Kerrville Generator SOW - Updated 07-13-2020.docx

DOCX document 31 KB Posted

Attached to
J059--Amendment - Update SOW and CLINs
Solicitation number
36C25720Q0743
Issued by

About this file

This statement of work outlines the generator maintenance service requirements for the Kerrville Veterans Affairs hospital campus. The contractor shall provide quarterly inspections, annual inspections and maintenance, triennial inspections and maintenance, load bank testing, and on-call service for five generators ranging from 125KW to 600KW in capacity. Services include inspection, testing, preventative maintenance, repairs, fluid changes, filter replacements, and documentation of results. The contract term is one base year plus four option years. The contractor must check in daily with the engineering office, perform all work between 0800 and 1630 hours Monday through Friday, and provide technicians who pass a VA background check and tuberculosis screening.

View the file

Other files

File Type Posted
36C25720Q0743 0002_1.docx DOCX document
UPDATED CLIN STRUCTURE 07-14-2020.docx DOCX document
36C25720Q0743 0001_1.docx DOCX document
36C25720Q0743 0001.pdf PDF
36C25720Q0743.docx DOCX document
WD 2015-5293 (Kerr County).pdf PDF
36C25720Q0743_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Update 07/13/2020

Kerrville VA Generator Maintenance Service

1. Title of Project: Generator Maintenance Service for the Kerrville VA Hospital located at 3600 Memorial Blvd, Kerrville, TX 78028. Contractor shall check in daily with the Engineering Office upstairs Bldg. 29 and utilize the Contractor’s Sign-In Log. Work performed shall be between 0800-1630 daily, Monday – Friday, no holidays. This is an Annual Service, Inspection, and Repair Service Contract.

2. General: This is a Firm-Fixed Price Contract. The Contractor shall provide all labor, equipment, tools, materials, parts, supplies, software, transportation, supervision, and any other items and services necessary to accomplish the inspection testing, and service described herein.

3. Scope of Work: The Contractor shall perform 4 quarterly inspections, PM Level 1, in accordance with manufacture’s recommendations and accepted industry standards on each of the following generators;

· Caterpillar 600 KW diesel powered standby generator,

· Onan 230 KW diesel powered standby generator,

· Cummins, model 750DQCB (x2) diesel powered standby generator,

· Cummins model 300DQDAC diesel powered standby generator,

· WisperWatt 125 KW portable standby generator.

The Contractor will perform 1 annual inspection PM level 2 during the Apr-May-June Quarter in accordance with manufacture’s recommendations and accepted industry standards on each of the following generator’s;

· Caterpillar 600 KW diesel powered standby generator,

· Onan 230 KW diesel powered standby generator,

· Cummins, model 750DQCB (x2) diesel powered standby generator,

· Cummins model 300DQDAC diesel powered standby generator,

· WisperWatt 125 KW portable standby generator.

Contractor will perform 1 annual load bank test (2-hour resistive type) on the following generators (This will require a standby generator to be on site in case of emergency);

· Caterpillar 600 KW diesel powered standby generator,

· Onan 230 KW diesel powered standby generator,

· Cummins, model 750DQCB (x2) diesel powered standby generator,

· Cummins model 300DQDAC diesel powered standby generator,

· WisperWatt 125 KW portable standby generator.

Contractor will top off fluids (coolant, batteries, oil, etc.) and make minor adjustments and repairs when inspections are done for all PM checks. Minor repairs include changing fuses, corroded wiring, relays, clamps, cracked hoses, etc. Minor repairs are included in this contract. Minor repairs include work requiring less than 30 minutes of total labor during any one quarterly, annual, or triennial inspection. Minor repairs include parts and materials totaling less than $50 during any one quarterly, annual, or triennial inspection.

Major repairs are not included in this contract. Major repairs include changing internal gaskets, engine work, internal gen-set work, etc. Major repairs include work requiring 30 minutes or more of total labor time during any one quarterly, annual, or triennial inspection. Major repairs include parts and materials in excess of $50 total during any one quarterly, annual, or triennial inspection.

Contractor will perform Quarterly inspections, on 13 automatic transfer switches as described below in the schedule, item 13.

Batteries to be replaced every two (2) years.

The Triennial inspection and maintenance will be completed during the first quarter of years (1) and (4) of the 5-year contract. The annual inspection and maintenance will be completed during the first quarter of years (2), (3) and (5) of the 5-year contract. Quarterly inspections will be completed quarterly during the first month of each quarter. The bid schedule shall reflect this schedule for the option years.

Schedule (Items 1-16):

1.Quarterly PM Level 1 on Generator Caterpillar 600 KW:
a.General – Visual inspection of overall condition of unit to foreign objects, loose or broken fittings, guards and components.
b.General – Wipe off unit- Clean oil, coolant, fuel and acid deposits. Sweep generator area.
c.Cooling System – Radiator/Heat Exchanger: Visual inspection for leaks, damage, and debris. Check louver operation.
d.Cooling System – Coolant – Visual inspection for correct level and condition of coolant (rust, oil, and contaminants). Check coolant conditioner concentration and temperature protection. Inspect filler cap gasket and sealing surface.
e.Cooling System – Hoses and Connections: Visual inspection of all hoses for deterioration.
f.Cooling System – Fan Drive Pulley and Fan: Inspect for loose or worn pulleys and lube fan drive bearings if needed. Check fan operation and clearance.
g.Cooling System – Fan Belts: Inspect for wear and deterioration.
h.Cooling System – Jacket Water Heater: Inspect for proper operation.
i.Cooling System – Water Pump: Visual and operational inspection for leaks or unusual noises.
j.Fuel System – Fuel Tank: Visually inspect fuel tank system for leaks and fuel level. Test day tank pump for proper operation.
k.Fuel System- Water Trap/Separator: Drain water from fuel tank or water separator when possible.
l.Fuel System – Fuel Lines and Connections: Inspect for leaks.
m.Fuel System – Governor and Controls: Inspect governor oil level. Inspect controls and linkage.
n.Fuel System – Fuel Filters (Primary/Secondary): Inspect for damage and leaks.
o.Air Induction and Exhaust System – Air Filter Service Indicator: Note reading. Inspect & reset indicator.
p.Air Induction and Exhaust System – Air Filter: Inspect.
q.Air Induction and Exhaust System – Air Inlet System: Inspect piping and air filter housing for damage. Clean air filters housing if air filter is replaced. Inspect housing seals and gaskets.
r.Air Induction and Exhaust System – Turbocharger: Inspect for oil leakage or exhaust leakage. Check for unusual noises and proper operation.
s.Air Induction and Exhaust System – Exhaust Manifold: Inspect for damage, missing hardware, evidence of exhaust leakage. Inspect for oil slobbering.
t.Air Induction and Exhaust System – Exhaust System: Inspect silencer and piping for damage, corrosion, or leakage. Check rain cap. Check supports for vibration damage.
u.Lube Oil System – Oil Level: Inspect for correct oil level. Visually inspect unit for leaks.
v.Lube Oil System – Inspect Oil Filter and Oil Pressure Gauge: Check for proper operation.
w.Lube Oil System – Crankcase Breather: Inspect connections and hoses for deterioration.
x.Lube Oil System - Oil sample analysis
y.Starting System – Batteries: Inspect for damage or leakage, clean battery(s). Clean and tighten all battery cable connections as needed.
z.Starting System – Batteries (Specific Gravity): Check electrolyte level and specific gravity.
aa.Starting System – Battery Charger: Inspect for operation, terminals, and wiring.
bb.Starting System – Starting Motor: Inspect electrical connections and wiring. For air starters, inspect oil jar and feeder operation.
cc.Starting System – Operational: Check for abnormal engagement and cranking noises.
ddStarting System – Alternator: Inspect connections and mounting hardware. Inspect belts, pulley and voltage output.
ee.Engine Monitors and Safety Controls – Safety Controls: Inspect
ff.Engine Monitors and Safety Controls – Remote Annunciator and Alarms: Inspect
gg.Control Panel – Start Controls – Manual/Auto: Operational check for proper operation. Check automatic start (if allowed).
hh.Control Panel – Voltmeter: Inspect
ii.Control Panel – Ammeter: Inspect
jj.Control Panel – Frequency Meter: Inspect
2.Quarterly PM Level 1 on Generator Onan 230 KW:
a.General – Visual inspection of overall condition of unit to foreign objects, loose or broken fittings, guards and components.
b.General – Wipe off unit- Clean oil, coolant, fuel and acid deposits. Police generator area.
c.Cooling System – Radiator/Heat Exchanger: Visual inspection for leaks, damage, and debris. Check louver operation.
d.Cooling System – Coolant – Visual inspection for correct level and condition of coolant (rust, oil, and contaminants). Check coolant conditioner concentration and temperature protection. Inspect filler cap gasket and sealing surface.
e.Cooling System – Hoses and Connections: Visual inspection of all hoses for deterioration.
f.Cooling System – Fan Drive Pulley and Fan: Inspect for loose or worn pulleys and lube fan drive bearings if needed. Check fan operation and clearance.
g.Cooling System – Fan Belts: Inspect for wear and deterioration.
h.Cooling System – Jacket Water Heater: Inspect for proper operation.
i.Cooling System – Water Pump: Visual and operational inspection for leaks or unusual nosises.
j.Fuel System – Fuel Tank: Visually inspect fuel tank system for leaks and fuel level. Test day tank pump for proper operation.
k.Fuel System- Water Trap/Separator: Drain water from fuel tank or water separator when possible.
l.Fuel System – Fuel Lines and Connections: Inspect for leaks.
m.Fuel System – Governor and Controls: Inspect governor oil level. Inspect controls and linkage.
n.Fuel System – Fuel Filters (Primary/Secondary): Inspect for damage and leaks.
o.Air Induction and Exhaust System – Air Filter Service Indicator: Note reading. Inspect & reset indicator.
p.Air Induction and Exhaust System – Air Filter: Inspect.
q.Air Induction and Exhaust System – Air Inlet System: Inspect piping and air filter housing for damage. Clean air filters housing if air filter is replaced. Inspect housing seals and gaskets.
r.Air Induction and Exhaust System – Turbocharger: Inspect for oil leakage or exhaust leakage. Check for unusual noises and proper operation.
s.Air Induction and Exhaust System – Exhaust Manifold: Inspect for damage, missing hardware, evidence of exhaust leakage. Inspect for oil slobbering.
t.Air Induction and Exhaust System – Exhaust System: Inspect silencer and piping for damage, corrosion, or leakage. Check rain cap. Check supports for vibration damage.
u.Lube Oil System – Oil Level: Inspect for correct oil level. Visually inspect unit for leaks.
v.Lube Oil System – Inspect Oil Filter and Oil Pressure Gauge: Check for proper operation.
w.Lube Oil System – Crankcase Breather: Inspect connections and hoses for deterioration.
x.Lube Oil System - Oil sample analysis
y.Starting System – Batteries: Inspect for damage or leakage, clean battery(s). Clean and tighten all battery cable connections as needed.
z.Starting System – Batteries (Specific Gravity): Check electrolyte level and specific gravity.
aa.Starting System – Battery Charger: Inspect for operation, terminals, and wiring.
bb.Starting System – Starting Motor: Inspect electrical connections and wiring. For air starters, inspect oil jar and feeder operation.
cc.Starting System – Operational: Check for abnormal engagement and cranking noises.
ddStarting System – Alternator: Inspect connections and mounting hardware. Inspect belts, pulley and voltage output.
ee.Engine Monitors and Safety Controls – Safety Controls: Inspect
ff.Engine Monitors and Safety Controls – Remote Annunciator and Alarms: Inspect
gg.Control Panel – Start Controls – Manual/Auto: Operational check for proper operation. Check automatic start (if allowed).
hh.Control Panel – Voltmeter: Inspect
ii.Control Panel – Ammeter: Inspect
jj.Control Panel – Frequency Meter: Inspect
3.Quarterly PM Level 1 on Cummins, model 750DQCB (x2) diesel powered standby generator and Cummins model 300DQDAC diesel powered standby generator:
a.General – Visual inspection of overall condition of unit to foreign objects, loose or broken fittings, guards and components.
b.General – Wipe off unit- Clean oil, coolant, fuel and acid deposits. Police generator area.
c.Cooling System – Radiator/Heat Exchanger: Visual inspection for leaks, damage, and debris. Check louver operation.
d.Cooling System – Coolant – Visual inspection for correct level and condition of coolant (rust, oil, and contaminants). Check coolant conditioner concentration and temperature protection. Inspect filler cap gasket and sealing surface.
e.Cooling System – Hoses and Connections: Visual inspection of all hoses for deterioration.
f.Cooling System – Fan Drive Pulley and Fan: Inspect for loose or worn pulleys and lube fan drive bearings if needed. Check fan operation and clearance.
g.Cooling System – Fan Belts: Inspect for wear and deterioration.
h.Cooling System – Jacket Water Heater: Inspect for proper operation.
i.Cooling System – Water Pump: Visual and operational inspection for leaks or unusual nosises.
j.Fuel System – Fuel Tank: Visually inspect fuel tank system for leaks and fuel level. Test day tank pump for proper operation.
k.Fuel System- Water Trap/Separator: Drain water from fuel tank or water separator when possible.
l.Fuel System – Fuel Lines and Connections: Inspect for leaks.
m.Fuel System – Governor and Controls: Inspect governor oil level. Inspect controls and linkage.
n.Fuel System – Fuel Filters (Primary/Secondary): Inspect for damage and leaks.
o.Air Induction and Exhaust System – Air Filter Service Indicator: Note reading. Inspect & reset indicator.
p.Air Induction and Exhaust System – Air Filter: Inspect.
q.Air Induction and Exhaust System – Air Inlet System: Inspect piping and air filter housing for damage. Clean air filters housing if air filter is replaced. Inspect housing seals and gaskets.
r.Air Induction and Exhaust System – Turbocharger: Inspect for oil leakage or exhaust leakage. Check for unusual noises and proper operation.
s.Air Induction and Exhaust System – Exhaust Manifold: Inspect for damage, missing hardware, evidence of exhaust leakage. Inspect for oil slobbering.
t.Air Induction and Exhaust System – Exhaust System: Inspect silencer and piping for damage, corrosion, or leakage. Check rain cap. Check supports for vibration damage.
u.Lube Oil System – Oil Level: Inspect for correct oil level. Visually inspect unit for leaks.
v.Lube Oil System – Inspect Oil Filter and Oil Pressure Gauge: Check for proper operation.
w.Lube Oil System – Crankcase Breather: Inspect connections and hoses for deterioration.
x.Lube Oil System - Oil sample analysis
y.Starting System – Batteries: Inspect for damage or leakage, clean battery(s). Clean and tighten all battery cable connections as needed.
z.Starting System – Batteries (Specific Gravity): Check electrolyte level and specific gravity.
aa.Starting System – Battery Charger: Inspect for operation, terminals, and wiring.
bb.Starting System – Starting Motor: Inspect electrical connections and wiring. For air starters, inspect oil jar and feeder operation.
cc.Starting System – Operational: Check for abnormal engagement and cranking noises.
ddStarting System – Alternator: Inspect connections and mounting hardware. Inspect belts, pulley and voltage output.
ee.Engine Monitors and Safety Controls – Safety Controls: Inspect
ff.Engine Monitors and Safety Controls – Remote Annunciator and Alarms: Inspect
gg.Control Panel – Start Controls – Manual/Auto: Operational check for proper operation. Check automatic start (if allowed).
hh.Control Panel – Voltmeter: Inspect
ii.Control Panel – Ammeter: Inspect
jj.Control Panel – Frequency Meter: Inspect
4.Quarterly PM Level 1 on WisperWatt 125 KW:
a.General – Visual inspection of overall condition of unit to foreign objects, loose or broken fittings, guards and components.
b.General – Wipe off unit- Clean oil, coolant, fuel and acid deposits. Police generator area.
c.Cooling System – Radiator/Heat Exchanger: Visual inspection for leaks, damage, and debris. Check louver operation.
d.Cooling System – Coolant – Visual inspection for correct level and condition of coolant (rust, oil, and contaminants). Check coolant conditioner concentration and temperature protection. Inspect filler cap gasket and sealing surface.
e.Cooling System – Hoses and Connections: Visual inspection of all hoses for deterioration.
f.Cooling System – Fan Drive Pulley and Fan: Inspect for loose or worn pulleys and lube fan drive bearings if needed. Check fan operation and clearance.
g.Cooling System – Fan Belts: Inspect for wear and deterioration.
h.Cooling System – Jacket Water Heater: Inspect for proper operation.
i.Cooling System – Water Pump: Visual and operational inspection for leaks or unusual nosises.
j.Fuel System – Fuel Tank: Visually inspect fuel tank system for leaks and fuel level. Test day tank pump for proper operation.
k.Fuel System- Water Trap/Separator: Drain water from fuel tank or water separator when possible.
l.Fuel System – Fuel Lines and Connections: Inspect for leaks.
m.Fuel System – Governor and Controls: Inspect governor oil level. Inspect controls and linkage.
n.Fuel System – Fuel Filters (Primary/Secondary): Inspect for damage and leaks.
o.Air Induction and Exhaust System – Air Filter Service Indicator: Note reading. Inspect & reset indicator.
p.Air Induction and Exhaust System – Air Filter: Inspect.
q.Air Induction and Exhaust System – Air Inlet System: Inspect piping and air filter housing for damage. Clean air filters housing if air filter is replaced. Inspect housing seals and gaskets.
r.Air Induction and Exhaust System – Turbocharger: Inspect for oil leakage or exhaust leakage. Check for unusual noises and proper operation.
s.Air Induction and Exhaust System – Exhaust Manifold: Inspect for damage, missing hardware, evidence of exhaust leakage. Inspect for oil slobbering.
t.Air Induction and Exhaust System – Exhaust System: Inspect silencer and piping for damage, corrosion, or leakage. Check rain cap. Check supports for vibration damage.
u.Lube Oil System – Oil Level: Inspect for correct oil level. Visually inspect unit for leaks.
v.Lube Oil System – Inspect Oil Filter and Oil Pressure Gauge: Check for proper operation.
w.Lube Oil System – Crankcase Breather: Inspect connections and hoses for deterioration.
x.Lube Oil System - Oil sample analysis
y.Starting System – Batteries: Inspect for damage or leakage, clean battery(s). Clean and tighten all battery cable connections as needed.
z.Starting System – Batteries (Specific Gravity): Check electrolyte level and specific gravity.
aa.Starting System – Battery Charger: Inspect for operation, terminals, and wiring.
bb.Starting System – Starting Motor: Inspect electrical connections and wiring. For air starters, inspect oil jar and feeder operation.
cc.Starting System – Operational: Check for abnormal engagement and cranking noises.
ddStarting System – Alternator: Inspect connections and mounting hardware. Inspect belts, pulley and voltage output.
ee.Engine Monitors and Safety Controls – Safety Controls: Inspect
ff.Engine Monitors and Safety Controls – Remote Annunciator and Alarms: Inspect
gg.Control Panel – Start Controls – Manual/Auto: Operational check for proper operation. Check automatic start (if allowed).
hh.Control Panel – Voltmeter: Inspect
ii.Control Panel – Ammeter: Inspect
jj.Control Panel – Frequency Meter: Inspect
5.Annual PM Level 2 on Generator Caterpillar 600 KW:
a.Fuel System – Fuel Filter: Replace
b.Lube Oil System – Oil and Filter: Change
c.Lube Oil System – S.O.S: Obtain oil sample for analysis. All analysis will be delivered to VA for record keeping.
d.Lube Oil System – Crankcase Breather: Inspect and Clean
e.Air Induction System – Turbocharger: Check for oil leakage or unusual noises
f.Engine Monitors and Safety Controls – Gauge: Inspect, replace if broken
g.Engine Monitors and Safety Controls – Safety Controls: Inspect for proper operation.
h.Engine Monitors and Safety Controls – Remote Annunciator and Alarms: Inspect
i.Engine Monitors and Safety Controls – Sending Unit Switches
j.Generator – Rear Bearing: lubricate per manufactures specs
k.Generator – Vibration Isolators: inspect condition
l.Control Panel – Circuit breakers: Inspect for free movement. Inspect connections.
6.Annual PM Level 2 on Generator Onan 230 KW:
a.Fuel System – Fuel Filter: Replace
b.Lube Oil System – Oil and Filter: Change
c.Lube Oil System – S.O.S: Obtain oil sample for analysis. All analysis will be delivered to VA for record keeping.
d.Lube Oil System – Crankcase Breather: Inspect and Clean
e.Air Induction System – Turbocharger: Check for oil leakage or unusual noises
f.Engine Monitors and Safety Controls – Gauge: Inspect, replace if broken
g.Engine Monitors and Safety Controls – Safety Controls: Inspect for proper operation.
h.Engine Monitors and Safety Controls – Remote Annunciator and Alarms: Inspect
i.Engine Monitors and Safety Controls – Sending Unit Switches
j.Generator – Rear Bearing: lubricate per manufactures specs
k.Generator – Vibration Isolators: inspect condition
l.Control Panel – Circuit breakers: Inspect for free movement. Inspect connections.
7.Annual PM Level 2 on Cummins, model 750DQCB (x2) diesel powered standby generator and Cummins model 300DQDAC diesel powered standby generator:
a.Fuel System – Fuel Filter: Replace
b.Lube Oil System – Oil and Filter: Change
c.Lube Oil System – S.O.S: Obtain oil sample for analysis. All analysis will be delivered to VA for record keeping.
d.Lube Oil System – Crankcase Breather: Inspect and Clean
e.Air Induction System – Turbocharger: Check for oil leakage or unusual noises
f.Engine Monitors and Safety Controls – Gauge: Inspect, replace if broken
g.Engine Monitors and Safety Controls – Safety Controls: Inspect for proper operation.
h.Engine Monitors and Safety Controls – Remote Annunciator and Alarms: Inspect
i.Engine Monitors and Safety Controls – Sending Unit Switches
j.Generator – Rear Bearing: lubricate per manufactures specs
k.Generator – Vibration Isolators: inspect condition
l.Control Panel – Circuit breakers: Inspect for free movement. Inspect connections.
8.Annual PM Level 2 on Generator WisperWatt 125 KW:
a.Fuel System – Fuel Filter: Replace
b.Lube Oil System – Oil and Filter: Change
c.Lube Oil System – S.O.S: Obtain oil sample for analysis. All analysis will be delivered to VA for record keeping.
d.Lube Oil System – Crankcase Breather: Inspect and Clean
e.Air Induction System – Turbocharger: Check for oil leakage or unusual noises
f.Engine Monitors and Safety Controls – Gauge: Inspect, replace if broken
g.Engine Monitors and Safety Controls – Safety Controls: Inspect for proper operation.
h.Engine Monitors and Safety Controls – Remote Annunciator and Alarms: Inspect
i.Engine Monitors and Safety Controls – Sending Unit Switches
j.Generator – Rear Bearing: lubricate per manufactures specs
k.Generator – Vibration Isolators: inspect condition
l.Control Panel – Circuit breakers: Inspect for free movement. Inspect connections.
9.Triennial (Every 3 years) PM Level 3 on Generator Caterpillar 600 KW:
a.Cooling System – Thermostats: Replace
b.Cooling System – Fan Belts: Replace
c.Cooling System – Hoses: Replace all cooling system hoses including jacket water heater hoses
d.Starting System – Batteries: Replace every 2 years
e.Starting System – Alternator Belt: Replace
f.Air Induction System – Air Filter: Replace
10.Triennial (Every 3 years) PM Level 3 on Generator Onan 230 KW:
a.Cooling System – Thermostats: Replace
b.Cooling System – Fan Belts: Replace
c.Cooling System – Hoses: Replace all cooling system hoses including jacket water heater hoses
d.Starting System – Batteries: Replace every 2 years
e.Starting System – Alternator Belt: Replace
f.Air Induction System – Air Filter: Replace
11.Triennial (Every 3 years) PM Level 3 on Cummins, model 750DQCB (x2) diesel powered standby generator and Cummins model 300DQDAC diesel powered standby generator:
a.Cooling System – Thermostats: Replace
b.Cooling System – Fan Belts: Replace
c.Cooling System – Hoses: Replace all cooling system hoses including jacket water heater hoses
d.Starting System – Batteries: Replace every 2 years
e.Starting System – Alternator Belt: Replace
f.Air Induction System – Air Filter: Replace
12.Triennial (Every 3 years) PM Level 3 on Generator WisperWatt 125 KW:
a.Cooling System – Thermostats: Replace
b.Cooling System – Fan Belts: Replace
c.Cooling System – Hoses: Replace all cooling system hoses including jacket water heater hoses
d.Starting System – Batteries: Replace every 2 years
e.Starting System – Alternator Belt: Replace
f.Air Induction System – Air Filter: Replace
13.Transfer switches – 13 ATS’s as described below quarterly. Unless annually indicated by PM Level 2 only:

a. Perform visual inspection of all wiring and connections for signs of tracking, overheating, and insulation deterioration.

b. Check manual switches for free movement and contact continuity. (de-energized switch only)

c. Check all time delay settings.

d. Check condition of main and arcing contacts and auxiliary contacts. (de-energized switch PM Level 2 only)

e. Inspect ground wires.
f. Inspect lug connections and mounting insulator bolts (de-energized switch).
g. Check for proper transfer operation and sequencing of time control relays if allow (PM Level 2 only)
h. Perform infrared heat scan on all contacts and connections.

ENCLOSURE

a.Wipe down.
b.Clean interior of enclosure and remove accumulated dust and/or dirt.
c.Check door closure, locking bar, and mechanism for proper operation.

MISCELLANEOUS

a.Record findings of the inspection. Note corrective action taken.
b.Report unsafe conditions.

ATS-1/Automatic Transfer Switch #1 Mfg: Russelectric Location Room#102, Building # 90 277/480v 3 phase 400 Amp

ModelRTBDNB-4003CEF
Serial No31265-1A

ATS-2

Automatic Transfer Switch #2 Mfg: Russelectric Location: Room # 102, Building # 90 277/480v 3 phase 400 Amp

ModelRTBDNB-4003CEF
Serial No31265-2A

ATS-3

Automatic Transfer Switch #3 Mfg: Russelectric Location: Room # 102, Building # 90 277/480v 3 phase 600 Amp

ModelRTBDNB-6003CEF
Serial No31265-6A

ATS-4

Automatic Transfer Switch #4 Mfg: Russelectric Location: Room # 102, Building # 90 277/480v 3 phase 400 Amp

ModelRTBDNB-4003CEF
Serial No31265-3A

ATS-5

Automatic Transfer Switch #5 Mfg: Russelectric Location: Room # 101, Building 90 277/480v 3 phase 600 Amp

ModelRTS30-ABLB6003AMF1-RPCS01
Serial No39357-2A/B

ATS-6

Automatic Transfer Switch #6 Mfg: Russelectric Location: Room # 102, Building # 90 120/208v 3 phase 400 Amp

ModelRTBDNB-4003CEF
Serial No31265-5A

ATS-7

Automatic Transfer Switch #7 MFG: Russelectric Location: Room #2A104, Building # 96 277/480v 3 phase 400 Amp Model RTBDNB-4003CEF Serial No 31265-4B

ATS-8

Automatic Transfer Switch #8 MFG Russelectric Location Building #96 277/480v 3 phase 100 Amp Model RTS30-ABLB1003AMF1-RPCS01 Serial 39357-1C/D

ATS-9

Automatic Transfer Switch #9 MFG Russelectric Location Building #96 277/480v 3 phase 100 Amp Model RTS30-ABLB1003AMF1-RPCS01 Serial 39357-1A/B

ATS-10

Automatic Transfer Switch #10 Mfg: Asco 300 series 480 V 3 Phase 1600 Amp Ser # 333290

ATS-11

Automatic Transfer Switch #11 MFG Russelectric Location Building #97 277/480v 3 phase 800 Amp Model RTS30-ABLB8003AMF1-RPCS01 Serial 39357-3A/B

ATS-12

Automatic Transfer Switch #12 MFG Russelectric Location Building #97 277/480v 3 phase 100 Amp Model RTS30-ABLB1003AMF1-RPCS01 Serial 39357-4A

ATS-13

Automatic Transfer Switch #13 Location Outside Building 84 for Boiler Plant Mfg: ONAN Mod # OTPCC-5004089 Ser # J010300899 480 V 3 Phase 600 Amp P/N 0306-4408-18

14.Annual Load Bank Testing – Annual Load Bank Testing will be conducted on the Main Hospital Generator, Caterpillar 600 KW, for 2 hours at 100% of nameplate data. All Results will be recorded and documentation of results given to VA for records.
15.Annual Load Bank Testing – Annual Load Bank Testing will be conducted on Boiler Plant Generator, Onan 230 KW, for 2 hours at 100% of nameplate data. All Results will be recorded and documentation of results given to VA for records.
16.Annual Load Bank Testing – Annual Load Bank Testing will be conducted on Chiller Plant Generators (x2), Cummins, model 750DQCB (x2) diesel powered standby generators, for 2 hours at 100% of nameplate data. All Results will be recorded, and documentation of results given to VA for records.
17.Annual Load Bank Testing – Annual Load Bank Testing will be conducted on Building 96 Generator, Cummins model 300DQDAC diesel powered standby generator, for 2 hours at 100% of nameplate data. All Results will be recorded and documentation of results given to VA for records.
18.Contractor shall provide service calls as requested by the VA COR. These calls will be billed separately and are not a part of this contract other than providing a set unit price for each service call. Price for each service call, not to exceed 4 hours on site time = $350.00. Service calls will provide basic troubleshooting, repair, and minor part replacement inclusive in set price quoted above. Major parts are not covered in the set price quoted above. Major repairs and parts will be billed separately; time and materials. All service calls shall be performed within 4 hours (on site) of call. After Hours Service Calls are defined as Mon – Fri, 1700-0700 daily and Weekends and Holidays. Normal Service Calls are defined as Mon – Fri, 0700-1700.
19.Miscellaneous

Documentation: Contractor shall, within 5 business days, provide a detailed report and analysis, both electronic and hard copy of all work performed and results to the CO or his/her designated representative. Color photographs embedded into the report shall be provided if applicable and/or requested. Report shall contain, at a minimum, date of service, amount of time spent on service, technician’s name(s), systems tested/inspected and results. Contractor shall provide a detailed narrative and line item cost estimate for repairs or replacement not covered above, if applicable, within 5 working days. Contractor shall provide a single point of contact with all contact information.

Single Point of Contact: Contractor shall provide a Single Point of Contact to the government for the management of this contract, to include scheduling, billing, work proposals, etc.

Scheduling and Daily Briefings: Contractor shall electronically (in e-mail) schedule all PMs at least 2 weeks prior to arrival with the COR. COR concurrence is required in order to ensure adequate staff coverage availability. Contractor shall submit at the 2-week notification interval the daily work plan, including hour-by-hour plan of action, materials needed, workers on site, etc. Contractor shall report into the COR daily upon arrival, prior to conducting any work and go over the submitted work plan. The Contractor shall provide a detailed out brief daily, prior to departure.

Information Systems Officer, Information Protection: The contractor will not have access to VA Desktop computers, nor will they have access to online resources belonging to the government while conducting services. The C&A requirements do not apply, and a Security Accreditation Package is not required.

Privacy Officer: The contractor will not have access to Patient Health Information (PHI) nor will they have the capability of accessing patient information during the services provided to the VA.

Safety Requirements: In the performance of this contract, the Contractor shall take such safety precautions as the Contracting Officer may determine to be reasonably necessary to protect the lives and health of occupants of the building. The Contracting Officer shall notify the Contractor of any safety issues and the action necessary to correct these issues. Such notice, when served to the Contractor or his representative at the work site shall be deemed sufficient for the corrective actions to be taken. If the Contractor fails or refuses to comply promptly, the Contracting Officer may issue an order stopping all or part of the work and hold the Contractor in default.

Waste Disposal and Recycling: All batteries, used coolant, used oil, used fuel, etc. will be disposed of by the Contractor. Contractor shall dispose of all materials off-site and provide a record of disposal to include weight/amount, place of disposal, name of Contractor, etc. All materials shall be recycled to the maximum extent possible and documentation shall be provided to the government showing proof of recycling efforts.

Badging: All Contractor personnel performing work on site will be required to pass a background investigation completed by the VA, submit to fingerprinting, and wear an approved VA-provided badge at all times while on site in the performance of work.

Tuberculosis Testing: All Contractor personnel performing work on site will be required to show proof of recent (within 1 year) Tuberculosis testing, showing a negative result.

Infection Control Training: All Contractor personnel performing work on site will be required to complete a 2-hour training course provided by the VA.