Regulated Building Materials Survey Report.pdf
PDF 5 MB Posted
- Solicitation number
- 36C25625R0015
About this file
This is a Regulated Building Materials Survey Report prepared by Mabbett & Associates for Miller-Remick, LLC examining asbestos-containing materials (ACM) and lead-containing paint (LCP) in the inpatient and outpatient pharmacies at G.V. Sonny Montgomery VAMC in Jackson, MS in support of planned physical security upgrades.
The survey identified one ACM - red duct sealant containing 10% Chrysotile asbestos in approximately 100 square feet of material in the outpatient pharmacy. Fire doors were assumed to contain asbestos but were not sampled due to inaccessibility. For LCP testing, 10 paint chip samples were collected and analyzed, with none exceeding EPA/HUD standards of 0.5 mg/Kg or 1.0 mg/cm². The report recommends that identified ACM must be removed by a licensed asbestos abatement contractor prior to renovation activities, and although lead levels were below limits, OSHA regulations still apply for any paint disturbance during construction. The survey work was conducted on April 13, 2023 by certified inspectors from Mabbett and ECS Southeast, LLP.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 586-22-105 - PRE-BID RFIs - COMPLETE.docx | DOCX document | |
| EXHIBIT A PERFORMANCE RELEVANCY SURVEY - 586-22-105.pdf | ||
| 586-22-105 Pharmacy Physical Security Upgrade Sign-in Sheet.pdf | ||
| 36C25625R0015 0001.docx | DOCX document | |
| 36C25625R0015_RFP Document.docx | DOCX document | |
| 586-22-105 Specifications.pdf | ||
| Past and Present Performance Questionnaire.docx | DOCX document | |
| Wage Determination MS20240075.pdf | ||
| Contractor Evaluation Form.docx | DOCX document | |
| SOW_Pharmacy Physical Security Upgrade.docx | DOCX document | |
| 586-22-105 Drawings.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
p
REG
ULATED BUI
LDING MATERIALS
SURVEY REPORT
A/E Design Services for Pharmacy Physical Security Upgrades VA Project No. 586-22-105
G.V. Sonny Montgomery VAMC 1500 E. Woodrow Wilson Avenue Jackson, MS 39216
Mabbett Project No. R2023038.000
April 30, 2023v2
Prepared For:
Miller-Remick, LLC.
1040 Kings Highway North Suite 700 Cherry Hill, NJ 08034
© 2023, Mabbett & Associates, Inc.
Mabbett & Associates, Inc. www.mabbett.com 105 Central Street, Suite 4100 Stoneham, MA 02180-1260 T. 781-275-6050 F: 781-954-5155
Massachusetts | Virginia | Rhode Island | New York
REGULATED BUILDING MATERIALS SURVEY REPORT
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. i April 30, 2023 Project No. R2023038.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
ACKNOWLEDGEMENT
This Regulated Building Materials Survey Report has been prepared by Mabbett & Associates, Inc. (Mabbett®) for the A/E Design Services for Pharmacy Physical Security Upgrades at the G.V. Sonny Montgomery VAMC located in Jackson, Mississippi. The information presented herein is based on the facts and information conveyed to or received by Mabbett during the preparation of this report. If any of the information provided to Mabbett that was used in preparing this report is incorrect, incomplete, or subject to change, Mabbett would wish to alter its opinions accordingly. In addition, the professional opinions and information contained in this report are based solely on the requirements of the applicable regulations and technical data as known to Mabbett as of the date of this report and considered applicable to this report.
Mabbett does not claim to have identified all hazardous materials that could be present in the facility. Mabbett has conducted this assessment with reasonable care and has performed this project in accordance with industry standards. There can be no assurances, and Mabbett makes no assurances, that the information, research, and technology used to prepare this report may not change in the future, thus affecting the results reported herein.
The attached Regulated Building Materials Survey Report was prepared by Mr. Kevin M. Donovan, Senior Environmental, Health & Safety Specialist of Mabbett & Associates, Inc.
This report has been reviewed and approved by:
Michael F. Delaney Director, Building Sciences Group
KMD/MFD:fmz
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. ii April 30, 2023 Project No. R2023038.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
TABLE OF CONTENTS
SECTION PAGE
1.0 INTRODUCTION
2.0 ASBESTOS CONTAINING MATERIAL (ACM) SURVEY
2.1 Sampling Methodology
2.2 Analytical Methodology
2.3 ACM Results
3.0 LEAD CONTAINING PAINT (LCP) SURVEY
3.1 Sampling Methodology
3.2 Analytical Methodology
3.3 LCP Results
4.0 RECOMMENDATIONS
4.1 Asbestos
4.2 Lead Containing Paint
TABLES
Table 1 - Estimated Quantities of ACM
Table 2 - Paint Chip Analytical Results
APPENDICES
Appendix A – Summary of Asbestos Bulk Sampling Results Appendix B – ECS Southeast Asbestos Survey Report Appendix C – LCP Lab Report and Chain of Custody
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Page 1 April 30, 2023 Project No. R2023083.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
1.0 INTRODUCTION
Mabbett and Associates, Inc. (Mabbett®), with support from local asbestos inspection consulting firm ECS Southeast, LLP (ECS), performed a survey for regulated building materials (RBM) as part of the A/E Design Services for Pharmacy Physical Security Upgrades at the G.V. Sonny Montgomery VAMC located in Jackson, Mississippi, VA Project No. 586-22-105. The survey was limited to the basement level inpatient pharmacy and first floor outpatient pharmacy. Site survey work was performed on April 13th, 2023, by Certified Asbestos Inspector Mr.
Kevin Donovan of Mabbett and Mississippi licensed asbestos inspector Mr. Taylor L Pack (ABI-00011150) and consisted of the following activities:
Asbestos Containing Material (ACM) survey of suspect materials [analysis by Polarized Light Microscopy
(PLM).
Lead Containing Paint (LCP) sampling (analysis by Flame Atomic Absorption Spectrophotometry [AA].
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Page 2 April 30, 2023 Project No. R2023083.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
2.0 ASBESTOS CONTAINING MATERIAL (ACM) SURVEY
A visual screening inspection was conducted to identify locations of suspect ACM and to design the sampling program. Only areas that may be impacted by the renovation and physical security upgrades in the pharmacy’s project and that were accessible during the survey were inspected with reasonable efforts made to access pertinent areas. Destructive investigation of operating equipment was not conducted.
2.1 Sampling Methodology
Bulk suspect ACM samples were collected using EPA National Emissions Standards for Hazardous Air Pollutants (NESHAP), 40 CFR Part 763. This method describes sampling for friable surfacing material, thermal system insulation, and miscellaneous material. Asbestos Hazard Emergency Response Act (AHERA) protocols were also employed. Suspect ACM sampling was conducted according to the following standard sampling protocol:
Friable surfacing material:
• At least three bulk samples shall be collected from each homogeneous area of surfacing material that is 1,000 ft2 or less.
• At least five bulk samples shall be collected from each homogeneous area of surfacing material that is greater than 1,000 ft2 but less than or equal to 5,000 ft2.
• At least seven bulk samples shall be collected from each homogeneous area of surfacing material that is greater than 5,000 ft2.
Thermal system insulation:
• At least three bulk samples shall be collected from each homogeneous area of thermal system insulation.
• At least one bulk sample shall be collected from each homogeneous area of patched thermal system insulation.
• Sufficient samples shall be collected from elbows and fittings.
• Bulk samples shall not be collected from any homogeneous area where the inspector determines that the thermal system insulation is fiberglass, foam glass, rubber, or other non-ACM.
Miscellaneous material (e.g., joint compound, roofing, gaskets, floor coverings, decorative coatings, wire insulation).
• At least two bulk samples shall be collected from each homogeneous area of miscellaneous material that is less than 100 ft2.
• At least three bulk samples shall be collected from each homogeneous area of miscellaneous material that is greater than 100 ft2.
Areas that were inaccessible or where the survey was limited to visual observation only:
within walls within enclosed pipe/duct chases inside mechanical equipment/ductwork inside electrical equipment
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Page 3 April 30, 2023 Project No. R2023083.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
2.2 Analytical Methodology
Seventy (70) bulk samples were collected from twenty-four (24) homogeneous areas and submitted under chain of custody (COC) procedures to EMSL Analytical, Inc. of Baton Rouge, Louisiana (NVLAP Laboratory ID 200375-0).
Bulk samples were analyzed by PLM using AHERA method 40CFR 763 with EPA Method 600/R-93/116 using polarized light microscopy.
2.3 ACM Results
The USEPA, Occupational Safety and Health Administration (OSHA), and the Mississippi Department of Environmental Quality (MDEQ) define any material that contains greater than one percent (>1%) asbestos as ACM.
One (1) material was found to contain greater than one percent (>1%) asbestos. Asbestos Bulk Sampling Results are summarized in Appendix A. The laboratory report and COC documentation are provided in Appendix B, ECS Asbestos Survey Report, dated April 21, 2023.
Estimated quantities of materials identified as ACM are presented in Table 1.
Table 1 Estimated Quantities of ACM
A/E Design Services for Pharmacy Physical Security Upgrades G.V. Sonny Montgomery VAMC
Location Description of Material Percent and Type of Asbestos Estimated Quantity
Outpatient Pharmacy Red Duct Sealant 10% Chrysotile 100 Square Feet
Mabbett also observed fire doors on the 1st floor which were not accessible for inspection or sampling. Fire doors material are assumed ACM.
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Page 4 April 30, 2023 Project No. R2023083.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
3.0 LEAD CONTAINING PAINT (LCP) SURVEY
An LCP survey was conducted by collecting and analyzing paint chips from painted surfaces and systems that may be impacted by the pharmacy renovate/physical security upgrades project.
3.1 Sampling Methodology
Paint chip samples are collected using a sharp hand tool to score and peel paint off a 1 square inch (or larger) area of the substrate. Different tools such as chisels, putty knives, and hammers may also be needed in the collection of paint chips. Tools are cleaned after each sample to prevent cross contamination. Collected paint chip samples are submitted under COC procedures to an accredited laboratory and analyzed via Flame Atomic Absorption Spectrophotometry (AA).
3.2 Analytical Methodology
The regulations addressing LCP in non-residential buildings are focused on occupational exposures involved with paint-disturbing activities and related waste-disposal activities. Occupational exposure to lead is regulated by OSHA regulation 29 CFR 1926.62, Lead in Construction, as well as other applicable state and local regulations. An LCP survey cannot determine a safe level of lead for the purpose of paint-disturbing/waste-disposal activities but is intended to provide guidance as to the locations of surfaces containing lead.
Contractors may use this information to better determine where worker exposures to airborne lead and other hazards may occur. They can then assess the potential magnitude of exposure to their employees and identify the controls necessary to limit health risks. This information can also be used for pre-characterization of demolition waste streams prior to toxicity characteristic leaching procedure (TCLP) sampling in accordance with 40 CFR Part 261.
Ten (10) samples, each from different homogenous areas, were collected during this survey. Paint chip samples were submitted under COC procedures to Scientific Analytical Institute Inc. (SAI) of Greensboro, North Carolina.
Analysis was conducted using EPA SW-846 Test Method 7000B: Flame Atomic Absorption Spectrophotometry.
3.3 LCP Results
A concentration of lead greater than or equal to 0.5 mg/Kg percent by weight or 1.0 mg/cm² exceeds EPA and HUD residential standards and is considered an indicator of risk. The results of this LCP sampling survey identified none of the samples that indicate risk and are presented in Table 2. The laboratory report and COC documentation are provided in Appendix C.
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Page 5 April 30, 2023 Project No. R2023083.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
TABLE 2
Paint Chip Analytical Results
A/E Design Services for Pharmacy Physical Security Upgrades G.V. Sonny Montgomery VAMC
Sample No. Location Substrate and Component Color Result
(% by weight) Pb-01 Outpatient Pharmacy Metal Door Frame Gray 0.012% Pb-02 Outpatient Pharmacy Entry Gypsum Wall White <0.0033% Pb-03 Outpatient Pharmacy Metal Door Gray 0.0089% Pb-04 Outpatient Pharmacy Mens Room Plaster Wall Blue 0.049% Pb-05 Outpatient Pharmacy Gypsum Column White <0.0032% Pb-06 Inpatient Pharmacy (Entry) Metal Door Frame Tan <0.041% Pb-07 Inpatient Pharmacy (Shortage) Gypsum Wall Tan <0.0036%
Pb-08 Inpatient Pharmacy Metal Door Gray <0.0057%
Pb-09 Inpatient Pharmacy (Break Area) Gypsum Wall Blue <0.0067% Pb-10 Inpatient Pharmacy (Janitors Closet) Metal Door Frame Tan 0.0079%
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Page 6 April 30, 2023 Project No. R2023083.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
4.0 RECOMMENDATIONS
4.1 Asbestos
Identified ACM must be removed by a licensed asbestos abatement contractor prior to being disturbed by renovation activities. Any suspect materials encountered during renovation or demolition activities that were not identified in this report as being non-ACM should be assumed to be ACM unless sample results prove otherwise.
Suspect ACM that may be present within the walls, above inaccessible hard ceilings, or in other inaccessible locations, should be assumed to contain asbestos if discovered during any renovation or demolition process or until otherwise verified.
4.2 Lead Containing Paint
Paint chip sampling conducted as part of this survey indicated that lead was not detected above the EPA limit of
0.5 mg/Kg percent by weight or 1.0 mg/cm² on a tested painted surface. The requirements under OSHA Standard 29 CFR 1926.62, Lead Exposure in Construction; Interim Final Rule, are applicable to renovation and demolition activities that disturb these materials.
OSHA does not recognize a “safe” level of lead in paint. Depending on the method of removal used, even trace amounts of lead in paint may result in airborne concentrations of lead during removal. An employer or contractor who disturbs or removes lead paint must comply with OSHA Standard 29 CFR 1926.62, Lead Exposure in Construction; Interim Final Rule.
Accordingly, this LCP survey cannot determine a safe level of lead for the purpose of paint-disturbing activities during the Pharmacy Upgrade project. This report is intended to provide guidance as to the location of LCP so it can be controlled, abated, and/or disposed of properly during the Pharmacy Upgrade project. The results of this survey should be used to determine where worker exposures to airborne lead may occur. Additionally, this information should also be used to assess the potential for exposure to workers, and for determining appropriate controls necessary to limit his or her health risks during this project.
Representative samples of LCP waste to be generated during building renovation, or following demolition but prior to disposal, should be collected and analyzed using toxicity characteristic leaching procedure (TCLP) in accordance with 40 CFR Part 261. Management and disposal of lead containing waste must be done in accordance with all applicable local, state, and federal regulations.
OSHA regulations may require certain procedures for any paint that contains lead, even if it does not exceed the residential standards. All LCP areas identified, regardless of the level of lead content, should either be sampled and analyzed using TCLP and then handled/disposed of accordingly, or segregated from other large-scale debris and managed as hazardous waste in accordance with federal, state, and local hazardous waste disposal regulations.
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Appendix A April 30, 2023 Project No. R2023038.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
APPENDIX A
Summary of Asbestos Bulk Sampling Results
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Appendix A April 30, 2023 Project No. R2023038.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
APPENDIX A
Summary of Asbestos Bulk Sampling Results
A/E Design Services for Pharmacy Physical Security Upgrades G.V. Sonny Montgomery VAMC
Sample No. Sample Location Description of Material
Percent and Type of
Asbestos A1 Outpatient Pharmacy 12” x 12” Tan Floor Tile with Specks and Black Mastic NAD
A1 Outpatient Pharmacy 12” x 12” Tan Floor Tile with Specks and Black Mastic NAD
A2 Outpatient Pharmacy 12” x 12’’ Tan Floor Tile with Specks and Black Mastic NAD
A2 Outpatient Pharmacy 12” x 12” Tan Floor Tile with Specks and Black Mastic NAD
A3 Outpatient Pharmacy 12” x 12” Tan Floor Tile with Specks and Black Mastic NAD
A3 Outpatient Pharmacy 12” x 12” Tan Floor Tile with Specks and Black Mastic NAD
A4 Outpatient Pharmacy White 12” x 12” Floor Tile with Specks and Yellow Mastic NAD
A4 Outpatient Pharmacy White 12” x 12” Floor Tile with Specks and Yellow Mastic NAD
A5 Outpatient Pharmacy White 12” x 12” Floor Tile with Specks and Yellow Mastic NAD
A5 Outpatient Pharmacy White 12” x 12” Floor Tile with Specks and Yellow Mastic NAD
A6 Outpatient Pharmacy White 12” x 12” Floor Tile with Specks and Yellow Mastic NAD
A6 Outpatient Pharmacy White 12” x 12” Floor Tile with Specks and Yellow Mastic NAD
A7 Outpatient Pharmacy Vinyl Wood Floor with Grey Adhesive NAD
A8 Outpatient Pharmacy Vinyl Wood Floor with grey Adhesive NAD
A9 Outpatient Pharmacy Vinyl Wood Floor with Grey Adhesive NAD
A10 Loading Dock Door Black Caulk NAD
A11 Loading Dock Door Black Caulk NAD
A12 Loading Dock Door Black Caulk NAD
A13 Loading Dock Brick Mortar NAD
A14 Loading Dock Brick Mortar NAD
A15 Loading Dock Brick Mortar NAD
A16 Loading Dock Orange 12” x 12” Floor Tile with Specks and Black Mastic NAD
A16 Loading Dock Orange 12” x 12” Floor Tile with Specks and Black Mastic NAD
A17 Loading Dock Orange 12” x 12” Floor Tile with Specks and Black Mastic NAD
A17 Loading Dock Orange 12” x 12” Floor Tile with Specks and Black Mastic NAD
A18 Loading Dock Orange 12” x 12” Floor Tile with Specks and Black Mastic NAD
A18 Loading Dock Orange 12” x 12” Floor Tile with Specks and Black Mastic NAD
A19 Loading Dock Grey Ceiling Texture NAD
A20 Loading Dock Grey Ceiling Texture NAD
A21 Loading Dock Grey Ceiling Texture NAD
A22 Loading Dock 4” Covebase with Yellow Adhesive NAD
A22 Loading Dock 4” Covebase with Yellow Adhesive NAD
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Appendix A April 30, 2023 Project No. R2023038.000 Miller-Remick Jackson VAMC Pharmacy RBM Survey Report Final
APPENDIX A
Summary of Asbestos Bulk Sampling Results
A/E Design Services for Pharmacy Physical Security Upgrades G.V. Sonny Montgomery VAMC
Sample No. Sample Location Description of Material
Percent and Type of
Asbestos A23 Loading Dock 4” Covebase with Yellow Adhesive NAD
A23 Loading Dock 4” Covebase with Yellow Adhesive NAD
A24 Loading Dock 4” Covebase with Yellow Adhesive NAD
A24 Loading Dock 4” Covebase with Yellow Adhesive NAD
A25 Loading Dock Gypsum with Joint Compound NAD
A25 Loading Dock Gypsum with Joint Compound NAD
A26 Loading Dock Gypsum with Joint Compound NAD
A26 Loading Dock Gypsum with Joint Compound NAD
A27 Loading Dock Gypsum with Joint Compound NAD
A27 Loading Dock Gypsum with Joint Compound NAD
A28 Loading Dock 6” Covebase with Yellow Adhesive NAD
A28 Loading Dock 6” Covebase with Yellow Adhesive NAD
A29 Loading Dock 6” Covebase with Yellow Adhesive NAD
A29 Loading Dock 6” Covebase with Yellow Adhesive NAD
A30 Loading Dock 6” Covebase with Yellow Adhesive NAD
A30 Loading Dock 6” Covebase with Yellow Adhesive NAD
A31 Outpatient Pharmacy Plaster Wall NAD
A32 Outpatient Pharmacy Plaster Wall NAD
A33 Outpatient Pharmacy Plaster Wall NAD
A36 Outpatient Pharmacy Yellow Pipe Insulation with White/Silver Backing NAD
A37 Outpatient Pharmacy Yellow Pipe Insulation with White/Silver Backing NAD
A38 Outpatient Pharmacy Yellow Pipe Insulation with White/Silver Backing NAD
A34 Outpatient Pharmacy Black Sink Coat NAD
A35 Outpatient Pharmacy Black Sink Coat NAD
A39 Outpatient Pharmacy Tan Sprinkler Sealant NAD
A40 Outpatient Pharmacy Tan Sprinkler Sealant NAD
A41 Outpatient Pharmacy Tan Sprinkler Sealant NAD
A42 Outpatient Pharmacy 2’ x 4’ White Ceiling Tile Fissured NAD
A43 Outpatient Pharmacy 2’ x 4’ White Ceiling Tile Fissured NAD
A44 Outpatient Pharmacy 2’ x 4’ White Ceiling Tile Fissured NAD
A45 Outpatient Pharmacy Red Duct Sealant 10% Chrysotile
A46 Outpatient Pharmacy Red Duct Sealant 10% Chrysotile
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Appendix A April 30, 2023
APPENDIX A
Summary of Asbestos Bulk Sampling Results
A/E Design Services for Pharmacy Physical Security Upgrades G.V. Sonny Montgomery VAMC
Sample No. Sample Location Description of Material
Percent and Type of
Asbestos A47 Outpatient Pharmacy Red Duct Sealant 10% Chrysotile
A48 Outpatient Pharmacy Red Fire Stop NAD
A49 Outpatient Pharmacy Red Fire Stop NAD
A50 Outpatient Pharmacy 2’ x 2’ White Ceiling Tile Fissured NAD
A51 Outpatient Pharmacy 2’ x 2’ White Ceiling Tile Fissured NAD
A52 Outpatient Pharmacy 2’ x 2’ White Ceiling Tile Fissured NAD
A53 Inpatient Pharmacy 2’ x 4’ White Ceiling Tile Fissured NAD
A54 Inpatient Pharmacy 2’ x 4’ White Ceiling Tile Fissured NAD
A55 Inpatient Pharmacy 2’ x 4’ White Ceiling Tile Fissured NAD
A56 Inpatient Pharmacy White Fiberglass End Sealant NAD
A57 Inpatient Pharmacy White Fiberglass End Sealant NAD
A58 Inpatient Pharmacy White Fiberglass End Sealant NAD
A59 Inpatient Pharmacy Gypsum with Joint Compound NAD
A60 Inpatient Pharmacy Gypsum with Joint Compound NAD
A61 Inpatient Pharmacy Gypsum with Joint Compound NAD
A62 Inpatient Pharmacy 2’ x 4’ White Ceiling Tile Smooth NAD
A63 Inpatient Pharmacy 2’ x 4’ White Ceiling Tile Smooth NAD
A64 Inpatient Pharmacy 2’ x 4’ White Ceiling Tile Smooth NAD
A65 Inpatient Pharmacy Tan Sprinkler Sealant NAD
A66 Inpatient Pharmacy Tan Sprinkler Sealant NAD
A67 Inpatient Pharmacy Tan Sprinkler Sealant NAD
A68 Inpatient Pharmacy Grey Duct Sealant NAD
A69 Inpatient Pharmacy Grey Duct Sealant NAD
A70 Inpatient Pharmacy Grey Duct Sealant NAD
Notes: NAD = No Asbestos Detected
A/E Design Services for Pharmacy Physical Security Upgrades | G.V. Sonny Montgomery VAMC | Jackson, MS
© 2023, Mabbett & Associates, Inc. Appendix B April 30, 2023
APPENDIX B
ECS Southeast Asbestos Survey Report
ASBESTOS SURVEY
VA MEDICAL CENTER - INPATIENT & OUTPATIENT PHARMACIES
1500 E WOODROW WILSON AVENUE
JACKSON, MISSISSIPPI 39216
ECS PROJECT NO. 49:20021
FOR: MABBETT & ASSOCIATES, INC.
APRIL 21, 2023
April 21, 2023
Mr. Michael Delaney
Mabbett & Associates, Inc.
105 Central Street
Suite 1400
Stoneham, Massachusetts 02180 delaney@mabbett.com
ECS Project No. 49:20021
Reference: Asbestos Survey, VA Medical Center - Inpatient & Outpatient Pharmacies, 1500 E Woodrow Wilson Avenue, Jackson, Mississippi
Dear Mr. Delaney:
ECS Southeast, LLP (ECS) is pleased to provide Mabbett & Associates, Inc. with the results of the above referenced Asbestos Survey performed at VA Medical Center - Inpatient & Outpatient Pharmacies located at 1500 E Woodrow Wilson Avenue in Jackson, Mississippi. This report summarizes our observations, analytical results, findings, and recommendations related to the work performed.
The work described in this report was performed by ECS in general accordance with the Scope of Services described in ECS Proposal Number 49:36899P and the terms and conditions of the agreement authorizing those services.
ECS appreciates this opportunity to provide Mabbett & Associates, Inc. with our services. If we can be of further assistance to you, please do not hesitate to contact us.
Sincerely, ECS Southeast, LLP
Taylor Pack Lindsey Thompson, REM Environmental Scientist Environmental Principal tpack@ecslimited.com lthompson@ecslimited.com 225-224-2583 502-493-7100
133 W. Oxmoor Road, Suite 205, Birmingham, Alabama 35209 • T: 205-588-5099 • F: 703-834-5527 • ecslimited.com NC Engineering No. F-1078 • NC Geology No. C-553 • SC Engineering No. 3239
EXECUTIVE SUMMARY
The subject property is improved with a hospital building reportedly originally constructed in the 1950s. The purpose of the survey was to determine if asbestos-containing materials (ACMs) are present on the subject property. Areas included in this survey were the Inpatient and Outpatient pharmacies, which are scheduled for renovation to upgrade finishes and repair security issues.
Based on the laboratory analysis of the bulk samples collected during the survey, the following materials were reported to contain asbestos:
• Red duct sealant in Outpatient Pharmacy
ECS assumes that the following materials contain asbestos, but the materials were not sampled:
• Fireproof doors
The executive summary is an integral portion of this report, however, ECS recommends the report be read in its entirety ii
PAGETABLE OF CONTENTS
1.0 SITE DESCRIPTION
2.0 PURPOSE
3.0 METHODOLOGY
3.1 Asbestos-Containing Materials
4.0 RESULTS
4.1 Asbestos-Containing Materials
4.2 Suspect or Assumed Asbestos-Containing Materials
5.0 RECOMMENDATIONS AND REGULATORY REQUIREMENTS
5.1 Asbestos-Containing Materials
6.0 LIMITATIONS
iii
TABLE OF APPENDICES
Appendix I: Figures
Appendix II: Site Photographs
Appendix III: Laboratory Report(s)
Appendix IV: Certifications/Licenses iv
1.0 SITE DESCRIPTION
The subject property is improved with a VA hospital building located at 1500 E Woodrow Wilson Avenue in Jackson, Mississippi. Sample areas include the Inpatient Pharmacy and Outpatient Pharmacy. Building finishes observed within the sample areas appeared to consist of floor tiles on concrete sub-floor, the wall systems consist of drywall, plaster walls, and/or brick walls, and the ceiling systems consist of a suspended drop ceiling which is composed of ceiling tiles and drywall.
2.0 PURPOSE
The purpose of the Asbestos Survey was to identify ACMs which may require special handling and/ or disposal if removed during construction activities. The identification of ACMs may require trained labor, regulated work practices, and special disposal.
3.0 METHODOLOGY
ECS performed the authorized Scope of Services in general accordance with our proposal, standard industry practice and methods specified by regulation for the identification of ACMs.
3.1 Asbestos-Containing Materials
The non-destructive asbestos survey was performed by an asbestos inspector who has received EPA accredited training and is licensed by Mississippi. Samples of suspect ACMs were collected utilizing hand tools and placed into individual, labeled plastic bags. Unique bulk suspect ACM samples were submitted to ESML in Baton Rouge, Louisiana for analysis via Polarized Light Microscopy (PLM) in accordance with current EPA-600 methodology. Materials consisting of additional layers were analyzed separately. ESML is listed as an accredited laboratory by the National Voluntary Laboratory Accreditation Plan (NVLAP) managed by the National Institute of Standards and Technology (NIST) for bulk sample analysis by currently approved EPA methodology by PLM.
During the survey, ECS attempted to identify suspect ACMs in readily accessible areas. However, due to the destructive means required to identify some materials, certain areas were deemed inaccessible (i.e. behind walls or sub grade materials) and were not surveyed for suspect ACMs. Unidentified suspect ACMs may be located in these and/or other inaccessible areas.
Samples were collected in general accordance with EPA Standard 40 CFR 763 Subpart E, Asbestos Hazard Emergency Response Act (AHERA) and OSHA Standard 29 CFR 1926.1101 Inspection Protocol.
Multiple samples of each unique material were submitted.
4.0 RESULTS
The following is a summary of laboratory results, findings and observations.
4.1 Asbestos-Containing Materials
In total, 70 bulk samples from 24 homogeneous areas were submitted to the laboratory of which 88 layers were analyzed.
April 21, 2023
ECS Project # 49:20021
Summary of Asbestos-Containing Materials Identified
Location Material Description Analytical Result Category
Outpatient Pharmacy
Red Duct Sealant (A-45, 46, 47)
10% Chrysotile Category II Non-Friable
4.2 Suspect or Assumed Asbestos-Containing Materials
Due to the inaccessibility or the destructive means that asbestos sampling requires, additional suspect ACMs may remain within the building hidden behind inaccessible areas that include, but are not limited to, sub-grade walls, structural members, topping slabs, sub-grade sealants, flooring located below underlayments, areas behind exterior walls, pipe trenches, and subsurface utilities, etc.
These areas were deemed inaccessible and were not assessed.
If these materials are discovered during construction activities, they should be presumed to contain asbestos and be treated as ACMs or be sampled immediately upon discovery and prior to disturbance for asbestos content by a certified asbestos inspector in accordance with 29 CFR 1926.1101.
5.0 RECOMMENDATIONS AND REGULATORY REQUIREMENTS
Based on our understanding of the purpose of the Asbestos Survey, the results of laboratory analysis, and our findings and observations, ECS presents the following recommendations.
5.1 Asbestos-Containing Materials
ECS recommends where a material type has been identified as asbestos-containing that other materials with similar color, texture, age and size throughout the building’s interior and exterior be assumed to contain asbestos. Please refer to Section 4.1 for a complete list of building materials that were reported positive for asbestos and to Section 4.2 for materials that were assumed to contain asbestos.
If ACMs are to be removed, it is recommended that an industrial hygienist monitor the project.
This involves collecting air samples from within and outside abatement work areas to monitor the asbestos abatement contractor’s work practices over the course of the project. The industrial hygienist should evaluate if the asbestos abatement work is in accordance with project specifications, U.S. EPA regulation 40 CFR Part 61-National Emission Standards for Hazardous Air Pollutants Subpart M: National Emission Standard for Asbestos, and U.S. Occupational Safety and Health Administration (OSHA) regulation 29 CFR 1926.1101 – Asbestos in Construction. The industrial hygienist should assess each work area to monitor the removal of ACMs. Only after the industrial hygienist has determined the identified ACMs have been removed should final clearance air samples be collected (if necessary).
Suspect ACMs not observed due to inaccessibility or not sampled due to the destructive means that sampling would require may also be encountered during construction activities. At the time of the survey, only limited destructive means were used to locate or sample suspect ACMs; therefore, additional suspect ACMs may remain within inaccessible areas that include, but are not limited
April 21, 2023 to, sub-grade walls, structural members, topping slabs, exterior areas, sub-grade sealants, flooring located below underlayments, vapor barriers, pipe trenches and other subsurface utilities, etc. If additional suspect ACMs are uncovered which were not accessible during this survey, it is recommended that these materials either be assumed to contain asbestos or be sampled prior to disturbance upon discovery for asbestos content by an asbestos inspector in accordance with 29 CFR 1926.1101.
6.0 LIMITATIONS
The conclusions and recommendations presented within this report are based upon a reasonable level of assessment within normal bounds and standards of professional practice for a site in this particular geographic setting. ECS is not responsible or liable for the discovery and elimination of hazards that may potentially cause damage, accidents, or injuries.
The observations, conclusions, and recommendations pertaining to environmental conditions at the subject site are necessarily limited to conditions observed, and/or materials reviewed at the time this study was undertaken. No warranty, expressed or implied, is made with regard to the conclusions and recommendations presented within this report. This report is provided for the exclusive use of the client. This report is not intended to be used or relied upon in connection with other projects or by other unidentified third parties without the written consent of ECS and the client.
Our recommendations are in part based on federal, state, and local regulations and guidelines. ECS does not assume the responsibility of the person(s) in charge of the site, or otherwise undertake responsibility for reporting to any local, state, or federal public agencies, any conditions at the site that may present a potential danger to public health, safety, or the environment. Under this scope of services, ECS assumes no responsibility regarding any response actions initiated as a result of these findings. General compliance with regulations and response actions are the sole responsibility of the Client and should be conducted in accordance with local, state, and/or federal requirements.
April 21, 2023
Appendix I: Figures
Legend:
A-# Asbestos Sample Location
Asbestos Sample Negative
Asbestos Sample Positive
Notes:
Not to scale
Figure 2 Asbestos Sample Locations (Outpatient
Pharmacy) VA Medical Center
1500 E Woodrow Wilson Ave Jackson, Mississippi
ECS Project No. 49:20021
A-23
A-22
A-21
A-20A-19
A-18 A-17 A-16
A-15
A-14
A-13
A-12 A-11
A-10
A-9
A-8 A-7
A-6 A-5
A-4
A-3
A-2
A-1
A-45
A-44
A-43
A-42
A-41 A-40
A-39 A-38 A-37 A-36
A-35 A-34
A-33A-32A-31
A-30
A-29 A-28
A-27
A-26
A-25
A-24
A-52
A-51
A-50
A-49A-48
A-47 A-46
Legend:
A-# Asbestos Sample Location
Asbestos Sample Negative
Notes:
Not to scale
Figure 3 Asbestos Sample Locations (Inpatient
Pharmacy Ceiling and Above) VA Medical Center
1500 E Woodrow Wilson Ave Jackson, Mississippi
ECS Project No. 49:20021
A-70 A-69
A-68
A-67
A-66
A-65
A-64
A-63
A-62 A-61
A-60
A-59
A-58 A-57 A-56
A-55
A-54
A-53
Appendix II: Site Photographs
1 - View of front of facility
2 - View of drywall and joint compound
3 - View of floor tiles and mastic
4 - View of 6 inch cove base
5 - View of ceiling tiles
6 - View of brick mortar, ceiling texture, and door sealant
7 - View of sprinkler sealant
8 - View of fire stop
9 - Typical view above drop ceiling
10 - View of 4 inch covebase
Appendix III: Laboratory Report(s)
EMSL Analytical, Inc.
18369 Petroleum Drive Baton Rouge, LA 70809
Tel/Fax: (225) 755-1920 / (225) 755-1989 http://www.EMSL.com / batonrougelab@emsl.com
252301822EMSL Order:
Customer ID: ENCS55
Customer PO:
Project ID:
Attention: Phone:Taylor Pack (225) 337-5567
Fax:ECS Southeast, LLP (864) 987-1615
Received Date:1200 Woodruff Road 04/13/2023 4:17 PM
Analysis Date:Suite H-12 04/19/2023
Collected Date:Greenville, SC 29607 04/13/2023
Project: VA Center Jackson 49:20021
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
A-1-Floor Tile
252301822-0001
None DetectedNon-fibrous (Other)100%Gray/White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Tan 12x12 floor tile w/specks & black mastic
HA: 1
A-1-Mastic
252301822-0001A
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Tan 12x12 floor tile w/specks & black mastic
HA: 1
A-2-Floor Tile
252301822-0002
None DetectedNon-fibrous (Other)100%Tan/White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Tan 12x12 floor tile w/specks & black mastic
HA: 1
A-2-Mastic
252301822-0002A
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Tan 12x12 floor tile w/specks & black mastic
HA: 1
A-3-Floor Tile
252301822-0003
None DetectedNon-fibrous (Other)100%Gray/White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Tan 12x12 floor tile w/specks & black mastic
HA: 1
A-3-Mastic
252301822-0003A
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Tan 12x12 floor tile w/specks & black mastic
HA: 1
A-4-Floor Tile
252301822-0004
None DetectedNon-fibrous (Other)100%Tan/White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- White 12x12 floor tile w/specks & yellow mastic
HA: 2
A-4-Adhesive
252301822-0004A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- White 12x12 floor tile w/specks & yellow mastic
HA: 2
A-5-Floor Tile
252301822-0005
None DetectedNon-fibrous (Other)100%Tan/White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- White 12x12 floor tile w/specks & yellow mastic
HA: 2
A-5-Adhesive
252301822-0005A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- White 12x12 floor tile w/specks & yellow mastic
HA: 2
Initial report from: 04/20/2023 13:26:24
Page 1 of 7ASB_PLM_0008_0001 - 1.78 Printed: 4/20/2023 12:26 PM
Tel/Fax: (225) 755-1920 / (225) 755-1989 http://www.EMSL.com / batonrougelab@emsl.com
252301822EMSL Order:
Customer ID: ENCS55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
A-6-Floor Tile
252301822-0006
None DetectedNon-fibrous (Other)100%Tan/White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- White 12x12 floor tile w/specks & yellow mastic
HA: 2
A-6-Adhesive
252301822-0006A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- White 12x12 floor tile w/specks & yellow mastic
HA: 2
A-7
252301822-0007
None DetectedNon-fibrous (Other)100%Brown/Black
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Vinyl wood floor w/grey adhesive
HA: 3
A-8
252301822-0008
None DetectedNon-fibrous (Other)100%Brown/Black
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Vinyl wood floor w/grey adhesive
HA: 3
A-9
252301822-0009
None DetectedNon-fibrous (Other)100%Brown/Black
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Vinyl wood floor w/grey adhesive
HA: 3
A-10
252301822-0010
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Loading dock door -
Black caulk
HA: 4
A-11
252301822-0011
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Loading dock door -
Black caulk
HA: 4
A-12
252301822-0012
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Loading dock door -
Black caulk
HA: 4
A-13
252301822-0013
None DetectedNon-fibrous (Other)100%Gray/Red
Non-Fibrous
Heterogeneous
Loading dock - Brick mortar
HA: 5
A-14
252301822-0014
None DetectedNon-fibrous (Other)100%Gray/Red
Non-Fibrous
Homogeneous
Loading dock - Brick mortar
HA: 5
A-15
252301822-0015
None DetectedNon-fibrous (Other)100%Gray/Red
Non-Fibrous
Homogeneous
Loading dock - Brick mortar
HA: 5
A-16-Floor Tile
252301822-0016
None DetectedNon-fibrous (Other)100%Tan/White
Non-Fibrous
Homogeneous
Loading dock -
Orange 12x12 floor tile w/specks & black mastic
HA: 6
A-16-Mastic/Adhesive
252301822-0016A
None DetectedNon-fibrous (Other)100%Black/Yellow
Non-Fibrous
Homogeneous
Loading dock -
Orange 12x12 floor tile w/specks & black mastic
HA: 6
Page 2 of 7ASB_PLM_0008_0001 - 1.78 Printed: 4/20/2023 12:26 PM
Tel/Fax: (225) 755-1920 / (225) 755-1989 http://www.EMSL.com / batonrougelab@emsl.com
252301822EMSL Order:
Customer ID: ENCS55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
A-17-Floor Tile
252301822-0017
None DetectedNon-fibrous (Other)100%Tan/White
Non-Fibrous
Homogeneous
Loading dock -
Orange 12x12 floor tile w/specks & black mastic
HA: 6
A-17-Mastic/Adhesive
252301822-0017A
None DetectedNon-fibrous (Other)100%Black/Yellow
Non-Fibrous
Homogeneous
Loading dock -
Orange 12x12 floor tile w/specks & black mastic
HA: 6
A-18-Floor Tile
252301822-0018
None DetectedNon-fibrous (Other)100%Tan/White
Non-Fibrous
Homogeneous
Loading dock -
Orange 12x12 floor tile w/specks & black mastic
HA: 6
A-18-Mastic/Adhesive
252301822-0018A
None DetectedNon-fibrous (Other)100%Black/Yellow
Non-Fibrous
Homogeneous
Loading dock -
Orange 12x12 floor tile w/specks & black mastic
HA: 6
A-19
252301822-0019
None DetectedNon-fibrous (Other)100%Gray/Tan
Non-Fibrous
Homogeneous
Loading dock - Grey ceiling texture
HA: 7
A-20
252301822-0020
None DetectedNon-fibrous (Other)100%Gray/Tan
Non-Fibrous
Homogeneous
Loading dock - Grey ceiling texture
HA: 7
A-21
252301822-0021
None DetectedNon-fibrous (Other)100%Gray/Tan
Non-Fibrous
Homogeneous
Loading dock - Grey ceiling texture
HA: 7
A-22-Cove Base
252301822-0022
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Loading dock - 4in
Covebase w/yellow adhesive
HA: 8
A-22-Glue
252301822-0022A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Loading dock - 4in
Covebase w/yellow adhesive
HA: 8
A-23-Cove Base
252301822-0023
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Loading dock - 4in
Covebase w/yellow adhesive
HA: 8
A-23-Glue
252301822-0023A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Loading dock - 4in
Covebase w/yellow adhesive
HA: 8
A-24-Cove Base
252301822-0024
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Loading dock - 4in
Covebase w/yellow adhesive
HA: 8
A-24-Glue
252301822-0024A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Loading dock - 4in
Covebase w/yellow adhesive
HA: 8
A-25-Joint Compound
252301822-0025
None DetectedNon-fibrous (Other)100%Non-Fibrous
Homogeneous
Loading dock -
Gypsum w/joint compound
Page 3 of 7ASB_PLM_0008_0001 - 1.78 Printed: 4/20/2023 12:26 PM
Tel/Fax: (225) 755-1920 / (225) 755-1989 http://www.EMSL.com / batonrougelab@emsl.com
252301822EMSL Order:
Customer ID: ENCS55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
HA: 9
A-25-Drywall
252301822-0025A
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Loading dock -
Gypsum w/joint compound
HA: 9
A-26-Joint Compound
252301822-0026
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Loading dock -
Gypsum w/joint compound
HA: 9
A-26-Drywall
252301822-0026A
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Loading dock -
Gypsum w/joint compound
HA: 9
A-27-Joint Compound
252301822-0027
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Loading dock -
Gypsum w/joint compound
HA: 9
A-27-Drywall
252301822-0027A
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Loading dock -
Gypsum w/joint compound
HA: 9
A-28-Cove Base
252301822-0028
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Loading dock - 6in
Covebased w/yellow adhesive
HA: 10
A-28-Glue
252301822-0028A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Loading dock - 6in
Covebased w/yellow adhesive
HA: 10
A-29-Cove Base
252301822-0029
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Loading dock - 6in
Covebased w/yellow adhesive
HA: 10
A-29-Glue
252301822-0029A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Loading dock - 6in
Covebased w/yellow adhesive
HA: 10
A-30-Cove Base
252301822-0030
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Loading dock - 6in
Covebased w/yellow adhesive
HA: 10
A-30-Glue
252301822-0030A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Loading dock - 6in
Covebased w/yellow adhesive
HA: 10
A-31
252301822-0031
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Plaster Wall
HA: 11
A-32
252301822-0032
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Plaster Wall
HA: 11
A-33
252301822-0033
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Plaster Wall
HA: 11
Page 4 of 7ASB_PLM_0008_0001 - 1.78 Printed: 4/20/2023 12:26 PM
Tel/Fax: (225) 755-1920 / (225) 755-1989 http://www.EMSL.com / batonrougelab@emsl.com
252301822EMSL Order:
Customer ID: ENCS55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
A-36
252301822-0034
None DetectedNon-fibrous (Other)20%Glass80%Tan/Silver/Yellow
Non-Fibrous
Heterogeneous
Outpatient Pharmacy
- Yellow pipe insallation w/white/silver backing
HA: 13
A-37
252301822-0035
None DetectedNon-fibrous (Other)20%Glass80%Tan/Silver/Yellow
Fibrous
Heterogeneous
Outpatient Pharmacy
- Yellow pipe insallation w/white/silver backing
HA: 13
A-38
252301822-0036
None DetectedNon-fibrous (Other)20%Glass80%Tan/Silver/Yellow
Fibrous
Heterogeneous
Outpatient Pharmacy
- Yellow pipe insallation w/white/silver backing
HA: 13
A-34
252301822-0037
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Black sink coat
HA: 12
A-35
252301822-0038
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Black sink coat
HA: 12
A-39
252301822-0039
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Tan sprinkler sealant
HA: 14
A-40
252301822-0040
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Tan sprinkler sealant
HA: 14
A-41
252301822-0041
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Tan sprinkler sealant
HA: 14
A-42
252301822-0042
None DetectedNon-fibrous (Other)35%Cellulose
Glass
50%
15%
Gray/Tan/White
Fibrous
Homogeneous
Outpatient Pharmacy
- White 4x2 ceiling tile fissured
HA: 15
A-43
252301822-0043
None DetectedNon-fibrous (Other)35%Cellulose
Glass
50%
15%
Gray/Tan/White
Fibrous
Homogeneous
Outpatient Pharmacy
- White 4x2 ceiling tile fissured
HA: 15
A-44
252301822-0044
None DetectedNon-fibrous (Other)35%Cellulose
Glass
50%
15%
Gray/Tan/White
Fibrous
Homogeneous
Outpatient Pharmacy
- White 4x2 ceiling tile fissured
HA: 15
A-45
252301822-0045
10% ChrysotileNon-fibrous (Other)90%Red
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Red duct sealant
HA: 16
A-46
252301822-0046
10% ChrysotileNon-fibrous (Other)90%Red
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Red duct sealant
HA: 16
A-47
252301822-0047
10% ChrysotileNon-fibrous (Other)90%Red
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Red duct sealant
HA: 16
Page 5 of 7ASB_PLM_0008_0001 - 1.78 Printed: 4/20/2023 12:26 PM
Tel/Fax: (225) 755-1920 / (225) 755-1989 http://www.EMSL.com / batonrougelab@emsl.com
252301822EMSL Order:
Customer ID: ENCS55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
A-48
252301822-0048
None DetectedNon-fibrous (Other)100%Red
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Red fire stop
HA: 17
A-49
252301822-0049
None DetectedNon-fibrous (Other)100%Red
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- Red fire stop
HA: 17
A-50
252301822-0050
None DetectedNon-fibrous (Other)35%Cellulose
Glass
50%
15%
Gray/Tan/White
Fibrous
Homogeneous
Outpatient Pharmacy
- White 2x2w ceiling tile fissured
HA: 18
A-51
252301822-0051
None DetectedNon-fibrous (Other)35%Cellulose
Glass
50%
15%
Gray/Tan/White
Fibrous
Homogeneous
Outpatient Pharmacy
- White 2x2w ceiling tile fissured
HA: 18
A-52
252301822-0052
None DetectedNon-fibrous (Other)35%Cellulose
Glass
50%
15%
Gray/Tan/White
Non-Fibrous
Homogeneous
Outpatient Pharmacy
- White 2x2w ceiling tile fissured
HA: 18
A-53
252301822-0053
None DetectedNon-fibrous (Other)35%Cellulose
Glass
50%
15%
Gray/Tan/White
Fibrous
Homogeneous
Inpatient Pharmacy -
White 4x2 fissured ceiling tile
HA: 19
A-54
252301822-0054
None DetectedNon-fibrous (Other)35%Cellulose
Glass
50%
15%
Gray/Tan/White
Fibrous
Homogeneous
Inpatient Pharmacy -
White 4x2 fissured ceiling tile
HA: 19
A-55
252301822-0055
None DetectedNon-fibrous (Other)35%Cellulose
Glass
50%
15%
Gray/Tan/White
Fibrous
Homogeneous
Inpatient Pharmacy -
White 4x2 fissured ceiling tile
HA: 19
A-56
252301822-0056
None DetectedNon-fibrous (Other)100%White/Yellow
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
White fiberglass end sealant
HA: 20
A-57
252301822-0057
None DetectedNon-fibrous (Other)100%White/Yellow
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
White fiberglass end sealant
HA: 20
A-58
252301822-0058
None DetectedNon-fibrous (Other)100%White/Yellow
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
White fiberglass end sealant
HA: 20
A-59
252301822-0059
None DetectedNon-fibrous (Other)100%Peach
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
Gypsum w/joint compound
HA: 21
A-60
252301822-0060
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
Gypsum w/joint compound
HA: 21
A-61
252301822-0061
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
Gypsum w/joint compound
HA: 21
Page 6 of 7ASB_PLM_0008_0001 - 1.78 Printed: 4/20/2023 12:26 PM
Tel/Fax: (225) 755-1920 / (225) 755-1989 http://www.EMSL.com / batonrougelab@emsl.com
252301822EMSL Order:
Customer ID: ENCS55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
A-62
252301822-0062
None DetectedNon-fibrous (Other)20%Glass80%White/Yellow
Fibrous
Homogeneous
Inpatient Pharmacy -
White 4x2 smooth ceiling tile
HA: 22
A-63
252301822-0063
None DetectedNon-fibrous (Other)20%Glass80%White/Yellow
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
White 4x2 smooth ceiling tile
HA: 22
A-64
252301822-0064
None DetectedNon-fibrous (Other)20%Glass80%White/Yellow
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
White 4x2 smooth ceiling tile
HA: 22
A-65
252301822-0065
None DetectedNon-fibrous (Other)100%Gray/Tan
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
Tan sprinkler sealant
HA: 23
A-66
252301822-0066
None DetectedNon-fibrous (Other)100%Gray/Tan
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
Tan sprinkler sealant
HA: 23
A-67
252301822-0067
None DetectedNon-fibrous (Other)100%Gray/Tan
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
Tan sprinkler sealant
HA: 23
A-68
252301822-0068
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
Grey duct sealant
HA: 24
A-69
252301822-0069
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
Grey duct sealant
HA: 24
A-70
252301822-0070
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Inpatient Pharmacy -
Grey duct sealant
HA: 24
A…
This is the start of the file's text. The full file is on GovTribe.