18708 Final Report Bldg 163.pdf
PDF 26 MB Posted
- Attached to
- Y1DA--36C257-26-AP-0163 | NEW CON FY26 | CTX 674-16-016 - Remodel Amphitheater (VA-26-00003450)
- Solicitation number
- 36C25726R0011
About this file
This document is a 2012 Asbestos Reinspection Report for Building 163 at the Central Texas Veterans Health Care System's Olin E. Teague VA Medical Center in Temple, Texas. The comprehensive report details a thorough asbestos inspection conducted by ALTEC Environmental Consulting, LLC, which complies with the Asbestos Hazard Emergency Response Act (AHERA) requirements. The inspection involved visually examining all accessible areas for suspect asbestos-containing materials (ACM), collecting bulk samples, and analyzing them through EMSL Laboratories.
Key findings include the identification of multiple asbestos-containing materials across various building areas such as floor tiles, pipe insulations, fire doors, gaskets, and air handling unit blankets. The report provides detailed tables documenting homogeneous areas, sample locations, condition assessments, and removal priorities. Notably, the inspection revealed asbestos-containing materials in various locations including the crawlspace, basement, first, second, third, fourth, and fifth floors, with a particular sample (TE-12-353-013) containing 15% chrysotile asbestos in a brown flange gasket located in the southeast quadrant of the emergency generator room. The report includes recommendations for management, periodic surveillance, and potential future abatement actions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25726R0011 0004.docx | DOCX document | |
| 36C25726R0011 0003.docx | DOCX document | |
| Sheet T0.01.pdf | ||
| 36C25726R0011 0002.docx | DOCX document | |
| Sign-in Sheet.pdf | ||
| 36C25726R0011 0001_1.docx | DOCX document | |
| 36C25726R0011 0001.docx | DOCX document | |
| 36C25726R0011.pdf | ||
| Attachment 4 - Itemized Cost Breakdown.xlsx | XLSX spreadsheet | |
| Attachment 1 - 67416016 Remodel Amphitheater 100 percent CD Drawings.pdf | ||
| Attachment 5 - VHA Pre-Construction Risk Assessment.pdf | ||
| Attachment 3 - 67416016 Remodel Amphitheater 100 percent CD Material Board.pdf | ||
| Attachment 2 - 6716016 Remodel Amphitheater 100 percent CD Specs.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2012 Asbestos Reinspection
INTRODUCTION
2012 ASBESTOS REINSPECTION REPORT
CENTRAL TEXAS VETERANS HEALTH CARE SYSTEM
WACO VA MEDICAL CENTER
SCOPE OF WORK
1. This asbestos reinspection complies with the requirements of Asbestos Hazard
Emergency Response Act (AHERA).
2. Each facility inspection was performed by an accredited inspector.
3. For each facility, the inspector performed the following tasks:
a. Visually inspected all accessible areas for suspect asbestos-containing material
(ACM).
b. Asbestos bulk samples were collected of all suspected materials and the samples were analyzed by EMSL Laboratories which is an NVLAP-accredited laboratory authorized to analyze asbestos bulk samples.
c. If any of the asbestos bulk samples contained asbestos from 1% to 5% in asbestos content, then the laboratory was requested to perform a Polarized Light
Microscopy (PLM) point count of that material for a more accurate analysis.
d. After reviewing the results from the asbestos bulk samples and subsequent point counting, homogeneous areas were determined for the various asbestos-containing materials.
e. Homogeneous area tables were prepared and condition summaries were completed.
f. A report was then completed that is outlined in the report section that follows this scope of work.
g. A management planner reviewed all work provided above and verified that the plan met all AHERA requirements. The appropriate response actions were recommended and the reinspection signed and dated. This report included the accreditation number of inspectors and planners. A copy of the 2012 Asbestos
Reinspection Report was submitted to the owner.
MANAGEMENT PLAN RECOMMENDATIONS
The following general notes are for all facilities inspected during the Asbestos Reinspection:
1. Removal Priorities were developed for each homogeneous area. The Removal Priorities are an indicator of priorities for future repair work or abatement work to be scheduled as financial budgets allow. Please see the 2012 Reinspection Condition and Removal
Priority Table for further details.
2. The current condition of material was listed for each homogeneous area. The condition, location, and potential for disturbance factors are used for the hazard ranking. Please see the 2012 Reinspection Condition and Removal Priority Table for the condition summaries.
3. Records for custodial, janitorial, and maintenance staff who have received two-hour awareness training should be filed in the Management Plan.
4. Any new custodial, janitorial, or maintenance staff that have the potential to come in contact with asbestos-containing materials (ACM) are required to attend a two-hour awareness training class. Records of training for new employees should be filed in the
Management Plan.
5. The Designated Person is required to inform workers and building occupants at least once a year about the Management Plan. This includes information about inspections, response actions, and post-response action activities that are planned or in progress.
6. Maintenance areas (boiler rooms, janitor closets, etc.) are required to have warning labels where ACM is located. Install warning labels in these areas as needed. Some older labels may have come loose and are no longer visible. Post the labels in a prominent location.
7. Review the enclosed 2012 Reinspection Condition and Removal Priority Table for maintenance actions that may be required and to establish priorities and budgets for future repair and abatement work.
8. Periodic “Surveillance Inspections” are required every six (6) months. This inspection should indicate the condition of the material and provide recommendations for repair or potential removal. Consistency of inspections is desired and, therefore, should be performed by the same individual(s) for all facilities. An accredited inspector is not required, but is recommended. Records of Surveillance Inspections should be filed in both the administrative and facility Management Plans.
9. “Reinspections” are required every three (3) years. Updated information should be added to the Management Plan.
10. An accredited “Supervisor” should be on staff or available on a contract basis per
AHERA guidelines. Certification paperwork should be filed in the training section of the
Management Plan.
11. ACM should only be removed by contractors licensed and accredited in the State of
Texas. Response actions related to abatement activity should be filed in the Management
Plan. Removal of limited amounts of asbestos by the accredited Supervisor and trained individuals is within the scope of the Management Plan.
12. Notification should be provided to “outside contractors” about ACM within the facility.
This should include such trades or services as telephone, electrical, plumbing, air conditioning, and other construction work. A form should be created for this purpose and placed in the Management Plan.
13. New building construction and portable buildings added to a facility are required to be inspected and sampled for ACM. In lieu of this, a letter from the architect, engineer, or manufacturer can be obtained that states “no ACM were specified or used in the facility.”
A copy of this letter is to be filed with the Management Plan at the facility. This letter will cancel the requirement for sampling.
14. Abatement Costs were developed for each homogeneous area and per facility. The estimated abatement cost is for budget purposes only. The cost is based on the area of material and estimated abatement costs for this material. The cost is for abatement only and does not include abatement design, air monitoring, or project observation costs.
REPORT SECTION
2012 ASBESTOS REINSPECTION REPORT
WACO VA MEDICAL CENTER
This report will include a combination of the following sections:
ACM Homogeneous Areas Summary Table and Drawings
This section provides a quick table reference to all asbestos-containing homogeneous areas found during the reinspection, and to drawings with the asbestos-containing homogeneous areas found during the 2012 asbestos reinspection.
This section will not be included in the building reports that did not require any sampling due to no suspected ACM being present. The section will also not be included if asbestos bulk samples were collected and the results indicated no asbestos-containing materials were found in that building.
Condition and Removal Priority Table
This section provides a table with the current condition, potential for disturbance, and removal priority for each homogeneous area.
Master Summary Table – Asbestos Bulk Samples
This table provides a listing of all asbestos bulk samples taken to date.
no suspected ACM being present.
Asbestos-Containing Bulk Samples
This table provides a listing of all asbestos-containing bulk samples.
2012 Reinspection – Inspection Logs
This section provides the field inspection logs for samples taken during the 2012 asbestos reinspection.
Bulk Sample Location Drawings
This section provides drawings with sample locations for all asbestos bulk samples.
Site and sample location drawings will be included in the building reports that did not require any sampling due to no suspected ACM being present.
2012 Reinspection – Photographs
This section provides photographs of all asbestos bulk samples taken during the 2012 asbestos reinspection.
2012 Reinspection – Laboratory Reports
This section provides all laboratory analytical results.
Certifications
This section provides certifications for all Inspectors, the Management Planner who reviewed this Management Plan, and the laboratory that performed the bulk sample analysis.
Periodic Surveillance Forms
This section includes the forms to be completed during the periodic surveillance inspections required every six (6) months.
This section will not be required for building reports that did not require any sampling due to no suspected ACM being present. This section will also not be required if asbestos bulk samples
Management Plan Updates
This section includes the records of any asbestos abatement activities that are completed at the subject site. Notifications, daily notes, drawings, etc., should be placed in this section. This would also include air-monitoring data from asbestos abatement projects.
Response Actions
This section includes the records of any internal asbestos abatement or operation and maintenance activities that may be completed by VA employees. This would include any drawings, field notes, and air monitoring that was completed.
Training Documents
This section includes the records of training for the Designated Person and accredited
Supervisor, as well as the two-hour awareness training for the custodial, janitorial, and maintenance staff.
CONTRACTOR
2012 ASBESTOS REINSPECTION REPORT
OLIN E. TEAGUE VA MEDICAL CENTER
This 2012 Asbestos Reinspection was provided by:
Contractor:
ALTEC Environmental Consulting, LLC
10100 Woolworth Road
Keithville, LA 71047
(318) 687-3771 (Office)
(318) 687-9923 (Fax)
INSPECTORS:
Jerry Heidecker David Hopper
LA Certificate No. 3I166471 LA Certificate No. 3I134762
Donald R. Joiner Bradley Kennon
LA Certificate No. 3I112937 LA Certificate No. 3I182667
Rodney Lewis
LA Certificate No. 3I169456
MANAGEMENT PLANNER:
Robert B. Raines III, P.E.
LA Certificate No. 3P103065 – Management Planner
Accreditation Agency: Louisiana Department of Environmental Quality which is a recognized EPA accreditation agency
ACM HOMOGENEOUS AREAS
SUMMARY TABLE AND DRAWINGS
OLIN E. TEAGUE V. A. MEDICAL CENTER
2012 THREE-YEAR ASBESTOS REINSPECTION
ACM HOMOGENEOUS AREAS SUMMARY TABLE
Floor Flooring Materials Ceiling Materials TSI Materials Miscellaneous Materials
Crawlspace
Central No ACM No ACM No ACM No ACM
Crawlspace
South No ACM No ACM HMA-03 Pipe Insulation and Fittings HMA-04 Gaskets
Floor Flooring Materials Ceiling Materials TSI Materials Miscellaneous Materials
Basement
North No ACM No ACM No ACM No ACM
Basement
Central HMA-01 9"x9" Floor Tile and Mastic No ACM No ACM HMA-06 Fire Doors
Basement
South No ACM No ACM No ACM
HMA-05 Air Handling Unit Blanket
HMA-06 Fire Doors
HMA-08 Flange Gasket
Floor Flooring Materials Ceiling Materials TSI Materials Miscellaneous Materials
1-Northeast
HMA-01 9"x9" Floor Tile and Mastic
HMA-02 12"x12" Floor Tile and
Mastic
No ACM No ACM HMA-06 Fire Doors
1-Northwest HMA-01 9"x9" Floor Tile and Mastic No ACM No ACM HMA-06 Fire Doors
1-Southeast
HMA-01 9"x9" Floor Tile and Mastic
HMA-02 12"x12" Floor Tile and
Mastic
No ACM No ACM HMA-06 Fire Doors
1-Southwest HMA-01 9"x9" Floor Tile and Mastic No ACM No ACM HMA-06 Fire Doors
1-West No ACM No ACM No ACM HMA-06 Fire Doors
Building 163 - Crawlspace
Building 163 - Basement
Building 163 - First Floor
Building 163 - Second Floor
ACM HOMOGENEOUS AREAS SUMMARY TABLE
Building 163 - Crawlspace Floor Flooring Materials Ceiling Materials TSI Materials Miscellaneous Materials
2-North No ACM No ACM No ACM HMA-06 Fire Doors
2-Southeast
HMA-01 9"x9" Floor Tile and Mastic
HMA-02 12"x12" Floor Tile and
Mastic
No ACM No ACM HMA-06 Fire Doors
2-Southwest HMA-01 9"x9" Floor Tile and Mastic No ACM No ACM HMA-06 Fire Doors
Floor Flooring Materials Ceiling Materials TSI Materials Miscellaneous Materials
3 No ACM No ACM HMA-03 Pipe Insulation and Fittings HMA-06 Fire Doors
Floor Flooring Materials Ceiling Materials TSI Materials Miscellaneous Materials
4 No ACM No ACM HMA-03 Pipe Insulation and Fittings HMA-06 Fire Doors
Floor Flooring Materials Ceiling Materials TSI Materials Miscellaneous Materials
5 No ACM No ACM No ACM HMA-06 Fire Doors
Floor Flooring Materials Ceiling Materials TSI Materials Miscellaneous Materials
Mechanical
Room No ACM No ACM No ACM HMA-05 Air Handling Unit Blanket
Floor Flooring Materials Ceiling Materials TSI Materials Miscellaneous Materials
First Floor
Roof No ACM No ACM No ACM No ACM
Building 163 - Fifth Floor
Building 163 - Fifth Floor - Roof
Building 163 - Roof (Over First Floor)
Building 163 - Second Floor
Building 163 - Third Floor
Building 163 - Fourth Floor
Crawlspace
Basement
First Floor
Second Floor
Third Floor
Fourth Floor
Fifth Floor
Roof
CONDITION AND REMOVAL PRIORITY TABLE
Qualitative Rankings and Quantitative (Numerical) Ratings for Current Condition
Qualitative Ranking Numerical Rating Description of Current Condition
Surfacing material has no visible damage or small amounts of damage; covering on thermal system Good 8, 9, 10 insulation is intact or has small amounts of damage; miscellaneous materials intact; no visible debris or small amounts of debris.
Surfacing material has moderate but not extensive amounts of visible damage; covering on thermal system
F 4 5 6 7 insulation is cut or torn, exposing moderate but not extensive amounts of insulation; moderate but notair ‘ ‘
‘ extensive damage to miscellaneous materials such as floor tile; moderate but not extensive amounts of visible dust and debris..
Extensive damage to surfacing material; covering on thermal system insulation is cut or torn extensively and Poor 1, 2, 3 insulation itself is damage; miscellaneous materials such as floor tile extensively damaged and underlying mastic exposed; extensive amounts of dust and debris.
2 Qualitative Rankings and Quantitative (Numerical) Ratings for Potential for Disturbance
. Assessment FactorsQualitative Ranking Numerical Rating .
Physical Disturbance Environmental Disturbance
Vibration: vibration from operating machinery, HVAC Low 1, 2, 3 equipment, and so forth
Accessibility: accessibility during normal operations Air/Dust: air currents strong enough to dislodge loose
ACM; airborne dust that can erode material Medium 4,5,6,7
Corrosive: corrosive atmosphere or liquids that can Activities: activities that people do and how erode the covering or matrix often they do them High 8, 9, 10 Water Damage: water damage from leaking roof, pipe or other source
Qualitative Rankings and Quantitative (Numerical) Ratings for Removal Priority
Qualitative Ranking Numerical Rating Description of Current Condition High 1, 2, 3 Address short-term
Medium 4, 5, 6, 7 Address with on-going maintenance procedures
Low 8, 9. 10 Maintain in good condition
CONDITION AND REMOVAL PRIORITY TABLE
Rating Based On Rating Based On
HMA-03 163
Crawlspace
South Pipe Insulation and Fittings Yes No 7 Damage 2 Access 10
HMA-04 163
Crawlspace
South Gaskets No No 9 Intact 1 Maintenance 10
HMA-01 163
Basement
Central 9x9 Floor Tile and Mastic No No 10 Intact 2
Floor
Maintenance
HMA-06 163
Basement
Central Fire Doors No No 10 Intact 1 Maintenance 10
HMA-01 163
Basement
South 9x9 Floor Tile and Mastic
HMA-02 163
Basement
South 12x12 Floor Tile and Mastic
HMA-05 163
Basement
South Air Handling Unit Blanket Yes No 8 Damage 2 Access 10
HMA-06 163
Basement
South Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-08 163
Basement
South Flange Gasket No No 8 Intact 4 Maintenance 2
HMA-01 163 1-Northeast 9x9 Floor Tile and Mastic No No 10 Intact 2 Floor
Maintenance
HMA-02 163 1-Northeast 12x12 Floor Tile and Mastic No No 10 Intact 2 Floor
Maintenance
HMA-06 163 1-Northeast Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-01 163 1-Northwest 9x9 Floor Tile and Mastic No No 10 Intact 2 Floor
Maintenance
Material Description
Building 163 - First Floor
Removal
Priority
Building 163 - Basement
Current Condition
Building 163 - Crawlspace
Accessibility
Yes/No
Restricted
Potential for
Disturbance 2Homogeneous
Area No.
Bldg Floor
Friable
Yes/No
Abated as of 2012 Reinspection
Abated as of 2012 Reinspection
CONDITION AND REMOVAL PRIORITY TABLE
Material Description Removal
Priority
Current Condition 1Accessibility
Yes/No
Restricted
Potential for
Disturbance 2Homogeneous
Area No.
Bldg Floor
Friable
Yes/No
HMA-06 163 1-Northwest Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-01 163 1-Southeast 9x9 Floor Tile and Mastic No No 10 Intact 2 Floor
Maintenance
HMA-02 163 1-Southeast 12x12 Floor Tile and Mastic No No 10 Intact 2 Floor
Maintenance
HMA-06 163 1-Southeast Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-01 163 1-Southwest 9x9 Floor Tile and Mastic No No 10 Intact 2 Floor
Maintenance
HMA-06 163 1-Southwest Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-06 163 1-West Fire Doors Yes No 10 Intact 1 Maintenance 10
CONDITION AND REMOVAL PRIORITY TABLE
Material Description Removal
Priority
Current Condition 1Accessibility
Yes/No
Restricted
Potential for
Disturbance 2Homogeneous
Area No.
Bldg Floor
Friable
Yes/No
HMA-06 163 2-North Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-01 163 2-Southeast 9x9 Floor Tile and Mastic No No 10 Intact 2 Floor
Maintenance
HMA-02 163 2-Southeast 12x12 Floor Tile and Mastic No No 10 Intact 2 Floor
Maintenance
HMA-06 163 2-Southeast Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-01 163 2-Southwest 9x9 Floor Tile and Mastic No No 10 Intact 2 Floor
Maintenance
HMA-06 163 2-Southwest Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-03 163 3 Pipe Insulation and Fittings Yes No 7 Damage 2 Access 10
HMA-06 163 3 Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-03 163 4 Pipe Insulation and Fittings Yes No 7 Damage 2 Access 10
HMA-06 163 4 Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-06 163 5 Fire Doors Yes No 10 Intact 1 Maintenance 10
HMA-05 163
Mechanical
Room Air Handling Unit Blanket Yes No 8 Intact 2 Access 10
Building 163 - Fifth Floor - Roof
Building 163 - Fourth Floor
Building 163 - Second Floor
Building 163 - Third Floor
Building 163 - Fifth Floor
MASTER SUMMARY TABLE
ASBESTOS BULK SAMPLES
SUMMARY OF BULK SAMPLES TAKEN TO DATE
(determined by Point Count Analysis)
Building Floor Room Sample ID Material Description
163 N BA Pipe BA OT-09-293-0001 3" horizontal pipe - yellow insulation, white wrap
163 N BA Pipe BA OT-09-293-0002 5" horizontal pipe - yellow insulation, white wrap
163 N BA Pipe BA OT-09-293-0003 8" horizontal pipe - yellow insulation, white wrap
163 N BA Pipe BA OT-09-293-0004 3" valve - yellow insulation, white wrap, white mud
163 N BA Pipe BA OT-09-293-0005 Black felt, black wrap, black mastic
163 Basement Sub BA OT-09-293-0006 Brown insulation, black mastic
163 Basement Pipe BA OT-09-293-0007 Yellow insulation, silver tape, white mud
163 Basement #6 Stairs OT-09-293-0008 Tan 12x12 floor tile, black mastic
163 Basement BD 101 OT-09-293-0009 White tape
163 Basement BC 101 OT-09-293-0010 Gray insulation, white wrap
163 Basement BC 126B OT-09-293-0011 Tan 12x12 floor tile, black mastic
163 Basement BC 121 OT-09-293-0012 Light tan 12x12 floor tile, yellow mastic
163 Basement CB 15 OT-09-293-0013 White 2x4 ceiling tile
163 Basement BC 107 OT-09-293-0014 Tan 12x12 floor tile, yellow mastic
163 Basement BC 110A OT-09-293-0015 White sheetrock, white tape, mud
163 Basement BB 107 OT-09-293-0016 White 2x4 ceiling tile
163 Basement CB 7 OT-09-293-0017 Light tan 12x12 floor tile, black mastic
163 Basement CB 7 OT-09-293-0018 5" horizontal pipe - yellow insulation, white wrap
163 Basement BD 111A OT-09-293-0019 2" horizontal pipe - yellow insulation, white wrap
163 Basement BD 111A OT-09-293-0020 Brown cove molding, yellow mastic
163 Basement #3 Stairs OT-09-293-0021 White wall coating
163 Basement BB 128 OT-09-293-0022 Layer 1 - white 9x9 floor tile
163 Basement BB 128 OT-09-293-0022 Layer 2 - black mastic
163 Basement BB 128 OT-09-293-0023 5" horizontal pipe - yellow insulation, white wrap
163 Basement BB 129A OT-09-293-0024 White plaster
163 Basement BB 129C OT-09-293-0025 Yellow insulation, silver wrap, white overspray
163 Basement BD 107 OT-09-293-0063 Gray 12x12 floor tile, yellow mastic
163 Basement BD 108E OT-09-293-0064 White 2x4 ceiling tile
163 Basement BC 150 OT-09-293-0065 Yellow insulation, silver tape, white mud
163 Basement BC 150 OT-09-293-0066 5" elbow - yellow insulation, white wrap, white mud
163 Basement BC 150 OT-09-293-0067 8" horizontal pipe - yellow insulation, white wrap
163 Basement BC 150 OT-09-293-0068 10" valve - yellow insulation, white wrap
163 Basement BC 150 OT-09-293-0069 Brown cloth, black mastic
163 Basement BB 114 OT-09-293-0070 3" vertical pipe - yellow insulation, white wrap, white mud
163 Basement BB 114 OT-09-293-0071 5" horizontal pipe - yellow insulation, brown wrap
163 Basement BB 114 OT-09-293-0072 5" elbow - pink insulation, brown wrap, white mud
163 Basement BB 114 OT-09-293-0073 3" horizontal pipe - yellow insulation, brown wrap
163 Basement BB 114 OT-09-293-0074 Black cloth, black mastic, brown cardboard insulation, black cloth, black mastic
163 Basement BA 118 OT-09-293-0075 4" horizontal pipe - yellow insulation, brown wrap
163 Basement BA 118 OT-09-293-0076 4" elbow - yellow insulation, white tape, mud
163 Basement BD 116B OT-09-293-0077 White block insulation, white wrap
163 Basement BA 118 OT-09-293-0078 Black mastic, white compound
163 Basement CB6 OT-09-293-0079 2" horizontal pipe - yellow insulation, white wrap
163 Basement CB6 OT-09-293-0080 Yellow insulation, silver wrap, white mud
163 Basement BA 115 OT-09-293-0081 2" horizontal pipe - yellow insulation, white wrap
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non Asbestos-Containing Material
Purple = Abated
SUMMARY OF BULK SAMPLES TAKEN TO DATE
(determined by Point Count Analysis)
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non Asbestos-Containing Material
Purple = Abated
163 Basement BA 115 OT-09-293-0082 White 2x4 ceiling tile
163 Basement BA 116 OT-09-293-0083 Layer 1 - tan 12x12 floor tile
163 Basement BA 116 OT-09-293-0083 Layer 2 - black mastic
163 Basement CB6 OT-09-293-0084 Layer 1 - tan 9x9 floor tile
163 Basement CB6 OT-09-293-0084 Layer 2 - black mastic
163 Basement CB6 OT-09-293-0085 Black cove molding, brown mastic
163 Basement BA 107 OT-09-293-0086 White 2x2 ceiling tile
163 Basement BA 107 OT-09-293-0087 4" horizontal pipe - yellow insulation, white wrap
163 Basement BA 107 OT-09-293-0088 Gray backing board
163 Basement BA 111 OT-09-293-0089 Gray plaster
163 Basement BA CB1 OT-09-293-0090 Rubber tile 20x20 floor tile, yellow mastic, black mastic
163 Basement BA 201 OT-09-293-0091 White 2x2 ceiling tile
163 Basement BA 214 OT-09-293-0092 5" horizontal pipe - yellow, white wrap
163 Basement BA 228 OT-09-293-0093 Sheetrock, white tape, white mud
163 Basement BA 229 OT-09-293-0094 Yellow linoleum
163 Basement BA 229 OT-09-293-0095 5" vertical pipe - yellow insulation, white wrap
163 Basement BA 229 OT-09-293-0096 Brown cove molding, brown glue
163 Basement BA 112 OT-09-293-0097 5" horizontal pipe - yellow insulation, white wrap
163 Basement BA 112 OT-09-293-0098 Layer 1 - white with blue specks 12x12 floor tile
163 Basement BA 112 OT-09-293-0098 Layer 2 - yellow mastic
163 Basement BA 108 OT-09-293-0099 Layer 1 - brown 12x12 floor tile
163 Basement BA 108 OT-09-293-0099 Layer 2 - black mastic
163 Basement BD 111 OT-09-293-0100 8" horizontal pipe - yellow insulation, white wrap
163 Basement BD 111 OT-09-293-0101 Tank end cap - yellow insulation, white wrap
163 Basement BD 111 OT-09-293-0102 3" elbow - white insulation, white wrap
163 Basement BA 108B OT-09-293-0103 Black gasket, black mastic
163 Basement BA 18B OT-09-293-0104 White plaster
163 Basement BA 108B OT-09-293-0105 12" vertical pipe - pink insulation, white wrap
163 Basement BA 108B OT-09-293-0106 Tank blanket, black insulation
163 crawl crawl OT-09-293-0107 White tape, mud
163 crawl crawl OT-09-293-0108 8" horizontal pipe - yellow insulation, white wrap
163 crawl crawl OT-09-293-0109 7" horizontal pipe - yellow insulation, white wrap
163 crawl crawl OT-09-293-0110 Brown insulation, black mastic
163 crawl crawl OT-09-293-0111 4" horizontal pipe - yellow insulation, white wrap
163 crawl crawl OT-09-293-0112 Layer 1 - 9" elbow - white wrap
163 crawl crawl OT-09-293-0112 Layer 2 - 9" elbow - yellow insulation
163 crawl crawl OT-09-293-0113 4" horizontal pipe - black insulation, white wrap
163 crawl crawl OT-09-293-0114 4" horizontal pipe - yellow insulation, white wrap
163 crawl crawl OT-09-293-0115 4" horizontal pipe - yellow insulation, white wrap
163 Basement crawl OT-09-293-0116 2" horizontal pipe - yellow insulation, white wrap
163 Basement crawl OT-09-293-0117 5" horizontal pipe - black insulation, white wrap
163 Basement crawl OT-09-293-0118 5" elbow - pink insulation, white wrap
163 Basement crawl OT-09-293-0119 7" horizontal pipe - yellow insulation, brown wrap
163 Basement crawl OT-09-293-0120 10" elbow - gray block insulation, white wrap
163 Basement crawl OT-09-293-0121 7" vertical pipe - yellow insulation, white wrap
SUMMARY OF BULK SAMPLES TAKEN TO DATE
(determined by Point Count Analysis)
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non Asbestos-Containing Material
Purple = Abated
163 Basement crawl OT-09-293-0122 7" elbow - yellow insulation, white wrap
163 Basement crawl OT-09-293-0123 2" horizontal pipe - yellow insulation, white wrap
163 Basement crawl OT-09-293-0124 Layer 1 - 2" T - white wrap
163 Basement crawl OT-09-293-0124 Layer 2 - 2" T - yellow insulation
163 Basement crawl OT-09-293-0124 Layer 3 - 2" T - white mud
163 Basement crawl OT-09-293-0125 3" horizontal pipe - yellow insulation, brown wrap
163 Basement crawl OT-09-293-0126 3" T - yellow insulation, white wrap
163 Basement crawl OT-09-293-0127 15" horizontal pipe - gray block, white wrap
163 Basement crawl OT-09-293-0128 Black gasket on 15" pipe
163 Basement BA 109 OT-09-293-0129 White plaster
163 Basement BA 121 OT-09-293-0130 White linoleum
163 Basement South mech OT-09-293-0131 2" vertical pipe - black insulation
163 Basement South mech OT-09-293-0132 Yellow insulation, white wrap
163 1 1D 100 OT-09-293-0133 White 2x4 ceiling tile
163 1 C1-41 OT-09-293-0134 5" horizontal pipe - white insulation, white wrap
163 1 Stair #6 OT-09-293-0135 Tan 12x12 floor tile, black mastic
163 1 1C28 OT-09-293-0136 Yellow insulation, white wrap
163 1 1C28 OT-09-293-0137 5" vertical pipe - yellow insulation, white wrap
163 1 C1 41A OT-09-293-0138 6" horizontal pipe - yellow insulation, white wrap
163 1 1D 105 OT-09-293-0139 Tan 12x12 floor tile, black mastic
163 1 1C39 OT-09-293-0140 Brown cove molding, brown mastic
163 1 Hall OT-09-293-0141 6" horizontal pipe - yellow insulation, white wrap
163 1 1C14 OT-09-293-0142 White tape, white mud
163 1 C121 OT-09-293-0143 White linoleum
163 1 C121 OT-09-293-0144 White linoleum, tan 12x12 floor tile, black mastic
163 1 C121 OT-09-293-0145 Gray linoleum
163 1 1B 159 OT-09-293-0146 White 2x4 ceiling tile
163 1 1B 149 OT-09-293-0147 Gray 12x12 floor tile, yellow mastic
163 1 1B45 OT-09-293-0148 Yellow insulation, white wrap
163 1 1B45 OT-09-293-0149 7" vertical pipe - yellow insulation, white wrap
163 1 1B 152 OT-09-293-0150 Layer 1 - white 9x9 floor tile
163 1 1B 152 OT-09-293-0150 Layer 2 - black mastic
163 1 1B 150 OT-09-293-0151 Brown cove molding, brown mastic
163 1 1B 154 OT-09-293-0152 Layer 1 - white with blue specks 12x12 floor tile
163 1 1B 154 OT-09-293-0152 Layer 2 - black mastic
163 1 1B 154A OT-09-293-0153 White 2x2 ceiling tile
163 1 1B 161C OT-09-293-0154 White 2x2 ceiling tile
163 1 1B 161 OT-09-293-0155 Layer 1 - dark brown 12x12 floor tile
163 1 1B 161 OT-09-293-0155 Layer 2 - yellow mastic
163 1 1B 161 OT-09-293-0155 Layer 3 - black mastic
163 1 C1-54 OT-09-293-0156 3" horizontal pipe - yellow insulation, white wrap
163 1 C1-54 OT-09-293-0157 White 2x4 ceiling tile
163 1 Stair #4 OT-09-293-0158 Tan 12x12 floor tile, yellow mastic
163 1 C1-22 OT-09-293-0159 Layer 1 - tan 12x12 floor tile
163 1 C1-22 OT-09-293-0159 Layer 2 - yellow mastic
SUMMARY OF BULK SAMPLES TAKEN TO DATE
(determined by Point Count Analysis)
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non Asbestos-Containing Material
Purple = Abated
163 1 C1-22 OT-09-293-0159 Layer 3 - black mastic
163 1 1B-79A OT-09-293-0160 Tan 12x12 floor tile, yellow mastic
163 1 1B-79A OT-09-293-0161 Brown cove molding, yellow mastic
163 1 1B-41 OT-09-293-0162 Tan 12x12 floor tile, black mastic
163 1 C1-21 OT-09-293-0163
Tan 12x12 floor tile, yellow mastic, tan 12x12 floor tile, black mastic
163 1 c1-21 OT-09-293-0164 White sheetrock tape, mud
163 1 C1-32 OT-09-293-0165 White sheetrock tape, white mud
163 1 1B-43 OT-09-293-0166 Layer 1 - white 9x9 floor tile
163 1 1B-43 OT-09-293-0166 Layer 2 - black mastic
163 1 1B-22 OT-09-293-0167 White 2x4 ceiling tile
163 1 1B 164 OT-09-293-0168 Layer 1 - white 12x12 floor tile with blue specks
163 1 1B 164 OT-09-293-0168 Layer 2 - black mastic
163 1 1B 164 OT-09-293-0169 White 12x12 ceiling tile, brown glue dots
163 1 1B 167 OT-09-293-0170 White 2x2 ceiling tile
163 2 AP 207 OT-09-293-0171 White plaster
163 2 B150 OT-09-293-0172 Layer 1 - white 9x9 floor tile
163 2 B150 OT-09-293-0172 Layer 2 - black mastic
163 2 B150 OT-09-293-0173 5" vertical pipe - yellow insulation, white wrap
163 2 B150 OT-09-293-0174 5" elbow - yellow insulation, white wrap, white mud
163 2 B150 OT-09-293-0175 Black cove molding, brown mastic
163 1 1B 169 OT-09-293-0176 2" horizontal pipe - yellow insulation, white wrap
163 1 1D 117 OT-09-293-0177 Light tan 12x12 floor tile, yellow mastic
163 1 C1 23 OT-09-293-0178 5" elbow - yellow insulation, white wrap
163 1 C1 23 OT-09-293-0179 5" horizontal pipe - yellow insulation, white wrap
163 1 1A 117 OT-09-293-0180 White 2x2 ceiling tile
163 1 1A 152 OT-09-293-0181 White linoleum
163 1 1D 127 OT-09-293-0182 Gray vibration isolator
163 1 1D 127 OT-09-293-0183 Yellow insulation, white tape, white wrap
163 1 1D 127 OT-09-293-0184 9" horizontal pipe - yellow insulation, white wrap
163 1 1D 127 OT-09-293-0185 8" valve blanket - yellow insulation, white wrap, white mud
163 1 1D 127 OT-09-293-0186
8" valve end cap - yellow insulation, white wrap, white mud
163 1 1B 165 OT-09-293-0187 Yellow insulation, white wrap
163 1 1A 150 OT-09-293-0188 Layer 1 - white 9x9 floor tile
163 1 1A 150 OT-09-293-0188 Layer 2 - black mastic
163 1 C1 26A OT-09-293-0189 Gray 12x12 floor tile, yellow mastic
163 1 1A 119 OT-09-293-0190 Blue linoleum
163 1 1A 140 OT-09-293-0191 Layer 1 - tan 12x12 floor tile
163 1 1A 140 OT-09-293-0191 Layer 2 - black mastic
163 1 South Hall OT-09-293-0192 White 2x4 ceiling tile
163 1 1A 156 OT-09-293-0193 Brown baseboard, yellow mastic
163 1 2 SW Elev OT-09-293-0194 Layer 1 - brown 12x12 floor tile
163 1 2 SW Elev OT-09-293-0194 Layer 2 - yellow mastic
SUMMARY OF BULK SAMPLES TAKEN TO DATE
(determined by Point Count Analysis)
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non Asbestos-Containing Material
Purple = Abated
163 1 1A 153 OT-09-293-0195 White plaster
163 1 Stair 2 OT-09-293-0196 White cloth
163 1 1A 1456 OT-09-293-0197 Light tan 12x12 floor tile, yellow mastic
163 1 1A 598B OT-09-293-0198 Layer 1 - tan 12x12 floor tile
163 1 1A 598B OT-09-293-0198 Layer 2 - black mastic
163 1 1A 598B OT-09-293-0198 Layer 3 - yellow mastic
163 1 1A 154 OT-09-293-0199 5" vertical pipe - yellow insulation, white wrap
163 1 1A 176 OT-09-293-0200 Layer 1 - tan 9x9 floor tile
163 1 1A 176 OT-09-293-0200 Layer 2 - black mastic
163 1 C1 27 OT-09-293-0201 Tan 12x12 floor tile, black mastic
163 2 AP 208 OT-09-293-0202 12" vertical pipe - yellow insulation, white wrap
163 2 AP 208 OT-09-293-0203 13" valve cap - yellow insulation, white wrap, white mud
163 2 AP 208 OT-09-293-0204 24" vertical pipe - yellow insulation, white wrap
163 1 Roof Roof OT-09-293-0205 Yellow insulation, silver wrap, black backing
163 1 Roof Roof OT-09-293-0206 Yellow insulation, white wrap, white mud
163 1 Roof Roof OT-09-293-0207 Black roofing tar
163 1 Roof Roof OT-09-293-0208 Yellow insulation, white wrap, white tape
163 2 2C 117 OT-09-293-0209 2" vertical pipe - yellow insulation, white wrap
163 2 2C 117 OT-09-293-0210 5" horizontal pipe - yellow insulation, white wrap
163 2 2C 117 OT-09-293-0211 Yellow insulation, white mud
163 2 AP 208 OT-09-293-0212 1" horizontal pipe - black tape, black mastic
163 2 C2-2 OT-09-293-0213 White sheetrock, white tape, white mud
163 2 C2-2 OT-09-293-0214 White 2x4 ceiling tile
163 2 C2-2 OT-09-293-0215 Layer 1 - tan 12x12 floor tile
163 2 C2-2 OT-09-293-0215 Layer 2 - black mastic
163 2 2B 154B OT-09-293-0216 2" horizontal pipe - yellow insulation, white wrap
163 2 2B 147 OT-09-293-0217 4" horizontal pipe - yellow insulation, white wrap
163 2 2B 142 OT-09-293-0218 2" T - yellow insulation, white wrap
163 2 C2-1 OT-09-293-0219 Layer 1 - tan 12x12 floor tile, black mastic
163 2 C2-1 OT-09-293-0219 Layer 2 - black mastic
163 2 C2-1 OT-09-293-0220 Brown cove molding, brown mastic
163 2 C2-1 OT-09-293-0221 Yellow mastic, tan 12x12 floor tile, black mastic
163 2 C2-1 OT-09-293-0222
4" horizontal pipe - white wrap, yellow insulation, white mastic
163 2 C2 28A OT-09-293-0223 Gray spray on
163 2 C2-28 OT-09-293-0224 Sheetrock, white tape, white mud
163 2 C2-28 OT-09-293-0225 White 2x4 ceiling tile
163 2 2A 128 OT-09-293-0226 3" vertical pipe - yellow insulation, white wrap
163 2 2A 128 OT-09-293-0227 Yellow insulation, white wrap
163 2 2A 123 OT-09-293-0228 Layer 1 - white 9x9 floor tile
163 2 2A 123 OT-09-293-0228 Layer 2 - black mastic
163 2 2B 149 OT-09-293-0229 Layer 1- white 9x9 floor tile
163 2 2B 149 OT-09-293-0229 Layer 2 - black mastic
163 2 2B 149 OT-09-293-0230 Layer 1 - brown baseboard
163 2 2B 149 OT-09-293-0230 Layer 2 - brown mastic
SUMMARY OF BULK SAMPLES TAKEN TO DATE
(determined by Point Count Analysis)
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non Asbestos-Containing Material
Purple = Abated
163 2 2B 149 OT-09-293-0230 Layer 3 - white joint compound
163 5 568 OT-09-293-0231 Light tan 12x12 floor tile, yellow mastic
163 5 542 OT-09-293-0232 5" horizontal pipe - yellow insulation, white wrap
163 5 561 OT-09-293-0233 Light tan 12x12 floor tile, yellow mastic
163 2 2C 39 OT-09-293-0234 Tan 12x12 floor tile, yellow mastic
163 2 2B 143 OT-09-293-0235 3" horizontal pipe - yellow insulation, white wrap
163 2 2B 143 OT-09-293-0236 3" vertical pipe - yellow insulation, white wrap
163 2 2B 144 OT-09-293-0237 White sheetrock, white tape, white mud
163 5 520 OT-09-293-0238 Layer 1 - tan 12x12 floor tile
163 5 520 OT-09-293-0238 Layer 2 - yellow mastic
163 5 C501 OT-09-293-0239 White 2x4 ceiling tile
163 5 554 OT-09-293-0240 White 2x4 ceiling tile
163 5 Roof Roof OT-09-293-0241 White tape, mud
163 Roof Mech Room OT-09-293-0242 White wrap, brown wrap, yellow insulation
163 Roof Mech Rm B OT-09-293-0243 Black vibration isolator
163 Roof Mech Rm A OT-09-293-0244 White block insulation, white wrap
163 Roof Mech Rm A OT-09-293-0245 1" vertical pipe - black wrap, black mastic
163 Roof Mech Rm A OT-09-293-0246 7" horizontal pipe - yellow insulation, white wrap
163 Roof Mech Rm A OT-09-293-0247 3" horizontal pipe - yellow insulation, white wrap
163 Roof Mech Rm A OT-09-293-0248 5" valve - yellow insulation, white wrap
163 Roof Mech Rm A OT-09-293-0249 White block insulation, white wrap
163 Roof Mech Rm A OT-09-293-0250 White block insulation, white wrap
163 4 Svc Elev OT-09-293-0285 White 2x2 ceiling tile
163 4 Svc Elev OT-09-293-0286 Blue 12x12 floor tile, yellow mastic
163 4 457 OT-09-293-0287 Tan 12x12 floor tile, yellow mastic
163 4 C-4-5 OT-09-293-0288 Layer 1 - green 12x12 floor tile
163 4 C-4-5 OT-09-293-0288 Layer 2 - yellow mastic
163 4 C-4-5 OT-09-293-0288 Layer 3 - black mastic
163 4 C-4-4 OT-09-293-0289 3" vertical pipe - yellow insulation, white wrap
163 4 426 OT-09-293-0290 Tan 12x12 floor tile, yellow mastic
163 4 427 OT-09-293-0291 White 2x2 ceiling tile
163 4 427 OT-09-293-0292 1" vertical pipe - black insulation, black mastic
163 4 437 OT-09-293-0293 Layer 1 - dark pink 12x12 floor tile
163 4 437 OT-09-293-0293 Layer 2 - yellow mastic
163 4 Hall OT-09-293-0294 White sheetrock, white tape, mud
163 4 C-4-8 OT-09-293-0295 3" vertical pipe - yellow insulation, white wrap
163 4 Fire OT-09-293-0296 Green 12x12 floor tile, yellow mastic
163 4 421 OT-09-293-0297 Layer 1- dark brown 12x12 floor tile
163 4 421 OT-09-293-0297 Layer 2 - yellow mastic
163 4 404 OT-09-293-0298 Dark brown 12x12 floor tile, yellow mastic
163 4 459 OT-09-293-0299 White duct insulation
163 4 459 OT-09-293-0300 White 2x2 ceiling tile
163 3 318 OT-09-293-0801 Tan 12x12 floor tile, yellow mastic
163 3 North Hall OT-09-293-0802 Pink 12x12 floor tile, yellow mastic
163 3 359 OT-09-293-0803 Brown 12x12 floor tile, yellow mastic
SUMMARY OF BULK SAMPLES TAKEN TO DATE
(determined by Point Count Analysis)
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non Asbestos-Containing Material
Purple = Abated
163 3 320 OT-09-293-0804 2" horizontal pipe - yellow insulation, white wrap
163 3 320 OT-09-293-0805 Layer 1 - 2" elbow - white wrap
163 3 320 OT-09-293-0805 Layer 2 - 2" elbow - white block insulation
163 3 320 OT-09-293-0806 White 2x4 ceiling tile
163 3 324 OT-09-293-0807 2" horizontal pipe - yellow insulation, white wrap
163 3 324 OT-09-293-0808 Layer 1 - 2" elbow - white wrap
163 3 324 OT-09-293-0808 Layer 2 - 2" elbow - white block insulation
163 3 Fire OT-09-293-0809 Pink 12x12 floor tile, yellow mastic
163 3 Fire OT-09-293-0810 Gray cove molding, brown mastic
163 3 326D OT-09-293-0811 1" vertical pipe - black tape, mastic
163 3 308 OT-09-293-0812 Brown 12x12 floor tile, yellow mastic
163 3 330 OT-09-293-0813 White 2x2 ceiling tile
163 3 329B OT-09-293-0814 1" valve - black insulation
163 3 331 OT-09-293-0815 Brown linoleum, gray backing
163 3 341B OT-09-293-0816 1" horizontal pipe - black insulation
163 3 344 OT-09-293-0817 White sheetrock, white sheetrock tape, mud
163 3 344 OT-09-293-0818 White 2x4 ceiling tile
163 3 358A OT-09-293-0819 5" horizontal pipe - yellow insulation, white wrap
163 Basement BA 220 OT-09-293-0820 Tan 12x12 floor tile, black mastic
163 2 2D 105 OT-09-293-0831 5" horizontal pipe - yellow insulation, white wrap
163 2 2 North OT-09-293-0832 White 2x4 ceiling tile
163 Basement BB 112 OT-09-293-0833 White 2x4 ceiling tile
163 Basement BB 1121 OT-09-293-0834 2" horizontal pipe - yellow insulation, white wrap
163 Basement BA 108B OT-09-293-1101 1" vertical pipe - black insulation, black mastic
163 Basement BD116B TE-12-353-013 Brown flange gasket
ASBESTOS-CONTAINING BULK SAMPLES
LIST OF ASBESTOS-CONTAINING SAMPLES
Building Floor Room Sample ID Material Description
163 Basement BB 128 OT-09-293-0022 Layer 1 - white 9x9 floor tile
163 Basement BB 128 OT-09-293-0022 Layer 2 - black mastic
163 Basement BA 18B OT-09-293-0104 White plaster
163 Basement crawl OT-09-293-0120 10" elbow - gray block insulation, white wrap
163 Basement crawl OT-09-293-0124 Layer 3 - 2" T - white mud
163 Basement crawl OT-09-293-0128 Black gasket on 15" pipe
163 1 1B 152 OT-09-293-0150 Layer 2 - black mastic
163 1 1B 154 OT-09-293-0152 Layer 1 - white with blue specks 12x12 floor tile
163 1 1B 154 OT-09-293-0152 Layer 2 - black mastic
163 1 1B-43 OT-09-293-0166 Layer 2 - black mastic
163 1 1B 164 OT-09-293-0168 Layer 1 - white 12x12 floor tile with blue specks
163 1 1B 164 OT-09-293-0168 Layer 2 - black mastic
163 2 B150 OT-09-293-0172 Layer 2 - black mastic
163 1 1A 150 OT-09-293-0188 Layer 2 - black mastic
163 1 1A 176 OT-09-293-0200 Layer 2 - black mastic
163 2 C2-2 OT-09-293-0215 Layer 2 - black mastic
163 2 C2-1 OT-09-293-0219 Layer 2 - black mastic
163 2 2A 123 OT-09-293-0228 Layer 1 - white 9x9 floor tile
163 2 2A 123 OT-09-293-0228 Layer 2 - black mastic
163 2 2B 149 OT-09-293-0229 Layer 1- white 9x9 floor tile
163 2 2B 149 OT-09-293-0229 Layer 2 - black mastic
163 Roof Mech Rm A OT-09-293-0244 White block insulation, white wrap
163 Roof Mech Rm A OT-09-293-0249 White block insulation, white wrap
163 Roof Mech Rm A OT-09-293-0250 White block insulation, white wrap
163 3 341B OT-09-293-0816 1" horizontal pipe - black insulation
163 Basement BD116B TE-12-353-013 Brown flange gasket
Red = Asbestos-Containing Material (ACM)
2012 REINSPECTION INSPECTION LOG
Client: Date: January 10, 2013
Location: Inspector(s): Jerry Heidecker & Rodney Lewis
1901 Veterans Memorial Drive, Temple, Texas
Building: 163
Note: Red = Asbestos-Containing Material Blue = Non Asbestos-Containing Material Green = Non Asbestos-Containing Material
(determined by Point Count analysis)
Sample ID Material Description Material
Category Friability Condition Location
Asbestos
% Type
TE-12-353-013 Brown flange gasket M NF 8 Southeast quadrant of emergency generator, room BD116B
15% chrysotile
Material Category: T=TSI S=Surfacing M=Miscellaneous Friability: F=Friable NF=Non-Friable Condition: Good = 8, 9, 10 Fair = 4, 5, 6, 7 Poor = 1, 2, 3
GOOD = Surfacing material has no visible damage or small amounts of damage; covering on thermal system insulation is intact or has small amounts of damage; miscellaneous materials intact; no visible debris or small amounts of debris. FAIR = Surfacing material has moderate but not extensive amounts of visible damage; covering on thermal system insulation is cut or torn, exposing moderate but not extensive amounts of insulation; moderate but not extensive damage to miscellaneous materials such as floor tile; moderate but not extensive amounts of visible dust and debris. POOR = Extensive damage to surfacing material; covering on thermal system insulation is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile extensively damaged and underlying mastic exposed; extensive amounts of dust and debris.
Central Texas Veterans Health Care System
Olin E. Teague V.A. Medical Center
ASBESTOS INSPECTION LOG
ND=None Detected NA=Not AnalyzedPlease use the following guidelines when reading this report:
BULK SAMPLE LOCATION DRAWINGS
Third Floor
Fourth Floor
Fifth Floor
Roof
2012 REINSPECTION PHOTOGRAPHS
OLIN E. TEAGUE VA MEDICAL CENTER - BUILDING 163
TEMPLE, TEXAS
JANUARY 10, 2013
sample contains asbestos sample does not contain asbestos non-asbestos containing material determined by point count analysis
TE-12-353-013
2012 REINSPECTION LABORATORY REPORTS
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077
Phone/Fax: (800) 220-3675 / (856) 786-5974 http://www.emsl.com cinnasblab@EMSL.com
041300731
CustomerID: ALT50
CustomerPO:
ProjectID:
EMSL Order:
Attn: Dave Hopper
ALTEC Environmental Consultants, Inc.
10100 Woolworth Road
Keithville, LA 71047
Received: 01/11/13 10:00 AM
18708/ OLIN E. TEAGUE VA MEDICAL CENTER- 2012 RE-INSPECTION/ DEPARTMENT OF VETERAN AFFAIRS/ BLDG #163
Fax: (318) 687-9923
Phone: (318) 687-3771
Project:
1/11/2013Analysis Date:
1/10/2013Collected:
Sample Description Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 and/or EPA
600/M4-82-020 Method(s) using Polarized Light Microscopy
TE-12-353-013
041300731-0001
SE QUAD OF
EMERGENCY
ROOM #B01KB,
BLDG #163 -
BROWN
FLANGE GASKET
Tan/White/Red
Fibrous
Heterogeneous
Chrysotile15%Non-fibrous (other)85%
1THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.16.0 Printed: 1/11/2013 4:44:01 PM
Stephen Siegel, CIH, Laboratory Manager or other approved signatory
Analyst(s)
EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Reporting limit is 1%
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA-LAP, LLC-IHLAP Lab 100194, NYS ELAP 10872, NJ DEP 03036
Initial report from 01/11/2013 16:44:01
William Nguyen (1) http://www.emsl.com mailto:cinnasblab@EMSL.com
CERTIFICATIONS
z— r C
I
C pc)
C l)
‘-4 0.)
4-4
I
•—•—E•—re-i
Z r:—
L c t c c o
I c r
CC
C
4-4 0)0)Cz
0.)
C l)
CQ00)
Jerald Heidecker
3I166471
9/12/2012
166471
9/25/2013
ASBESTOS INSPECTOR
CB
C I
0 CD
Z
J
Z —
CD
‘e
CD
P w
— o O
C cm C CD
C
C L i fl o
CD 0
David Hopper
3I134762
2/3/2012
134762
2/14/2013
SG
Donald R Joiner
3I112937
9/12/2012
112937
9/29/2013
Professional Environmental Training
Occupational and Environmental Training Program
Awards this Certificate to
BRADLEY W. KENNON
Certificate No. TL-0993
For completion of the
3-HOUR COURSE
TEXAS ASBESTOS HEALTH PROTECTION ACT
November 3, 2012 9001 Airport Blvd., Suite 510
Houston, Texas 77061
713-921-8921
P sident, Fredy Polanco, M.S.
Instructor, Philip
Date of Course www.proenvtraining.com
Bradley Kennon
3I182667
8/16/2012
182667
8/1/2013
0 cm 0 c l Ct
C C
C t
O o S C
Lte •
C
0 I
. S — v s L
D
Rodney Lewis
3I169456
2/3/2012
169456
3/3/2013
SG
Robert B Raines III
3P103065
8/21/2012
103065
8/5/2013
ASBESTOS MANAGEMENT PLANNER
TEMPLE VA MEDICAL CENTER
6-MONTH ASBESTOS SURVEILLANCE
BUILDING 163
HMA Material Description Location Friable
Yes/No
Conditions at Last
Inspection1
Damage
Severity2
Conditions at Current
Inspection1
Comments
HMA-03
Pipe Insulation and
Fittings
South
HMA-04 Gaskets
South
HMA-01
9x9 Floor Tile and
Mastic
Central
HMA-06 Fire Doors
Central
Mastic Basement South Abated as of 2012 Reinspection
HMA-02
12x12 Floor Tile and
Mastic Basement South Abated as of 2012 Reinspection
HMA-05
Air Handling Unit
Blanket Basement South
HMA-06 Fire Doors Basement South
HMA-08 Flange Gasket Basement South
HMA-01
9x9 Floor Tile and
Mastic
Northeast
HMA-02
12x12 Floor Tile and
Mastic
Mastic
Northwest
Northwest
Mastic
Southeast
Mastic
HMA Material Description Location Friable
Yes/No
Conditions at Last
Inspection1
Damage
Severity2
Conditions at Current
Inspection1
Comments
HMA-01
9x9 Floor Tile and
Mastic
Southwest
HMA-06 Fire Doors First Floor West
North
Mastic
Mastic
Mastic
HMA-03
Pipe Insulation and
Fittings Third Floor
HMA-06 Fire Doors Third Floor
HMA-03
Pipe Insulation and
Fittings Fourth Floor
HMA-06 Fire Doors Fourth Floor
HMA-06 Fire Doors Fifth Floor
HMA-05
Air Handling Unit
Blanket
Fifth Floor-Roof
Mechanical Rm.
Conditions: G=Good R=Repaired D=Damaged SD= Significantly Damaged
Damage Severity: M=Minor O=Occasional X-Extensive P=Punctures N=None
Printed Competent Person’s Name
Asbestos Inspector Certification Number and Expiration Date
Signature
Surveillance Inspection Date
File details come from the government source that posted it. Updated .