Submittal 28 31 00 PD2 00 Fire Alarm Product Data.pdf

PDF 8 MB Posted

Attached to
Y1DA--674-22-801 Upgrade Fire Alarm System Phase 2 Federal contract opportunity
Solicitation number
36C25722B0021
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17

About this file

This federal solicitation is for upgrading the fire alarm system at the Temple VA medical center in Temple, Texas. The project number is 674-22-801. The solicitation is seeking proposals to replace the existing fire alarm system with a new addressable fire alarm system that meets all current codes and standards. Proposals are due by a specified date. The awarded contract will have a one year period of performance. The work will be conducted through the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--674-22-801 Upgrade Fire Alarm System Phase 2, newest first.
File Type Posted
36C25722B0021 0012.docx DOCX document
Temple Fire Alarm Phase II - Addendum 002.pdf PDF
Building 202 with existing mechanical drawings.pdf PDF
163 Mechanical drawings.pdf PDF
2nd set of RFIs 36C25722B0021 Upgrade Fire Alarm System.docx DOCX document
36C25722B0021 0011.docx DOCX document
204 Mechanical Drawings.pdf PDF
36C25722B0021 0010.docx DOCX document
36C25722B0021 0009.docx DOCX document
36C25722B0021 0008.docx DOCX document
36C25722B0021 0007.docx DOCX document
Sign in sheet for 2nd Site visit .pdf PDF
36C25722B0021 0006.docx DOCX document
RFIs 36C25722B0001 Upgrade Fire Alarm System Phase 2.docx DOCX document
Temple Phase II Addendum 1 Summary.doc DOC document
Responses RFI Upgrade Fire Alarm System Phase 2.docx DOCX document
VA TEM FA ADDENDUM 1 Drawings Phase 2 signed.pdf PDF
VA TEM FA ADDENDUM 1 Specifications Phase 2.pdf PDF
Submittal 28 31 00 PD 00 Fire Alarm Product Data.pdf PDF
Professional Seals FPE signed.pdf PDF
VA TEM FA ADDENDUM 1 Narrative Phase 2.pdf PDF
36C25722B0021 0005.docx DOCX document
36C25722B0021 0004.docx DOCX document
36C25722B0021 0003.docx DOCX document
36C25722B0021 0002.docx DOCX document
36C25722B0021 0001.docx DOCX document
VA TEMPLE PHASE II - DESIGN NARRATIVE_01.pdf PDF
VA TEMPLE PHASE II - BID SET SPECS_SIGNED_01.pdf PDF
VA TEMPLE PHASE II - BID SET SUBMISSION_SIGNED_01.pdf PDF
36C25722B0021_1.docx DOCX document
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Submittal Detailed with Comments and Links

28 31 00

PD2-00

22105 SBC Replace Fire Alarm - Temple, Texas (1)

28 31 00 PD2 - Fire Alarm Product Data

Subject Fire Alarm Product Data

Status Submitted n

Spec Section

28 31 00 - Fire Detection and Alarm

Submittal Package

Responsible Company

Department of Veteran Affairs - Temple

Spec Sub Section

Product Data

Type

Manufacturer's Data

Location

Project

Importance

Urgent

Author

Southern Building Company

Jack Robinson

Resolved By

DESCRIPTION Jack Robinson on 11/1/2022 10:29 AM

Please review & Comment

DOCUMENTS FOR REVIEW Jack Robinson on 11/1/2022 10:31 AM

File

Temple VA Fire Al...

Jack Robinson

Page 1 of 1Printed on: 11/1/2022ProjectSight https://prod.projectsightapp.trimble.com/web/FileLibrary.aspx?orgid=80e32d47-4f2f-4ed7-b467-f1f351c902e0&projid=5&Req=file&nomsg=1&sharelink=1&Key=1850

EDWARDS® Catalog u Power Supplies and Accessories

L I F E S A F E T Y & I N C I D E N T M A N A G E M E N T

12.03.20 Page 1 of 2 D A T A S H E E T E85010-0127

Not to be used for installation purposes. Issue 1.3

Sealed Lead-Acid Batteries

Overview Rechargeable sealed lead-acid batteries are ideal for use as a secondary (standby) power source as defined by NFPA 72. Their low maintenance and high energy density make them ideal for fire alarm signaling applications.

Standard Features

• Rechargeable

• Non-spillable

• Non-hazardous

• Low maintenance

• High energy density

Application When multiple power supplies are provided, each power supply’s battery requirements should be calculated individually. Consult the specific system manual to determine battery capacity require-ments.

Safety Information Due to a battery’s low internal resistance and high power density, high levels of short circuit current can develop across battery terminals. Put on protective eye covering and remove all jewelry before working on batteries. Do not rest tools or cables on the battery, and only use insulated tools. Follow all manufacturers installation instructions and diagrams when installing or maintaining batteries.

Temple VA Fire Alarm Data Sheets - Part Two[1].pdf

LIFE SAFETY & INCIDENT MANAGEMENT

Contact us

Phone: 800-655-4497 (Option 4) Email: edwards.fire@carrier.com Website: edwardsfiresafety.com

8985 Town Center Pkwy Bradenton, FL 34202

© 2020 Carrier All rights reserved.

12.03.20Page 2 of 2 D A T A S H E E T E85010-0127 Not to be used for installation purposes. Issue 1.3

Ordering Information

Specifications Case Material ABS Thermoplastic Regulatory Information DOT Class 60, Batteries, non-hazardous, non-spillable Operating Environment 32° F to 120° F (0° C to 49° C) 0 to 93% RH, Non-condensing

Catalog # Description Shipping Weight, lb (kg) Terminal 12V4A 4.5 Ah Sealed Lead Acid Battery - 12 Vdc 5 (2.27) T1/T2 12V6A5 7.6 Ah Sealed Lead Acid Battery - 12 Vdc 6 (2.72) T1/T2 12V10A 10.5 Ah Sealed Lead Acid Battery - 12 Vdc 10 (4.45) T2 12V17A 18 Ah Sealed Lead Acid Battery - 12 Vdc 13 (5.90) T3 12V24A 26 Ah Sealed Lead Acid Battery - 12 Vdc 20 (9.07) T10/M5 12V40A 40 Ah Sealed Lead Acid Battery - 12 Vdc 32 (14.51) T6/M6 12V50A 50 Ah Sealed Lead Acid Battery - 12 Vdc 40 (18.14) T6/M6 12V65A 65 Ah Sealed Lead Acid Battery - 12 Vdc 49 (22.23) T6/M6

Temple VA Fire Alarm Data Sheets - Part Two[1].pdf frontdesk Highlight frontdesk Highlight frontdesk Highlight frontdesk Highlight

Page 1 of 8 D A T A S H E E T E85014-0003 Not to be used for installation purposes. Issue 2.2

06-24-20

L I F E S A F E T Y & I N C I D E N T M A N A G E M E N T

7120-1657:

Overview EST4 Remote Annunciators provide front panel system status and control functions located conveniently anywhere on the EST4 network. Annunciators can be as simple as a couple of LED indicator strips, or complex enough to support up to two LCD displays, an audio telephone interface, and hundreds of control points and indicators — all in a single enclosure.

Up to 576 tactile switches and 576 LED indicators may be mounted in a single EST4 annunciator cabinet. Control Display Modules (CDMs), comprise a column of programmable buttons accompanied by one or two LED indicator positions per button.

Indicator-only modules hold up to 24 indicators. Switch and indicator module LEDs can be set to any of five colors, providing an additional level of feedback.

All remote annunciators feature color-matched cabinets and distinctive metallic bronze (Pantone Coated PMS# P 171-16 C, Pantone RGB# 81 75 67, and RAL Classic/RAL Design# 7022) doors for a readily-identifiable and consistent look throughout the facility.

Thanks to EST4's ingenious communications protocol, network data — as well as telephone and audio data — is carried on a single fiber optic cable or twisted wire pair. This multi-use capacity has an enormous cost-savings potential compared with conventional audio transmission, reducing not only installation costs, but also simplifying ongoing system maintenance.

Slide-in LED and switch labeling makes it easy to incorporate right into the annunciator design such information aids as descriptive text, color-coding, icons, and local languages. For custom floorplans or facility maps, EST4 offers LED driver boards perfectly suited to operate in most graphic annunciators.

EST4 Remote Annunciators 4-xxANN Series

Standard Features

• Connection Over High-speed Life Safety Network

Annunciator network and audio data carried on a single fiber or twisted pair.

• Optional Color LCD Display Touch screen capability supplements control buttons for quick, intuitive access to key system status and control functions.

• Wide Range of Annunciator Configurations From a two-slot model holding a single LCD display to 24-slot cabinets for complex annunciation.

• Supports Two LCD Displays Providing users with a simplified sequence of operations.

• Convenient Programming Built-in support for radio groups of up to 24 switches in size.

• Slide-in Switch and Indicator Labels A simple, effective means to customize annunciator appearance and messaging.

• Programmable LED Flash Rates and Colors Easy to see, quick to understand.

• Clean and robust door designs

• Support for all Common Networking Media Annunciators connect over any combination of twisted pair wire, Multi-mode fiber, Single Mode fiber, and even CAT5 cable.

4-2ANN and 4-4ANN shown with optional equipment.

Page 2 of 8 D A T A S H E E T E85014-0003

Application Use EST4 remote annunciators where a compact system status display is needed. Annunciator configuration can range from a couple of LED indicator strips, to complex arrangements supporting in a single enclosure up to two LCD displays, paging microphone, firefighter telephone and hundreds of control points and indicators.

EST4 annunciators support a range of options that make them ideal for Mass Notification, Life Safety and other emergency communications purposes. They can be used as Central Control Stations (CCS), Autonomous Control Units (ACU), Local Operating Console (LOC), and combination units from which initiated Mass Notifica tion functions can be controlled.

Cabinets may be surface or semi-flush mounted for installation expediency and aesthetic appeal.

Annunciators connect over the high-speed EST4 network, which supports copper or fiber-optic communications in any combination. Network data and audio data share the same cabling. This results in more efficient deployment with fewer cables needed and fewer connections to be made.

The 2 wide, 4 wide, and 6 wide, 4-xANNMT series, annunciator wallboxes come standard with surface mounting trims and semi-flush mounting trims.

The 8 space, 16 space and 24 space 4-xxANNMT series wallboxes are designed for surface mount applications. Their depth is kept to a minimum to allow the least amount of room penetration. When semi-flush mounting is required, order the standard 3-CAB5B, 7B, or 14B wallbox.

4-2ANNMT, 4-4ANNMT, and 4-6ANNMT included side trim installation for surface mount applications

Installation and Mounting

Side Trim

4-2ANNMT

Side Trim

4-2ANNMT, 4-4ANNMT, and 4-6ANNMT included trim installation for semi-flush mount applications

Bottom Trim

Top Trim

4-2ANNMT

Engineering Specification The Life Safety system shall incorporate annunciation of Alarm, Supervisory, Trouble and Monitor operations. Annunciation must be through the use of both LED display strips complete with a means to custom label each LED as to its function. LED color shall be selectable at configuration time. Where applicable control switches must be provided. Switches with LEDs must provide positive feed back to the operator of remote equipment status. A color touchscreen LCD display with basic common control LEDs and switches shall be provided. Optionally a second color touchscreen display may be added to support audio and telephone operations. The Common Control Switches and LEDs provided as minimum will be: Reset switch and LED, Alarm Silence switch and LED, Panel Silence switch and LED, Drill switch and LED. It must be possible to add additional common controls as required through the use of modular display / control units. The LCD must provide the emergency user, hands free viewing of the first highest priority event. System events must automatically be placed in queues. It shall be possible to view specific event types separately. The total number of active events by type must be displayed. It must be possible to customize the designations of all user interface LEDs and switches for local language requirements.

It must be possible to route system event messages to specific annunciator locations. It must be possible for the annunciator to contain a paging microphone and fire fighter telephone.

See Specifications Table for 4-8ANNMT, 4-16ANNMT, 4-24ANNMT mounting options.

Page 3 of 8 D A T A S H E E T E85014-0003

Dimensions, wallboxes

14.27 in.

36.25 cm

2.67 in.

6.78 cm

14.35 in.

36.45 cm

13.12 in.

33.32 cm

12.73 in.

32.33 cm

14.35 in.

36.45 cm

13.72 in.

34.85 cm

13.20 in.

33.53 cm

2.22 in.

5.64 cm

(1) (2)

2.20 in.

5.08 cm

13.20 in.

33.53 cm

13.72 in.

34.85 cm

17.14 in.

43.54 cm

2.20 in.

5.08 cm

18.76 in.

47.65 cm

2.20 in.

5.08 cm

18.68 in.

47.45 cm

18.76 in.

47.65 cm

13.20 in.

33.53 cm

2.67 in.

6.78 cm

(1) (2)

8.31in.

(21.11 cm)

9.93 in.

25.22 cm

13.20 in.

33.53 cm

13.72 in.

34.85 cm

2.20 in.

5.08 cm

2.20 in.

5.08 cm

9.93 in.

25.22 cm

9.86 in.

25.04 cm

2.26 in.

5.74 cm

(1) (2)

13.20 in.

33.53 cm

4-2ANNMT Wallbox Assembly, Surface and Semi-flush Mounting (both trims are included)

4-4ANNMT Wallbox Assembly, Surface and Semi-flush Mounting (both trims are included)

4-6ANNMT Wallbox Assembly, Surface and Semi-flush Mounting (both trims are included)

Semi-flush mount (trim installed top and bottom) Surface mount (trim installed right and left sides)

Semi-flush mount (trim installed top and bottom) Surface mount (trim installed right and left sides)

Semi-flush mount (trim installed top and bottom) Surface mount (trim installed right and left sides)

Page 4 of 8 D A T A S H E E T E85014-0003

2.28 in.

5.79 cm

26.37 in.

66.98 cm

25.25 in.

64.14 cm

2.28 in.

5.79 cm

23.87 in.

60.63 cm

2.26 in.

5.74 cm

17.00 in.

43.18 cm 3.56 in.

9.04 cm

Dimensions, wallboxes

4-8ANNMT Wallbox Assembly, Surface Mount For semi-flush mounting, use a 3-CAB5B wallbox.

4-24ANNMT Wallbox Assembly, Surface Mount For semi-flush mounting, use a 3-CAB14B wallbox.

4-16ANNMT Wallbox Assembly, Surface Mount For semi-flush mounting, use a 3-CAB7B wallbox.

Dimensions, door assemblies

8.31 in. 2.20 in.

10.18 in.

(25.86 cm)

(21.10 cm) (5.58 cm)

2.02 in.

(5.13 cm)

13.20 in.

(33.53 cm)

13.12 in.

(33.32 cm)

13.72 in.

(34.85 cm)

8.31 in. 2.20 in.

10.18 in.

(25.86 cm)

(21.10 cm) (5.58 cm)

2.02 in.

(5.13 cm)

13.20 in.

(33.53 cm)

13.12 in.

(33.32 cm)

13.72 in.

(34.85 cm)

4-2ANN Series Door Assembly 4-4ANN Series Door Assembly

12.72 in.

14.60 in.

(37.08 cm)

(32.31 cm)

2.20 in.

(5.60 cm)

2.73 in.

(6.93 cm)

13.20 in.

(33.53 cm)

13.12 in.

(33.32 cm)

13.72 in.

(34.85 cm)

12.72 in.

14.60 in.

(37.08 cm)

(32.31 cm)

2.20 in.

(5.60 cm)

2.73 in.

(6.93 cm)

13.20 in.

(33.53 cm)

13.12 in.

(33.32 cm)

13.72 in.

(34.85 cm)

Page 5 of 8 D A T A S H E E T E85014-0003

Wiring

Dimensions, door assemblies continued

24.19 in.

4.03 in. 3.86 in.

(9.80 cm)(10.24 cm)

(44.53 cm)

17.53 in.

(61.44 cm)

6.22 in.

(15.80 cm)

4-CAB8D installed on a 3-CAB5B wallbox.

Can be surface mounted or semiflush mounted.

4-CAB8D installed on a 4-8ANNMT wallbox.

Can be surface mounted only

4-CAB8D Series Door Assembly

4-CAB16D Series Door Assembly

25.52 in.

3.82 in.

(9.70 cm)

3.93 in.

(9.98 cm)

27.64 in.

(70.20 cm)

(70.20 cm)

6.03 in.

(25.32 cm)

4-CAB16D installed on a 3-CAB7B wallbox.

Can be surface mounted or simi-flush mounted.

4-CAB16D installed on a 4-16ANNMT wallbox.

Can be surface mounted only.

37.77 in.

3.82 in. 3.93 in.

27.64 in.

(70.20 cm)

(19.73 cm)

(9.70 cm) (9.98 cm)

6.01 in.

(15.27 cm)

4-CAB24D Series Door Assembly

4-CAB24D installed on a 3-CAB14B wallbox.

Can be surface mounted or simi-flush mounted.

4-CAB24D installed on a 4-24ANNMT wallbox.

Can be surface mounted only.

Supports any combination of SFP network controllers

From previous SFP. Use appropriate SFP network controller to match installed cable

To next SFP. Use appropriate SFP network controller to match installed cable

Optional redundant 24 Vdc

UL listed power supply, 24 Vdc eth1eth0

4-6ANN Series Door Assembly

13.20 in.

13.12 in.

(33.32 cm)

17.13 in.

19.01 in.

(48.28 cm)

(43.51 cm)

2.20 in.

(5.60 cm)

2.92 in.

(7.42 cm)

(33.53 cm)

13.72 in.

(34.85 cm)

13.20 in.

13.12 in.

(33.32 cm)

17.13 in.

19.01 in.

(48.28 cm)

(43.51 cm)

2.20 in.

(5.60 cm)

2.92 in.

(7.42 cm)

(33.53 cm)

13.72 in.

(34.85 cm)

Page 6 of 8 D A T A S H E E T E85014-0003

Technical Specifications Annunciator Assemblies Each annunciator space holds a control-display module. LCD displays, 4-MIC and 4-FT take two spaces.

4-2ANN 4-4ANN 4-6ANN 4-8ANN 4-16ANN 4-24ANN

Number of Spaces Two Four Six Eight Sixteen Twenty-four

Wallbox, Surface Mounting

4-2ANNMT 4-4ANNMT 4-ANNMT

4-8ANNMT 4-16ANNMT 4-24ANNMT

Wallbox, Semi-flush Mounting 3-CAB5B 3-CAB7B 3-CAB14B

Agency Approvals: UL, ULC, FM, CSFM

Door Color Metallic Bronze (Pantone Coated PMS# P 171-16 C, Pantone RGB# 81 75 67, and RAL Classic/RAL Design# 7022)

Wallbox Color Black

4-ANNCPU Central Processor Comes standard with annunciator assemblies.

Voltage 16 to 32Vdc

Current draw Standby Alarm/Active

183 mA at 16 VDC; 125 mA at 24 VDC; 119 mA at 32 VDC 188 mA at 16 VDC; 125 mA at 24 VDC; 124 mA at 32 VDC

USB support One USB 3.0, Type A – female port One USB 3.0, Type B – female port

SFP support Supports all 4-NET series SFPs. Refer to EST4 Network Controllers Catalog sheet 85014-0008 for details.

Wire Size TB1 backup power connection 12 to 18 AWG (2.5 to 1.0 mm²)

Operating Temperature 32 to 120°F (0 to 49°C)

Operating relative Humidity 0 to 93% noncondensing

Option modules 4-ANNAUDTEL: Annunciator Audio/Telephone interface module. Adds audio and telephone processing capabilities to the 4-ANNCPU, required for the use of the 4-MIC and/or 4-FT with the 4-ANNCPU.

SFP Network Controllers

Model # Description Network Interconnection Media Supported

4-NET-CAT

100 Mbps

SFP

Network Controller

Cable type - Cat 5e or better Connector type - RJ-45 Distance 328 ft. (100 m) max

4-NET-MM

Multi-mode fiber-optic SFP Network Controller

SFP network media interface, multi-mode fiber-optic, supports 50/125 μ (OM3/ OM4) fiber pair up to 1.24 mi. (2 km), 62.5/125 μ (OM1) fiber pair up to 0.62

mi. (1 km), or a 100/140 μ fiber pair up to 150 m. Order one 4-NET-MM for “in” wiring and one for "out" wiring for connections from previous node and to next node as required. Each 4-NET-MM supports one multi-mode fiber pair between network cards.

4-NET-SM

Single-mode fiber-optic SFP Network Controller

Single mode 9/125 μ (G.652) fiber pair up to 6.2 miles (10 km). Order one 4-NET-SM for “in” wiring from the previous node and a second 4-NET-SM for “out” network wiring to the next node. Each 4-NET-SM supports one single-mode fiber pair between network cards

4-NET-SMH

Single-mode fiber-optic SFP Network Controller High output

Single-mode fiber-optic, high-power output, with a 9/125 μ (G.652) fiber pair up to 24.8 mi (40km). Order one 4-NET- SMH for “in” wiring from the previous node and a second 4-NET-SMH for “out” network wiring to the next node.

Each 4-NET-SMH supports one single-mode fiber pair between network cards.

4-NET-SMU

Single-mode fiber-optic SFP Network Controller Bi-Directional

Bi-directional, single-mode fiber-optic with a 9/125 μ (G.652) fiber up to 6.2 miles (10 km). The 4-NET-SMU must be paired with a 4-NET-SMD over one single-mode fiber between network cards.

4-NET-SMD

Single-mode fiber-optic SFP Network Controller Bi-Directional

Bi-directional, single-mode fiber-optic with a 9/125 μ (G.652) fiber up to 6.2 miles (10 km). The 4-NET-SMD must be paired with a 4-NET-SMU over one single-mode fiber between network cards.

4-NET-TP

2 Mbps Twisted Pair SFP Network Controller

Twisted pair. Following specifications are between any two panels.

• 16 to 22 AWG (1.3 to 0.33 mm²)

• Six twists per foot minimum

• Circuit Capacitance 0.09 μF max.

• 5,000 ft. (1,524 m) between any two panels

• Circuit resistance 90 Ω max.

4-NET-TP-

HC

0.3 Mbps

Twisted Pair SFP Network Controller

Twisted pair or Shielded twisted pair.

Following specifications are between any two panels.

• 16 to 24 AWG (1.3 to 0.20 mm²)

• Six twists per foot minimum

• 5,000 ft. (1,524 m) between any two nodes with unshielded twisted pair

• Circuit capacitance 0.3 μF max.

• 3280 ft. (1,000 m) between any two nodes shielded twisted pair

• Circuit resistance 90 Ω max.

Refer to Data Sheet E85014-0008 for additional details on SFP network controllers.

Page 7 of 8 D A T A S H E E T E85014-0003

Ordering Information, annunciators and accessories Model #

(SKU)

Description Shipping Weight

4-2ANN

LCD Annunciator - Comes with 4-LCDANN color touchscreen display, 4-ANNCPU, metallic bronze outer door and black inner door. Order wallbox assembly model 4-2ANNMT and required network Controllers 4-NET-XX separately (see Note 1).

10.3lb (4.67kg)

4-4ANN

Metallic bronze Annunciator supports 4 slots (1 row of 4). Comes with 4-ANNCPU, metallic bronze outer door and black inner door. Order wall Mounting assembly 4-4ANNMT, required network controllers 4-NET-XX series (See note 1), any user interfaces and filler plates separately.

11.5lb (5.22kg)

4-6ANN

Metallic bronze Annunciator, 6 slots (1 row of 6). Comes with 4-ANNCPU, metallic bronze outer door and black inner door. Order wall Mounting assembly 4-6ANNMT, required network Controllers 4-NET-XX series (see Note 1), any user interfaces and required filler plates separately.

12.5lb (5.67kg)

4-8ANN

Metallic bronze Annunciator, 8 slots (2 rows of 4). Comes with 4-ANNCPU, metallic bronze outer and black inner doors. Order wall Mounting assembly 4-8ANNMT (surface mounting), or 3-CAB5B (Semi-flush mounting) required network Controllers 4-NET-XX series (see Note 1), End User interfaces and required filler plates separately.

24.5lb (11.11kg)

4-16ANN

Metallic bronze Annunciator, 16 slots (2 rows of 8). Comes with 4-ANNCPU, metallic bronze outer and black inner doors. Order wall Mounting assembly 4-16ANNMT (Surface mount) or 3-CAB7B (semi-flush mount), required network Controllers 4-NET-XX series (see Note 1), end user interfaces and required filler plates separately.

37.9lb (17.19kg)

4-24ANN

Metallic bronze Annunciator, 24 slots (3 rows of 8). Comes with 4-ANNCPU, metallic bronze outer and black inner doors. Order wall mounting assembly 4-24ANNMT, required network Controllers 4-NET-XX series (see Note 1), and End User interfaces and required filler plates separately.

52.9lb (24.02kg)

Accessories and Related Equipment

4-LCDANN

Color LCD display, includes silicon rubber common control buttons, mounts in remote annunciators, communicates to 4-ANNCPU. Comes with interconnect cable. LCD ordered separately for mounting in 4-4ANN or 4-6ANN. 4-2ANN comes with one 4-LCDANN.

1.90lb (0.85kg)

4-LCDLE

Color LCD display, includes silicon rubber common control buttons, mounts in remote annunciators sizes 4-8ANN, 4-16ANN or 4-24ANN, communicates to 4-ANNCPU. Comes with interconnect cable

1.9lb (0.85kg)

4-LCDAUD

TELANN

LCD display for control of paging and fire fighter telephone. Comes with one 4-LCDAUDTEL and mounting and cabling hardware for mounting in 4-16ANNMT or 4-24ANNMT enclosures where separate LCD display of Audio and Telephone is required. Is not supported in other annunciator sizes. Order annunciator application specific equipment separately.

1.8lb (0.81kg)

4-ANNCPU

Annunciator Central Processor Unit (CPU), provides mounting for up to two network controllers (see note 1), one USB device port, one USB host port and one 4-ANNAUDTEL module.

1.0lb (0.45kg)

4-24L Control Display Module with 24 indicators. See note 2. 0.6lb (0.27kg) 4-24L12S Control Display Module with 24 indicators and 12 switches. See Note 2. 0.7lb (0.29kg) 4-24L18S Control Display Module with - 24 indicators and 18 switches See Note 2. 0.7lb (0.29kg) 4-24L24S Control Display Module with - 24 indicators and 24 switches. See Note 2. 0.7lb (0.29kg) 4-FIL Fills one indicator/switch space on inner doors when no Switch or LED strips are installed. 0.1lb (0.04kg)

4-MIC

Audio paging microphone. Requires 4-ANNAUDTEL support card be installed on the 4-ANNCPU card.

Can be mounted in 4-4ANN through 4-24ANN annunciators

1.2lb (0.54kg)

4-FT

Master Fire Fighters telephone. Requires a 4-ANNAUDTEL support card be installed on the 4-ANNCPU card.

Can be mounted in 4-4ANN through 4-24ANN annunciators.

1.4lb (0.64kg)

4-ANN

AUDTEL

Annunciator Audio/Telephone interface module. Adds audio and telephone processing capabilities to the 4-ANNCPU, required for the use of the 4-MIC and/or 4-FT with the 4-ANNCPU.

0.3lb (0.14kg)

4-CPUGRPH Graphic Annunciator Central Processor Module. See Note 3. 1.5lb (0.68kg) 3-EVDVR LED/SWITCH Driver Module Assembly for ENVOY graphics. See Note 3. 0.4lb (0.18kg) 3-EVDVRA LED/SWITCH Driver Module Assembly for Third-party Graphics. See Note 3. 0.7lb (0.32kg) 3-EVPWR Power Supply Assembly space for one 4-CPUGRPH for ENVOY Graphics. See Note 3. 0.2lb (0.09kg)

3-EVPWRA

Power Supply Assembly c/w 19 inch rail mounting chassis assembly space for one 4-CPUGRPH for Third-party Graphics. See Note 3.

2.9lb (1.34kg)

3-EVDVRX Plastic mounting extrusion 19” mounting - for up to 3 3-EVDVRAs. See Note 3. 0.9lb (0.41kg)

Note 1: Refer to Catalog Sheet part number E85014-0008 for a complete list and description of available Network Controllers.

Note 2: Refer to Catalog Sheet part number E85014-0006 for a complete description of Control Display Modules.

Note 3: SKU not FM approved.

Temple VA Fire Alarm Data Sheets - Part Two[1].pdf

Page 8 of 8 D A T A S H E E T E85014-0003

06-24-20

LIFE SAFETY & INCIDENT MANAGEMENT

Contact us

Phone: 800-655-4497 (Option 4) Email: edwards.fire@carrier.com Website: edwardsfiresafety.com

8985 Town Center Pkwy Bradenton, FL 34202

© 2020 Carrier All rights reserved.

Ordering Information, wallboxes and replacement parts Model #

(SKU)

Description Shipping Weight

Wallboxes

4-2ANNMT

Mounting assembly for 4-2ANN, two wide annunciator. Supports surface or semi-flush mounting. Comes with black wallbox, surface mounting plastic fillers and semi-flush trim.

6.4lb (2.9kg)

4-4ANNMT

Mounting assembly for 4-4ANN, four wide annunciator. Supports surface or semi-flush mounting. Comes with black wallbox, surface mounting plastic fillers and semi-flush trim.

9.0lb (4.08kg)

4-6ANNMT

Mounting assembly for 4-6ANN, six wide annunciator. Supports surface or semi-flush mounting. Comes with wallbox, surface mounting plastic fillers and semi-flush trip.

10.3lb (4.67kg)

4-8ANNMT

Mounting assembly for 4-8ANN, four wide x two row high annunciator. Supports surface mounting.

19.0lb (8.62kg)

3-CAB5B

Wallbox – Black Semi-flush wallbox, ideal for use when semi-flush mounting 4-8ANN annunciators.

20.0lb (9.07kg)

4-16ANNMT

Surface Mount Wall box assembly for eight wide by two high annunciators (16 spaces)

27.0lb(12.25kg)

3-CAB7B

Wallbox – Black Semi-flush wallbox, ideal for use when semi-flush mounting 4-16ANN annunciators.

29.5lb (13.38kg)

4-24ANNMT

Surface mount wallbox assembly for eight wide by three high annunciator (24 spaces).

37.0lb (16.78kg)

3-CAB14B

Wallbox – Black Semi-flush wallbox, ideal for use when semi-flush mounting 4-24ANN annunciators.

40.8lb (18.5kg)

Service Replacement Parts

4-2ANND

Service replacement metallic bronze Annunciator Door for 4-2ANN annunciators includes the inner and outer doors.

7.7lb (3.5kg)

4-4ANND

Service replacement metallic bronze Annunciator Door for 4-4ANN annunciators includes the inner and outer doors.

10lb (4.5kg)

4-6ANND

Service replacement metallic bronze Annunciator Door for 4-6ANN annunciators, includes the inner and outer door

11lb (5kg)

4-CAB8D

Service replacement metallic bronze door for 3-CAB5B or 4-8ANNMT - four spaces wide by two high (8 spaces) Includes inner (black) door and outer metallic bronze door.

23lb (10.4kg)

4-CAB8DR

Red door for 3-CAB5B - four spaces wide by two high (8 spaces).

Includes inner (black) door and outer red door. May be used to provide a red door for 4-8ANN annunciators.

23lb (10.4kg)

4-CAB16DR

Red door for 3-CAB7B - eight spaces wide by two high (16 spaces). Includes inner (black) door and outer red door. May be used to provide a red door for 4-16ANN annunciators.

36lb (16.3kg)

4-CAB24DR

Red door for 3-CAB14B - eight spaces wide by three high (24 spaces). Includes inner (black) door and outer red door. May be used to provide a red door for 4-24ANN annunciators

51lb (23.1kg)

4-2ANNFA

Service replacement part - plastic frame assembly with mounting screws for 4-2ANN annunciators

1.5lb (0.68kg)

4-4ANNFA

Service replacement part - plastic frame assembly with mounting screws for 4-4ANN annunciators.

2lb (0.91kg)

4-6ANNFA

Service replacement part - plastic frame assembly with mounting screws for 4-6ANN annunciators.

2lb (0.91kg)

4-4X2ANNFA

Service replacement part – plastic frame assembly with mounting screws for 4-8ANN annunciators and 4-CAB5D door assemblies.

3lb (1.36kg)

4-8ANNFA

Service replacement part - plastic frame assembly with mounting screws for 4-CAB16D and 4-CAB21D(L) door assemblies.

3lb (1.36kg)

Temple VA Fire Alarm Data Sheets - Part Two[1].pdf mailto:edwards.fire%40carrier.com?subject= https://www.edwardsfiresafety.com

EDWARDS® Catalog u Power Supplies and Accessories

Page 1 of 4 D A T A S H E E T E85005-0125 Not to be used for installation purposes. Issue 1.2

03/24/21

Remote Booster Power Supplies

BPS6A, BPS10A

Overview The Booster Power Supply (BPS) is a UL 864, 10th Edition listed power supply. It is a 24 Vdc filtered-regulated, and supervised unit that can easily be configured to provide additional notification appliance circuits (NACs) or auxiliary power for Mass Notification/ Emergency Communication (MNEC), as well as life safety applica-tions.

The BPS contains the circuitry to monitor and charge internal or external batteries. Its steel enclosure has room for up to two 10 ampere-hour batteries. The BPS has four Class B (convert-ible to two Class A) NACs. These can be activated in one or two groups from the BPS’s unique dual input circuits.

The BPS is available in 6.5 or 10 ampere models. Each output circuit has a capacity of three amperes; total current draw cannot exceed the unit’s rating.

The BPS meets current UL requirements and is listed under the following standards:

Standard (CCN) Description UL864 10th edition (UOXX) Fire Alarm Systems UL636 (ANET, UEHX7) Holdup Alarm Units and Systems UL609 (AOTX, AOTX7) Local Burglar Alarm Units and Systems UL365 (APAW, APAW7) Police Station Connected Burglar Alarm Units and Systems UL1076 (APOU, APOU7) Proprietary Burglar Alarm System Units UL1610 (AMCX) Central Station Alarm Unit ULC-S527 (UOXXC) Control Units, Fire Alarm (Canada) ULC-S303 (AOTX7) Local Burglar Alarm Units and Systems (Canada) C22.2 No. 205 Signaling Equipment (Canada)

Standard Features

• Allows for reliable filtered and regulated power to be installed where needed

• Cost effective system expansion

• Provides for Genesis and Enhanced Integrity notification ap-pliance synchronization

• Supports coded output operation

• Self-restoring overcurrent protection

• Multiple signal rates

• Can be cascaded or controlled independently

• Easy field configuration

• On-board diagnostic LEDs identify wiring or internal faults

• Standard EDWARDS keyed lockable steel cabinet with re-movable door

• 110 and 230 Vac models available

• Accommodates 18 to 12 AWG wire sizes

• Optional tamper switch

• Dual battery charging rates

• Optional earthquake hardening: OSHPD seismic pre-approval for component Importance Factor 1.5

7300-1657:

S3424

476-91-E Vol.13

Temple VA Fire Alarm Data Sheets - Part Two[1].pdf

Page 2 of 4 D A T A S H E E T E85005-0125 Not to be used for installation purposes. Issue 1.2

Application The BPS provides additional power and circuits for notification ap-pliances and other 24 Vdc loads. It is listed for indoor dry locations and can easily be installed where needed.

Fault conditions are indicated on the on-board diagnostic LEDs, opening the BPS input sense circuit and the trouble relay (if programmed). While this provides indication to the host system, the BPS can still be activated upon command. A separate AC Fail contact is available on the BPS circuit board, which can be programmed for trouble or AC Fail. There are seven on-board diagnostic LEDs: one for each NAC fault, one for battery fault, one for ground fault, and one for AC power.

The unique dual-input activation circuits of the BPS can be acti-vated by any voltage from 6 to 45 VDC (filtered-regulated) or 11 to 33 Vdc (full-wave rectified, unfiltered). The first input circuit can be configured to activate 1-4 of the four possible outputs. The second input circuit can be configured to control circuits 3 and 4.

When outputs are configured for auxiliary operation, these circuits can be configured to stay on or automatically deactivate 30 sec-onds after AC power is lost. This feature makes these circuits ideal for door holder applications. The BPS also has a separate 200 mA 24 Vdc output that can be used to power internal activation modules.

BPS NACs can be configured for a 3-3-3 temporal or continuous output. This makes the BPS ideal for applications requiring signal-ing rates that are not available from the main system.

In addition to the internally generated signal rates, the BPS can also be configured to follow the coded signal rate of the main system NACs. This allows for the seamless expansion of existing NACs.

The BPS enclosure has mounting brackets for up to three Signa-ture modules to the right of the circuit board.

Engineering Specification Supply, where needed, EDWARDS BPS Series Booster Power Supplies (BPS) that are interconnected to and supervised by the main system. The BPS shall function as a stand-alone auxiliary power supply with its own fully-supervised battery compliment.

The BPS battery compliment shall be sized to match the require-ments of the main system. The BPS shall be capable of supervis-ing and charging batteries having the capacity of 24 ampere-hours for Mass Notification/Emergency Communication (MNEC), life safety applications.

<<The BPS shall be capable of installation for a seismic com-ponent Importance Factor of 1.5.>> The BPS shall provide a minimum of four independent, fully supervised Class B circuits that can be field configurable for notification appliance circuits or auxiliary 24 Vdc power circuits. BPS NACs shall be convertible to a minimum of two Class A NACs. Each BPS output circuit shall be rated at 3 amperes at 24 Vdc. Each output circuit shall be pro-vided with automatically restoring overcurrent protection. The BPS shall be operable from the main system NAC and/or EDWARDS Signature Series control modules. BPS NACs shall be configurable for continuous or 3-3-3 temporal rate. Fault conditions on the BPS shall not impede operation of main system NAC. The BPS shall be provided with ground fault detection circuitry and a separate AC fail relay.

Front View

All knockouts for 3/4 in conduit

(1.9 cm)

S id e V ie w

S id e V ie w

Top View

D1

D2 D3

D4

D5

D6

Notes

1. Maintain 1/4-inch (6 mm) spacing between power-limited and nonpower-limited wiring or use type FPL, FPLR, or FPLP cable per NEC.

[2] Power-limited and supervised when not configured as auxiliary power. Non-supervised when configured as auxiliary power.

[3] Source must be power-limited. Source determines supervision.

4. When using larger batteries, make sure to position the battery terminals towards the door.

D1 D2 D3 D4 D5 D6

17.0 in (43.2 cm)

3.5 in (8.9 cm)

13.0 in (33.0 cm)

6.5 in (16.5 cm)

3.375 in (8.6 cm)

12.0 in (30.4 cm)

Dimensions

Wire routing

Page 3 of 4 D A T A S H E E T E85005-0125

Typical Wiring

Single or cascaded booster anywhere on a notification appliance circuit

Existing NAC end-of-line resistors are not required to be installed at the booster’s terminals. This allows multiple boosters to be driven from a single NAC circuit without the need for special configurations.

Configuring the Booster for AC Power Fail delay operation*

OUT

OUT

NC

Sense 1

Sense 2

Trouble

COM

COM

COM

IN

IN

NO

TB2

TB1

UL listed

EOL 15 KW

Notification appliance circuit (NAC)

Notification appliance circuit (NAC)

T B

200 mA AUX

Continuous

EOL 47 K

48 37 26

CC1(S) module

48 37 26

CC1(S) module

[1] [1]

EOL 47 K

NAC1/

AUX1

NAC2/

AUX2

NAC3/

AUX3

NAC4/

AUX4

UL listed

EOL 15 KW

[3]

Fire Alarm

Control Panel

NAC Circuit

NAC Circuit

NAC output #1

To next signaling device, booster, or

EOL resistor

NAC output #2

NAC output #3

NAC output #4

S e n s e

In p u t

S e n s e

In p u t

Booster Power

Supply

Multiple CC1(S) modules using the BPS’s sense inputs

OUT

OUT

NC

Sense 1

Sense 2

Trouble

COM

COM

COM

IN

IN

NO

TB2

TB1

UL listed

EOL 15 kÙ

Notification appliance circuit (NAC)

Notification appliance circuit (NAC)

T B

200 mA AUX

Continuous

Data out to next device

Data in from previous device or Signature controller

EOL 47 kÙ

48 37 26

CC1(S) module [1][3]

NAC1/

AUX1

NAC2/

AUX2

NAC3/

AUX3

NAC4/

AUX4

UL listed

EOL 15 kÙ

CT1

module [4]

Data out to next device

Data in from previous device or Signature controller

+ + *The Booster supports AC Power fail delay of three hours via its trouble contact when dip switch SW2-6 is on. All other troubles are reported to supervising module or panel without delay via Sense inputs.

Phone: 800-655-4497 (Option 4) Email: edwards.fire@carrier.com Website: edwardsfiresafety.com

8985 Town Center Pkwy Bradenton, FL 34202

© 2021 Carrier All rights reserved.

03/24/21Page 4 of 4 D A T A S H E E T E85005-0125 Not to be used for installation purposes. Issue 1.2

1. Maximum of 8 Amps can be used for auxiliary output.

1. Requires installation of sepa-rate battery cabinet.

2. For earthquake anchorage, including detailed mounting weights and center of gravity detail, refer to Seismic Applica-tion Guide 3101676. Approval of panel anchorage to site structure may require local AHJ, structural or civil engineer review.

Specifications

Ordering Information

Model 6.5 amp Booster 10 amp Booster AC Line Voltage 120VAC or 220-240VAC 50/60Hz

390 watts 120VAC or 220-240VAC 50/60Hz

580 watts Notification Appliance Circuit Ratings

3.0A max. per circuit @ 24Vdc nominal 6.5A max total all NACs

3.0A max. per circuit @ 24Vdc nominal 10A max total all NACs

Trouble Relay 2 Amps @ 30Vdc

Auxiliary Outputs Four configurable outputs replace NACs 1, 2, 3 or 4. as auxiliary outputs and 200 mA dedicated auxiliary. (See note 1.)

Input Current (from an existing NAC)

3mA @ 12Vdc, 6mA @ 24Vdc

Booster Internal Supervisory Current

70mA + 35 mA for each circuit set to AUX

Booster Internal Alarm Current

270mA

Signature Mounting Space

Accomodates three two-gang modules.

Maximum Battery Size 10 Amp Hours (2 of 12V10A) in cabinet up to 24 Amp hours with external battery cabinet for fire applications.

Terminal Wire Gauge 18-12 AWG Relative Humidity 0 to 93% non condensing @ 32°C Temperature Rating 32° to 120°F (0° to 49°C) NAC Wiring Styles Class A or Class B Output Signal Rates Continuous, 3-3-3 temporal, or follow installed panel’s NAC.

Ground Fault Detection Enable or Disable via jumper Agency Listings UL, ULC, CSFM

Catalog Number

Description Shipping Wt. lb (kg)

BPS6A 6.5 Amp Booster Power Supply 13 ( 5.9) BPS6AC 6.5 Amp Booster Power Supply (ULC) 13 ( 5.9) BPS6A/230 6.5 Amp Booster Power Supply (220V) 13 ( 5.9) BPS10A 10 Amp Booster Power Supply 13 ( 5.9) BPS10AC 10 Amp Booster Power Supply (ULC) 13 ( 5.9) BPS10A/230 10 Amp Booster Power Supply (220V) 13 ( 5.9)

Related Equipment 12V6A5 7.2 Amp Hour Battery, two required 3.4 (1.6) 12V10A 10 Amp Hour Battery, two required 9.5 (4.3) 3-TAMP Tamper switch BPS-CVR Electronics Protective Cover BC-1EQ Seismic Kit for BC-1. Order BC-1 separately. See note 2 BPSEQ Seismic kit for BPS6A or BPS10 Booster Power Supplies. See note 2 BC-1 Battery Cabinet (up to 2 - 40 Amp Hour Batteries) 58 (26.4) BC-2 Battery Cabinet (up to 2 - 17 Amp Hour Batteries) 19 (8.6) 12V17A 18 Amp Hour Battery, two required (see note 1) 13 ( 5.9) 12V24A 24 Amp Hour Battery, two required (see note 1) 20 (9.07)

Temple VA Fire Alarm Data Sheets - Part Two[1].pdf

EDWARDS® Catalog Intelligent Initiating Devices

03/23/21 Page 1 of 4 D A T A S H E E T E85001-1001 Not to be used for installation purposes. Issue 1.4

CERTIFIED

E12345

SAFETY

SIGNALING

US

Helps Reduce Cooking Nuisance Alarms

UL 268 7th Ed.

Intelligent Smoke Detector

SIGA-OSD

Overview The Signature Optica Series SIGA-OSD smoke detector brings advanced optical (photoelectric) technology to a practical design that increases efficiency, saves installation time, cuts costs, and extends life safety and property protection capabilities. Continuous self-diagnostics ensure reliability over the long-haul, while environmental compensation helps reduce maintenance costs.

Like all Signature Optica Series detectors, the SIGA-OSD is an intelligent device that gathers analog information from multiple optical sensors, converting this data into digital signals. Utilizing dual optical wavelengths combined with multiple detection angles, the SIGA-OSD differentiates particles that are not representative of actual smoke. Particle data is input into digital filters which feed a series of ratios removing signal patterns that are typical of nuisance sources, thus reducing unwanted alarms. To make an alarm decision, the detector’s on-board microprocessor measures and analyzes all optical sensor readings and compares this information to preprogrammed settings.

Standard Features

• Multi-criteria optical smoke sensing technology

• Wide 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) smoke obscuration

• Uses Existing Wiring

• Integrated nuisance rejection reducing unwanted alarms from general cooking particulates

• Listed to UL 268 7th edition

• Automatic Device Mapping

• Up To 250 Total Signature Addresses Per Loop

• Two Levels of Environmental Compensation

• Two Levels of Dirty Detector Warning

• Twenty Pre-Alarm Settings

• Five Sensitivity Settings

• Non-Volatile Memory

• Electronic Addressing

• Automatic Day/Night Sensitivity Adjustment

• Bicolor (Green/Red) Status LED

• Standard, Relay, Fault Isolator, and Audible Mounting Bases

• Sensor Markings Provide Easy Testing Identification

Note: Some features described here may not be supported by all control systems. Check your control panel’s Installation and Operation Guide for details.

7272-1657:

Temple VA Fire Alarm Data Sheets - Part Two[1].pdf

Page 2 of 4 D A T A S H E E T E85001-1001 Not to be used for installation purposes. Issue 1.4

Application The SIGA-OSD detects particles from a wide range of combustion sources and will trigger an alarm when smoke density in the chamber reaches preprogrammed level. Thanks to its high-performance reflective response technology, the smoke sensor responds quickly and reliably to a wide range of fire types, including both fast and slow burning fires fueled by combustibles typically found in modern multi-use buildings.

Compatibility The SIGA-OSD detector is compatible only with control panels using a Signature Loop controller.

Installation

Self-locking tab

LED Indicator

Signature Series detectors mount to North American 1-gang boxes, 3-1/2 inch or 4 inch octagon boxes, and to 4 inch square electrical boxes 1-1/2 inches (38 mm) deep. They mount to European BESA and 1-gang boxes with 60.3 mm fixing centers. See mounting base installation and wiring for more information.

Sensing and reporting technology The microprocessor in each detector provides additional benefits – Self-diagnostics and History Log, Automatic Device Mapping, and Fast, Stable Communication.

Self-diagnostics and History Log - Each Signature Series detector constantly runs self-checks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in the detector’s non-volatile memory

Automatic Device Mapping - The loop controller learns where each device’s serial number address is installed relative to other devices on the circuit. The mapping feature provides supervision of each device’s installed location to prevent a detector from being reinstalled (after cleaning, etc.) in a different location from where it was originally.

Fast Stable Communication - On-board intelligence means less information needs to be sent between the detector and the loop controller. Other than regular supervisory polling response, the detector only needs to communicate with the loop controller when it has something new to report.

Testing & Maintenance Each detector automatically identifies when it is dirty or defective and causes a “dirty detector” message. The detector’s sensitivity measurement can also be transmitted to the loop controller.

A sensitivity report may be printed to satisfy NFPA sensitivity measurements, which must be conducted at the end of the first year and every two years thereafter.

The user-friendly maintenance program shows the current state of each detector and other pertinent messages. Single detectors may be turned off temporarily from the control panel. Availability of maintenance features is dependent on the fire alarm system used.

Accessories Detector mounting bases have wiring terminals that are accessible from the “room-side” after mounting the base to the electrical box. The bases mount to North American 1-gang boxes and to 3½ inch or 4 inch octagon boxes, 1½ inches (38 mm) deep. They also mount to European BESA and 1-gang boxes with

60.3 mm fixing centers. The SIGA-SB4, SIGA-RB4, and SIGA-IB4 mount to North American 4 inch sq. electrical boxes in addition to the above boxes. They include the SIGA-TS4 Trim Skirt, which is used to cover the “mounting ears” on the base. The SIGA-AB4G mounts to a 4 inch square box only.

SIGA-IB

Isolator Base

SIGA-LED

Remote LED

SIGA-RB

Relay Base

SIGA-SB

Standard Base

SIGA-AB4G/T/LF

Audible Base

Remote LED SIGA-LED - The remote LED connects to the SIGA-SB or SIGA-SB4 Standard Base only. It features a North American size 1-gang plastic faceplate with a white finish and red alarm LED.

SIGA-TS4 Trim Skirt - Supplied with 4 inch bases, it can also be ordered separately to use with the other bases to help hide surface imperfections not covered by the smaller bases.

Sounder Bases - Signature Series sounder bases are designed for use where localized or group alarm signaling is required.

• SIGA-AB4G bases provide sounder capability to Signature Series to heat and smoke detectors. They are not intended for use with combination carbon monoxide detectors in Fire-plus-CO mode.

• SIGA-AB4GT bases provide sounder capability to Signature Series smoke and heat detectors, as well as carbon monoxide detectors when used with a SIGA-TCDR Temporal Pattern Generator.

• SIGA-AB4G-LF bases provide 520 Hz low frequency sounder capability to Signature Series smoke and heat detectors, as well as carbon monoxide detectors when used with a SIGA-TCDR Temporal Pattern Generator. The SIGA-AB4G-LF is suitable for applications requiring low frequency audible tones.

Page 3 of 4 D A T A S H E E T E85001-1001 Not to be used for installation purposes. Issue 1.4

Isolator Detector Base, SIGA-IB, SIGA-IB4

This base includes a built-in line fault isolator for use on Class A circuits. A detector must be installed for it to operate. The isolator base does not support the SIGA-LED Remote LED.

The isolator operates as follows:

- a short on the line causes all isolators to open within 23 msec.

- at 10 msec intervals,beginning on one side of the Class A circuit nearest the loop controller, the isolators close to provide the next isolator down the line with power.

- when the isolator next to the short closes, it reopens within 10 msec.

The process repeats beginning on the other side of the loop controller.

Typical Wiring The detector mounting bases accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.5mm2), and #12 AWG (2.5mm²) wire sizes.

Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation.

Standard Detector Base, SIGA-SB, SIGA-SB4

This is the basic mounting base for EDWARDS Signature Series detectors. The SIGA- LED Remote LED is supported by this Base.

Max resistance per wire must not exceed 10 Ohms

DATA IN (-)

DATA IN (+)

From Signature Controller or Previous Device

DATA OUT (-)

DATA OUT (+)

To Next Device

Remote LED

Term Description 1 Not Used

2 DATA IN/OUT (+)

3 Not Used

4 DATA IN (-)

4 Remote LED (-) 5 Remote LED (+) 6 Not Used

7 DATA OUT (-)

Relay Detector Base, SIGA-RB, SIGA-RB4

This base includes a relay.

Normally Open or Normally Closed operation is selected during installation. The dry contact is rated for 1 amp (pilot duty) @ 30 Vdc. The relay’s position is supervised to avoid accidentally jarring it out of position. The SIGA-RB can be operated as a control relay if programmed to do so at the control panel. The relay base does not support the SIGA-LED Remote LED.

CONTACT RATING

1.0 Amp @ 30 VDC

(Pilot Duty)

Term Description 1 Normally Open

2 DATA IN/OUT (+)

3 Common

4 DATA IN (-)

5 Not Used 6 Normally-Closed

7 DATA OUT (-)

Term Description 1 Not Used

2 DATA IN/OUT (+)

3 DATA IN (-)

4 Not Used 5 Not Used

6 DATA OUT (-)

7 Not Used

Audible Sounder Bases, Fire Mode

AB4GT, AB4G, AB4G-LF sounder bases

SIGA-AB4G-LF:

Output Mode

Default = Fire Cut/remove jumper for Fire plus CO

SIGA-AB4G:

Tone Setting

Default = Temporal Cut/remove jumper for Steady

SIGA-AB4GT,

SIGA-AB4G,

SIGA-AB4G-LF:

Volume Setting

Default = High Cut/remove jumper for low dB

-- 24 Vdc out

To next base or EOL relay

Data out to next Signature device

24 Vdc in From power supply or previous base

Data in From Signature Controller or previous device

DATA- DATA- DATA+

SIG+ SIG- OUT IN IN/OUT

Jumper cuts

Warnings & Cautions

• This detector does not operate without electrical power.

As fires frequently cause power interruption, discuss further safeguards with the local fire protection specialist.

• This detector does not sense fires in areas where smoke cannot reach the detector. Smoke from fires in walls, roofs, or on the opposite side of closed doors may not reach the detector.

• In Canada, install according to CAN/ULC-S524 Standard for the Installation of Fire Alarm Systems, CSA C22.1 Canadian Electrical Code, and the local authority having jurisdiction.

Phone: 800-655-4497 (Option 4) Email: edwards.fire@carrier.com Website: edwardsfiresafety.com

8985 Town Center Pkwy Bradenton, FL 34202

© 2021 Carrier All rights reserved.

03/23/21Page 4 of 4 D A T A S H E E T E85001-1001 Not to be used for installation purposes. Issue 1.4

Dimensions

Specifications Operating voltage 15.20 to 19.95 VDC Normal operating current 32 µA Alarm current 45 µA Smoke Sensitivity Range UL/ULC: 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) obscuration Vibration level 10 to 35 Hz, with an amplitude of 0.01 in.

Air velocity 0 to 4,000 ft./min (0 to 20 m/s) Wall mounting 12 in. (305 mm) max. from ceiling Compatible bases See Ordering Information Compatible detector testers Testifire 1000, Testifire 2000 Operating environment 32 to 120°F (0 to 49°C), 0 to 93% RH, noncondensing Construction High Impact Engineering Polymer, White Storage temperature -4 to 140°F (-20 to 60°C) Environmental compensation Automatic Agency Listings CAN/ULC-S529, UL 268-7, UL 268A, CSFM

Ordering Information Catalog Number

Description Ship Wt.

lbs (kg)

SIGA-OSD Intelligent Optical Smoke Detector 0.4 (0.16)

Accessories SIGA-SB Detector Mounting Base - Standard

0.2 (.09)

SIGA-SB4 4-inch Detector Mounting Base c/w Trim Skirt SIGA-RB Detector Mounting Base w/Relay SIGA-RB4 4-inch Detector Mounting Base w/Relay, c/w Trim Skirt SIGA-IB Detector Mounting Base w/Fault Isolator SIGA-IB4 4-inch Detector Mounting Base w/ Fault Isolator, c/w Trim Skirt SIGA-LED Remote Alarm LED (not for EN54 applications) SIGA-AB4G Audible (Sounder) Base for Fire Detectors 0.3 (0.15) SIGA-AB4G-LF Low Frequency Audible (Sounder) Base for CO and/or Fire Detectors 0.3 (0.15) SIGA-AB4GT Audible (Sounder) Base for CO and/or Fire Detectors 0.3 (0.15) SIGA-TS4 Trim Skirt (supplied with 4-inch bases) 0.1 (0.04) SIGA-TS Trim Skirt - (optional for non 4-inch bases) 0.1 (0.04) SIGA-DMP Detector Mounting Plate 3.0 (1.4) SIGA-RTA Detector Removal Tool SIGA-VA Detector Cleaning Tool

Temple VA Fire Alarm Data Sheets - Part Two[1].pdf frontdesk Highlight

04-05-20 Page 1 of 4 D A T A S H E E T E85001-0647

EDWARDS® Catalog Intelligent Initiating Devices

L I F E S A F E T Y & I N C I D E N T M A N A G E M E N T

Intelligent Heat Detectors

SIGA-HRD, SIGA-HFD

Overview The Signature Series smoke detectors bring advanced sensing technology to a practical design that increases efficiency, saves installation time, cuts costs, and extends property protection capabilities. Continuous self-diagnostics ensures reliability over the long-haul, while the latest thermister technology makes these detectors ideal wherever dependable heat detection is required.

The SIGA-HRD is an intelligent fixed temperature/rate-of-rise fire detector. It monitors the temperature of the surrounding air and analyzes the data from the sensor to determine whether to initiate an alarm. The rate-of-rise heat function quickly detects a fast, flaming fire. The fixed-temperature heat function detects fire when the air temperature near the detector exceeds the alarm point.

The SIGA-HFD is an intelligent fixed-temperature heat detec-tor that contains a fixed-temperature heat sensor rated at 135 °F (57.2 °C). It does not have a rate-of-rise function. The heat sensor monitors the temperature of the air in its surroundings and the detector analyzes the data to determine when the air temperature near the detector exceeds the device’s alarm point.

Standard Features Note: Some features described here may not be supported by all control systems. Check your control panel’s Installation and Operation Guide for details.

• Next Generation Heat…