONS FOR
PATCH CABLE REQUIREMENTS.
INDICATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR FUTURE USE.
CONTRACTOR TO PROVIDE STAINLESS STEEL, SINGLE-GANG WALL PLATE AT ALL LOCATIONS.
'W'
'AP'
'B'
NOTES:
REFERENCE TECHNOLOGY GENERAL NOTES, PLAN KEYED NOTES, AND ALL OTHER
SYSTEM LEGENDS/NOTES. THE STRUCTURED CABLING SYSTEM CONTRACTOR SHALL
PROVIDE AND INSTALL CATEGORY 6 CABLE TO ALL SYSTEMS' EQUIPMENT REQUIRING
NETWORK CONNECTIVITY.
VRS
#MU
D E
V
IC
E S
VIDEO SURVEILLANCE LEGEND
DESCRIPTIONSYMBOLG
R O
U P
INTERIOR VIDEO SURVEILLANCE CAMERA.
VANDAL RESISTANT, WEATHER PROOF, EXTERIOR SECURITY CAMERA.
VIDEO RECORDING SERVER. REFERENCE SPECIFICATIONS FOR INFORMATION
CONCERNING ANALOG OR IP BASED TYPE SYSTEM.
INDICATES THE LOCATION OF A VIDEO SURVEILLANCE MAIN
NOTES:
1. REFERENCE VIDEO SURVEILLANCE SCHEDULE AND DIVISION 28
SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS
M
M
DC
M
GB
IDP
SDC
ODC
WSR
KP
M
R
DB
D E
V
IC
E S
INTRUSION DETECTION LEGEND
DESCRIPTIONSYMBOLG
R O
U P
DESIGNATES THE LOCATION OF THE INTRUSION DETECTION SYSTEM, CONTROL PANEL,
ELECTRICAL CONTRACTOR TO PROVIDE 120V POWER TO PANEL
FLUSH MOUNTED MAGNETIC DOOR CONTACT.
SURFACE MOUNTED MAGNETIC DOOR CONTACT.
OVERHEAD DOOR, SURFACE MOUNTED DOOR CONTACT.
INTRUSION DETECTION SYSTEM ARM/DISARM KEYPAD.
STANDARD RANGE WALL MOUNTED MOTION DETECTOR.
MEDIUM RANGE WALL MOUNTED MOTION DETECTOR.
LONG RANGE WALL MOUNTED MOTION DETECTOR.
CEILING MOUNTED, 360° MOTION DETECTOR.
RELAY/MONITOR MODULE
DURESS BUTTON
WIRELESS SECURITY RECEIVER. ELECTRICAL CONTRACTOR TO PROVIDE ONE (1)
SINGLE GANG BACK BOX WITH A 1" CONDUIT ROUTING TO THE NEAREST ACCESSIBLE
CEILING. MOUNT AT 12" BELOW THE FINISHED CEILING, BUT DO NOT EXCEED 12'-0" AFF.
NOTES:
1. REFERENCE ACCESS CONTROL SCHEDULE, DIVISION 8 AND DIVISION 28 SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS
CEILING MOUNTED GLASS BREAK DETECTOR
ACP
PIR
DR
DS
PB
MS
DO
CR
CR
DS
LA
DC
D E
V
IC
E S
ACCESS CONTROL LEGEND
DESCRIPTIONSYMBOLG
R O
U P
WALL OR MULLION MOUNTED ACCESS CONTROL PROXIMITY CARD READER.
ACCESS CONTROL PROXIMITY CARD READER THAT IS INTEGRATED INTO THE DOOR
HARDWARE.
DOOR RELEASE BUTTON
MOTION REQUEST TO EXIT DEVICE
DESIGNATES THE LOCATION OF THE ACCESS CONTROL SYSTEM, CONTROL PANEL.
ELECTRICAL CONTRACTOR TO PROVIDE 120V. POWER TO PANEL. PROVIDE NETWORK
CABLE TO PANEL AND COORDINATE WITH THE OWNER'S TECHNOLOGY DEPARTMENT ON
ACQUIRING AN IP ADDRESS.
WALL OR MULLION MOUNTED, 2-WAY AUDIO/VIDEO INTERCOM DOOR STATION.
DOOR MOUNTED, 2-WAY AUDIO/VIDEO INTERCOM DOOR STATION.
2-WAY AUDIO/VIDEO INTERCOM MASTER STATION.
ADA AUTO DOOR OPEN BUTTON. SHOWN FOR REFERENCE ONLY, BUTTON AND AUTO DOOR
OPERATOR PROVIDED AND INSTALLED BY THE DOOR SYSTEM INSTALLER.
AUTO DOOR OPERATOR. OPERATOR TO BE PROVIDED AND INSTALLED BY THE DOOR
SYSTEM INSTALLER.
WALL MOUNTED, LOCAL ALARM SOUNDER.
DPDT MAGNETIC DOOR CONTACT/DOOR POSITION SENSOR. FLUSH MOUNTED IN DOOR
FRAME, UNLESS NOTED OTHERWISE
NOTES:
1. REFERENCE ACCESS CONTROL SCHEDULE, DETAILS, AND DIVISION 28
SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS
DESCRIPTIONTEXT
INDICATES THAT THE DESIGNATED DEVICE IS TO BE WALL MOUNTED AT SPECIFIED HEIGHT
OR IN COMPLIANCE WITH CODE REQUIREMENTS. ALL WALL MOUNTED HEIGHTS ARE TO BE
CONFIRMED WITH THE PROJECT'S ARCHITECT PRIOR TO ROUGH-IN.
INDICATES THAT THE DESIGNATED DEVICE SHALL BE WEATHER PROOF AND RATED FOR
EXTERIOR CONDITIONS INSTALLATION.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE COUNTERTOP. A
NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC
HEIGHT ABOVE COUNTER. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S
ARCHITECT PRIOR TO ROUGH-IN.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE FINISHED FLOOR.
A NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC
HEIGHT ABOVE FINISHED FLOOR. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S
ARCHITECT PRIOR TO ROUGH-IN.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE GRADE LEVEL. A
NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC
HEIGHT ABOVE GRADE. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S
ARCHITECT PRIOR TO ROUGH-IN.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE SURFACE MOUNTED. CONTRACTOR TO
PROVIDE ALL MATERIALS REQUIRED FOR A COMPLETE, SURFACE MOUNTED SOLUTION. ALL
SURFACE MOUNTED PRODUCTS SHALL BE APPROVED BY THE PROJECT'S
ARCHITECT PRIOR TO PROCUREMENT AND/OR INSTALLATION.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE MOUNTED ON THE UNDERSIDE OF THE
ELEVATED CANOPY.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED UNDER A RAISED FLOOR
SYSTEM.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE CORNER MOUNTED AT SPECIFIED HEIGHT.
ALL WALL MOUNTED HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT
PRIOR TO ROUGH-IN.
TYPICAL SUBSCRIPTS LEGEND
'WM'
'WP'
'AC'
'AFF'
'AG'
'SM'
'UC'
'UF'
'CM'
TECHNOLOGY GENERAL NOTES
1. CONTRACTOR SHALL COORDINATING WITH DBR ENGINEERING PRIOR TO THE
INSTALLATION OF RACKS AND RACK EQUIPMENT. NO RACKS SHALL BE PERMANENTLY
INSTALLED WITHOUT WRITTEN APPROVAL OF THE PROPOSED LOCATIONS.
2. THE SELECTED, INSTALLING CONTRACTOR MUST BE A CERTIFIED INTEGRATOR/
INSTALLER AUTHORIZED BY THE SPECIFIED SYSTEM MANUFACTURER TO INSTALL THE
CABLE PLANT AND CONNECTIVITY PRODUCTS. REFER TO SPECIFICATIONS FOR
PRODUCT TYPE AND DESCRIPTION.
3. SYSTEM WIRING AND EQUIPMENT INSTALLATION SHALL BE IN ACCORDANCE WITH
GOOD ENGINEERING PRACTICES AS ESTABLISHED BY ANSI/EIA/TIA, BICSI, AND THE
NEC.
4. ALL WIRING SHALL MEET ALL STATE AND LOCAL ELECTRICAL CODES.
5. ALL TELECOMMUNICATIONS SYSTEMS EQUIPMENT AND MOUNTING LOCATIONS SHALL BE
IN COMPLIANCE WITH ADA ACCESSIBILITY STANDARDS.
6. ALL INDUSTRY STANDARD CATEGORY 6 CABLING PRACTICES MUST BE FOLLOWED
FOR ALL DATA CABLING.
7. ALL DATA CABLES ARE TO BE INSTALLED WITH A MINIMUM OF 12 INCHES OF
SEPARATION FROM AC POWER CABLES, INTERCOM, FIRE ALARM, SECURITY CABLES
IN ANY PARALLEL OPEN WIRE RUN.
8. ALWAYS CROSS OTHER SYSTEM CABLES AT A 90 DEGREE ANGLE.
9. ALL CABLES AND TERMINATION COMPONENTS SHALL BE MACHINE LABELED AT BOTH
ENDS. LABEL ALL CABLES PER TS DRAWINGS AND/OR SPECIFICATIONS. FINAL
CABLE/OUTLET IDENTIFICATION LABELS SHALL BE COORDINATED WITH THE OWNER
AND DBR.
10. CONTRACTOR TO PROVIDE LIGHTNING PROTECTION ON ALL COMMUNICATION CABLE
BETWEEN BUILDINGS.
11. ALL EXPOSED CABLING ROUTED IN PLENUM SHALL BE PLENUM-RATED. ALL
NON PLENUM-RATED CABLING INSTALLED IN PLENUM SPACES SHALL BE INSTALLED
IN CONDUIT.
12. NO TERMINATION OR SPLICES SHALL BE INSTALLED IN OR ABOVE CEILINGS
UNLESS NOTED NOTED OTHERWISE.
13. CONTRACTOR SHALL MAINTAIN WALL RATING WITH PROPER FIRE BLOCKING
14. ALL CABLE INSTALLED SHALL ROUTE TO THE CENTER OF THE ROOM IN WHICH IT
SERVES AND THEN TO THE OUTLET LOCATION IT IS INTENDED FOR. EACH CABLE
SHALL HAVE A 10' SERVICE LOOP AT THE CENTER OF EACH ROOM AND A 3'
SERVICE LOOP ABOVE EACH OUTLET LOCATION.
15. THE SYSTEM INSTALLER SHALL PROPERLY SUPPORT ALL INSTALLED SYSTEM CABLING
FROM A PANDUIT J-MOD CABLE SUPPORT SYSTEMS AS DETAILED IN SPECIFICATIONS.
NO CABLING SHALL BE ROUTED AND TIED DIRECTLY TO BUILDING STEEL, CEILING
GRID SUPPORT, CONDUIT, PIPING, OR DUCTWORK. PANDUIT J-MOD SUPPORT SYSTEM
SHALL BE DIRECTLY CONNECTED TO THE BUILDING'S STEEL JOIST. IN LOCATION
WHERE THE BOTTOM OF THE JOIST IS MORE THAN 5' ABOVE THE CEILING, THE
SYSTEM INSTALLER SHALL PROVIDE AND INSTALL THREADED ROD AND ALL REQUIRED
MATERIALS TO CONNECT THE THREADED ROD TO THE BUILDING STEEL AND THE
CABLE SUPPORT SYSTEM TO THE THREADED ROD. CABLE PATHWAY SHALL NOT BE
HIGHER THAN 5' ABOVE THE CEILING AT ANY LOCATIONS.
16. CONTRACTOR TO PROVIDE AND INSTALL ALL REQUIRED CABLING AND COMPONENTS
TO FURNISH TWO (2) ANALOG TELEPHONE CABLES TO THE FIRE ALARM SYSTEM.
CONTRACTOR TO COORDINATE WITH THE SYSTEM INSTALLER FOR EXACT LOCATIONS
AND TERMINATION INSTRUCTIONS PRIOR TO INSTALLATION.
17. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6 CABLE TO THE BUILDING'S
ACCESS CONTROL HEAD END PANEL. TERMINATION OF THIS CABLE SHALL BE
COORDINATED WITH THE SYSTEM INSTALLER.
18. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6 CABLE TO THE
BUILDING'S INTRUSION DETECTION PANEL. TERMINATION OF THIS CABLE SHALL BE
COORDINATED WITH THE SYSTEM INSTALLER.
19. PROVIDE AND INSTALL ONE (1) CATEGORY 6 CABLE TO EACH LIGHTING
CONTROL HUB ON THE ENTIRE PROJECT. COORDINATE EXACT QUANTITY AND
LOCATIONS WITH THE LIGHTING CONTROL SYSTEM INSTALLER. CONTRACTOR TO
ASSUME A MINIMUM OF FIVE (5) PER PROJECT.
20. CONTRACTOR TO PROVIDE AND INSTALL ONE (1) CATEGORY 6 DATA CIRCUITS TO
EACH PROJECTOR AND LCD ON THE ENTIRE PROJECT.
21. PROVIDE AND INSTALL ONE (1) CATEGORY 6 DATA CIRCUIT TO THE LOCAL AIR UNIT
CONTROLLER IN EACH MDF AND IDF.
22. PROVIDE AND INSTALL ONE (1) CATEGORY 6 DATA CIRCUIT TO EACH ACCESS
CONTROL VIDEO DOOR STATION ON THE ENTIRE PROJECT. COORDINATE EXACT
LOCATION AND TERMINATION REQUIREMENTS WITH THE DOOR STATION INSTALLER,
PRIOR TO INSTALLATION.
1. THE SECURITY SYSTEM INSTALLERS SHALL BE RESPONSIBLE FOR CONNECTING ALL APPLICABLE SYSTEM EQUIPMENT
TO THE OWNER'S NETWORK.
2. THE SYSTEM INSTALLER SHALL PROPERLY SUPPORT ALL INSTALLED SYSTEM CABLING FROM AN APPROVED CABLE SUPPORT SYSTEM AS DETAILED IN SPECIFICATIONS. NO CABLING SHALL BE ROUTED AND TIED DIRECTLY TO BUILDING STEEL, CEILING GRID SUPPORT, CONDUIT, PIPING, OR DUCTWORK. THE CABLE SUPPORT SYSTEM SHALL BE DIRECTLY CONNECTED TO THE BUILDING'S STEEL JOIST. AT LOCATIONS WHERE THE BOTTOM OF THE JOIST IS MORE THAN 5' ABOVE THE CEILING, THE SYSTEM INSTALLER SHALL PROVIDE AND INSTALL THREADED ROD AND ALL REQUIRED MATERIALS TO CONNECT THE THREADED ROD TO THE BUILDING STEEL AND THE CABLE SUPPORT SYSTEM TO THE THREADED ROD. CABLE PATHWAY SHALL NOT BE HIGHER THAN 5' ABOVE THE CEILING AT ANY LOCATIONS.
3. SECURITY CAMERA SYSTEM INSTALLER SHALL PROVIDE A CEILING MOUNTED INSTALLATION KIT RECOMMENDED BY THE MANUFACTURER OF THE CAMERA. EACH CEILING MOUNTED CAMERA KIT SHALL HAVE A SUPPORT WIRE ATTACHED TO THE BUILDING'S STRUCTURE TO PREVENT THE CAMERA FROM DROPPING TO THE FLOOR AT ANY TIME.
AT NO POINT SHALL THE WEIGHT OF THE CEILING MOUNTED SECURITY CAMERA BE SUPPORTED BY THE CEILING GRID
SYSTEM OR CEILING TILES. ALL CEILING MOUNTED CAMERAS SHALL BE FLUSH MOUNTED.
4. ALL EXTERIOR AND WALL MOUNTED CAMERA LOCATIONS AND MOUNTING HEIGHTS MUST BE COORDINATED WITH THE OWNER PRIOR TO ROUGH-IN. COORDINATION MEETINGS SHALL BE SCHEDULED THROUGH THE ARCHITECT'S PROJECT
MANAGER.
5. PROVIDE AND INSTALL MAGNETIC DOOR CONTACT AT ALL ROOF HATCHES ON THE ENTIRE PROJECT. CONTACTS TO BE
CONNECTED TO THE BUILDINGS INTRUSION DETECTION SYSTEM.
6. CONTRACTOR TO PROVIDE AND INSTALL A MONITOR RELAY AND ALL REQUIRED MATERIALS TO CONNECT THE RELAY TO THE FREEZER/COOLER TEMPERATURE GAUGE AND BACK TO THE INTRUSION DETECTION SYSTEM, THE INTRUSION DETECTION SYSTEM SHALL BE PROGRAMMED TO NOTIFY THE OWNER'S DESIGNATED PERSONNEL IN THE EVENT OF
EXTENSIVE CHANGE IN TEMPERATURE.
SECURITY GENERAL NOTES
1. EVERY SYMBOL SHOWN ON LEGEND MAY NOT APPEAR ON DRAWINGS. REFER TO GENERAL ELECTRICAL NOTES FOR
WALL-MOUNTED DEVICE MOUNTING HEIGHTS.
2. REFERENCE SPECIFICATIONS FOR MATERIALS AND METHODS.
3. COMPLETE INSTALLATION OF ALL PRODUCTS SHALL BE IN COMPLIANCE WITH ALL CODES, INDUSTRY STANDARDS, COMMON PRACTICES AND MANUFACTURER'S INSTRUCTIONS.
4. ALL EXTERIOR AND WALL MOUNTED CAMERA LOCATIONS AND MOUNTING HEIGHTS MUST BE COORDINATED WITH THE OWNER PRIOR TO ROUGH-IN. COORDINATION MEETINGS SHALL BE SCHEDULED THROUGH THE ARCHITECT'S PROJECT
MANAGER.
NOTES TO CONTRACTOR
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF EACH SYSTEM SHALL BE A DEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. PROJECTS ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TO MAIN CONTROL PANELS, REMOTE POWER SUPPLIES AND ALL HEAD END EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATIONS AND CONNECTIONS WITH
THE PROJECT'S ELECTRICAL CONTRACTOR.
2. THE PROJECT'S ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL IN CONDUITS, BACK BOXES, JUNCTION BOXES, RACEWAYS, AND SLEEVES REQUIRED TO ESTABLISH CLEAR PATHWAYS FOR ALL SYSTEMS. ALL CONDUITS, SLEEVES, BOXES, AND RACEWAYS SHALL BE PROPERLY SIZED TO
MAINTAIN A 40% MAXIMUM FILL RATIO.
3. ALL EXPOSED SYSTEM'S WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS SHALL BE ROUTED IN CONDUIT, PROVIDED AND INSTALLED BY THE PROJECT'S ELECTRICAL CONTRACTOR. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4".
4. EACH SYSTEM INSTALLER SHALL BE RESPONSIBLE FOR ENSURING ALL EXTERIOR WALL PENETRATIONS ARE
PROPERLY SEALED TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
5. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. IF EXTERIOR CONDUITS ARE REQUIRED FOR A COMPLETE INSTALLATION, EACH SYSTEM CONTRACTOR SHALL COORDINATE WITH THE
PROJECTS CONSULTANT PRIOR TO ANY ROUGH-IN.
6. EACH SYSTEM INSTALLER SHALL PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL CONDUIT STUB
OUTS AND SLEEVES TO PREVENT CABLE DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE
INSTALLATION. CUTTING BUSHING AND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE EXCEPTED.
7.
ALL CABLE SHALL BE ROUTED DOWN CORRIDORS, PARALLEL AND PERPENDICULAR TO THE BUILDING WALLS AND STRUCTURE. CABLE TO EACH DEVICE SHALL BRANCH OFF OF A MAIN CORRIDOR TRUNK. ROUTING CABLES THROUGH CLASSROOMS, OFFICES, STORAGE ROOMS, RESTROOMS OR ANY TYPE OF ROOM OTHER THAN A CORRIDOR WILL NOT BE ACCEPTED. ENTER ALL ROOMS ABOVE THE ASSOCIATED ROOM DOORWAY.
GENERAL NOTES
H
RACK
ABM
LSC
M
S
D E
V
IC
E S
LOCAL SOUND SYSTEM LEGEND
DESCRIPTIONSYMBOLG
R O
U P
VENUE SPECIFIC LOCAL SOUND SYSTEM SPEAKER. *# TO BE
REPLACED WITH ALPHANUMERIC TEXT INDICATING THE
ASSOCIATED VENUE AND SPEAKER NUMBER.
VENUE SPECIFIC LOCAL SOUND SYSTEM CONTROL PLATE. *#
TO BE REPLACED WITH ALPHANUMERIC TEXT INDICATING THE
ASSOCIATED VENUE AND CONTROL PLATE NUMBER.
VENUE SPECIFIC LOCAL SOUND SYSTEM MICROPHONE INPUT.
*# TO BE REPLACED WITH ALPHANUMERIC TEXT INDICATING
THE ASSOCIATED VENUE AND MIC INPUT NUMBER.
VENUE SPECIFIC LOCAL SOUND SYSTEM HANGING MICROPHONE.
*# TO BE REPLACED WITH ALPHANUMERIC TEXT INDICATING
THE ASSOCIATED VENUE AND MIC NUMBER.
VENUE SPECIFIC LOCAL SOUND SYSTEM 3.5MM AUXILIARY INPUT
AND BLUETOOTH MIXER. *# TO BE REPLACED WITH
ALPHANUMERIC TEXT INDICATING THE ASSOCIATED VENUE AND
MIXER NUMBER. CONTRACTOR TO PROVIDE AND INSTALL A
RECESSED ENCLOSURE WITH FLUSH MOUNTED, LOCKABLE
DOOR. DEVICE TO BE MOUNTED AT +42" AFF.
INDICATED THE LOCATION OF THE VENUE SPECIFIC LOCAL
SOUND SYSTEM HEAD END RACK. AMPLIFIERS, DSPS, AND ALL
OTHER HEAD END EQUIPMENT SHALL BE INSTALLED IN THIS
RACK/CABINET.
WIRELESS MICROPHONE ANTENNA. REFERENCE SPECIFICATIONS FOR MORE
INFORMATION.
ASSISTED LISTENING ANTENNA. REFERENCE SPECIFICATIONS FOR MORE INFORMATION.
NOTES:
1.
REFERENCE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS
WA
ALA
DESCRIPTIONTEXT
INDICATES THAT THE DEVICE IS EXISTING TO REMAIN. CONTRACTOR
TO REMOVE DEVICE AND PLACE IN THE SAME LOCATION AS NEEDED.
INDICATES THAT THE DEVICE IS EXISTING AN IS TO BE REMOVED.
CONTRACTOR TO REMOVE THE DEVICE AND RETURN TO OWNER.
INDICATES THAT THE DEVICE IS EXISTING AND SHALL BE REPLACED.
REFERENCE NEW SYSTEM LAYOUT FOR EXACT LOCATIONS.
INDICATES THAT THE DEVICE IS EXISTING AND SHALL BE REMOVED
AND RELOCATED TO A LOCATION INDICATED ON THE DRAWINGS.
REFERENCE NEW SYSTEM LAYOUT FOR EXACT LOCATIONS.
SUBSCRIPTS LEGEND - EXISTING DEVICES
'E'
'D'
'R'
'RR'
AVC
S
D E
V
IC
E S
AUDIO/VIDEO LEGEND
DESCRIPTIONSYMBOL
'AV-*#'
INDICATES THE LOCATION OF A VIDEO PROJECTOR # TO BE REPLACED WITH "C" OR "W".
"C" INDICATES THAT THE DEVICE IS A CEILING MOUNTED DEVICE AND "W" INDICATES IT
IS TO BE WALL MOUNTED. CONTRACTOR TO PROVIDE AND INSTALL A PROJECTOR,
CEILING OR WALL MOUNTING KIT, AND PATCH CABLES AS REQUIRED TO CONNECT AT
BOTH ENDS.
INDICATES THAT THE DESIGNATED TECHNOLOGY OUTLET IS INTENDED FOR AN
AUDIO/VIDEO (A/V) INPUT. CONTRACTOR TO PROVIDE AND INSTALL A FLOOR MOUNTED
OR WALL MOUNTED BOX AS INDICATED. (2) 1.25" CONDUITS FROM THE BOX TO THE
NEAREST, PLENUM ACCESSIBLE CEILING WITHIN THE SAME ROOM. ALL FLOOR AND
WALL MOUNTED BOXES SHALL BE A MINIMUM OF 2-GANGS.
*# - WHEN REPLACED WITH A '1' (AV-1) ONLY, THE OUTLET SHALL BE A
STANDALONE, LOCAL INPUT TIED TO A LOCAL VIDEO DISPLAY (FSD, CMP, WMP, AV-2,
ETC.). THIS OUTLET WILL NOT BE ASSOCIATED WITH ANY SYSTEM FOR ROUTING TO
DISPLAYS LOCATED IN ANY OTHER PORTION OF THE PROJECT. IF NOT REPLACED WITH
A '1' SEE THE NOTES AT THE BOTTOM OF THE LEGEND FOR ADDITIONAL INSTRUCTIONS.
INDICATES THE LOCATION OF A FLAT PANEL VIDEO DISPLAY. CONTRACTOR TO
PROVIDE AND INSTALL TWO (2) CATEGORY 6 UTP NETWORK CABLE TO ALL LOCATIONS
SHOWN ON THE ENTIRE PROJECT.
*# - WHEN REPLACED WITH A '1' (FSD-1) ONLY, THE OUTLET SHALL BE A
STANDALONE AND ONLY HAVE THE CATEGORY 6 CABLE ROUTED TO IT, FROM THE
MDF/IDF SERVING THE DEVICES AREA ROOM.
*# - WHEN REPLACED WITH A '2' (FSD-2) ONLY, THE OUTLET SHALL HAVE THE
CATEGORY 6 CABLE ROUTED TO IT, FROM THE MDF/IDF SERVING THE DEVICES AREA,
AND THE CABLING FROM THE ASSOCIATED AV-1.
EACH FSD OUTLET SHALL BE A 2-GANG BOX AND TWO (2) 1.25” CONDUITS STUBBING
INTO THE ROOMS ACCESSIBLE CEILING. PROVIDE ONE DOUBLE-GANG FACEPLATE WITH
TWO (2) DECORA PORTS. PROVIDE A DECORA STYLE INSERT THAT ACCEPTS THE STYLE
OF DATA JACK BEING USED FOR STRUCTURED CABLING. WHEN THERE IS A LOCAL A/V
INPUT ASSOCIATED WITH THE DISPLAY, PROVIDE A DECORA INSERT THAT CONFORMS
WITH THE SYSTEMS SPECIFIED. OTHERWISE PROVIDE A BLANK INSERT IN THE SECOND
PORT.
INDICATES THE LOCATION OF A WALL MOUNTED, INTERACTIVE VIDEO DISPLAY.
PROVIDE AND INSTALL A/V CABLE FROM THE ASSOCIATED AV-1 AS PER SYSTEM
SPECIFICATIONS. RACEWAY SHALL CONSIST OF A 2-GANG BOX AND TWO (2) 1.25”
CONDUITS STUBBING INTO THE ROOMS ACCESSIBLE CEILING. PROVIDE ONE DOUBLE-
GANG FACEPLATE WITH TWO (2) DECORA PORTS. PROVIDE A DECORA STYLE INSERT
THAT ACCEPTS THE STYLE OF DATA JACK BEING USED FOR STRUCTURED CABLING.
WHEN THERE IS A LOCAL A/V INPUT ASSOCIATED WITH THE DISPLAY, PROVIDE A
DECORA INSERT THAT CONFORMS WITH THE SYSTEMS SPECIFIED. OTHERWISE
PROVIDE A BLANK INSERT IN THE SECOND PORT.
INDICATES THE LOCATION OF A USB INPUT PLATE THAT SHALL TRANSMIT USB SIGNAL
TO THE ASSOCIATED USB OUTPUT PLATE. RACEWAY SHALL CONSIST OF ONE (1) 1"
CONDUIT AND A SINGLE GANG BACK BOX.
INDICATES THE LOCATION OF A USB OUTPUT PLATE THAT SHALL RECEIVE USB SIGNAL
FROM THE USB ASSOCIATED INPUT PLATE. RACEWAY SHALL CONSIST OF ONE (1) 1"
CONDUIT AND A SINGLE GANG BACK BOX.
INDICATES THE THE LOCATION OF A LOCAL SOUND REINFORCEMENT/PRESENTATION
SPEAKER.
*# - WHEN REPLACED WITH AN 'L', THE SPEAKER SHALL BE FOR LOCAL
INSTRUCTIONAL PRESENTATION AUDIO AND POWERED BY THE SPECIFIED CLASSROOM
PRESENTATION AMPLIFIER.
*# - WHEN REPLACED WITH 'SM', THE SPEAKER SHALL BE DEDICATED TO A SPEECH
PRIIVACY/SOUND MASKING SYSTEM.
INDICATES THE LOCATION OF AN AUDIO/VIDEO CONTROL PLATE. RACEWAY SHALL
CONSIST OF ONE (1) A BACK BOX WITH A 1" CONDUIT ROUTING INTO THE ACCESSIBLE
CEILING SPACE WITHIN THE SAME ROOM. AV SYSTEM INSTALLER TO COORDINATE THE
CONTROL BACK BOX SIZE REQUIREMENT WITH THE PROJECT'S ELECTRICAL
CONTRACTOR.
'FSD-*#'
G R
O U
P
NOTES:
A. IN THE EVENT THAT '*#* IS NOT DEFINED IN THE OUTLET DESCRIPTION, THE DEVICE SHALL BE CONSIDERED A STANDALONE DEVICE, SERVING THE SYSTEM WITHIN THE SAME SPACE OR THE FOLLOWING SHALL APPLY:
*# - UNLESS SPECIFICALLY NOTED OTHERWISE, THE FOLLOWING SHALL APPLY TO EACH DEVICE SHOWN
ON THE ENTIRE PROJECT:
* SHALL BE REPLACED WITH ALPHABETICAL CHARACTERS THAT SHALL INDICATE THE SPECIFIC VENUE
THAT THE DEVICE IS ASSOCIATED WITH.
# SHALL BE REPLACED WITH A NUMERIC VALUE THAT SHALL IDENTIFY THE SPECIFIC DEVICE WITHIN THE
SPECIFIC VENUE.
B. THE AUDIO/VIDEO SYSTEM INTEGRATOR SHALL COORDINATE ALL BOX AND CONDUIT SIZE REQUIREMENTS
PRIOR TO ROOUGH-IN BY THE PROJECTS ELECTRICAL CONTRACTOR.
C. REFERENCE SCOPE MATRIX AND PROJECT SPECIFICATIONS FOR INSTRUCTIONS REGARDING THE PROVIDING
AND INSTALLATION OF VIDEO DISPLAYS, PROJECTORS, SCREENS, MOUNTS, AND LIFTS.
#MP'
'IVD'
'USB-T'
'USB-R'
RESPONSIBILITY MATRIX
SCOPE OF WORK RESPONSIBILITY
OFOI
DIV 27 - COMMUNICATIONS
TECHNOLOGY SCOPE
AUDIO-VIDEO SYSTEM
DIV 28 - SECURITY SYSTEMS
VIDEO SURVEILLANCE SYSTEM
ACCESS CONTROL SYSTEM
INTRUSION DETECTION SYSTEM
STRUCTURED CABLING
CABLE TRAY IN ER/TR
CABLE PATHWAY OUTSIDE ER/TR
TELECOM GROUNDING SYSTEM
BACK BOXES, CONDUITS/SLEEVES
EQUIPMENT RACKS/CABINETS
WIRELESS ACCESS POINTS
NETWORK SWITCHES
UPS
TELEPHONES
WORKSTATION PC
LOCAL SOUND SYSTEM
FLAT PANEL DISPLAY (TV)
FLAT PANEL DISPLAY (TV) MOUNTS
DIGITAL SIGNAGE PLAYER
AV SWITCHER
AV CONTROL PANEL
AV EQUIPMENT CABINETS
AV CABLING
NETWORK CABLING REQUIRED
LECTERN
BACK BOXES, CONDUITS/SLEEVES
CAMERAS AND LICENSES
CAMERA MOUNTS
CAMERA NETWORK CABLING
PoE SWITCHES
VMS SERVERS
VIEWING STATION
BACK BOXES, CONDUITS/SLEEVES
EQUIPMENT RACKS/CABINETS
CARD READERS
DOOR CONTACTS
ELECTRIFIED LOCKS
REX INSIDE DOOR
PUSH TO EXIT
PIR SENSORS
LOW VOLTAGE POWER SUPPLY
ACCESS CONTROL PANELS
EQUIPMENT RACKS/CABINETS
BACK BOXES, CONDUITS/SLEEVES
COMPOSITE CABLING
NETWORK CABLING REQUIRED
CREDENTIAL CARDS
BADGE PRINTERS
MOTION SENSORS
GLASS BREAK SENSORS
ALARM/DISALARM KEY PAD
INTRUSION DETECTION PANEL (IDP)
DOOR CONTACTS
DATA CABLING TO IDP
PHONE OR INTERNET SERVICES
INTRUSION ALARM CABLING
BACK BOXES, CONDUITS/SLEEVES
OFCI CFCI
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PDU X
BACKBONE CABLING X
OFOI OFCI CFCI
OFOI OFCI CFCI
OFOI OFCI CFCI
OFOI OFCI CFCI
X
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENT 2
(100%)
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
DESIGNER OF RECORD STAMPCONSULTANT
7 8 9 10321 4 5 6
200 E. Grayson Street, Suite 207
San Antonio, Texas 78215
210.530.0755 www.westeastdesign.com
Texas Registered Architectural Firm
WestEast Design Group JV, LLC Elk Consortium +
REMODEL AMPHITHEATER
674-16-016
CENTRAL TEXAS VETERANS HEALTH CARE SYSTEM
1901 S. 1ST STREET TEMPLE, TEXAS 76504STRUCTURAL ENGINEER
AV CONSULTANT MEP ENGINEER
ALDERSON & ASSOCIATE
7700 TORINO STE. 101, SAN ANTONIO, TX 78229
210.614.1110
DEAN@ALDERSON-INC.COM
DBR
9601 MCALLISTER FREEWAY STE. 410,
SAN ANTONIO, TX 78257
210.546.0200
BUHLRICH@DBRINC.COM
LUNDY & FRANKE ENGINEERING, INC
549 HEIMER, SAN ANTONIO, TX 78232
210.979.7900 ext. 6
FRANKE@LUNDYFRANKE.COM
DEAN ALDERSON
SHAWN FRANKE
BRIAN UHLRICH
APRIL 29, 2025 AC HG12/16/25
A u to d e s k D o c s /2
.0
V A
T e m p le -A m p h it h e a te r
R e m o d e l/
V A
T e m p le A m p h it h e a te r_ V
A
.r v t
/1 /2
:2
:1
P
M
T0.01
TECHNOLOGY SYMBOL LEGEND
Revisions: Date:
Addendum 1 12/16/25
| _Technology Bound - Addendum 1.pdf |
| Sheets |
| T0.01 - TECHNOLOGY SYMBOL LEGEND |
File details come from the government source that posted it. Updated .