This document is an Addendum (No. 001) for the Remodel Amphitheater project for Central Texas Veterans, issued on 12/16/2025. The addendum, prepared by ELK Consortium + WestEast Design Group JV, LLC, updates the technology documentation by adding an Audio Visual Responsibility Matrix to Sheet T0.01. The document specifies that bidders must incorporate this addendum into their bids and acknowledge its receipt, with the changes taking precedence over original contract documents. The project involves technology systems integration, including detailed specifications for communications, security systems, audio-visual equipment, and network infrastructure, with a comprehensive responsibility matrix delineating the scope of work for various technological components.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELK Consortium + WestEast Design Group JV, LLC 2797 Valencia Lane Schertz, Texas 78154 M 940.642.9158

Addendum PROJECT Remodel Amphitheater

674-16-016 PROJECT No. WestEast Design Group, LLC:

22480

TO COR, Mr. Tyrone Bennett Central Texas Veterans 1901 Veterans Memorial Drive, Temple, TX 76504

ADD No. 001

ISSUE DATE 12/16/2025

ISSUED FOR: Bidding

VIA EMAIL

FROM Jon Quebe West East Design Group, LLC 200 E. Grayson Street, Suite 207 San Antonio, TX 78215 210.530.0755

This addendum shall be considered part of the Contract Documents and is issued to change or delete from or otherwise explain the drawings and specifications. Where provisions of this addendum differ from those of the original contract documents, this addendum shall have precedence over the original drawings and specifications and shall govern.

Bidders are hereby notified that they shall incorporate this addendum in their bids, and it shall be construed that the Contractor's Bid shall reflect with full knowledge, all items, changes and modifications to the contract documents herein specified. Bidders shall acknowledge receipt of this addendum in the space provided on the contractor’s bid form.

Description

Technology Audio Visual Responsibility Matrix added to Sheet T0.01.

Drawing

1. Sheet T0.01 (Updated 12-16-2025)

END OF ADDENDUM No.1

9990 Richmond Avenue

South Building, Suite 300

Houston, TX 77042 v 713.914.0888

ADDENDUM 1

www.dbrinc.com TBPE Firm Registration No. 2234

DATE

December 16, 2025

ISSUE TITLE

ADDENDUM 1

PROJECT 240006.000 CISD VA Ampitheater

The work described herein shall be added to the scope of work defined by the contract documents or it shall modify the scope of work defined by the contract documents as described. This work shall become a part of the contract documents by addendum.

DRAWINGS

TECHNOLOGY

ITEM 1. T0.01 – TECHNOLOGY SYMBOL LEGEND

a. Added Responsibility matrix to sheet.

END OF ADDENDUM 1

D E

V

IC

E S

TECHNOLOGY LEGEND

DESCRIPTIONSYMBOLG

R O

U P

'D#'

INDICATES THE LOCATION OF A NEW TECHNOLOGY OUTLET. CONTRACTOR TO PROVIDE FACEPLATE

WITH A MINIMUM OF 4-PORTS AT EACH LOCATION UNLESS OTHERWISE NOTED. ELECTRICAL

CONTRACTOR TO PROVIDE A DOUBLE GANG BACK BOX WITH A SINGLE GANG REDUCER RING AND A 1" EMT CONDUIT FROM THE BOX TO THE NEAREST ACCESSIBLE CEILING. SOME EXISTING BUILDINGS

MAY REQUIRE SURFACE MOUNTED RACEWAY. ELECTRICAL CONTRACTOR TO PROVIDE AND

INSTALL RACEWAY AS SPECIFIED AND DESIGNATE IN THE ELECTRICAL CONTRACT DOCUMENTS.

SYSTEM INSTALLER TO PROVIDE AND INSTALL A PLASTIC PROTECTIVE BUSHING, ON EACH CONDUIT

STUB-OUT, TO PREVENT CABLE DAMAGE.

INDICATES THE LOCATION OF A FLOOR MOUNTED TECHNOLOGY OUTLET. ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL A FLOOR BOX WITH (1) 1" CONDUIT PER EVERY (6) CABLES INSTALLED. ALL CONDUITS SHALL ROUT FROM THE FLOOR BOX, DIRECTLY TO THE WALL INDICATED AND STUB-UP

INTO THE NEAREST ACCESSIBLE PLENUM CEILING

INDICATES THE LOCATION OF A CEILING MOUNTED OUTLET. CONTRACTOR SHALL MOUNT THIS

OUTLET AT +12" ABOVE THE CEILING AND COORDINATE ALL FINAL LOCATIONS WITH OTHER TRADES ON THE PROJECT TO VERIFY THAT THE LOCATION OF THE OUTLET MAINTAINS 12" OF CLEARANCE

FROM THE FRONT OF THE FACEPLATE FOR OWNER ACCESS. ELECTRICAL CONTRACTOR SHALL

ROUTE (1) 1" CONDUIT FROM THE BUILDING STRUCTURE TO A SINGLE GANG BACK BOX MOUNTED AT 5' OR LESS ABOVE THE FINISHED CEILING. SECURE CONDUIT AND BACK BOX TO INSURE MINIMAL

SWAY MOVEMENT.

DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE USE OF A

NETWORK CONNECTION. THE '#' SHALL BE REPLACED WITH NUMERIC TEXT THAT IDENTIFIES THE

TOTAL NUMBER OF CATEGORY 6, NETWORK CABLES THAT ARE TO BE INSTALLED AT THE

TECHNOLOGY OUTLET LOCATION. CONTRACTOR TO PROVIDE AND INSTALL CATEGORY 6 NETWORK

CABLES, CATEGORY 6 CONNECTORS, STAINLESS STEEL FACEPLATES WITH IDENTIFICATION

WINDOWS, LABELS, BLANK INSERTS, AND ANY OTHER MATERIALS REQUIRED TO FURNISH A

COMPLETE FUNCTIONAL AND TESTED OUTLET LOCATION. ALL FACEPLATES PROVIDED SHALL

CONTAIN A MINIMUM 4-PORTS AND SHALL BE APPROPRIATELY SIZED TO ACCOMMODATE THE

NUMBER OF CIRCUITS BEING INSTALLED AT THIS TECHNOLOGY OUTLET LOCATION. MAXIMUM OF

SIX(6) DATA CABLES PER OUTLET.

DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE USE OF A WALL

MOUNTED TELEPHONE CONNECTION. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6

NETWORK CABLE, (1) CATEGORY 6 CONNECTOR, STAINLESS STEEL WALL TELEPHONE FACEPLATE, LABELS, AND ANY OTHER MATERIALS REQUIRED TO FURNISH A COMPLETE FUNCTIONAL AND

TESTED CIRCUIT AT EACH LOCATION SHOWN. CONTRACTOR SHALL MOUNT THIS OUTLET AT +42" AFF AND COORDINATE ALL FINAL LOCATIONS WITH OTHER TRADES ON THE PROJECT TO VERIFY THAT THE LOCATION OF THE OUTLET MAINTAINS 8" OF CLEARANCE ON ALL FOUR SIDES OF THE BACK BOX.

OUTLETS SHALL REMAIN CLEAR OF ROOM DOORS, CABINET DOORS, APPLIANCE DOORS, AND

SLIDING DRAWERS.

DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE USE OF A

WIRELESS ACCESS POINT CONNECTION. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6

NETWORK CABLE, (1) CATEGORY 6 CONNECTOR, STAINLESS STEEL FACEPLATE WITH

IDENTIFICATION WINDOWS, LABELS, AND ANY OTHER MATERIALS REQUIRED TO FURNISH A

COMPLETE FUNCTIONAL AND TESTED CIRCUIT AT EACH LOCATION SHOWN. REFERENCE

SPECIFICATIONS FOR PATCH CABLE REQUIREMENTS.

INDICATES THE LOCATION OF AN IP VIDEO SURVEILLANCE CAMERA. CONTRACTOR TO PROVIDE AND

INSTALL CATEGORY 6 NETWORK CABLES, CATEGORY 6 CONNECTORS, STAINLESS STEEL

FACEPLATES WITH IDENTIFICATION WINDOWS, LABELS, BLANK INSERTS, AND ANY OTHER

MATERIALS REQUIRED TO FURNISH A COMPLETE FUNCTIONAL AND TESTED OUTLET LOCATION. ALL

FACEPLATES PROVIDED SHALL SHALL BE APPROPRIATELY SIZED TO ACCOMMODATE THE NUMBER

OF CIRCUITS BEING INSTALLED AT THIS OUTLET LOCATION. REFERENCE SPECIFICATIONS FOR

PATCH CABLE REQUIREMENTS.

INDICATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR FUTURE USE.

CONTRACTOR TO PROVIDE STAINLESS STEEL, SINGLE-GANG WALL PLATE AT ALL LOCATIONS.

'W'

'AP'

'B'

NOTES:

REFERENCE TECHNOLOGY GENERAL NOTES, PLAN KEYED NOTES, AND ALL OTHER

SYSTEM LEGENDS/NOTES. THE STRUCTURED CABLING SYSTEM CONTRACTOR SHALL

PROVIDE AND INSTALL CATEGORY 6 CABLE TO ALL SYSTEMS' EQUIPMENT REQUIRING

NETWORK CONNECTIVITY.

VRS

#MU

D E

V

IC

E S

VIDEO SURVEILLANCE LEGEND

DESCRIPTIONSYMBOLG

R O

U P

INTERIOR VIDEO SURVEILLANCE CAMERA.

VANDAL RESISTANT, WEATHER PROOF, EXTERIOR SECURITY CAMERA.

VIDEO RECORDING SERVER. REFERENCE SPECIFICATIONS FOR INFORMATION

CONCERNING ANALOG OR IP BASED TYPE SYSTEM.

INDICATES THE LOCATION OF A VIDEO SURVEILLANCE MAIN

NOTES:

1. REFERENCE VIDEO SURVEILLANCE SCHEDULE AND DIVISION 28

SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS

M

M

DC

M

GB

IDP

SDC

ODC

WSR

KP

M

R

DB

D E

V

IC

E S

INTRUSION DETECTION LEGEND

DESCRIPTIONSYMBOLG

R O

U P

DESIGNATES THE LOCATION OF THE INTRUSION DETECTION SYSTEM, CONTROL PANEL,

ELECTRICAL CONTRACTOR TO PROVIDE 120V POWER TO PANEL

FLUSH MOUNTED MAGNETIC DOOR CONTACT.

SURFACE MOUNTED MAGNETIC DOOR CONTACT.

OVERHEAD DOOR, SURFACE MOUNTED DOOR CONTACT.

INTRUSION DETECTION SYSTEM ARM/DISARM KEYPAD.

STANDARD RANGE WALL MOUNTED MOTION DETECTOR.

MEDIUM RANGE WALL MOUNTED MOTION DETECTOR.

LONG RANGE WALL MOUNTED MOTION DETECTOR.

CEILING MOUNTED, 360° MOTION DETECTOR.

RELAY/MONITOR MODULE

DURESS BUTTON

WIRELESS SECURITY RECEIVER. ELECTRICAL CONTRACTOR TO PROVIDE ONE (1)

SINGLE GANG BACK BOX WITH A 1" CONDUIT ROUTING TO THE NEAREST ACCESSIBLE

CEILING. MOUNT AT 12" BELOW THE FINISHED CEILING, BUT DO NOT EXCEED 12'-0" AFF.

NOTES:

1. REFERENCE ACCESS CONTROL SCHEDULE, DIVISION 8 AND DIVISION 28 SPECIFICATIONS FOR ADDITIONAL

INFORMATION AND REQUIREMENTS

CEILING MOUNTED GLASS BREAK DETECTOR

ACP

PIR

DR

DS

PB

MS

DO

CR

CR

DS

LA

DC

D E

V

IC

E S

ACCESS CONTROL LEGEND

DESCRIPTIONSYMBOLG

R O

U P

WALL OR MULLION MOUNTED ACCESS CONTROL PROXIMITY CARD READER.

ACCESS CONTROL PROXIMITY CARD READER THAT IS INTEGRATED INTO THE DOOR

HARDWARE.

DOOR RELEASE BUTTON

MOTION REQUEST TO EXIT DEVICE

DESIGNATES THE LOCATION OF THE ACCESS CONTROL SYSTEM, CONTROL PANEL.

ELECTRICAL CONTRACTOR TO PROVIDE 120V. POWER TO PANEL. PROVIDE NETWORK

CABLE TO PANEL AND COORDINATE WITH THE OWNER'S TECHNOLOGY DEPARTMENT ON

ACQUIRING AN IP ADDRESS.

WALL OR MULLION MOUNTED, 2-WAY AUDIO/VIDEO INTERCOM DOOR STATION.

DOOR MOUNTED, 2-WAY AUDIO/VIDEO INTERCOM DOOR STATION.

2-WAY AUDIO/VIDEO INTERCOM MASTER STATION.

ADA AUTO DOOR OPEN BUTTON. SHOWN FOR REFERENCE ONLY, BUTTON AND AUTO DOOR

OPERATOR PROVIDED AND INSTALLED BY THE DOOR SYSTEM INSTALLER.

AUTO DOOR OPERATOR. OPERATOR TO BE PROVIDED AND INSTALLED BY THE DOOR

SYSTEM INSTALLER.

WALL MOUNTED, LOCAL ALARM SOUNDER.

DPDT MAGNETIC DOOR CONTACT/DOOR POSITION SENSOR. FLUSH MOUNTED IN DOOR

FRAME, UNLESS NOTED OTHERWISE

NOTES:

1. REFERENCE ACCESS CONTROL SCHEDULE, DETAILS, AND DIVISION 28

SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS

DESCRIPTIONTEXT

INDICATES THAT THE DESIGNATED DEVICE IS TO BE WALL MOUNTED AT SPECIFIED HEIGHT

OR IN COMPLIANCE WITH CODE REQUIREMENTS. ALL WALL MOUNTED HEIGHTS ARE TO BE

CONFIRMED WITH THE PROJECT'S ARCHITECT PRIOR TO ROUGH-IN.

INDICATES THAT THE DESIGNATED DEVICE SHALL BE WEATHER PROOF AND RATED FOR

EXTERIOR CONDITIONS INSTALLATION.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE COUNTERTOP. A

NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC

HEIGHT ABOVE COUNTER. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S

ARCHITECT PRIOR TO ROUGH-IN.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE FINISHED FLOOR.

A NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC

HEIGHT ABOVE FINISHED FLOOR. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S

ARCHITECT PRIOR TO ROUGH-IN.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE GRADE LEVEL. A

NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC

HEIGHT ABOVE GRADE. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S

ARCHITECT PRIOR TO ROUGH-IN.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE SURFACE MOUNTED. CONTRACTOR TO

PROVIDE ALL MATERIALS REQUIRED FOR A COMPLETE, SURFACE MOUNTED SOLUTION. ALL

SURFACE MOUNTED PRODUCTS SHALL BE APPROVED BY THE PROJECT'S

ARCHITECT PRIOR TO PROCUREMENT AND/OR INSTALLATION.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE MOUNTED ON THE UNDERSIDE OF THE

ELEVATED CANOPY.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED UNDER A RAISED FLOOR

SYSTEM.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE CORNER MOUNTED AT SPECIFIED HEIGHT.

ALL WALL MOUNTED HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT

PRIOR TO ROUGH-IN.

TYPICAL SUBSCRIPTS LEGEND

'WM'

'WP'

'AC'

'AFF'

'AG'

'SM'

'UC'

'UF'

'CM'

TECHNOLOGY GENERAL NOTES

1. CONTRACTOR SHALL COORDINATING WITH DBR ENGINEERING PRIOR TO THE

INSTALLATION OF RACKS AND RACK EQUIPMENT. NO RACKS SHALL BE PERMANENTLY

INSTALLED WITHOUT WRITTEN APPROVAL OF THE PROPOSED LOCATIONS.

2. THE SELECTED, INSTALLING CONTRACTOR MUST BE A CERTIFIED INTEGRATOR/

INSTALLER AUTHORIZED BY THE SPECIFIED SYSTEM MANUFACTURER TO INSTALL THE

CABLE PLANT AND CONNECTIVITY PRODUCTS. REFER TO SPECIFICATIONS FOR

PRODUCT TYPE AND DESCRIPTION.

3. SYSTEM WIRING AND EQUIPMENT INSTALLATION SHALL BE IN ACCORDANCE WITH

GOOD ENGINEERING PRACTICES AS ESTABLISHED BY ANSI/EIA/TIA, BICSI, AND THE

NEC.

4. ALL WIRING SHALL MEET ALL STATE AND LOCAL ELECTRICAL CODES.

5. ALL TELECOMMUNICATIONS SYSTEMS EQUIPMENT AND MOUNTING LOCATIONS SHALL BE

IN COMPLIANCE WITH ADA ACCESSIBILITY STANDARDS.

6. ALL INDUSTRY STANDARD CATEGORY 6 CABLING PRACTICES MUST BE FOLLOWED

FOR ALL DATA CABLING.

7. ALL DATA CABLES ARE TO BE INSTALLED WITH A MINIMUM OF 12 INCHES OF

SEPARATION FROM AC POWER CABLES, INTERCOM, FIRE ALARM, SECURITY CABLES

IN ANY PARALLEL OPEN WIRE RUN.

8. ALWAYS CROSS OTHER SYSTEM CABLES AT A 90 DEGREE ANGLE.

9. ALL CABLES AND TERMINATION COMPONENTS SHALL BE MACHINE LABELED AT BOTH

ENDS. LABEL ALL CABLES PER TS DRAWINGS AND/OR SPECIFICATIONS. FINAL

CABLE/OUTLET IDENTIFICATION LABELS SHALL BE COORDINATED WITH THE OWNER

AND DBR.

10. CONTRACTOR TO PROVIDE LIGHTNING PROTECTION ON ALL COMMUNICATION CABLE

BETWEEN BUILDINGS.

11. ALL EXPOSED CABLING ROUTED IN PLENUM SHALL BE PLENUM-RATED. ALL

NON PLENUM-RATED CABLING INSTALLED IN PLENUM SPACES SHALL BE INSTALLED

IN CONDUIT.

12. NO TERMINATION OR SPLICES SHALL BE INSTALLED IN OR ABOVE CEILINGS

UNLESS NOTED NOTED OTHERWISE.

13. CONTRACTOR SHALL MAINTAIN WALL RATING WITH PROPER FIRE BLOCKING

14. ALL CABLE INSTALLED SHALL ROUTE TO THE CENTER OF THE ROOM IN WHICH IT

SERVES AND THEN TO THE OUTLET LOCATION IT IS INTENDED FOR. EACH CABLE

SHALL HAVE A 10' SERVICE LOOP AT THE CENTER OF EACH ROOM AND A 3'

SERVICE LOOP ABOVE EACH OUTLET LOCATION.

15. THE SYSTEM INSTALLER SHALL PROPERLY SUPPORT ALL INSTALLED SYSTEM CABLING

FROM A PANDUIT J-MOD CABLE SUPPORT SYSTEMS AS DETAILED IN SPECIFICATIONS.

NO CABLING SHALL BE ROUTED AND TIED DIRECTLY TO BUILDING STEEL, CEILING

GRID SUPPORT, CONDUIT, PIPING, OR DUCTWORK. PANDUIT J-MOD SUPPORT SYSTEM

SHALL BE DIRECTLY CONNECTED TO THE BUILDING'S STEEL JOIST. IN LOCATION

WHERE THE BOTTOM OF THE JOIST IS MORE THAN 5' ABOVE THE CEILING, THE

SYSTEM INSTALLER SHALL PROVIDE AND INSTALL THREADED ROD AND ALL REQUIRED

MATERIALS TO CONNECT THE THREADED ROD TO THE BUILDING STEEL AND THE

CABLE SUPPORT SYSTEM TO THE THREADED ROD. CABLE PATHWAY SHALL NOT BE

HIGHER THAN 5' ABOVE THE CEILING AT ANY LOCATIONS.

16. CONTRACTOR TO PROVIDE AND INSTALL ALL REQUIRED CABLING AND COMPONENTS

TO FURNISH TWO (2) ANALOG TELEPHONE CABLES TO THE FIRE ALARM SYSTEM.

CONTRACTOR TO COORDINATE WITH THE SYSTEM INSTALLER FOR EXACT LOCATIONS

AND TERMINATION INSTRUCTIONS PRIOR TO INSTALLATION.

17. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6 CABLE TO THE BUILDING'S

ACCESS CONTROL HEAD END PANEL. TERMINATION OF THIS CABLE SHALL BE

COORDINATED WITH THE SYSTEM INSTALLER.

18. CONTRACTOR TO PROVIDE AND INSTALL (1) CATEGORY 6 CABLE TO THE

BUILDING'S INTRUSION DETECTION PANEL. TERMINATION OF THIS CABLE SHALL BE

COORDINATED WITH THE SYSTEM INSTALLER.

19. PROVIDE AND INSTALL ONE (1) CATEGORY 6 CABLE TO EACH LIGHTING

CONTROL HUB ON THE ENTIRE PROJECT. COORDINATE EXACT QUANTITY AND

LOCATIONS WITH THE LIGHTING CONTROL SYSTEM INSTALLER. CONTRACTOR TO

ASSUME A MINIMUM OF FIVE (5) PER PROJECT.

20. CONTRACTOR TO PROVIDE AND INSTALL ONE (1) CATEGORY 6 DATA CIRCUITS TO

EACH PROJECTOR AND LCD ON THE ENTIRE PROJECT.

21. PROVIDE AND INSTALL ONE (1) CATEGORY 6 DATA CIRCUIT TO THE LOCAL AIR UNIT

CONTROLLER IN EACH MDF AND IDF.

22. PROVIDE AND INSTALL ONE (1) CATEGORY 6 DATA CIRCUIT TO EACH ACCESS

CONTROL VIDEO DOOR STATION ON THE ENTIRE PROJECT. COORDINATE EXACT

LOCATION AND TERMINATION REQUIREMENTS WITH THE DOOR STATION INSTALLER,

PRIOR TO INSTALLATION.

1. THE SECURITY SYSTEM INSTALLERS SHALL BE RESPONSIBLE FOR CONNECTING ALL APPLICABLE SYSTEM EQUIPMENT

TO THE OWNER'S NETWORK.

2. THE SYSTEM INSTALLER SHALL PROPERLY SUPPORT ALL INSTALLED SYSTEM CABLING FROM AN APPROVED CABLE SUPPORT SYSTEM AS DETAILED IN SPECIFICATIONS. NO CABLING SHALL BE ROUTED AND TIED DIRECTLY TO BUILDING STEEL, CEILING GRID SUPPORT, CONDUIT, PIPING, OR DUCTWORK. THE CABLE SUPPORT SYSTEM SHALL BE DIRECTLY CONNECTED TO THE BUILDING'S STEEL JOIST. AT LOCATIONS WHERE THE BOTTOM OF THE JOIST IS MORE THAN 5' ABOVE THE CEILING, THE SYSTEM INSTALLER SHALL PROVIDE AND INSTALL THREADED ROD AND ALL REQUIRED MATERIALS TO CONNECT THE THREADED ROD TO THE BUILDING STEEL AND THE CABLE SUPPORT SYSTEM TO THE THREADED ROD. CABLE PATHWAY SHALL NOT BE HIGHER THAN 5' ABOVE THE CEILING AT ANY LOCATIONS.

3. SECURITY CAMERA SYSTEM INSTALLER SHALL PROVIDE A CEILING MOUNTED INSTALLATION KIT RECOMMENDED BY THE MANUFACTURER OF THE CAMERA. EACH CEILING MOUNTED CAMERA KIT SHALL HAVE A SUPPORT WIRE ATTACHED TO THE BUILDING'S STRUCTURE TO PREVENT THE CAMERA FROM DROPPING TO THE FLOOR AT ANY TIME.

AT NO POINT SHALL THE WEIGHT OF THE CEILING MOUNTED SECURITY CAMERA BE SUPPORTED BY THE CEILING GRID

SYSTEM OR CEILING TILES. ALL CEILING MOUNTED CAMERAS SHALL BE FLUSH MOUNTED.

4. ALL EXTERIOR AND WALL MOUNTED CAMERA LOCATIONS AND MOUNTING HEIGHTS MUST BE COORDINATED WITH THE OWNER PRIOR TO ROUGH-IN. COORDINATION MEETINGS SHALL BE SCHEDULED THROUGH THE ARCHITECT'S PROJECT

MANAGER.

5. PROVIDE AND INSTALL MAGNETIC DOOR CONTACT AT ALL ROOF HATCHES ON THE ENTIRE PROJECT. CONTACTS TO BE

CONNECTED TO THE BUILDINGS INTRUSION DETECTION SYSTEM.

6. CONTRACTOR TO PROVIDE AND INSTALL A MONITOR RELAY AND ALL REQUIRED MATERIALS TO CONNECT THE RELAY TO THE FREEZER/COOLER TEMPERATURE GAUGE AND BACK TO THE INTRUSION DETECTION SYSTEM, THE INTRUSION DETECTION SYSTEM SHALL BE PROGRAMMED TO NOTIFY THE OWNER'S DESIGNATED PERSONNEL IN THE EVENT OF

EXTENSIVE CHANGE IN TEMPERATURE.

SECURITY GENERAL NOTES

1. EVERY SYMBOL SHOWN ON LEGEND MAY NOT APPEAR ON DRAWINGS. REFER TO GENERAL ELECTRICAL NOTES FOR

WALL-MOUNTED DEVICE MOUNTING HEIGHTS.

2. REFERENCE SPECIFICATIONS FOR MATERIALS AND METHODS.

3. COMPLETE INSTALLATION OF ALL PRODUCTS SHALL BE IN COMPLIANCE WITH ALL CODES, INDUSTRY STANDARDS, COMMON PRACTICES AND MANUFACTURER'S INSTRUCTIONS.

4. ALL EXTERIOR AND WALL MOUNTED CAMERA LOCATIONS AND MOUNTING HEIGHTS MUST BE COORDINATED WITH THE OWNER PRIOR TO ROUGH-IN. COORDINATION MEETINGS SHALL BE SCHEDULED THROUGH THE ARCHITECT'S PROJECT

MANAGER.

NOTES TO CONTRACTOR

1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF EACH SYSTEM SHALL BE A DEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. PROJECTS ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TO MAIN CONTROL PANELS, REMOTE POWER SUPPLIES AND ALL HEAD END EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATIONS AND CONNECTIONS WITH

THE PROJECT'S ELECTRICAL CONTRACTOR.

2. THE PROJECT'S ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL IN CONDUITS, BACK BOXES, JUNCTION BOXES, RACEWAYS, AND SLEEVES REQUIRED TO ESTABLISH CLEAR PATHWAYS FOR ALL SYSTEMS. ALL CONDUITS, SLEEVES, BOXES, AND RACEWAYS SHALL BE PROPERLY SIZED TO

MAINTAIN A 40% MAXIMUM FILL RATIO.

3. ALL EXPOSED SYSTEM'S WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS SHALL BE ROUTED IN CONDUIT, PROVIDED AND INSTALLED BY THE PROJECT'S ELECTRICAL CONTRACTOR. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4".

4. EACH SYSTEM INSTALLER SHALL BE RESPONSIBLE FOR ENSURING ALL EXTERIOR WALL PENETRATIONS ARE

PROPERLY SEALED TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

5. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. IF EXTERIOR CONDUITS ARE REQUIRED FOR A COMPLETE INSTALLATION, EACH SYSTEM CONTRACTOR SHALL COORDINATE WITH THE

PROJECTS CONSULTANT PRIOR TO ANY ROUGH-IN.

6. EACH SYSTEM INSTALLER SHALL PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL CONDUIT STUB

OUTS AND SLEEVES TO PREVENT CABLE DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE

INSTALLATION. CUTTING BUSHING AND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE EXCEPTED.

7.

ALL CABLE SHALL BE ROUTED DOWN CORRIDORS, PARALLEL AND PERPENDICULAR TO THE BUILDING WALLS AND STRUCTURE. CABLE TO EACH DEVICE SHALL BRANCH OFF OF A MAIN CORRIDOR TRUNK. ROUTING CABLES THROUGH CLASSROOMS, OFFICES, STORAGE ROOMS, RESTROOMS OR ANY TYPE OF ROOM OTHER THAN A CORRIDOR WILL NOT BE ACCEPTED. ENTER ALL ROOMS ABOVE THE ASSOCIATED ROOM DOORWAY.

GENERAL NOTES

H

RACK

ABM

LSC

M

S

D E

V

IC

E S

LOCAL SOUND SYSTEM LEGEND

DESCRIPTIONSYMBOLG

R O

U P

VENUE SPECIFIC LOCAL SOUND SYSTEM SPEAKER. *# TO BE

REPLACED WITH ALPHANUMERIC TEXT INDICATING THE

ASSOCIATED VENUE AND SPEAKER NUMBER.

VENUE SPECIFIC LOCAL SOUND SYSTEM CONTROL PLATE. *#

TO BE REPLACED WITH ALPHANUMERIC TEXT INDICATING THE

ASSOCIATED VENUE AND CONTROL PLATE NUMBER.

VENUE SPECIFIC LOCAL SOUND SYSTEM MICROPHONE INPUT.

*# TO BE REPLACED WITH ALPHANUMERIC TEXT INDICATING

THE ASSOCIATED VENUE AND MIC INPUT NUMBER.

VENUE SPECIFIC LOCAL SOUND SYSTEM HANGING MICROPHONE.

*# TO BE REPLACED WITH ALPHANUMERIC TEXT INDICATING

THE ASSOCIATED VENUE AND MIC NUMBER.

VENUE SPECIFIC LOCAL SOUND SYSTEM 3.5MM AUXILIARY INPUT

AND BLUETOOTH MIXER. *# TO BE REPLACED WITH

ALPHANUMERIC TEXT INDICATING THE ASSOCIATED VENUE AND

MIXER NUMBER. CONTRACTOR TO PROVIDE AND INSTALL A

RECESSED ENCLOSURE WITH FLUSH MOUNTED, LOCKABLE

DOOR. DEVICE TO BE MOUNTED AT +42" AFF.

INDICATED THE LOCATION OF THE VENUE SPECIFIC LOCAL

SOUND SYSTEM HEAD END RACK. AMPLIFIERS, DSPS, AND ALL

OTHER HEAD END EQUIPMENT SHALL BE INSTALLED IN THIS

RACK/CABINET.

WIRELESS MICROPHONE ANTENNA. REFERENCE SPECIFICATIONS FOR MORE

INFORMATION.

ASSISTED LISTENING ANTENNA. REFERENCE SPECIFICATIONS FOR MORE INFORMATION.

NOTES:

1.

REFERENCE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND

REQUIREMENTS

WA

ALA

DESCRIPTIONTEXT

INDICATES THAT THE DEVICE IS EXISTING TO REMAIN. CONTRACTOR

TO REMOVE DEVICE AND PLACE IN THE SAME LOCATION AS NEEDED.

INDICATES THAT THE DEVICE IS EXISTING AN IS TO BE REMOVED.

CONTRACTOR TO REMOVE THE DEVICE AND RETURN TO OWNER.

INDICATES THAT THE DEVICE IS EXISTING AND SHALL BE REPLACED.

REFERENCE NEW SYSTEM LAYOUT FOR EXACT LOCATIONS.

INDICATES THAT THE DEVICE IS EXISTING AND SHALL BE REMOVED

AND RELOCATED TO A LOCATION INDICATED ON THE DRAWINGS.

REFERENCE NEW SYSTEM LAYOUT FOR EXACT LOCATIONS.

SUBSCRIPTS LEGEND - EXISTING DEVICES

'E'

'D'

'R'

'RR'

AVC

S

D E

V

IC

E S

AUDIO/VIDEO LEGEND

DESCRIPTIONSYMBOL

'AV-*#'

INDICATES THE LOCATION OF A VIDEO PROJECTOR # TO BE REPLACED WITH "C" OR "W".

"C" INDICATES THAT THE DEVICE IS A CEILING MOUNTED DEVICE AND "W" INDICATES IT

IS TO BE WALL MOUNTED. CONTRACTOR TO PROVIDE AND INSTALL A PROJECTOR,

CEILING OR WALL MOUNTING KIT, AND PATCH CABLES AS REQUIRED TO CONNECT AT

BOTH ENDS.

INDICATES THAT THE DESIGNATED TECHNOLOGY OUTLET IS INTENDED FOR AN

AUDIO/VIDEO (A/V) INPUT. CONTRACTOR TO PROVIDE AND INSTALL A FLOOR MOUNTED

OR WALL MOUNTED BOX AS INDICATED. (2) 1.25" CONDUITS FROM THE BOX TO THE

NEAREST, PLENUM ACCESSIBLE CEILING WITHIN THE SAME ROOM. ALL FLOOR AND

WALL MOUNTED BOXES SHALL BE A MINIMUM OF 2-GANGS.

*# - WHEN REPLACED WITH A '1' (AV-1) ONLY, THE OUTLET SHALL BE A

STANDALONE, LOCAL INPUT TIED TO A LOCAL VIDEO DISPLAY (FSD, CMP, WMP, AV-2,

ETC.). THIS OUTLET WILL NOT BE ASSOCIATED WITH ANY SYSTEM FOR ROUTING TO

DISPLAYS LOCATED IN ANY OTHER PORTION OF THE PROJECT. IF NOT REPLACED WITH

A '1' SEE THE NOTES AT THE BOTTOM OF THE LEGEND FOR ADDITIONAL INSTRUCTIONS.

INDICATES THE LOCATION OF A FLAT PANEL VIDEO DISPLAY. CONTRACTOR TO

PROVIDE AND INSTALL TWO (2) CATEGORY 6 UTP NETWORK CABLE TO ALL LOCATIONS

SHOWN ON THE ENTIRE PROJECT.

*# - WHEN REPLACED WITH A '1' (FSD-1) ONLY, THE OUTLET SHALL BE A

STANDALONE AND ONLY HAVE THE CATEGORY 6 CABLE ROUTED TO IT, FROM THE

MDF/IDF SERVING THE DEVICES AREA ROOM.

*# - WHEN REPLACED WITH A '2' (FSD-2) ONLY, THE OUTLET SHALL HAVE THE

CATEGORY 6 CABLE ROUTED TO IT, FROM THE MDF/IDF SERVING THE DEVICES AREA,

AND THE CABLING FROM THE ASSOCIATED AV-1.

EACH FSD OUTLET SHALL BE A 2-GANG BOX AND TWO (2) 1.25” CONDUITS STUBBING

INTO THE ROOMS ACCESSIBLE CEILING. PROVIDE ONE DOUBLE-GANG FACEPLATE WITH

TWO (2) DECORA PORTS. PROVIDE A DECORA STYLE INSERT THAT ACCEPTS THE STYLE

OF DATA JACK BEING USED FOR STRUCTURED CABLING. WHEN THERE IS A LOCAL A/V

INPUT ASSOCIATED WITH THE DISPLAY, PROVIDE A DECORA INSERT THAT CONFORMS

WITH THE SYSTEMS SPECIFIED. OTHERWISE PROVIDE A BLANK INSERT IN THE SECOND

PORT.

INDICATES THE LOCATION OF A WALL MOUNTED, INTERACTIVE VIDEO DISPLAY.

PROVIDE AND INSTALL A/V CABLE FROM THE ASSOCIATED AV-1 AS PER SYSTEM

SPECIFICATIONS. RACEWAY SHALL CONSIST OF A 2-GANG BOX AND TWO (2) 1.25”

CONDUITS STUBBING INTO THE ROOMS ACCESSIBLE CEILING. PROVIDE ONE DOUBLE-

GANG FACEPLATE WITH TWO (2) DECORA PORTS. PROVIDE A DECORA STYLE INSERT

THAT ACCEPTS THE STYLE OF DATA JACK BEING USED FOR STRUCTURED CABLING.

WHEN THERE IS A LOCAL A/V INPUT ASSOCIATED WITH THE DISPLAY, PROVIDE A

DECORA INSERT THAT CONFORMS WITH THE SYSTEMS SPECIFIED. OTHERWISE

PROVIDE A BLANK INSERT IN THE SECOND PORT.

INDICATES THE LOCATION OF A USB INPUT PLATE THAT SHALL TRANSMIT USB SIGNAL

TO THE ASSOCIATED USB OUTPUT PLATE. RACEWAY SHALL CONSIST OF ONE (1) 1"

CONDUIT AND A SINGLE GANG BACK BOX.

INDICATES THE LOCATION OF A USB OUTPUT PLATE THAT SHALL RECEIVE USB SIGNAL

FROM THE USB ASSOCIATED INPUT PLATE. RACEWAY SHALL CONSIST OF ONE (1) 1"

CONDUIT AND A SINGLE GANG BACK BOX.

INDICATES THE THE LOCATION OF A LOCAL SOUND REINFORCEMENT/PRESENTATION

SPEAKER.

*# - WHEN REPLACED WITH AN 'L', THE SPEAKER SHALL BE FOR LOCAL

INSTRUCTIONAL PRESENTATION AUDIO AND POWERED BY THE SPECIFIED CLASSROOM

PRESENTATION AMPLIFIER.

*# - WHEN REPLACED WITH 'SM', THE SPEAKER SHALL BE DEDICATED TO A SPEECH

PRIIVACY/SOUND MASKING SYSTEM.

INDICATES THE LOCATION OF AN AUDIO/VIDEO CONTROL PLATE. RACEWAY SHALL

CONSIST OF ONE (1) A BACK BOX WITH A 1" CONDUIT ROUTING INTO THE ACCESSIBLE

CEILING SPACE WITHIN THE SAME ROOM. AV SYSTEM INSTALLER TO COORDINATE THE

CONTROL BACK BOX SIZE REQUIREMENT WITH THE PROJECT'S ELECTRICAL

CONTRACTOR.

'FSD-*#'

G R

O U

P

NOTES:

A. IN THE EVENT THAT '*#* IS NOT DEFINED IN THE OUTLET DESCRIPTION, THE DEVICE SHALL BE CONSIDERED A STANDALONE DEVICE, SERVING THE SYSTEM WITHIN THE SAME SPACE OR THE FOLLOWING SHALL APPLY:

*# - UNLESS SPECIFICALLY NOTED OTHERWISE, THE FOLLOWING SHALL APPLY TO EACH DEVICE SHOWN

ON THE ENTIRE PROJECT:

* SHALL BE REPLACED WITH ALPHABETICAL CHARACTERS THAT SHALL INDICATE THE SPECIFIC VENUE

THAT THE DEVICE IS ASSOCIATED WITH.

# SHALL BE REPLACED WITH A NUMERIC VALUE THAT SHALL IDENTIFY THE SPECIFIC DEVICE WITHIN THE

SPECIFIC VENUE.

B. THE AUDIO/VIDEO SYSTEM INTEGRATOR SHALL COORDINATE ALL BOX AND CONDUIT SIZE REQUIREMENTS

PRIOR TO ROOUGH-IN BY THE PROJECTS ELECTRICAL CONTRACTOR.

C. REFERENCE SCOPE MATRIX AND PROJECT SPECIFICATIONS FOR INSTRUCTIONS REGARDING THE PROVIDING

AND INSTALLATION OF VIDEO DISPLAYS, PROJECTORS, SCREENS, MOUNTS, AND LIFTS.

#MP'

'IVD'

'USB-T'

'USB-R'

RESPONSIBILITY MATRIX

SCOPE OF WORK RESPONSIBILITY

OFOI

DIV 27 - COMMUNICATIONS

TECHNOLOGY SCOPE

AUDIO-VIDEO SYSTEM

DIV 28 - SECURITY SYSTEMS

VIDEO SURVEILLANCE SYSTEM

ACCESS CONTROL SYSTEM

INTRUSION DETECTION SYSTEM

STRUCTURED CABLING

CABLE TRAY IN ER/TR

CABLE PATHWAY OUTSIDE ER/TR

TELECOM GROUNDING SYSTEM

BACK BOXES, CONDUITS/SLEEVES

EQUIPMENT RACKS/CABINETS

WIRELESS ACCESS POINTS

NETWORK SWITCHES

UPS

TELEPHONES

WORKSTATION PC

LOCAL SOUND SYSTEM

FLAT PANEL DISPLAY (TV)

FLAT PANEL DISPLAY (TV) MOUNTS

DIGITAL SIGNAGE PLAYER

AV SWITCHER

AV CONTROL PANEL

AV EQUIPMENT CABINETS

AV CABLING

NETWORK CABLING REQUIRED

LECTERN

BACK BOXES, CONDUITS/SLEEVES

CAMERAS AND LICENSES

CAMERA MOUNTS

CAMERA NETWORK CABLING

PoE SWITCHES

VMS SERVERS

VIEWING STATION

BACK BOXES, CONDUITS/SLEEVES

EQUIPMENT RACKS/CABINETS

CARD READERS

DOOR CONTACTS

ELECTRIFIED LOCKS

REX INSIDE DOOR

PUSH TO EXIT

PIR SENSORS

LOW VOLTAGE POWER SUPPLY

ACCESS CONTROL PANELS

EQUIPMENT RACKS/CABINETS

BACK BOXES, CONDUITS/SLEEVES

COMPOSITE CABLING

NETWORK CABLING REQUIRED

CREDENTIAL CARDS

BADGE PRINTERS

MOTION SENSORS

GLASS BREAK SENSORS

ALARM/DISALARM KEY PAD

INTRUSION DETECTION PANEL (IDP)

DOOR CONTACTS

DATA CABLING TO IDP

PHONE OR INTERNET SERVICES

INTRUSION ALARM CABLING

BACK BOXES, CONDUITS/SLEEVES

OFCI CFCI

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

PDU X

BACKBONE CABLING X

OFOI OFCI CFCI

OFOI OFCI CFCI

OFOI OFCI CFCI

OFOI OFCI CFCI

X

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION DOCUMENT 2

(100%)

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD STAMPCONSULTANT

7 8 9 10321 4 5 6

200 E. Grayson Street, Suite 207

San Antonio, Texas 78215

210.530.0755 www.westeastdesign.com

Texas Registered Architectural Firm

WestEast Design Group JV, LLC Elk Consortium +

REMODEL AMPHITHEATER

674-16-016

CENTRAL TEXAS VETERANS HEALTH CARE SYSTEM

1901 S. 1ST STREET TEMPLE, TEXAS 76504STRUCTURAL ENGINEER

AV CONSULTANT MEP ENGINEER

ALDERSON & ASSOCIATE

7700 TORINO STE. 101, SAN ANTONIO, TX 78229

210.614.1110

DEAN@ALDERSON-INC.COM

DBR

9601 MCALLISTER FREEWAY STE. 410,

SAN ANTONIO, TX 78257

210.546.0200

BUHLRICH@DBRINC.COM

LUNDY & FRANKE ENGINEERING, INC

549 HEIMER, SAN ANTONIO, TX 78232

210.979.7900 ext. 6

FRANKE@LUNDYFRANKE.COM

DEAN ALDERSON

SHAWN FRANKE

BRIAN UHLRICH

APRIL 29, 2025 AC HG12/16/25

A u to d e s k D o c s /2

.0

V A

T e m p le -A m p h it h e a te r

R e m o d e l/

V A

T e m p le A m p h it h e a te r_ V

A

.r v t

/1 /2

:2

:1

P

M

T0.01

TECHNOLOGY SYMBOL LEGEND

Revisions: Date:

Addendum 1 12/16/25

_Technology Bound - Addendum 1.pdf
Sheets
T0.01 - TECHNOLOGY SYMBOL LEGEND