Technical Questions and Answers.pdf
PDF 71 KB Posted
- Attached to
- N041--Variable Refrigerant Flow (VRF) Air Condition Units Federal contract opportunity
- Solicitation number
- 36C25724Q0193
About this file
This document contains a request for quote for the procurement and installation of two variable refrigerant flow air conditioning units. The Department of Veterans Affairs Network Contracting Office 17 is soliciting offers for a firm-fixed price contract as a Service-Disabled Veteran Owned Small Business set-aside. Offerors must be registered in the System for Award Management and proposals will be evaluated based on technical capability, past performance, and price in descending order of importance. A site visit is scheduled for January 16, 2024 and technical questions must be submitted by email no later than January 18, 2024. The selected contractor will provide all labor, materials, equipment, transportation, and supervision to install two 5-ton VRF units with one indoor and one outdoor unit each for the hospital's main telephone room in accordance with federal, state, and local regulations.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit Sign - In Sheet 01-16-2024.pdf | ||
| 36C25724Q0193 0001.pdf | ||
| Attachment 1 - Service Contract Act WD 2015-5237.pdf | ||
| 36C25724Q0193.pdf | ||
| 36C25724Q0193_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Questions and Answers
Request for Quote (RFQ) 36C25724Q0193
AC Unit Replacement
1. Is this project Tax Exempt?
Answer: Yes, the Federal Government is Tax exempt
2. Will Quick Sling Stands be acceptable for the condensers?
Answer: I’m told that they can provide this as an option but not preferred.
3. Will PVC be acceptable for the drain-off unit?
Answer: No, must be copper
4. Will a separate disconnect be required off of the indoor unit?
Answer: Yes, a separate disconnect is required
5. Does the drain need to be pumped or gravity-fed off of the indoor unit?
Answer: No, Gravity Feed is fine.