36C25718Q0546-014.xlsx

XLSX spreadsheet 35 KB Posted

Attached to
674-18-1-5065-0699 Correct Inaccessible Dampers Waco (VA-18-904878)
Solicitation number
36C25718Q0546
Issued by

About this file

36C25718Q0546 Waco BLDG 10 Damper Report FINAL.xlsx

View the file

Other files

File Type Posted
36C25718C0099-000.docx DOCX document
36C25718Q0546-00001002.pdf PDF
36C25718Q0546-00001001.pdf PDF
36C25718Q0546-00001000.docx DOCX document
36C25718Q0546-011.pdf PDF
36C25718Q0546-015.xlsx XLSX spreadsheet
36C25718Q0546-012.xlsx XLSX spreadsheet
36C25718Q0546-018.pdf PDF
36C25718Q0546-016.xlsx XLSX spreadsheet
36C25718Q0546-013.xlsx XLSX spreadsheet
36C25718Q0546-010.docx DOCX document
36C25718Q0546-017.xlsx XLSX spreadsheet
36C25718Q0546-009.docx DOCX document
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Texas Fire Suppression, Inc
100-B Don Currie Dr.
Jarrell, TX 76537
Fire Protection Systems • Commercial • Industrial • Institutional • Special Hazards • High Tech • Defense • Hangars • Retrofit • Service • Inspection • MaintenancePh: (512) 598-3959
Fax: (512) 598-3961
TX-SCR-G 1819205 * TX-ACR 1666099 * TX-ECR 1666599Date:April 2017
Report to:VA Waco CampusLocation or Building Inspected:Building 10
Contact:R. GriffinPhone:Fax:
Address:4800 Veterans Memorial Dr.email:
City, State:Waco, TXZip:76711Inspector:Dennis Thompson
Page1of2
Damper Testing Report Per NFPA 80 and EC.02.03.05 item 18
LocationDamper IDNotesPass/Fail
Room BIA103FD-B-006can't reach to remove from serviceN/A
Room B1B108FD-B-008no access/can't reach damperN/A
Room B1B108FD-B-009no access/can't reach damperN/A
Room 1B115AFD-1-001no access/can't reach damperN/A
Room 1B117FD-1-005damper will not closeF
ShaftFD-1-011no access/can't reach damperN/A
Bath/ShowerFD-1-012no access/can't reach damperN/A
Room 1A112FD-1-013no access/obstructed access panelN/A
Room 2B109FD-2-001no access/can't reach damperN/A
Room 2B215AFD-2-005no access/obstructed access panelN/A
Room 2A112AFD-2-018no access/can't reach damperN/A