36C25718Q0546-016.xlsx

XLSX spreadsheet 35 KB Posted

Attached to
674-18-1-5065-0699 Correct Inaccessible Dampers Waco (VA-18-904878)
Solicitation number
36C25718Q0546
Issued by

About this file

36C25718Q0546 Waco 91 Damper Report FINAL.xlsx

View the file

Other files

File Type Posted
36C25718C0099-000.docx DOCX document
36C25718Q0546-00001002.pdf PDF
36C25718Q0546-00001001.pdf PDF
36C25718Q0546-00001000.docx DOCX document
36C25718Q0546-014.xlsx XLSX spreadsheet
36C25718Q0546-011.pdf PDF
36C25718Q0546-015.xlsx XLSX spreadsheet
36C25718Q0546-012.xlsx XLSX spreadsheet
36C25718Q0546-018.pdf PDF
36C25718Q0546-013.xlsx XLSX spreadsheet
36C25718Q0546-010.docx DOCX document
36C25718Q0546-017.xlsx XLSX spreadsheet
36C25718Q0546-009.docx DOCX document
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Texas Fire Suppression, Inc
100-B Don Currie Dr.
Jarrell, TX 76537
Fire Protection Systems • Commercial • Industrial • Institutional • Special Hazards • High Tech • Defense • Hangars • Retrofit • Service • Inspection • MaintenancePh: (512) 598-3959
Fax: (512) 598-3961
TX-SCR-G 1819205 * TX-ACR 1666099 * TX-ECR 1666599Date:April 2017
Report to:VA Waco CampusLocation or Building Inspected:Building 91
Contact:R. GriffinPhone:Fax:
Address:4800 Memorial Dr.email:
City, State:Waco, TXZip:76711Inspector:Dennis Thompson
Page1of4
Damper Testing Report Per NFPA 80 and EC.02.03.05 item 18
LocationDamper IDNotesPass/Fail
Southeast officeFD-B-001no access / can't reach damperNA
Mechanical Room 2B-100FD-2-002damper did not closeF
Mechanical Room 2B-100FD-2-006no access/access panel too smallN/A
Mechanical Room 2A-109CFD-2-009no access/access panel too smallN/A
Mechanical Room 2A-109CFD-2-010no access/access panel too smallN/A
AtticFD-A-001no access/access panel too smallN/A
AtticFD-A-004no access/access panel too smallN/A
AtticFD-A-006no access/access panel too smallN/A
AtticFD-A-014damper did not closeF
`FD-A-017no access/access panel obstructedN/A
AtticFD-A-019no access/access panel too smallN/A
AtticFD-A-021no access/access panel too smallN/A
AtticFD-A-022no access/access panel too smallN/A
AtticFD-A-023no access/access panel too smallN/A
AtticFD-A-024no access/access panel too smallN/A
AtticFD-A-025no access/access panel too smallN/A
AtticFD-A-027no access/access panel too smallN/A
AtticFD-A-032no access/access panel obstructedN/A
AtticFD-A-034no access/access panel too smallN/A
AtticFD-A-037no access/access panel too smallN/A
AtticFD-A-038no access/access panel too smallN/A
AtticFD-A-039no access/access panel too smallN/A
AtticFD-A-043no access/access panel too smallN/A
AtticFD-A-044no access/access panel too smallN/A
AtticFD-A-045no access/access panel too smallN/A
AtticFD-A-046no access/access panel too smallN/A
AtticFD-A-047no access/access panel too smallN/A
AtticFD-A-049no access/access panel too smallN/A
AtticFD-A-050no access/access panel too smallN/A
AtticFD-A-051no access/access panel too smallN/A
AtticFD-A-052no access/access panel too smallN/A
AtticFD-A-053no access/access panel too smallN/A
AtticFD-A-054no access/access panel too smallN/A
AtticFD-A-055no access/access panel too smallN/A
AtticFD-A-056no access/access panel too smallN/A

image1.png